Chief Engineer Leh
HQ CE Leh Zone c/o 56 APO
PROVN OF CENTRALIZE HEATING SYSTEM (CHS) IN KLP ACCOMMODATION OF 22 WEU AT LEH
2023_MES_573846_2
180079/E8
Open Tender
Electrical and Maintenance Works
Lump-sum
715 days
LEH
As per tender documents
10 documents required · 10 mandatory
₹3,000
GE (I) (P) No. 1 LEH
₹6.2 L
Yes
30 Aug 2023
18 May 2023
15 Jul 2023
18 May 2023
6 Jul 2023
22 Jun 2023
18 May 2023 - 24 May 2023
Amount
NOTES : (i) Please refer Schedule 'A' Notes of tender documents. (ii) Schedule ‘A’ Part - I to X are Prepriced by MES. Bidders shall insert their lumpsum amount in the Green coloured field under Col-6 only. (iii) In case rate of any item is not quoted by the bidder, the rate for the same shall be considered as zero and no claim shall be entertained in this regard at a later stage.
SCHEDULE 'A' Part - I (BUILDINGS) Lump Sum price worked out by the Contractor for "Buildings" as listed in Schedule 'A' Part-I.
SCHEDULE 'A' Part - II (INTERNAL WATER SUPPLY ) Lump sum price worked out by the Contractor for "Internal Water Supply" as listed in Schedule 'A' Part-II.
SCHEDULE 'A' Part - III (INTERNAL ELECTRIFICATION ) Lump sum price worked out by the Contractor for "Internal Electrification" as listed in Schedule 'A' Part-III.
SCHEDULE 'A' Part - IV (TILING FOR FLOOR HEATING) Lump sum price worked out by the Contractor for "Tiling for Floor Heating" as listed in Schedule 'A' Part-IV.
SCHEDULE 'A' Part - V (MISC B/R WORK IN EXISTING BUILDING) Lump sum price worked out by the Contractor for "Misc B/R work in Existing Building" as listed in Schedule 'A' Part-V.
SCHEDULE 'A' Part - VI (ROAD / PATH ) Lump sum price worked out by the Contractor for "Road/ Path" as listed in Schedule 'A' Part-VI.
SCHEDULE 'A' Part - VII (SEWAGE DISPOSAL ) Lump sum price worked out by the Contractor for "Sewage Disposal" as listed in Schedule 'A' Part-VII.
SCHEDULE 'A' Part - VIII (EXTERNAL WATER SUPPLY) Lump sum price worked out by the Contractor for "External water supply" as listed in Schedule 'A' Part- VIII.
SCHEDULE 'A' Part - IX (EXTERNAL ELECTRIFICATION) Lump sum price worked out by the Contractor for "External Electrification" as listed in Schedule 'A' Part- IX.
SCHEDULE 'A' Part - X (EXCAVATION AND EARTHWORK) Lump sum price worked out by the Contractor for "Excavation and Earthwork" as listed in Schedule 'A' Part- X.
SCHEDULE 'A' PART - XI (MISCELLENEOUS B/R AND E/M ITEMS) Note : This schedule is not prepriced by MES and the rate indicated as "Rs. 0.00" under column 5 signifies this fact only. Bidder shall insert their rates in the Green coloured field under Column 6.
Supply and fixing 13mm thick nitrile rubber insulation of conductivity class "0", on pipe of size 25mm outer dia. alongwith 28 SWG Aluminium sheet Cladding complete all as specified.
Supply and fixing LED light fitting 1x 40W, 220V, 6500 K lighting fixture with high lumen output, environmental friendly, energy efficient ready to use pack AC decorative box type with driver, holder including LED tube light of same capacity connecting up with three core flexible copper conductor cable of size 1.5 sqmm from ceiling rose complete all as specified and directed. Make :- Havells Cat No. LHEXACP7IN1J040 / equivalent model of Wipro/ Philips/ Crompton
S&F LED security light, pressure die cast, aluminum housing, 30 watts capacity, 240V, IP 65 class, with suitable in-built electronic driver complete including fixed on a bracket made out of 3 mtr long medium grade GI pipe 40 mm dia. bent to shape as directed fitted on wall at a height not less than 6 mtr from ground with MS clamp, nuts and bolts and washers as required at site and including connecting luminaire to the nearest ceiling rose/junction box with 1.5 sqmm PVC insulated 3 core wire complete all as directed and specified. Make :- Havells Cat No. LHEXAYP7PN6K030 / equivalent model of Wipro/ Philips/ Crompton NOTE - Cost of all minor spares and jobs required for fixing of light fixture on wall and for electrical connections are deemed to be included in the quoted rate.
M & L for taking down Aluminium shutter of any description of size exceeding 1 sqm & not exceeding 2 sqm each complete, and bring it in the size of opening after disassemble all rails and styles and cutting glass so that size of aluminium members be intact and refixing the same including refixing of all new / old iron mongry (hinges, sliding bolt, tower bolt etc) complete all as specified
S&F Door seal strip fixing to door bottom including all necessary pasting & screw etc complete all as specified.
M&L for Valve pit of size (150 x 150 x 150 cm) (inner dimensions) consisting of random rubble uncoursed stone masonary in cement mortar 1:6, 50 mm thick coping with PCC 1:2:4 type B1 (using 20 mm graded stone aggregate) incl excavation and earth work and disposal of surplus soil to a distance not exc 50 mtr and depositing where all as directed by Engr-in-Charge, plastering internally with 15 mm thick in cement motor 1:6 and flush pointing externally in the same mortar as work proceeeds and mild steel sheet cover (3.15 mm thick) angle iron frame of 50x50x6 mm, handle and locking arrangement incl foldable wooden plank midway mounted on angle iron frame of 50x50x5 mm and painting with two coats of synthetic enamel paint over a coat of red oxide primer on steel surface complete all as specified and directed by Engr-in-charge.
Supplying and laying or passing through pipe, P.V.C. insulated unsheathed bright annealed bare copper conductor industrial cables & PVC insulated, PVC round sheathed multicore industrial Cables for voltage grade upto 1100 V. as per IS 694:1990. of size 1.5 Sq mm nominal cross sectional area and 4 core laid in trenches and pipes, clamp on wall and pole, making good distrubed surface as existing surface complete all as specified and as directed by the Engineer-in-Charge. (For FCU Connections from DG Set in Plant Room)
Supplying and laying or passing through pipe, P.V.C. insulated unsheathed bright annealed bare copper conductor industrial cables & PVC insulated, PVC round sheathed multicore industrial Cables for voltage grade upto 1100 V. as per IS 694:1990. of size 4Sq mm nominal cross sectional area and 4 core laid in trenches and pipes, clamp on wall and pole, making good distrubed surface as existing surface complete all as specified and as directed by the Engineer-in-Charge. (For FCU Connections from DG Set in Plant Room)
Supplying and laying or passing through pipe, P.V.C. insulated unsheathed bright annealed bare copper conductor industrial cables & PVC insulated, PVC round sheathed multicore industrial Cables for voltage grade upto 1100 V. as per IS 694:1990. of size 4 Sqmm nominal cross sectional area and 3 core laid in trenches and pipes, clamp on wall and pole, making good distrubed surface as existing surface complete all as specified and as directed by the Engineer-in-Charge. (For FCU Connections from DG Set in Plant Room)
Supply and fix mounting bracket for street light bent to shape as per requirement made of 40 mm bore medium grade GI tubing 3mtr long including clamp nuts, bolts and washers all as required at site or complete all as specified and as directed by the Engineer-in-Charge.
Supply, installation, testing and commissioning LT panel of suitable size as per IE rule and latest IS, factory made dust and vermin proof outdoor type made out of 3.15 mm thick CRCA sheet including seperate compartment for each MCCB & for cable and busbar, mounted on frame of MS angle iron 40mmx40mmx6 mm with front and back openable door with lock & Key including necessary grouting and double coat powder coated of grey colour painting complete with following accessories.The degree of protection of panel shall be IP-54 CPRI approved including foundation all as specified and directed including the following :- (Near Transformer at MRS) [a] MCCB 100 Amps 25 KA Four pole 415 volts with thermal setting - 01 No (i/c)
Supply and fix ON load change over switch 415 Volts in sheet metal enclosure 4 pole of capacity 100 Amps, Uro load (Position= Main Supp + DG Supp + Neutral) complete all as specified and directed.
S & F precast PCC 1:2:4 type B-2, Cable route indicator of size 15 cm x 15cm x 75 cm in dimensions with projection of 45cm above ground level and 30cm grouted in PCC 1:3:6 type C-2 foundation, the exposed surface shall be painted with brown colour above ground and HT 11000 Volt/ LT 1100 Volt marked in red colour all as specified and directed. Note:- Rate quoted by the contractor is deemed to be included for the earth work and PCC foundation etc.
Material and Labour for horizontal boring underground of dia. 100 mm bore for road crossing 3 mtr to 10 mtr and not exceeding 1.5 mtr in depth for laying of electric cable and GI tubing in soft/loose soil complete all as specified.
Supply and installation of 1200 litres capacity (MOC-LLDP) Septic tank for 8 to 10 users along with inlet, outlet, vent, internal piping, manhole cover, plastic media and all civil works like PCC of 150mm at base of pit, back filling work with sand and excavation complete all as specified. Make - Sintex product code-PWTS-AM-120-01
Supply and installation of 1200 litres capacity (MOC-LLDP) Soak pit tank for 8 to 10 users along with inlet, outlet, vent, internal piping, manhole cover, plastic media and all civil works like PCC of 150mm at base of pit, back filling work with sand and excavation complete all as specified. Make - Sintex product code - Soak pit 120-01
M & L for 200mm (OD) /170 mm (ID) diameter DWCPE (SN8) pipes, laid and jointed in trenches on concrete bed and jointed complete all as specified. Note :- Excavation, earth work and concrete bed shall be measured and paid separately.
SCHEDULE 'A' PART - XII (CENTRAL HEATING SYSTEM) Note : This schedule is not prepriced by MES and the rate indicated as "Rs. 0.00" under column 5 signifies this fact only. Bidder shall insert their rates in the Green coloured field under Column 6.
OIL FIRED BOILER Supply, installation, Testing & Commissioning of oil fired glycol based Hot Water Generator using Kerosene/HSD oil complete with combustion chamber fire tubes and equipment automatic monoblock burner assembly fire tubes, control panel with sequence controller, photo cell for flame failure, HT transfer electrodes, blower assembly, electric panel, mounting frame, pressure gauges at inlet and outlet suitable for operation on 50 Hz, 3/1 phase 415/220 Volts AC supply including suitable size of foundation as per manufacturer recommendation. Hot water inlet temp.=65 °C Hot water outlet temp.= 75 °C Make: (Make of Boiler : Riello / Thermax / Ecoflam/ Rapid Cool / Western ) (Make of Burner : Riello/ Ecoflam / Benton / Nuway) Note : (i) All the necessary accessories including essential safety measures as per Norms reqd for proper functioning of Hot water Generator shall be deemed to be included in quoted rate. (ii) Installation to be done as per Manufacturer's recommendation with all required accessories i.e foundation, base frame, vibration isolator, insulation etc as recommended by manufacturer, capacity at MSL and ambient temperature.
Plant 1 Capacity: 2,00,000 Kcal/Hr at MSL ( Out of 3 - Two Working & One standby)
Plant 2 Circuit 1 Capacity: 4,00,000 Kcal/Hr at MSL ( Out of 3 - Two Working & One standby)
Plant 2 Ciruit 1 Capacity: 2,00,000 Kcal/Hr at MSL (One Working)
Plant 2 Circuit 2 Capacity: 2,00,000 Kcal/Hr at MSL (Out of 3 - Two Working & One standby)
PRIMARY GLYCOL CIRCULATION CENTRIFUGAL PUMPS: Supply, installation, testing & commissioning of monoblock centrifugal pumps driven by suitable capacity electric motor coupled, suitable to operate on AC supply 415 volts, 3 Phase, 50 Hz and mechanical seal for ethylene glycol water mixture solution of 25 Mtr head complete with accessories including floating cement concrete foundation and isolation pads and all as specified and directed of follwing flow rate. Make : Armstrong / Grundfoss/ Wilo / Salomson Note :- Item to be suitable to operate under the climatic conditions of site.
200 LPM 25 Mtr head (Plant 1) (Two working one standby)
500 LPM 25 Mtr head (Plant 2 Circuit 1) (Two working one standby)
180 LPM 25 Mtr head (Plant 2 Circuit 2) (Two working one standby)
SECONDARY GLYCOL CIRCULATION CENTRIFUGAL PUMPS: Supply, installation, testing & commissioning of monoblock centrifugal pumps driven by suitable capacity electric motor coupled, suitable to operate on AC supply 415 volts, 3 Phase, 50 Hz and mechanical seal for ethylene glycol water mixture solution of 25 Mtr head complete with accessories including floating cement concrete foundation and isolation pads and all as specified and directed of 400 LPM flow rate. Make : Armstrong / Grundfoss/ Wilo / Salomson Note :- Item to be suitable to operate under the climatic conditions of site.
120 LPM 25 MTR head for Officers accomd I and II, CO residence, Servant Qtr, and Officers Mess 3 Nos (Two working one standby) (Plant 1 circuit 1)
80 LPM 25 MTR head for IPC Block (1 Nos one working one standby) (Plant 1 Circuit 2)
450 LPM 25 MTR head for ORS living, Cook House dining hall) (Two working one standby ( Plant 2 Circuit 1)
80 LPM 25 MTR head for JCOs accomd ( 1 No working one stanby) ( Plant 2 Circuit 2)
180 LPM 25 MTR Head for Qtr Guard and RHQ center 3 Nos (Two working One Standby) ( Plant 2 circuit 2)
Heat exchanger (PHE) : Supply, installation, testing & commissioning of plate type two circuits heat exchanger complete with all accessories suitable with the following operating characterastics. The plate of PHE shall be SS grade 316 of minimium 0.5 mm thick, with MS frame shall be 80 x 40 mm MS channel and size of frame shall be as per the size of pump, required 13 mm thick insulation, making connections all incoming and outgoing pipings complete as required and as specified. (circulation media 55% glycol and 45% water mixture) Primary Circuit :- i) Inlet gycol temperature : 75 Degree Centrigrade ii) Outlet gycol temperature : 65 Degree Centrigrade Secondary Circuit :- i) Inlet gycol water mixture 55 : 45, temperature : 55 Degree Centrigrade ii) Outlet gycol temperature : 45 Degree Centrigrade The PHEs shall be complete with three way diverting valve and thermostat. Following Rated heat exchange Capacity :
Rated heating capacity : 200000 kcal/hr (Plant 1) for Officers Accomd II, CO Residence, Servant Qts, Officers Mess, Officers Accomd I
Rated heating capacity : 40000 kcal/hr (Plant 1) for IPC Block
Rated heating capacity : 430000 kcal/hr (Plant 2) For S/L accomodation, Dinning Hall.
Rated heating capacity : 30000 kcal/hr (Plant 2) for JCOs accomadation
Rated heating capacity : 170000 kcal/hr (Plant 2) for RHQ center and Qtr Guard
GLYCOL MAKE UP CENTRIFUGAL PUMPS: Supply , installation, testing and commissioning of mono block Centrifugal Pump with Bronze impeller, driven by suitable capacity electric motor coupled, suitable to operate on AC supply 220 volts, single Phase, 50 Hz for glycol fluid make up and mixing complete with accessories including cement concrete foundation suitable for a flow rate of 5 LPM and 5 mtr head (One Working & One standby) . Note :- Item to be suitable to operate under the climatic conditions of site.
FLUE GAS CHIMNEY: Supply and installation of MS flue gas chimney for 2 lac kcal boiler shall be 200mm dia 3 mm thick pipe complete with 5mm thick base plate and 400mm dia cowl for 4 lac kcal/hr Boiler 250mm dia 3mm thick pipe complete with 5mm thick base plate and 600mm dia cowl minimum 1.2 m above the highest point of the plant room and including connection from boiler to main chimney fabricated from 3 mm MS sheet. The item shall be complete with the mounting/ fixing arrangement. The generators shall be connected to a independent chimney. The portion of the chimney in side the building shall be insulated with fiber glass insulation wool of 24kg/cum. The item shall be complete with mounting/fixing arrangement 200 mm for 2 Lac kcal boiler and 300mm for 4 lac kcal boiler.
EXPANSION TANK: Supply & Installation of overhead expansion tank of size 1000 Litres MS 3mm thick sheet complete covered with 13 mm closed cell Nitrile insulation complete with removable lid, in/out /drain/ overflow system mounting arrangement and complete connection.
Supply & Installation of overhead expansion tank of size 500 Litres MS 3mm thick sheet complete covered with 13 mm closed cell Nitrile insulation complete with removable lid, in/out /drain/ overflow system mounting arrangement and complete connection
GLYCOL FLUID TANK. Supply & Installation of External tank 1000 Liters capacity 3mm thick MS Tank shall be mounted on 50mm dia MS pipe legs welded to the tank and the height of the tank above ground shall be 400mm Complete with removable lid, in/ out/ drains/ overflows system, mounting arrangement and complete with connection.
BULK OIL STORAGE TANK: Supply, installation, testing connecting with the system and commissioning of Horizontal Cylindrical oil storage tank made out of mild steel. Design temperature 30 deg C and design pressure atmosphere + static head of liquid Storage Cap.(Nominal): 10 KL Gross capacity (Not exceeding : 10.2 KL) Shell thickness : 4 mm End Plate Thickness: 6 mm Tank shall be complete with manhole, lifting lugs, vent pipe dip stick inlet out let connections including excavation as per manufacturer recommendation, partially burring under ground and excavation will not be paid separately. Note : The tank and structure shall be painted with two coats of black Japan anti corrosive paint.
DAY OIL STORAGE TANK: Supply, installation, testing and commissioning of Kerosene/HSD oil Day service Tank rectangular MS construction with capacity of 990 Litres complete with inlet, outlet, drain, level indicator and dip stick with level chart. Tank will be made out of 3mm MS sheet and will be provided with supports made out of iron angle 50x50x5 mm thick base stage to keep tank at minimum ( 800 mm) above finished floor level.
TRANSFER GEAR OIL PUMPS K.OIL (SELF PRIMING) : Supply, installation, testing and commissioning of Rotary gear transfer pumps for capacity 15 LPM 10 Mtr head for K. Oil complete with base frame, foundation bolts, coupling and coupling guard and TEFC Flame Proof motor (1HP), and other accessories required for commissioning including cement concrete foundation. (One Working & One standby)
HSD OIL PIPING: Supply, installation, testing and commissioning of M.S. pipe including bends, reducers, flanges, nuts, bolts etc. complete in all respects of following sizes as under :-
40 mm dia pipe
25 mm dia pipe
Ball valves of sizes 25 mm
Non Return Valve 25mm
Y-Oil Strainer 25mm
Ball Valves 40 mm dia
Ball valves of sizes 15 mm
HOT GLYCOL FLUID PIPING Supplying and laying, connecting, fixing and testing of M S ERW ‘C’ class piping complete with fittings, duly insulated with closed cell elastomeric insulation 30 to 40 Kg/m³ density covered with shrink wrap polythene sheet for the following sizes of Hot Glycol fluid pipes complete all as specified and directed. Pipes running outside will be burried 1.2 mt below the ground level, cost of excavation and refilling will be paid saperately.
150 mm dia pipe insulated with 25 mm thick nitrile insulation
100 mm dia pipe insulated with 25 mm thick nitrile insulation
80 mm dia pipe with 25 mm thick nitrile insulation
65 mm dia pipe with19 mm thick nitrile insulation
50 mm dia pipe with19 mm thick nitrile insulation
40 mm dia pipe with19 mm thick nitrile insulation
32 mm dia pipe with13 mm thick nitrile insulation
25 mm dia pipe with13 mm thick nitrile insulation
25 mm dia PPR pipe
20 mm dia PPR pipe
HOT GLYCOL FLUID PIPING VALVES AND FITTINGS Supplying and laying, connecting, fixing and testing of Valve and fittings for the following sizes of Hot Glycol fluid pipes
Butterfly valves 150 mm
Butterfly valves 100 mm
Butterfly valves 80 mm
Butterfly valves 65 mm
Butterfly valves 50 mm
Butterfly valves 40 mm
Dual plate Non Return Valves 100 mm dia
Dual plate Non Return Valves 80 mm dia
Dual plate Non Return Valves 50 mm dia
Balancing Valves 100 mm dia
Balancing Valves 80 mm dia
Balancing Valves 65 mm dia
Balancing Valves 50 mm dia
Balancing Valves 40 mm dia
Ball valves 25 mm dia
Y Strainer 100 mm dia
Y Strainer 80 mm dia
Y Strainer 50 mm dia
Inlet/outlet valves of required size for FCUs / towel rad
Pressure gauges with cocks and syphon
Water flow switches
Automatic air purgers valves
Inlet/outlet copper /pex connection of size 12mm 2mtr length
GLYCOL CHARGE : Supply and first fill for makeup requirement for the first year of operation of glycol along with the necessary additives to be mixed with glycol as inhibitor (composed of a mixture of 5% sodium benzoate +0.03% sodium nitrate in 25% ethylene glycol) effective in preventing corrosion of metals at both room temperature and conditions of heating and supplied in barrels.
RADIANT HEATING FROM SLAB (Manifold to Manifold) : Supplying, Installing, testing & commissioning of followings for radiant heating system. PE-Xa pipe (Polyethylene cross linked pipe) of 16 mm O.D. with 2 mm thickness with anti-oxygen barrier in EVOH, complying with ENISO-15875 PE-Xa pipes to be embedded in slab. The pipes shall be fixed on 25 mm thick EPS insulation and embedded in light weight PCC 55 mm thick with centre to centre distance between PE-Xa pipes should be 100 mm. PE-Xa pipes shall be fixed with clips / Accessories as per Manufacturer's standard & details. The PE-Xa pipes should be complete as per specifications.
Supply and fix PE-Xa pipe (polyethylene cross link pipe) and other related accessories with oxygen diffusion barrier manufactured from peroxide cross linked polyethylene complying with EN ISO 15875. size 16 mm OD x 2mm thick.
Supply and fix Plastic track fixed in floor insulation for fixing Pipes complete all as specified and directed.
Supply and fix Pipe clips in between tracks complete all as specified and directed.
Supply and fix Cable ties all as specified and directed.
Supplying, Installing, testing & commissioning of followings for radiant heating system. Manifold with Box and Accessories (i) Manifolds Modular type brass/ SS manifolds for supply and return of glycol water mixture, each manifold box shall be with below mentioned required number of connections for radiant circuit with compression fittings. Supply manifold with bayonet connection to have flow control lock shield valve and adaptor connections. Return Manifold with Bayonet connection, balancing lock shield valve and adaptor connection. Modular type manifolds will be fixed by metallic adjustable brackets in powder coated manifold boxes. Manifolds shall have inlet and outlet Ball shut-off valve, pressure gauge, Automatic air vent valve, Valve for the system charge and discharge. Motorized by pass valve with digital thermostat will be provided for temperature control. The manifold valves shall comply to EN ISO 9001:2015, ISO 14001:2015, ISO 45001 and ISO 50001:2018 standards. ii) Manifold Box GI Powder coated & cabinet openable for operation & Maintenance. Size should be fixed to accommodate assembly mentioned below.
a) suitable for 2 +2 Loops
b) suitable for 3+3 Loops
c) suitable for 4+4 Loops
d) suitable for 5+5 Loops
e) Three way control valve with thermostat
Floor Insulation - EPS 25 mm thick - 30 kg/m3 density. The insulation shall be provided above slab in each room where Pex pipes shall be installed. Insulation shall be laid on cleaned floor Aluminised polythene sheet of 90 gsm to be provided above polystyrene and complete as per specificaton.
Wall Insulation - Insulation strip with adhesive 100 mm x 8 mm. And complete as per specificaton.
Supplying and laying plain cement concrete 1:3:6 using 10mm graded stone aggregate 60 mm thick embeding the radiant pipes
Manifold Box with accessories Manifold Box GI 1 mm Powder coated & cabinet openable for operation & Maintenance. Size should be fixed to accommodate assembly mentioned below.
suitable for 2 Loops
suitable for 3 Loops
suitable for 4 Loops
suitable for 5 Loops
CABLE TRAYS: Fabricating and installing 1.6 mm thick M.S. perforated Cable trays including horizontal and vertical bends, reducers, tees, cross members and other accessories as required and duly suspended from the ceiling with M.S. suspenders and including painting ( For cabling work in plant room) size 150 mm width x 50mm depth all as specified and as directed.
Supplying and laying on cable tray PVC round sheathed multicore industrial cable of size 3 core 6 Sq.mm (Copper conductor) 1100 V grade as per IS 694 : 1990 with glands and thimbles for connections all as specified and as directed.
Supplying and laying on cable tray PVC round sheathed multicore industrial cable of size 4 core 4 Sq.mm (Copper conductor) 1100 V grade as per IS 694 : 1990 with glands and thimbles for connections all as specified and as directed.
Supplying and laying on cable tray PVC round sheathed multicore industrial cable of size 4 core 1.5 Sq.mm (Copper conductor) 1100 V grade as per IS 694 : 1990 with glands and thimbles for connections all as specified and as directed.
ELECTRICAL ACCESSORIES Providing and fixing 6 SWG dia G.I. wire on surface of in recess for loop earthing interconnecting main panel and other electrical equipment
Providing and fixing M.V. danger notice plate of 200 mm x 150 mm, made of mild steel at least 2mm thick and vitreous enameled white on both sides and with inscription in signal red color on front side as required.
Providing “ No Smoking “ and “ Flammable” sign board as per requirement of Petroleum Rules and CCOE Nagpur).
Supply and fix Notice board ( Display Board) of size 1200 mmx 900 mm all as per TD drg No. CEDZ/ TD-1042/ 2011 dated 01/12/2011 for displaying the duty roaster description and including resuscitation chart in three languages for electric shock and burn injury complete all as specified and directed
FAN COIL UNITS Supplying, installing, testing and commissioning of decorative wall mounted fan coil units complete with EPS body Copper tube aluminium finned coil centrifugal fan decorative type, Direct driven fan (three speed) motor 230 volts AC supply, single phase, 50 Hz, unit to be equipped with remote control for ON/ OFF, speed control, swing control and LCD temperature display including making all connections for FCU of following capacity :-
Cap 6000 Kcal/hr
Cap 4500 Kcal/hr
Cap 3000 Kcal/hr
Supply and fix M.S. powder coated Towel Radiator of size 1100mm x 900mm all as specified and directed. Make :- Myson/ Mektek / Demarld
METAL CLADING : Providing and fixing of aluminium clading of 24 SWG on insulated pipes of following sizes (for exposed pipes and plant room only)
150 mm dia of pipe
100 mm dia of pipe
80 mm dia of pipe
65 mm dia of pipe
50 mm dia of pipe
40 mm dia of pipe
SCHEDULE 'A' PART - XIII (DG SET) Note : This schedule is not prepriced by MES and the rate indicated as "Rs. 0.00" under column 5 signifies this fact only. Bidder shall insert their rates in the Green coloured field under Column 6.
Supply, installation, test and commissioning of silent, Diesel engine driven factory assembled, floor mounted generating set of capacity 125KVA at NTP 0.8 power factor or nearest higher size, 3 phase, 4 wire, 50 Hz as per IS 10001/ 10002 and Alternator as per IS: 13364 to take 10% overload complete with safety control and metering equipments mounted on & including common base frame with acoustic enclosure (canopy), weather proof as per CPCB norms, powder coated all as per manufacturer's instructions manual and all as specified and comprising of the items/ accessories listed hereinafter :-
(A) Prime Mover : Directly coupled diesel engine, water cooled for deriving 125 KVA capacity, alternator electric start, four stroke confirming to latest IS-10001/10002 for continuous running and capable for taking 10% over load for 01 hour complete with following accessories :- (i) Fly wheel to suit flexible coupling. (ii) Flexible coupling with guards. (iii) Air cleaner with filters. (iv) Lubricating oil filter (v) Heavy duty radiator assembly with fan. (vi) Anti-vibration pads as recommended by manufacturers. (vii) PT pump with electronic gevernor of suitable capacity. (viii) Self starter 12 volts DC. (ix) Necessary arrangement for charging battery.
(x) Maintenance free battery 12 volts, 180 AH, duly charged -02 Nos, as recommended by manufacturer alongwith flexible copper battery lead and connector. Make :- Exide / Supersonic / Amaron (xi) Battery rack made out of MS angle iron 40 mm x 40 mm x 5 mm & 150 mm height - 01 No. (xii) Standard safety device. (xiii) Daily services fuel tank for full running capacity of DG set for min 12 hours enclosed within the canopy all as per CPCB with lever indicator inlet, fuel outlet drain plug, air vent and locking arrangements etc including fuel pipe connections with connected GI pipe medium grade from fuel tank to DG set and over flow from the DG set to fuel tank complete with gate valve.
(xiv) Exhaust system shall be provided with thermal insulation by using fire retardant/ non igniting foam conforming to BS-4735 to prevent excess heat radiation on the engine and safe for operator. (xv) Mechanical panel having following accessories :- (aa) Digital Lubrication oil temperature guage - 01 No. (ab) Digital Lubrication oil pressure guage - 01 No. (ac) Digital Water temperature guage - 01 No. (ad) Starting switch with key - 01 No. (ae) Battery voltmeter. (af) Indicator lamp etc. (ag) Digital Ammetar DC-01 No. (ah) Digital RPM meter-01 No. (aj) Safety measures:- (i) Low lubricant oil pressure trip. (ii) High coolent temp trip.(iii) Engine over speed trip.(iv) Battery charging alternator.(v) Emergency stop pressed.
(B) Alternator : Self regulated 3 phase with neutral 415 volts 50 Hz as per IS : 13364 complete with automatic voltage regulator and foot mounted including making cable connection. (C) Control AMF Panel: AMF control panel inside the floor mounted accoustic enclosure suitable for 125 KVA DG set with bypass assessment including all necessary operating and control device (to meet the requirement of above capacity plus 25% over load) such as contactors, MCCBs, CTs, volts meter, Ammeter, indicating lamp, frequency meter, energy meter with protection fuses for panel instrument battery charging ststem with indicator and cut off relays low and high oil pressure, high speed over load and earth fault protection, reverse current protection duly wired copper conductor cable and cable connection with lugs/thimbles complete as recommended by manufacturers and as directed.
(D) Repair tools and 2 years maintenance spare parts as per following :- Repair Tools :- (i) Ring spanner set of 10 - 01 set. (ii) Screw driver 6”, 8”, 12”, 14” & 24”- 02 each (iii) Double End Spanner set of 10 - 01 set. (iv) Adjustable spanner 12” – 04 Nos. (v) Cutting pliers – 01 No. (vi) Techo meter- 01 No. (vii) Tools kit box (only box) – 01 No. 2 Years' Spares :- (a) Fan belt set complete - 01 No (b) Lub oil filter - 01 Set (c) Fuel filter - 01 Set (d) Service manual and spare part catalog with guarantee card (e ) Shock treatment chart dully framed - 01 Set (f) First Aid Box - 01 set (g) Fire extinguisher foam type - 01 set (h) Fire extinguisher (Class 'A' &Class 'B' Type ) - 01 set. Engine Make :- Kirloskar Green Model No. 6K1080TA G2 / Mahindra Powerol / Cummins / Catter Pillar Alternator Make :- Kirloskar Electric / Crompton Greaves / Catter Pillar / Volvo
(E) ACOUSTIC ENCLOSURE :- Acoustic enclosure (canopy) suitable for 125 KVA DG shall be with the following provisions/ specifications :- (i) The enclosure fabricated out of CRCA sheet of 14 SWG suitable to accommodate the DG Set properly. (ii) The sheet metal components are hot dip seven tank pretreated. (iii) It is pure polyester based powder coated (inside as wall as outside). All nuts/bolts/hardwares are zinc coated with salt spray test as per ASTMB- 117. (iv) Battery is accommodated in a tray in the enclosure. (v) The doors are fitted with gasket with high quality EPON gasketed to avoid leakage of sound.
(vi) Sound proofing of enclosure is done with high quality rock wool/mineral wool conforming to IS 8131 of 50 mm thickness and density of 96 kg/cum. (vii) The wool is further covered with fiber glass cloth and perforated powder coated sheet, insulation level conforming to UL 94 HF1 class flamability. (viii) A special residential silencer is provided within the enclosure to control exhaust noise. (ix) Specially designed alternators are provided to control sound at air entry to the container and exhaust from the container. (x) Adequate ventilation is provided to meet requirement for combustion and heat removal. If required a blower is used to meet total air requirement and air changes.
(xi) Temperature of enclosure does not exceed beyond 50 degree C of ambient temperature. (xii) The enclosure is provided with “high enclosure temperature” safety device. (xiii) There is provision of emergency shutdown from out side the enclosure. (xiv) There is arrangement for proper illumination inside the canopy. (xv) Noise level is 75 DB (A) at 1 mtr distance. (xvi) Approved by CPCB.
Note :- (i) The quoted rate for DG Set is inclusive of PCC foundation. The foundation for DG Set should be made of PCC 1:2:4 type B1 using 20mm graded stone aggregates below the floor level minimum 300mm and 200 mm above floor platform and of suitable size as per manufacturers recommendations complete all as directed by Engineer-in-Charge. (ii) The DG Set shall be suitable to suit the climatic conditions of Leh, Ladakh which is (-30°C to +25°C) so as to give desired output including 10% over load. (iii) The DG Set shall be suitable for auto main failure function. (iv) AMF panel should of same manufacturer as that of DG Set or as recommended by manufacturer's Vendors and it should be CPRI approved. (v) The DHPP (fuel) required for testing of DG sets is deemed to be included in above quoted rate. (vi) Phase-I test will be carried out by Engineer-in-charge for no load and 100% load for 1 hour each and phase II test will be carried out in presence of SE/EI/IEM for no load, 25%, 50%, 75%, 100% for 11 hours and 110% for 1 hour over load.
M/S HIGHLAND ENGINEERING
NAFREF ENGINEERS PVT LTD
stage.html
html • 0.05 MB
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.04 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .