| Sl No | Description | Qty | Unit | JK Electric Engineers Pvt. Ltd. L1 | VINAY CONSTRUCTION COMPANY L2 |
|---|---|---|---|---|---|
| 1.00Description | |||||
| 1.01 | BoQ2 (PRICE SCHEDULE-I for supply of conductor, acessories andallied material) | 1 | Nos. | 3,46,46,442.26 ₹3.5 Cr | 3,68,93,334.79 ₹3.7 Cr |
| 1.02 | BoQ3 (PRICE SCHEDULE-II for Errection testing and commissioning of conductor, acessories andallied material) | 1 | Nos. | 77,70,980.8 ₹77.7 L | 73,15,138.5 ₹73.2 L |
| 1.03 | BoQ4 (PRICE SCHEDULE-III for suppy of material for line bay) | 1 | Nos. | 99,37,582.25 ₹99.4 L | 1,13,50,066 ₹1.1 Cr |
| 1.04 | BoQ2 (PRICE SCHEDULE-IV for errection testing and commissioning) | 1 | Nos. | 7,47,111.25 ₹7.5 L | 9,17,000 ₹9.2 L |
| 1.05 | BoQ2 (PRICE SCHEDULE-V for CIVIL WORKS) | 1 | Nos. | 28,67,080 ₹28.7 L | 26,24,000 ₹26.2 L |
Tender Value
₹5.6 Cr
EMD Value
₹11.2 L
Closing Date
3 Apr 2021, 4:00 pmClosed
Executive Engineer, TLMD-VIII, JKPTCL, Jammu
office of the Executive Engineer, TLMD-VIII, Ambedkar Chowk, Jammu
Stringing of second circuit of 132KV barn-jourian transmission line on already existing double circuit towers of 132 KV S/C Barn-Jourian transmission line along with construction of 132 KV Line bay at 132/33 KV Grid Station Jourian
2021_PDD_118380_1
E NIT no TLMD-VIII/J/31 of 2020-21 dt- 25/02/2021
Open Tender
Electrical Works
180 days
Grid Station kaleeth and TL from barn to kaleeth
Please refer Tender documents.
3 documents required · 3 mandatory
₹10,000
Executive Engineer, TLMD-VIII, JKPTCL, Jammu
₹11.2 L
office of the Executive Engineer, TLMD-VIII, Jammu
8 Apr 2021
26 Feb 2021
5 Apr 2021
26 Feb 2021
3 Apr 2021
26 Feb 2021
5 Mar 2021
Amount
Description
BoQ2 (PRICE SCHEDULE-I for supply of conductor, acessories andallied material)
BoQ3 (PRICE SCHEDULE-II for Errection testing and commissioning of conductor, acessories andallied material)
BoQ4 (PRICE SCHEDULE-III for suppy of material for line bay)
BoQ2 (PRICE SCHEDULE-IV for errection testing and commissioning)
BoQ2 (PRICE SCHEDULE-V for CIVIL WORKS)
Description of Work / Item(s)
Amount
Cost of the conductor and acessories including supply
Phase Plates 3 No Per Tower for S/C
Number Plates 1 No Per Tower
Circuit Plates 1 No. Per Tower for S/C
Bird Guard 3No Per Suspension Tower
Arching horns
Strengthening of Earthing of Towers
Counter Poise 50%
Nuts & Bolts
200 mm² ACSR Conductor,(a) Alumunium=30/3 mm(b) Steel=7/3 mm Overall dia 21mm.Approximate Wt 976Kg/Km Ultimate breaking Load=89.67 KN;including 1.5%sag and jumpering
Conductor Accessories
Mid Span Joints 3 No/Km
Vibration Dampers 2 No/Phase/Tower
Repair Sleeves For Conductor 9 No / Km for D/C
Aluminium Tape 1 No Per Km Of Line
OPGW,Dual window single-Mode with Mode field diameter 8.6-9.5 µm ,cladding diameter 125 µm ±1 µm,1.5% wastage included
OPGW/Earth Wire Accessoreis
Mid Span Joints 2No/Km
Vibration Dampers 2 No / Tower
Insulators
Disc Insulators 70 KN,Ball & Socket type, 145mm height and 255mm dia. Creepage total 430 mm and 260 mm protected. 3 No for S/C,6 No for D/C supension strings per tower @ 10 discs per string +10% for
ii. Disc Insulators 120 KN/90 KN,Ball & Socket type, 145mm height and 280mm dia. Creepage total 430 mm and 260 mm protected. 6 No.for S/C,12 No for D/C tension strings per tower @ 11 discs per string +10% for double string per tower (For 1.95 Towers)
Hardware fittings for conductor
Single Suspension Fittings for panther shall have minimum failing load of 50% ultimate strength of bundle conductors with Forged Steel Hanger free center type without bolt only having slipping strength 15% of ultimate strength of conductor.The ball and socket designation must be 16 mm. (3 No,S/C 6NoD/C Per Sus. Tower)
Single Tension Fittings for panther shall have minimum failing load of 100% ultimate strength of Bundle cnductors with compressive type Tension clamps having slipping strength 95% of ultimate Strength of conductors. The ball and socket designation must be 20mm. 90% (6 NoS/C,12NoD/C Per Ten. Towers)
Double Tension Fittings 10%
Double Suspension Fittings 10%
Hardware fitting for OPGW/Earth wire
Suspension/Tension Clamps S/C
Misc. items
Tag welding of towers
supply of spare 5% of material against S NO. 1 to 10 excluding S No. 2
Description of Work / Item(s)
Amount
Errection testing and commissioning cost of the conductor and acessories
Phase Plates 3 No Per Tower for S/C
Number Plates 1 No Per Tower
Circuit Plates 1 No. Per Tower for S/C
Bird Guard 3No Per Suspension Tower
Arching horns
Strengthening of Earthing of Towers
Counter Poise 50%
Nuts & Bolts
200 mm² ACSR Conductor,(a) Alumunium=30/3 mm(b) Steel=7/3 mm Overall dia 21mm.Approximate Wt 976Kg/Km Ultimate breaking Load=89.67 KN;including 1.5%sag and jumpering
Conductor Accessories
Mid Span Joints 3 No/Km
Vibration Dampers 2 No/Phase/Tower
Repair Sleeves For Conductor 9 No / Km for D/C
Aluminium Tape 1 No Per Km Of Line
OPGW,Dual window single-Mode with Mode field diameter 8.6-9.5 µm ,cladding diameter 125 µm ±1 µm,1.5% wastage included
OPGW/Earth Wire Accessoreis
Mid Span Joints 2No/Km
Vibration Dampers 2 No / Tower
Insulators
Disc Insulators 70 KN,Ball & Socket type, 145mm height and 255mm dia. Creepage total 430 mm and 260 mm protected. 3 No for S/C,6 No for D/C supension strings per tower @ 10 discs per string +10% for
ii. Disc Insulators 120 KN/90 KN,Ball & Socket type, 145mm height and 280mm dia. Creepage total 430 mm and 260 mm protected. 6 No.for S/C,12 No for D/C tension strings per tower @ 11 discs per string +10% for double string per tower (For 1.95 Towers)
Hardware fittings for conductor
Single Suspension Fittings for panther shall have minimum failing load of 50% ultimate strength of bundle conductors with Forged Steel Hanger free center type without bolt only having slipping strength 15% of ultimate strength of conductor.The ball and socket designation must be 16 mm. (3 No,S/C 6NoD/C Per Sus. Tower)
Single Tension Fittings for panther shall have minimum failing load of 100% ultimate strength of Bundle cnductors with compressive type Tension clamps having slipping strength 95% of ultimate Strength of conductors. The ball and socket designation must be 20mm. 90% (6 NoS/C,12NoD/C Per Ten. Towers)
Double Tension Fittings 10%
Double Suspension Fittings 10%
Hardware fitting for Earth wire
Suspension/Tension Clamps S/C
Misc. items
Tag welding of towers
Dismantling of Existing Earth wire and acessories including carriage of the same to the divisional store at Narwal Jammu
Description of Work / Item(s)
Amount
supply of EQUIPMENT and accessories for line bay.
3 pole, SF6 gas filled, out door Circuit Breaker , including all accessories, auxiliaries and marshalling boxes/Kiosks, (145KV, 1250 Amps of 3 phase,50 c/s and 31.5KA for 1 second).
145kV, 50c/s , 2000 Amp, 31.5kA for one second, Ac motor operated horizontal double break, outdoor type 3 pole Isolators without Earthing Blades
145kV, 50c/s , 2000 Amp, 31.5kA for one second, Ac motor operated horizontal double break, outdoor type 3 pole Isolators with One Earthing Blades
145kV, 50c/s , 2000 Amp, 31.5kA for one second, Ac motor operated horizontal double break, outdoor type 3 pole Isolators with Two Earthing Blades
Single phase, 50 c/s 145KV Current Transformers (800-400-200/1-1-1-1-1 A or as per site specifications), 31.5KA for one second, rated dynamic current 100KA(peak), Class A insulation, Burden 20 VA
Single Phase 50 c/s, outdoor metal oxide gapless type, 120KV (rms) Surge Arrestor including Surge counters/monitors, insulating base all associated accessories, auxiliaries.
132KV Control and Relay Panel for Line/Feeder completely wired including Substation automation supporting IEDs/numerical relays inlcuding Distance Recorder
Single phase, 50 c/s 132KV Capacitor Voltage Transformers (132/√3) KV/ (110/√3)V, One min power freq withstand 275KVrms
132KV Post Insulators Solid Core Type, Power Frequency Withstand Voltage 275KVP Dry lightning impulse withstand voltage ± 650 (KVP)
Structures
Galvanised structures
Galvanised Nuts and Bolts
Power and control cables
2 Core, 2.5 sq mm, 1100 V, PVC insulated, PVC sheathed, FRLS, galvanised steel wire/ strip armoured stranded copper conductor control cable complete
5 Core, 2.5 sq mm, 1100 V, PVC insulated, PVC sheathed, FRLS, galvanised steel wire/ strip armoured stranded copper conductor control cable complete
8 Core, 2.5 sq mm, 1100 V, PVC insulated, PVC sheathed, FRLS, galvanised steel wire/ strip armoured stranded copper conductor control cable complete
12 Core, 2.5 sq mm, 1100 V, PVC insulated, PVC sheathed, FRLS, galvanised steel wire/ strip armoured stranded copper conductor control cable complete
16 Core, 2.5 sq mm, 1100 V, PVC insulated, PVC sheathed, FRLS, galvanised steel wire/ strip armoured stranded copper conductor control cable complete
19 Core, 2.5 sq mm, 1100 V, PVC insulated, PVC sheathed, FRLS, galvanised steel wire/ strip armoured stranded copper conductor control cable complete
2 Core, 6 sq mm, 1100 V, PVC insulated, PVC sheathed, FRLS, galvanised steel wire/ strip armoured stranded copper conductor control cable complete
4 Core, 6 sq mm, 1100 V, PVC insulated, PVC sheathed, FRLS, galvanised steel wire/ strip armoured stranded copper conductor control cable Complete
4 Core, 16 sq mm, 1100 V, PVC insulated, PVC sheathed, FRLS, galvanised steel wire/ strip armoured stranded copper conductor control cable complete
Marshalling kiosk with Kiosk frames mild steel structural sections for pressed and shaped cold-rolled sheet steel, thickness not less than 2.0 mm. Frames shall be enclosed in cold-rolled sheet steel of thickness not less than 1.6 mm. Doors and covers shall also be cold rolled sheet steel of thickness not less than 1.6 mm. complete structures shall be rigid, self- supporting, free from flows, twists and bends. Dust and vermin proof construction and shall be provided with a degree of protection of IP: 55, with Copper Bar earthing. Finishing paint on panels shall be of shade 692 (smoke grey) of IS: 5. The inside shall be properly stoved. The paint thickness shall be at least 50 microns.
CONDUCTOR AND HARD WARE FITTINGS
500mm2 ACSR Moose Conductor (a)Aluminium =54/3.53 mm (b) Steel= 7/3.53 mm overall diameter =31.77mm Approx. Wt. =1998 kg/km ultimate strength = 159.60 KN
Single Tension Fittings For Single 500mm2 ACSR shall have minimum failing load of 100% ultimate strength of Bundle conductors with compressive type Tension clamps having slipping strength 95% of ultimate Strength of conductors. The ball and socket designation must be 20mm Minimum Ultimate strength (Tensile strength) shall be 70 KN.
Single Suspension Fittings For Single 500mm2 conductor shall have minimum failing load of 50% ultimate strength of bundle conductors with Forged Steel Hanger free center type without bolt only having slipping strength 15% of ultimate strength of conductor.The ball and socket designation must be 20mm.
Single Tension Fittings For Twin 500 mm2 ACSR shall have minimum failing load of 100% ultimate strength of Bundle conductors with compressive type Tension clamps having slipping strength 95% of ultimate Strength of conductors. The ball and socket designation must be 20mm. Minimum Ultimate strength (Tensile strength) shall be 70 KN.
Single Suspension Fittings For Twin 500mm2 conductor shall have minimum failing load of 50% ultimate strength of bundle conductors with Forged Steel Hanger free center type without bolt only having slipping strength 15% of ultimate strength of conductor.The ball and socket designation must be 20mm.
Disc Insulators 120 KN,Ball & Socket type, 145mm height and 280mm dia Creepage total 430 mm and 260 mm protected.
Disc Insulators 70 KN,Ball & Socket type, 145mm height and 255mm dia Creepage total 430 mm and 260 mm protected.
T Clamps 500mm2 /500mm2, made of Alluminium Alloy and shall comply in all respects with IS:5561-1970 (latest edition)
T Clamps Twin 500mm2 / Twin 500mm2 , made of Alluminium Alloy and shall comply in all respects with IS:5561-1970 (latest edition)
P I Clamps made of Alluminium Alloy and shall comply in all respects with IS:5561-1970 (latest edition)
P G Clamps made of Alluminium Alloy and shall comply in all respects with IS:5561-1970 (latest edition)
Earth Wire 7/3.15mm
Earthwire Tension Clamps comprise of compression type tension clamp with two ‘D’ shackles, jumper terminals, nuts & bolts and washers etc.slip strength shall not be less than 95% of the ultimate strength of the ground wire. Conductivity shall not be less than corresponding length of GSS
CABLE TRAYS/CABLE RACKS/ACCESSORIES
Cable Trays of size 400mm x 3000mm made of M.S angles 40x40x6mm,40x6 Flat.
Cable Trays of size 300mm x 2500mm made of M.S angles 40x40x6mm,40x6 Flat.
Lugs, Ferrules, Welding Material, Cotton Waste etc
Description of Work / Item(s)
Amount
Errection, testing and commissioning of EQUIPMENT and accessories for line bay.
3 pole, SF6 gas filled, out door Circuit Breaker , including all accessories, auxiliaries and marshalling boxes/Kiosks, (145KV, 1250 Amps of 3 phase,50 c/s and 31.5KA for 1 second).
145kV, 50c/s , 2000 Amp, 31.5kA for one second, Ac motor operated horizontal double break, outdoor type 3 pole Isolators without Earthing Blades
145kV, 50c/s , 2000 Amp, 31.5kA for one second, Ac motor operated horizontal double break, outdoor type 3 pole Isolators with One Earthing Blades
145kV, 50c/s , 2000 Amp, 31.5kA for one second, Ac motor operated horizontal double break, outdoor type 3 pole Isolators with Two Earthing Blades
Single phase, 50 c/s 145KV Current Transformers (800-400-200/1-1-1-1-1 A or as per site specifications), 31.5KA for one second, rated dynamic current 100KA(peak), Class A insulation, Burden 20 VA
Single Phase 50 c/s, outdoor metal oxide gapless type, 120KV (rms) Surge Arrestor including Surge counters/monitors, insulating base all associated accessories, auxiliaries.
132KV Control and Relay Panel for Line/Feeder completely wired including Substation automation supporting IEDs/numerical relays inlcuding Distance Recorder
Single phase, 50 c/s 132KV Capacitor Voltage Transformers (132/√3) KV/ (110/√3)V, One min power freq withstand 275KVrms
132KV Post Insulators Solid Core Type, Power Frequency Withstand Voltage 275KVP Dry lightning impulse withstand voltage ± 650 (KVP)
Structures
Galvanised structures
Galvanised Nuts and Bolts
Power and control cables
2 Core, 2.5 sq mm, 1100 V, PVC insulated, PVC sheathed, FRLS, galvanised steel wire/ strip armoured stranded copper conductor control cable complete
5 Core, 2.5 sq mm, 1100 V, PVC insulated, PVC sheathed, FRLS, galvanised steel wire/ strip armoured stranded copper conductor control cable complete
8 Core, 2.5 sq mm, 1100 V, PVC insulated, PVC sheathed, FRLS, galvanised steel wire/ strip armoured stranded copper conductor control cable complete
12 Core, 2.5 sq mm, 1100 V, PVC insulated, PVC sheathed, FRLS, galvanised steel wire/ strip armoured stranded copper conductor control cable complete
16 Core, 2.5 sq mm, 1100 V, PVC insulated, PVC sheathed, FRLS, galvanised steel wire/ strip armoured stranded copper conductor control cable complete
19 Core, 2.5 sq mm, 1100 V, PVC insulated, PVC sheathed, FRLS, galvanised steel wire/ strip armoured stranded copper conductor control cable complete
2 Core, 6 sq mm, 1100 V, PVC insulated, PVC sheathed, FRLS, galvanised steel wire/ strip armoured stranded copper conductor control cable complete
4 Core, 6 sq mm, 1100 V, PVC insulated, PVC sheathed, FRLS, galvanised steel wire/ strip armoured stranded copper conductor control cable Complete
4 Core, 16 sq mm, 1100 V, PVC insulated, PVC sheathed, FRLS, galvanised steel wire/ strip armoured stranded copper conductor control cable complete
Marshalling kiosk with Kiosk frames mild steel structural sections for pressed and shaped cold-rolled sheet steel, thickness not less than 2.0 mm. Frames shall be enclosed in cold-rolled sheet steel of thickness not less than 1.6 mm. Doors and covers shall also be cold rolled sheet steel of thickness not less than 1.6 mm. complete structures shall be rigid, self- supporting, free from flows, twists and bends. Dust and vermin proof construction and shall be provided with a degree of protection of IP: 55, with Copper Bar earthing. Finishing paint on panels shall be of shade 692 (smoke grey) of IS: 5. The inside shall be properly stoved. The paint thickness shall be at least 50 microns.
CONDUCTOR AND HARD WARE FITTINGS
500mm2 ACSR Moose Conductor (a)Aluminium =54/3.53 mm (b) Steel= 7/3.53 mm overall diameter =31.77mm Approx. Wt. =1998 kg/km ultimate strength = 159.60 KN
Single Tension Fittings For Single 500mm2 ACSR shall have minimum failing load of 100% ultimate strength of Bundle conductors with compressive type Tension clamps having slipping strength 95% of ultimate Strength of conductors. The ball and socket designation must be 20mm Minimum Ultimate strength (Tensile strength) shall be 70 KN.
Single Suspension Fittings For Single 500mm2 conductor shall have minimum failing load of 50% ultimate strength of bundle conductors with Forged Steel Hanger free center type without bolt only having slipping strength 15% of ultimate strength of conductor.The ball and socket designation must be 20mm.
Single Tension Fittings For Twin 500 mm2 ACSR shall have minimum failing load of 100% ultimate strength of Bundle conductors with compressive type Tension clamps having slipping strength 95% of ultimate Strength of conductors. The ball and socket designation must be 20mm. Minimum Ultimate strength (Tensile strength) shall be 70 KN.
Single Suspension Fittings For Twin 500mm2 conductor shall have minimum failing load of 50% ultimate strength of bundle conductors with Forged Steel Hanger free center type without bolt only having slipping strength 15% of ultimate strength of conductor.The ball and socket designation must be 20mm.
Disc Insulators 120 KN,Ball & Socket type, 145mm height and 280mm dia Creepage total 430 mm and 260 mm protected.
Disc Insulators 70 KN,Ball & Socket type, 145mm height and 255mm dia Creepage total 430 mm and 260 mm protected.
T Clamps 500mm2 /500mm2, made of Alluminium Alloy and shall comply in all respects with IS:5561-1970 (latest edition)
T Clamps Twin 500mm2 / Twin 500mm2 , made of Alluminium Alloy and shall comply in all respects with IS:5561-1970 (latest edition)
P I Clamps made of Alluminium Alloy and shall comply in all respects with IS:5561-1970 (latest edition)
P G Clamps made of Alluminium Alloy and shall comply in all respects with IS:5561-1970 (latest edition)
Earth Wire 7/3.15mm
Earthwire Tension Clamps comprise of compression type tension clamp with two ‘D’ shackles, jumper terminals, nuts & bolts and washers etc.slip strength shall not be less than 95% of the ultimate strength of the ground wire. Conductivity shall not be less than corresponding length of GSS
CABLE TRAYS/CABLE RACKS/ACCESSORIES
Cable Trays of size 400mm x 3000mm made of M.S angles 40x40x6mm,40x6 Flat.
Cable Trays of size 300mm x 2500mm made of M.S angles 40x40x6mm,40x6 Flat.
Lugs, Ferrules, Welding Material, Cotton Waste etc
Description of Work / Item(s)
Amount
Civil works including material in all respect
Cable Ducts With Covers
Main Duct of Size 1200mm x 1200mm with 6 mm M.S Chequered Trench Covers of size 1300x500 mm
Main Duct of Size 1200mm x 1200mm with 75mm Concrete Covers grade M15 of size 1300x500 mm
Sub Main Duct of Size 600mm x 600mm with 75mm Concrete Covers grade M15 of size 700x500 mm
Tee off Duct: 150mm sand filled HDPE pipes from Sub main to Equipments in the outdoor area
Earth Mat (40mm dia steel bars) as per approved design, Galavanised Iron (75mm x 12mm/ 50mm x 6 mm) risers for Equipment and Structural Earthing
Concreting of yard
Concreting of yard & Laying Of Gravel including beep holes and other allied works
CIVIL WORKS
Laying of 132KV Column foundations (as per Drawing)
Laying of 132KV Isolator foundations (as per Drawing)
Laying of 132KV SF6 Breaker foundations (as per Drawing)
Laying of 132KV CT foundations (as per Drawing)
Laying of 132KV PT/CVT foundations (as per Drawing)
Laying of 132KV LA foundations (as per Drawing)
Laying of 132KV Post Insulator foundations (as per Drawing)
VINAY CONSTRUCTION COMPANY
VINAY CONSTRUCTION COMPANY
JK Electric Engineers Pvt. Ltd.
VINAY CONSTRUCTION COMPANY
VINAY CONSTRUCTION COMPANY
JK Electric Engineers Pvt. Ltd.
stage.html
html • 0.03 MB
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Tendernotice_1.pdf
PDF • 0.74 MB
SBDNIT31.pdf
Tender Documents • 9.19 MB
BOQ_227267.xls
BOQ • 0.42 MB
Download all tender documents and submit your bid