Loading…
Loading…
| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | L1₹14.7 CrAccepted-AOC NIL NEAR BPCL PETROL PUMP MAKARPURA MANEJA VADODARA GUJARAT 390014 | VADODARA | GUJARAT | 390014 | ₹14.7 Cr | L1 | Accepted-AOC L1 Bidder |
| 2 | L2Rejected-Finance 6TH FLOOR CG HOUSE DR ANNIE BESANT ROAD WORLI MUMBAI MAHARASHTRA 400030 | MUMBAI | MAHARASHTRA | 400030 | - | L2 | Rejected-Finance L2 Bidder |
Tender Value
Refer Docs
Closing Date
17 Aug 2022, 3:00 pmClosed
Mr. Nilesh Sathe
thyssenKrupp Industrial Solutions (India) Private Limited (Formerly Uhde India Private Limited) Uhde House, L B S Marg, Vikhroli (W), Mumbai - 400083, India.
SUPPLY OF POWER TRANSFORMER FOR P25 PROJECT AT IOCL PANIPAT REFINERY
2022_REFHQ_151554_1
6745-PPM-000-CA-EL03
Limited
Electrical - All
240 days
IOCL Panipat Refinery
Please refer Tender documents
6 documents required · 6 mandatory
Exempted
23 Jan 2025
30 May 2022
18 Aug 2022
30 May 2022
17 Aug 2022
20 Jun 2022
SUPPLY OF POWER TRANSFORMER Design, construction, assembly, manufacturing, Painting, Inspection, testing of oil filled Power Transformer at vendor’s work. Packing, supply and delivery to site complete with all fittings, accessories and associated equipment which are required for efficient and trouble free operation Supervision of Installation, Testing and Commissioning along with Accessories, Commissioning spares, Special tools & Tackles and Third party Inspection for EPCM-2, P25 PROJECT at IOCL PANIPAT REFINERY as specified in Material Requisition.
Following transformer(s) complete with all accessories in accordance with these specifications. A) TR-118031 & TR-118032: 2 nos Transformers (1 Lot) 1. 66/6.9kV, 25/31.5 MVA, 3-phase, 50Hz, impedance as per data sheet, ONAN/ ONAF rating, Oil immersed, Conservator type transformer, On Load Tap Changer (OLTC), Marshalling Box & Cooling fan control cabinet Transformers shall be supplied with first fill of oil and 10% extra oil in non-returnable drums. 2. RTCC Panel (one per transformer) 3. Online PD Monitoring System for each transformer, complete with all accessories in accordance with this specification. 4.Online De-hydration facility (Online removal of moisture) shall be provided for each transformer with remote monitoring system of all parameters complete with all accessories in accordance with this specification. 5. Portable monitoring, setting, analysis & parameterization tool (Laptop) with Licensed copy of the operating softwares for Online PD Monitoring & online dehydration System
Following transformer(s) complete with all accessories in accordance with these specifications. A) TR-119031 & TR-119032: 2 nos Transformers (1 Lot) 1. 66/6.9kV, 16/20 MVA, 3-phase, 50Hz, impedance as per data sheet, ONAN/ ONAF rating, Oil immersed, Conservator type transformer, On Load Tap Changer (OLTC), Marshalling Box & Cooling fan control cabinet Transformers shall be supplied with first fill of oil and 10% extra oil in non-returnable drums. 2.RTCC Panel (one per transformer) 3.Online PD Monitoring System for each transformer, complete with all accessories in accordance with this specification 4.Online De-hydration facility (Online removal of moisture) shall be provided for each transformer with remote monitoring system of all parameters complete with all accessories in accordance with this specification. 5.Portable monitoring, setting, analysis & parameterization tool (Laptop) with Licensed copy of the operating softwares for Online PD Monitoring & online dehydration System.
Following transformer(s) complete with all accessories in accordance with these specifications. A) TR-119033 & TR-119034: 2 nos Transformers (1 Lot) 1.66/11kV, 25 MVA, 3-phase, 50Hz, impedance as per data sheet, ONAN rating, Oil immersed, Conservator type transformer, Off Circuit Tap Changer (OCTC), Marshalling Box & Cooling fan control cabinet. Transformers shall be supplied with first fill of oil and 10% extra oil in non-returnable drums. 2.RTCC Panel (one per transformer) 3. Online PD Monitoring System for each transformer, complete with all accessories in accordance with this specification. 4.Online De-hydration facility (Online removal of moisture) shall be provided for each transformer with remote monitoring system of all parameters complete with all accessories in accordance with this specification. 5.Portable monitoring, setting, analysis & parameterization tool (Laptop) with Licensed copy of the operating softwares for Online PD Monitoring & online dehydration System.
stage.html
html • 0.04 MB
tech_eval.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.05 MB
Download all tender documents and submit your bid