Mr. SUSHANT DESHPANDE
thyssenkrupp Uhde India Pvt Ltd (Formerly thyssenkrupp Industrial Solutions India Pvt Ltd)Vikhroli Mumbai India
Supply of AC UPS SYSTEM WITH BATTERIES FOR MSB UNIT FOR NREP as per Technical Specifications for Numaligarh Refinery Limited, Assam, INDIA.
2023_NRL_784292_1
TK-1P22A-MP-RFQ-0042
Open Tender
Miscellaneous Goods
Supply
300 days
Numaligarh Refinery Limited Assam
Please refer Tender documents
8 documents required · 8 mandatory
₹0
Exempted
5 Jun 2024
7 Dec 2023
20 Feb 2024
7 Dec 2023
19 Feb 2024
21 Dec 2023
7 Dec 2023 - 20 Dec 2023
Design, detail engineering, procurement, manufacturing,FAT, testing & inspection, packing, forwarding and supply till site including Commissioning spares, Special Tools & Tackles ,Consumables and Accessories in accordance with this specification including interface with Condition Monitoring System (CMS) & Electrical Control System (ECS) for Following AC UPS SYSTEM WITH BATTERIES FOR MSB UNIT as per specification in MR
Tag No. 1U64-SRR6-UPS-501: a) 200 kVA, 115 V, 50 Hz, 1 Phase, Parallel Redundant UPS with Common Static Type Stabilized Bypass supply, Redundant Ni-Cd Battery Bank (100% capacity each, back-up 200kVA for 0-30 min & 35kVA from 31-120min), ACDB, Battery isolator box with MCCB (flameproof suitable for Gas Group IIC), Battery bank stand, Interconnection cables from Battery charger to Battery bank and suitable termination arrangement with flameproof (Ex-d) nickel plated brass DC cable gland on either sides. Cell Booster(1 Lot) Cell booster: Input supply 240 V±10% AC, 50±3%Hz Output Voltage: 0-12 V DC Rating: 0.2 X Ah of cell Note:Cell booster shall be supplied with 10mtrs. long flexible copper conductor. Condition Monitoring System as per Specifications forabove UPS System(1 Lot)
Tag No. 1U64-SRR6-UPS-501: b) 225 kVA, 115 V, 50 Hz, 1 Phase, Parallel Redundant UPS with Common Static Type Stabilized Bypass supply, Redundant Ni-Cd Battery Bank (100% capacity each, back-up 225kVA for 0-30 min & 35kVA from 31-120min), ACDB, Battery isolator box with MCCB (flameproof suitable for Gas Group IIC),Battery bank stand, Interconnection cables from Battery charger to Battery bank and suitable termination arrangement with flameproof (Ex-d) nickel plated brass DC cable gland on either sides. Cell Booster(1 Lot) Cell booster: Input supply 240 V±10% AC, 50±3%Hz Output Voltage: 0-12 V DC Rating: 0.2 X Ah of cell Note:Cell booster shall be supplied with 10mtrs. long flexible copper conductor. Condition Monitoring System as per Specifications forabove UPS System(1 Lot)
Charges for SITE Supervision of Erection / Installation and Testing for SUPPLY OF AC UPS WITH BATTERIES FOR MSB UNIT FOR NREP PROJECT as per MR
Per diem charges for upto 8 hours work on normal working days.
Overtime rate / hour beyond normal 8 hours work on normal working days.
Overtime rate / hour for work on weekly off days / holidays (as applicable to Refinery site).
Charges for Training at Vendor Works for AC UPS WITH BATTERIES FOR MSB UNIT as specified in MR
Per diem charges for upto 8 hours work on normal working days.
Charges for Training at site for AC UPS WITH BATTERIES FOR MSB UNIT as specified in MR
Per diem charges for upto 8 hours work on normal working days.
Description of Work / Item(s)
Amount
BREAK-UP OF TOTAL MANDATORY SPARES PRICES SUPPLY OF AC UPS SYSTEM WITH BATTERIES FOR MSB UNIT FOR NREP- Tag No. 1U64-SRR6-UPS-501 (a) 200 kVA, 115 V, 50 Hz
BREAK-UP OF TOTAL MANDATORY SPARES PRICES SUPPLY OF AC UPS SYSTEM WITH BATTERIES FOR MSB UNIT FOR NREP- Tag No. 1U64-SRR6-UPS-501 b) 225 kVA, 115 V, 50 Hz
Description of Work / Item(s)
Amount
BREAK-UP OF TOTAL TWO YEARS OPERATIONAL SPARES PRICES SUPPLY OF AC UPS SYSTEM WITH BATTERIES FOR MSB UNIT FOR NREP- Tag No. 1U64-SRR6-UPS-501 (a) 200 kVA, 115 V, 50 Hz
BREAK-UP OF TOTAL TWO YEARS OPERATIONAL SPARES PRICES SUPPLY OF AC UPS SYSTEM WITH BATTERIES FOR MSB UNIT FOR NREP- Tag No. 1U64-SRR6-UPS-501 b) 225 kVA, 115 V, 50 Hz
Description of Work / Item(s)
Amount
Design, detail engineering, procurement, manufacturing, testing & inspection, packing, forwarding and supply till site including Commissioning spares, Special Tools & Tackles ,Consumables and Accessories in accordance with this specification including interface with Condition Monitoring System (CMS) & Electrical Control System (ECS) for Following AC UPS SYSTEM WITH BATTERIES FOR MSB UNIT as per specification in MR
Tag No. 1U64-SRR6-UPS-501: a) 200 kVA, 115 V, 50 Hz, 1 Phase, Parallel Redundant UPS with Common Static Type Stabilized Bypass supply, Redundant Ni-Cd Battery Bank (100% capacity each, back-up 200kVA for 0-30 min & 35kVA from 31-120min), ACDB, Battery isolator box with MCCB (flameproof suitable for Gas Group IIC), Battery bank stand, Interconnection cables from Battery charger to Battery bank and suitable termination arrangement with flameproof (Ex-d) nickel plated brass DC cable gland on either sides. Cell Booster Cell booster: Input supply 240 V±10% AC, 50±3%Hz Output Voltage: 0-12 V DC Rating: 0.2 X Ah of cell Condition Monitoring System as per Specifications forabove UPS System
Tag No. 1U64-SRR6-UPS-501: b) 225 kVA, 115 V, 50 Hz, 1 Phase, Parallel Redundant UPS with Common Static Type Stabilized Bypass supply, Redundant Ni-Cd Battery Bank (100% capacity each, back-up 225kVA for 0-30 min & 35kVA from 31-120min), ACDB, Battery isolator box with MCCB (flameproof suitable for Gas Group IIC),Battery bank stand, Interconnection cables from Battery charger to Battery bank and suitable termination arrangement with flameproof (Ex-d) nickel plated brass DC cable gland on either sides. Cell Booster Cell booster: Input supply 240 V±10% AC, 50±3%Hz Output Voltage: 0-12 V DC Rating: 0.2 X Ah of cell Condition Monitoring System as per Specifications forabove UPS System
Description of Work / Item(s)
Amount
ADDITION / DELETION Unit rates for addition / deletion of following for ACDB feeders if required to be operated later due to detailed engineering changes
6A, 1 phase, SFU Feeder complete with fixed module
10A, 1 phase, SFU Feeder complete with fixed module
16A, 1 phase, SFU Feeder complete with fixed module
20A, 1 phase, SFU Feeder complete with fixed module
32A, 1 phase, SFU Feeder complete with fixed module
63A, 1 phase, SFU Feeder complete with fixed module
80A, 1 phase, SFU Feeder complete with fixed module
100A, 1 phase, SFU Feeder complete with fixed module
125A, 1 phase, SFU Feeder complete with fixed module
250A, 1 phase, SFU Feeder complete with fixed module
450A, 1 phase, SFU Feeder complete with fixed module
Hitachi Hi-Rel Power Electronics Pvt. Ltd.
Hitachi Hi-Rel Power Electronics Pvt. Ltd.
Vertiv Energy Pvt Ltd
Hitachi Hi-Rel Power Electronics Pvt. Ltd.
Hitachi Hi-Rel Power Electronics Pvt. Ltd.
stage.html
html • 0.03 MB
tech_eval.pdf
boq_comp_chart.xlsx
xlsx
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.04 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .