Loading…
Loading…
| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | L1₹26.9 LAccepted-AOC | L1 | Accepted-AOC Lowest tenderer | |
| 2 | L2₹27.3 L+₹41,045 (1.53%)Rejected-Finance 2549 NATHA SINGH STREET MEHNA MOHALLA BATHINDA PB 151001 | BATHINDA | BATHINDA | PUNJAB | 151001 | L2 | Rejected-Finance Other than lowest tenderer | |
| 3 | L3₹27.5 L+₹60,031 (2.23%)Rejected-Finance NA | NA | NA | 121004 | L3 | Rejected-Finance Other than lowest tenderer | |
| 4 | L4₹28.8 L+₹1.9 L (7.13%)Rejected-Finance | L4 | Rejected-Finance Other than lowest tenderer |
Tender Value
₹25.0 L
EMD Value
₹50,080
Closing Date
9 Oct 2021, 6:00 pmClosed
Maj Aditya Gorhe
GE Utility Bathinda
PROVISION OF THREE PHASE POWER SUPPLY, LT ELECTRIC PANEL, SEMI HIGH MAST LIGHT,SECURITY LIGHT AND SPLIT TYPE AC AT BUILDING NO. P-248(K-I) AT BATHINDA UNDER GE(U) BATHINDA.
2021_MES_459098_3
8577/2021-22/E8
Open Tender
Miscellaneous Works
Item Rate
180 days
Garrison Engineer Utility Bathinda
class D cat b i
9 documents required · 9 mandatory
₹500
Garrison Engineer Utility Bathinda
₹50,080
Yes
23 Oct 2021
18 Sept 2021
11 Oct 2021
18 Sept 2021
9 Oct 2021
25 Sept 2021
Amount
SCHEDULE A PART I Excavation in trenches not exceeding 1.5 metre wide and not exceeding 1.5 metre in depth for foundation, laying of cables or pipes (where provided) and getting out in soft/loose soil including trimming the sides and forming bottom surfaces to required levels complete all as specified and as directed .
Supply and laying or fixing or laid in trenches/ ducts/ through pipes/ in floors / under roads/ hard standing /along poles and testing LT cable XLPE, PVC insulated screened, bedded, galvanised steel strip or wire armourd cable (heavy duty) 1100 volt grade with aluminium conductor having cross sectional area 16 Sqmm 4 core conforming to IS-7098 (Part-I -1988) complete all as specified and as directed.
Supply and laying or fixing or laid in trenches/ ducts/ through pipes/ in floors / under roads/ hard standing /along poles and testing LT cable XLPE, PVC outer sheath Type-1 insulated stranded copper conductor served with and inner sheathing of PVC tape ISI , colour red, yellow, blue and black , armoured with galvanised strip or wire and over all PVC sheathed stranded conductor conforming to IS - 7098 (Part I) with latest amendments of size cross sectional area 120 Sqmm 3.5 Core, 1100 Volts grade heavy duty complete all as specified and as directed by Engineer in charge.
M&L for sand cushioning with coarse sand in trenches for protection of underground electric cable, spread to uniform 23 cm thickness and punned down gently to 18 cm complete all as directed.
Supply and laying un-reinforced precast concrete cable cover, Class LV, Type 1, Flat size 250 mm x 150 mm x 40 mm as in protection layer complete all as specified and directed. Make :- Topaz / Mehtab
Supply and laying well burnt sub class B breicks old size bricks, laid flat dry, in trenches with width of the bricks laid to the axis of cable for cable protection complete all as specified and as directed.
Returning, filling in, including spreading, leveling, watering and well ramming in layers not exc 25cm thick complete all specified and directed.
Removal of surplus excavated soil to a distance not exceeding 50 metre and depositing where directed at a level not exceeding 1.5 metre above the starting point complete all specified and as directed.
Supply and laying or fixing GI tubing light grade 40 mm dia for cable protection including fitting complete with flat iron clamps size of flat iron 25mm x 4mm, nuts, bolts & washers complete fixed to poles / along wall / floor / under road / across the drain or nallah / laid in trench all as specified and directed by Engineer-in charge .
All as per serial item No. 09 above but for GI pipe 80 mm bore.
Supply and laying or fixing 20 mm dia PVC pipe for cable protection including fitting complete with flat iron clamps size of flat iron 25mm x 4mm, nuts, bolts & washers complete fixed to poles / along wall / floor / under road / across the drain or nallah / laid in trench all as specified and directed by Engineer-in charge .
Material and labour for making the hole under road and hard standing for laying and incluidng inserting Galvanised steel light grade pipe upto 80 mm dia including all fittings as required at site by mechanical drill system or Auger system and making the surface good as per existing surface completed all as specified and directed by Engineer-in-Charge. Note : Galvanised steel light grade pipe shall be measured and paid separately under respective item.
Supply, fabricating, installation, testing, commissioning and electrically connecting LT feeder pillar box cubical type of size 60 cm x 40 cm x 30 cm, 415 Volts, factory made, machine pressed, dust and vernim proof, out door type, made with CRCA sheet 3.15 mm thick. Feeder pillar box shall be powder coated with seven tank process for treatment of degrasing, pickling and two coats primer before giving the stove epoxy finish, Front opening with single door with provision of rubber beading and locking system including 100 amp aluminium bus bar set of four with provision of hole on bus bar for fixing of cable mounted on PVC / epoxy insulators and mounted on angle iron legs frame made with angle iron of size 25 mm x 25 mm x 5 mm and legs duly spray painted both internally and externally with two coats of synthetic enamel paint over a coat of red oxide primer, legs grouted in PCC (1:2:4) type B1 using 20 mm graded crushed stone aggregate including necessary earth work , including all provision of opening for incoming / outgoing cables and testing complete all as directed.
Supply, fabricating, installation, testing, commissioning and electrically connecting LT feeder pillar box cubical type of size 60 cm x 40 cm x 30 cm, 415 Volts, factory made, machine pressed, dust and vernim proof, out door type, made with CRCA sheet 3.15 mm thick. Feeder pillar box shall be powder coated with seven tank process for treatment of degrasing, pickling and two coats primer before giving the stove epoxy finish, Front opening with single door with provision of rubber beading and locking system including 320 amp copper bus bar of size 20 x 5 mm or 25 x 4 mm set of four with provision of hole on bus bar for fixing of cable mounted on PVC / epoxy insulators, including MCCB 320 Amp, 4 pole, 415 Volts rating with breaking capacity 50 KA, adustable setting = 80-100% and magneting setting - 01 No. and mounted on angle iron legs frame made with angle iron of size 25 mm x 25 mm x 5 mm and legs duly spray painted both internally and externally with two coats of synthetic enamel paint over a coat of red oxide primer, legs grouted in PCC (1:2:4) type B1 using 20 mm graded crushed stone aggregate including necessary earth work , including all provision of opening for incoming / outgoing cables and testing complete all as directed.
S&F LT cable junction box ,size 200 mm x 160 mm x 98 mm, insulated type , made out with Polycarbonate with glass fiber reinforced with MCB SP 'C' curve 2.5 Amp complete all as directed. Make: Hensel, Cat Part No. KF5255 / Siemens / Legrand/ABB/SCHNIDER. Note :- (i). Manufacturer should submit routine test certificate for CJB/PJB (ii).The Polycarbonate Junction Box shall be environment friendly, recyclabe, UV resistant, halogen & silicon free, anti acid & anti corrosive. (iii). The Junction Box shall be rated for Degree of ingress Protection IP 66 in accordance with IEC 60529. (iv).The gasket material of junction box shall be Polyurethane and the gasket shall be internally embedded. (v).The Junction Box shall be complies with requirements of the standards IEC 60998 - 1, IEC 60670 - 22 & IEC 60670 - 2 - 5. (vi). The Junction Box color according to RAL 9011. (vii).The manufacturer of Junction Box / Enclosure shall submit a copy of IEC Certificate . For beter safety the Polycarbonate enclosure and shall be fire retardant & self - extinguishing in accordance with IEC 60695 - 2 - 11, DIN VDE 0304 Part - 3, UL Subject 94 for Flammability V-2. It should be tested at Glow Wire test for 960 degree Centigrade. The impact strength of Polycarbonate enclosure / boards i.e. the Degree of protection against mechnical load shall be in accordance with EN 50298 - 98 for IK 08.
Earthing complete with GI earth plate electrode of size 60cm x 60cm x 6mm buried directly in ground vertically at a depth not less than 2.25 metre below normal ground level with top edge of earth plate at a depth not less than 1.5 metre below normal ground level sorrounded from all sides by 15cm thick and packed layer of charcoal dust and common salt fliing in alternate layers etc and connected to and including 32 x 6 mm GI strip upto 7.5 mtr by means of bolts, nuts, check nuts and washers made of galvanised iron and protected by light grade 20 mm dia GI pipe connected to main control board and GI pipe medium grade 40 mm bore for watering and including funnel, wire mesh, charcoal salt etc RCC pit cover flush to earth pit 50mm thick reinforced with 8mm TMT bar 100mmC/C and PCC chamber pit with PCC (1:3:6) type C1 (using 20mm graded aggregate) including excavation and earthwork disposal of surplus soil to distance not exceeding 50 metre) and testing after completion all as specified and shown on plate No 3 of SSR Part-I 2009.
Supply and fixing steel tubular swaged pole Single type 410 SP-55, (11 metre long) conforming to IS - 2713 (Part - I & II) including base plate, Final taper plug, bolts,nuts and screws with two coat of aluminium paint over a coat of red oxide primer and bitumen paint of complete pole upto embedded length and painting upto 1.5 mtr with alternate layer of yellow & black including marking Sr No of the poles all as specified. Note:- Necessary earthwork and cement concrete work shall be measured and paid seperately under respective items of schedule.
Material and Labour Pre Stressed concrete Pole 9.00 Mtr long 102 mm x 172 mm at top 102mm x 279 mm at bottom class 10 complying with requirements of IS-1678-1978 including painting of poles with two coats of synthetic enamel paint over a coat of primer with black and white strips 30 cm wide each up to 1.5 mtr height from top of PCC foundation block and numbering of poles complete all as specified and directed by Engineer-in-charge. (PCC for foundations and earth work shall be measured and paid for separately)
M&L for PCC (1:4:8) type D-2 using 40 mm graded crushed stone aggregate as in foundation of electric poles/struts etc including necessary formwork complete all as specified and directed. Note: Volume of poles/struts embedded in concrete shall be deducted during calculation the quantity of PCC for foundation and coping.)
M&L for PCC (1:2:4) type B-1 using 20 mm graded crushed stone aggregate as in coping of electric poles/struts etc including necessary formwork complete all as specified and directed. Note: Volume of poles/struts embedded in concrete shall be deducted during calculation the quantity of PCC for foundation and coping.)
S&F MCB DB including one No. of MCB triple pole and neutral 16 to 32 Amp 10 KA 415 Volts 'C' series including necessary clamps, nut, bolts complete all as directed.
S&F PVC insulated stranded copper conductor cable , sheathed 2.5 Sqmm three core 1100 Volts for connection of street light complete all as specified and directed.
S&F PVC insulated stranded copper conductor cable , sheathed 1.5 Sqmm three core 1100 Volts for connection of street light complete all as specified and directed.
Supply and fixing Street light bracket made out of 40mm dia GI tubing medium grade made to shape 1.5 Mtr long with fixing arrangement for LED fitting duly painted with two coats of synthetic aluminium paint over a coat of primer including two Nos of MS clamps and back plates fabricated from steel section including nuts, bolts, washer etc complete all as specified and directed by Engineer-in-charge.
Supply and fixing Energy efficient LED street light fitting of 60 Watt seasonal LDR with RTC control with dimmable type, including No. of LED bulbs as per manufacturers instructions for lighting of 60 watt , epoxy powder coated pressure die cast aluminium housing to act as heat sink for efficient dissipation of heat and toughened glass with IP 66 degree of protection, system luminous efficency more than 110 lumens / watt individual LED's should have lenses for better throw across and along road, PF>0.9 with voltage range 140 to 270 Volt, fitting should be provided wih inbuilt 10 KV minimum surge protection, with auto cut OFF above 300 V & auto switch ON normal voltage, short circuit and over voltage protection facility for Driver should be potted with electrolytic capacitor of 105 degree also with auto cut OFF above 300 V & auto switch ON normal voltage and fitting incluing making electrical connection for cable connection complete all as directed by Engr-in-Charge. Make HALONIX CAT NO. HLSLD-ML04-60-CWL-DIM / WIPRO LR0260W/HPL CCMSSL60W/HAVELLS CCMSLS60W/C&S INDUS-S60W/PHILIPS CCMSSL60W/CROMPTON SMARTSL60W. Note :- Cable for connection of LED light fitting shall be measured and paid under appropriate item of BoQ.
Supply and fixing energy efficient LED flood light fitting of 120 Watt epoxy powder coated pressure die cast aluminium housing to act as heat sink for efficient dissipation of heat and toughened glass with IP 66 degree of protection, system luminous efficency more than 100 lumens / watt individual LED's should have lenses for better throw across and along road, PF>0.9 with voltage range 140 to 270 Volt, fitting should be provided wih inbuilt 10 KV minimum surge protection, short circuit and over voltage protection facility for Driver Driver should be potted with electrolytic capacitor of 105 degree and fiiting including making electrical connection including bracket of suitable size upto 1.5 mtr long & MS Flat iron clamp, nuts and bolts of suitable size complete all as directed. Make- Polycab/ havells/ Halonix/ Crompton/ C & S/Wipro
Material and Labour Cross arms, bracings, supports, clamps and back plates fabricated from structural steel sections including nuts, bolts, washers, welding, bending cold or hot, drilling holes for bolts, in any shape or size as indicated or directed and inclusive of one primer coat, one under coat and one finishing coat of paint complete all as specified and directed by Engineer-in-charge. Note :- 1. The rate of one primer coat, one under coat and one finishing coat of paint is included in this item and nothing shall be paid extra on this account. 2. Payment shall be measured and paid only as per actual weight of Mild steel items. The weight of primer and paint shall not be considered duing measuerment and payment for this item.
Earthing complete with galvanised steel earth plate electrode 60cm x60cm x6mm thick buried directly in ground earth pit not less than 2.25 mtr deep below normal ground level ) with top edge of plate not less than 1.5m below ground level, connecting to the Galvanised iron earth lead wire 4.0 mm dia , by means of nuts, bolts, check nuts and washer etc of galvanised iron and earth lead protected by provision of GI pipe light grade 32mm bore light grade from earthing test point or main controling switch as directed including providing funnel with 20mm bore GI pipe light grade, wire mesh,charcoal or coke andcommon salt in alternative layer of 15 Cm (compactedd thickness) all round the earth electrode,concrete earth pit in PCC (1:2:4) type B-1 using 20mm graded stone agagregates with 50mm thick cover of RCC (1:2:4) (re-inforced with 8mm dia TMT bar @15 cm C/C bothways and MS bar handle made of 10mm dia bar) including necessary earth work in excavation,returning in and removal of surplus soil to a distance not exceeding 50mtr, all as per electrical plate No 3 of MES Schedule Part-I including earthing pit cover etc. complete all as directed.
SCHEDULE A PART II Supply, installing , testing and commissioning of cooling split type AC 1.5 tonne (indoor / out door unit complete) with star rating 5 (BEE / ISEER rating 2018), inverter technology, cordless remote control unit and with in built air ioniser and plazma filter for better indoor air quality with stand for outdoor unit, 230 Volt, 50 Hz, single Phase complete all as per maunfacturer instruction and direced by Engineer-in-Charge. Make: DAIKIN / HITACHI/ DAIKAIN/ O-GENERAL/ CARRIER/ VOLTAS/ BLUESTAR/ LG/ SAMSUNG/ FEEDERS LLOYD/ GODREJ Note:- Copper pipe, insulation material, PVC clamps , outdoor unit stand and water pipe for condensate as per requirement will be arranged by the contractor and the cost of the same are included in this item and nothing shall be paid extra on this account.
Supply and fixing and testing of 5.00 KVA capacity Voltage stablizer for automatic operation, single phase naturally air cooled , copper wound, indoor type & designed for input variation between 150V - 250V with output voltage stabilized at 230 V with accuracy of ± 2.5% complete all as per manufacturers instructions and directed by Engineer-in-Charge. Make :VINTEK ELECTRONICS (VOLINA) / V GUARD / POWER TECH / AE / GODREJ / VINITEC ELECTRONIC LABORATORY (VINITEC) / BLUE LINE.
Supply and fix Sheet metal enclosure with a two pin and earth plug and socket complete with one single pole MCB up to 32 Amps, 240 volt capacity and tested on completion complete all as specified and as directed. Make : HPL / HAGER / BENTEC INDIA LIMITED (BENTEC/BENLO) / LEGRAND / L&T / C&S ELECTRIC LIMITED (C&S) / BCH ELECTRIC LIMITED / UNIVERSAL SWITCH GEAR CONTROL/ POLY CAB WIRES PVT LIMITED / SCHNEIDER / MDS / HAVELLS INDIA LTD / SHALABH (INDIA) LTD (SHALABH SWITCHGEAR) / INDO ASIAN / NOVATEUR ELECTRICAL & DIGITAL SYSTEMS PVT LTD (INDOASIAN) / HPL ELECTRIC & POWER PVT LIMITED / ABB / SIEMENS.
Material and Labour for Sub main wiring with 2 single core 4 Sqmm , PVC insulated flame retardant low smoke cable with multistranded copper conductor cable ISI marked in and including 20mm dia PVC conduit medium quality conforming to 3537 Part-I & conduit accessories such as Tee , Elbow, junction box, reducer etc. with and including independent PVC insulated one single core 2.5 Sqmm flame retardant low smoke un-sheathed and multistranded copper earth wire complete all as specified. Make of wire : NICCO / FINOLEX / L&T / HAVELLS / RR KABEL LTD / GLOSTER CABLES LIMITED / POLYCAB WIRES PVT LTD (POLYCAB) / KALINGA CABLE & CONDUIT CO. (KALINGA PREMIUM) / BONTON CABLES INDIA PVT LTD (BONTON) / DNEO CABLES PVT LTD (DCAB) / HPL / PLAZA / ANCHOR / PARAGON / RICHA CABLES PVT LTD (RICHA) / KEI INDUSTRIES LTD / BENTEC INDIA LIMITED (BENTEC/BENLO) / BCH ELECTRIC LIMITED / ALCON WIRES & CABLES INDUSTRY Make of PVC Conduit: FINOLEX / SUPREME / PRECISION / TIRUPATI / AKG / PLAZA / POLYCAB WIRES PVT LTD (POLYCAB) / PRESTO PLAST / KALINGA CABLE & CONDUIT CO. (KALINGA PREMIUM) / RICHA CABLES PVT LTD. Notes:- (i) Two lengths of single core 4 Sqmm cable , one length of single core 2.5 Sqmm cable and 20mm dia of PVC conduit will be measured as one length)
Supply and fix MCB single pole 32 Amps, 240 volt capacity , 'C' curve complete all as specified and as directed.
VISHAV CONSTRUCTIONS
NAIB ENTERPRISES
Choice india
stage.html
html • 0.05 MB
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.04 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .