Tender Value
₹3.1 Cr
EMD Value
₹3.9 L
Closing Date
11 Feb 2022, 6:00 pmClosed
CWE
HQ 136 WORKS ENGINEERS PIN - 914136 C/O 99 APO
UPGRADATION OF EXISTING E/M INFRASTRUCTURE FOR POWER HOUSE AND RENEWAL REPLACEMENT OF BER E/M EQUIPMENTS UNDER GE GANGTOK
2021_MES_497648_1
CWE/136-WE/44 OF 2021-22
Open Tender
Electrical and Maintenance Works
Item Rate
364 days
Gangtok
Class A, Category b(ii)
8 documents required · 8 mandatory
₹2,000
GE Gangtok
₹3.9 L
Yes
10 Mar 2022
27 Dec 2021
12 Feb 2022
27 Dec 2021
11 Feb 2022
29 Jan 2022
27 Dec 2021 - 7 Jan 2022
Amount
Dismantling 2 pole structure and remove from existing location to Store Yard of MES complete all as specified and directed.
Dismantling 4 pole structure and remove from existing location to Store Yard of MES complete all as specified and directed.
Dismantling 6 pole structure and remove from existing location to Store Yard of MES complete all as specified and directed.
Dismantling complete including disconnecting the existing Transformer from 2-pole structure from all connections and accessories and shifting the Transformers from existing location to Store Yard of MES all as specified and directed.
Dismantling complete including disconnecting the existing DG Set from all connections and accessories and shifting the DG Set from existing location to Store Yard of MES all as specified and directed.
Dismantling complete including disconnecting the existing Voltage Stabilizers from all connections and accessories and Shifting the Voltage Stabilizers from existing location to Store Yard of MES all as specified and directed.
Supply, install, testing and commissioning of 11 KV Outdoor type RMU, one-side extensible IP67 type with internal copper bus bars, consisting of fixed type Motorized operated Load Break Switch-02 No as incomer and fixed type Motorized operated Vacuum Circuit Breaker-05 Nos as outgoing (CCVVVVV). All live parts, bus bars of RMU should be enclosed in tank to avoid multiple inter connections & sealed for life robotically for three sides and one side Motorized welded non magnetic / non ferrite / stainless steel tank Grade 304 of minimum 2.5 mm thick having IP 67 degree of protection filled with SF6 gas to fulfill the requirement as per IEC 60376, 60376 & 603760 B as insulation with leakage rate less than 0.1% per year tested as per IEC 62271-200. The unit shall have front cable entry for ease of installation. RMU should be complete with all accessories such as Terminal boots, VPIS, cable supports, all front cable terminations, mechanical indications ON/OFF, Manometer as per with IEC standards 62271-200, 60056, 60129, 60265, 60298, 60420, 60529 and 60694. Altitude of installation up to 2000 as per IEC 60120. The unit shall include the following with all necessary standard fitting required at site. RMU should be tested for an internal arc fault of 21kA for 1 sec for tank as per IEC62271-200 and paint shade and thickness should be 70-80 microns, complete all as specified and as directed. The outer enclosure shall cover the full length of the switch gear, to ensure IP55 protection for full door covering of complete switchgear. (Srl item No 7.00 is hereby continued as Srl item No 7.01 to 7.07)
RMU should be provided with maintenance free battery, charger (24V DC) and capacitor bank for emergency delivering for trip system complete with suitable capacity of ammeter and voltmeter incoming connections with 2.5 sqmm FRLS insulated copper conductor cable as required.
The unit shall include the following with all necessary standard fittings as required at site and incorporating the following accessories :
(a) 2 No. Incomer - LBS : (i) 630A Load Break Switch module for making of fault current alongwith Earth Switch of full making capacity. (ii) Short time breaking current - 21KA/ 3 sec. Making Capacity - 52.5KA (iii) Internal Arc - 21kA/1 sec for tank (iv) Nominal operating gas pressure - 1.3(minimum) Bar abs. (v) Power frequency withstand voltage - 28KV (vi) Impulse withstand voltage - 75KV (vii) Outdoor Enclosure - IP54 (viii) Front cover mechanism - IP2X (ix) Cable covers - 3X (x) Gas pressure manometer (with red & green zones) (xi) Cable box for front termination of the cable suitable upto 3 core 120 Sqmm, 11 KV XLPE cable (xii) Operation Counter (xiii) Fault Passage Indicator (Short circuit + Earth Fault) (xiv) Capacitive voltage indication fixed type system (xv) Stored Energy mechanism for Motorized operation (xvi) Ronis Key Interlock (if required) (xvii) Suitable site replaceable Cable bushings (xviii) Arc proof cable covers with self Interlocking mechanism between doors, earth switch, disconnector & VCB (xix) Right angle boots (push on type) (xx) Micropressor based numerical relay with O/L, E/F and S/C protection
(b) 5 nos. Outgoing - VCB: (i) 630A Vacuum Circuit Breaker module (ii) Short time current - 21KA/ 3 sec (iii) Internal Arc - 21kA/1 sec for tank (iv) Nominal operating gas pressure - 1.3(minimum) Bar abs. (v) Power frequency withstand voltage - 30KV (vi) Impulse withstand voltage - 81KV (vii) Outdoor Enclosure - IP67 (viii) Front cover mechanism - IP 5X (ix) Cable covers - 3X (x) Stored Energy mechanism for Motorized operation (xi) Cable box for front termination of the cable suitable upto 3 core 120 Sqmm, 11 KV XLPE cable (xii) Suitable site replaceable Cable bushings (xiii) Arc proof cable covers with self Interlocking mechanism between doors, earth switch, disconnector & VCB (xiv) Capacitive voltage indication fixed type system (xv) Digital Indications for breaker ON, OFF, EARTH, TRIP, Spring Charged-Discharged (xvi) Right angle boots (push on type) (xvii) Protection CT - 40-80/1A, Cl- 5P10, 2.5VA burden
(c) One No. Operation Handle for Motorized Operation (d) One No. Manometer. (h) Safety Interlocks Shall be provided as per relevant IEC/IS Standards and Manufacturers directions. (j) Above switchgear shall confirm to all relevant IEC/IS Standards. (e) Operation and instruction mannual with drawings - 01 Set. (f) All cable bushing should be replaceable type. (g) Module should be accommodated as per manufacture's design. (i) Necessary interlocking arrangement for safety and operations Vacuum Interrupter should be of make as below. Cable box should be arc proof with bolted door and interlocked with respective earthing switches. Doors should be removable for the ease access to terminate cables.
Note :- Rate Quoted by the firm for this item should include the cost of the following:-
(i) PCC work/ any civil work for foundation required for errection of VCB and other accessories all as standard norns. (MAKE: L&T/ABB/ Siemens/ Schnieder)
Supply, install, testing and commissioning of 11 KV Outdoor type RMU, one-side extensible IP67 type with internal copper bus bars, consisting of fixed type Motorized operated Load Break Switch-01 No as incomer and fixed type Motorized operated Vacuum Circuit Breaker-04 Nos as outgoing (CVVVV). All live parts, bus bars of RMU should be enclosed in tank to avoid multiple inter connections & sealed for life robotically for three sides and one side Motorized welded non magnetic / non ferrite / stainless steel tank Grade 304 of minimum 2.5 mm thick having IP 67 degree of protection filled with SF6 gas to fulfill the requirement as per IEC 60376, 60376 & 603760 B as insulation with leakage rate less than 0.1% per year tested as per IEC 62271-200. The unit shall have front cable entry for ease of installation. RMU should be complete with all accessories such as Terminal boots, VPIS, cable supports, all front cable terminations, mechanical indications ON/OFF, Manometer as per with IEC standards 62271-200, 60056, 60129, 60265, 60298, 60420, 60529 and 60694. Altitude of installation up to 2000 as per IEC 60120. The unit shall include the following with all necessary standard fitting required at site. RMU should be tested for an internal arc fault of 21kA for 1 sec for tank as per IEC62271-200 and paint shade and thickness should be 70-80 microns, complete all as specified and as directed. The outer enclosure shall cover the full length of the switch gear, to ensure IP55 protection for full door covering of complete switchgear. (Srl item No 8.00 is hereby continued as Srl item No 8.01 to 8.07)
RMU should be provided with maintenance free battery, charger (24V DC) and capacitor bank for emergency delivering for trip system complete with suitable capacity of ammeter and voltmeter incoming connections with 2.5 sqmm FRLS insulated copper conductor cable as required.
The unit shall include the following with all necessary standard fittings as required at site and incorporating the following accessories :
(a) 1 No. Incomer - LBS : (i) 630A Load Break Switch module for making of fault current alongwith Earth Switch of full making capacity. (ii) Short time breaking current - 21KA/ 3 sec. Making Capacity - 52.5KA (iii) Internal Arc - 21kA/1 sec for tank (iv) Nominal operating gas pressure - 1.3(minimum) Bar abs. (v) Power frequency withstand voltage - 28KV (vi) Impulse withstand voltage - 75KV (vii) Outdoor Enclosure - IP54 (viii) Front cover mechanism - IP2X (ix) Cable covers - 3X (x) Gas pressure manometer (with red & green zones) (xi) Cable box for front termination of the cable suitable upto 3 core 120 Sqmm, 11 KV XLPE cable (xii) Operation Counter (xiii) Fault Passage Indicator (Short circuit + Earth Fault) (xiv) Capacitive voltage indication fixed type system (xv) Stored Energy mechanism for Motorized operation (xvi) Ronis Key Interlock (if required) (xvii) Suitable site replaceable Cable bushings (xviii) Arc proof cable covers with self Interlocking mechanism between doors, earth switch, disconnector & VCB (xix) Right angle boots (push on type) (xx) Micropressor based numerical relay with O/L, E/F and S/C protection
(b) 4 nos. Outgoing - VCB: (i) 630A Vacuum Circuit Breaker module (ii) Short time current - 21KA/ 3 sec (iii) Internal Arc - 21kA/1 sec for tank (iv) Nominal operating gas pressure - 1.3(minimum) Bar abs. (v) Power frequency withstand voltage - 30KV (vi) Impulse withstand voltage - 81KV (vii) Outdoor Enclosure - IP67 (viii) Front cover mechanism - IP 5X (ix) Cable covers - 3X (x) Stored Energy mechanism for Motorized operation (xi) Cable box for front termination of the cable suitable upto 3 core 120 Sqmm, 11 KV XLPE cable (xii) Suitable site replaceable Cable bushings (xiii) Arc proof cable covers with self Interlocking mechanism between doors, earth switch, disconnector & VCB (xiv) Capacitive voltage indication fixed type system (xv) Digital Indications for breaker ON, OFF, EARTH, TRIP, Spring Charged-Discharged (xvi) Right angle boots (push on type) (xvii) Protection CT - 40-80/1A, Cl- 5P10, 2.5VA burden
(c) One No. Operation Handle for Motorized Operation (d) One No. Manometer. (h) Safety Interlocks Shall be provided as per relevant IEC/IS Standards and Manufacturers directions. (j) Above switchgear shall confirm to all relevant IEC/IS Standards. (e) Operation and instruction mannual with drawings - 01 Set. (f) All cable bushing should be replaceable type. (g) Module should be accommodated as per manufacture's design. (i) Necessary interlocking arrangement for safety and operations Vacuum Interrupter should be of make as below. Cable box should be arc proof with bolted door and interlocked with respective earthing switches. Doors should be removable for the ease access to terminate cables.
Note :- Rate Quoted by the firm for this item should include the cost of the following:-
(i) PCC work/ any civil work for foundation required for errection of VCB and other accessories all as standard norns. (MAKE: L&T/ABB/ Siemens/ Schnieder)
Supply, install, testing and commissioning of 11 KV Outdoor type RMU, one-side extensible IP67 type with internal copper bus bars, consisting of fixed type Motorized operated Load Break Switch-01 No as incomer and fixed type Motorized operated Vacuum Circuit Breaker-03 Nos as outgoing (CVVV). All live parts, bus bars of RMU should be enclosed in tank to avoid multiple inter connections & sealed for life robotically for three sides and one side Motorized welded non magnetic / non ferrite / stainless steel tank Grade 304 of minimum 2.5 mm thick having IP 67 degree of protection filled with SF6 gas to fulfill the requirement as per IEC 60376, 60376 & 603760 B as insulation with leakage rate less than 0.1% per year tested as per IEC 62271-200. The unit shall have front cable entry for ease of installation. RMU should be complete with all accessories such as Terminal boots, VPIS, cable supports, all front cable terminations, mechanical indications ON/OFF, Manometer as per with IEC standards 62271-200, 60056, 60129, 60265, 60298, 60420, 60529 and 60694. Altitude of installation up to 2000 as per IEC 60120. The unit shall include the following with all necessary standard fitting required at site. RMU should be tested for an internal arc fault of 21kA for 1 sec for tank as per IEC62271-200 and paint shade and thickness should be 70-80 microns, complete all as specified and as directed. The outer enclosure shall cover the full length of the switch gear, to ensure IP55 protection for full door covering of complete switchgear. (Srl item No 9.00 is hereby continued as Srl item No 9.01 to 9.07)
RMU should be provided with maintenance free battery, charger (24V DC) and capacitor bank for emergency delivering for trip system complete with suitable capacity of ammeter and voltmeter incoming connections with 2.5 sqmm FRLS insulated copper conductor cable as required.
The unit shall include the following with all necessary standard fittings as required at site and incorporating the following accessories :
(a) 1 No. Incomer - LBS : (i) 630A Load Break Switch module for making of fault current alongwith Earth Switch of full making capacity. (ii) Short time breaking current - 21KA/ 3 sec. Making Capacity - 52.5KA (iii) Internal Arc - 21kA/1 sec for tank (iv) Nominal operating gas pressure - 1.3(minimum) Bar abs. (v) Power frequency withstand voltage - 28KV (vi) Impulse withstand voltage - 75KV (vii) Outdoor Enclosure - IP54 (viii) Front cover mechanism - IP2X (ix) Cable covers - 3X (x) Gas pressure manometer (with red & green zones) (xi) Cable box for front termination of the cable suitable upto 3 core 120 Sqmm, 11 KV XLPE cable (xii) Operation Counter (xiii) Fault Passage Indicator (Short circuit + Earth Fault) (xiv) Capacitive voltage indication fixed type system (xv) Stored Energy mechanism for Motorized operation (xvi) Ronis Key Interlock (if required) (xvii) Suitable site replaceable Cable bushings (xviii) Arc proof cable covers with self Interlocking mechanism between doors, earth switch, disconnector & VCB (xix) Right angle boots (push on type) (xx) Micropressor based numerical relay with O/L, E/F and S/C protection
(b) 3 nos. Outgoing - VCB: (i) 630A Vacuum Circuit Breaker module (ii) Short time current - 21KA/ 3 sec (iii) Internal Arc - 21kA/1 sec for tank (iv) Nominal operating gas pressure - 1.3(minimum) Bar abs. (v) Power frequency withstand voltage - 30KV (vi) Impulse withstand voltage - 81KV (vii) Outdoor Enclosure - IP67 (viii) Front cover mechanism - IP 5X (ix) Cable covers - 3X (x) Stored Energy mechanism for Motorized operation (xi) Cable box for front termination of the cable suitable upto 3 core 120 Sqmm, 11 KV XLPE cable (xii) Suitable site replaceable Cable bushings (xiii) Arc proof cable covers with self Interlocking mechanism between doors, earth switch, disconnector & VCB (xiv) Capacitive voltage indication fixed type system (xv) Digital Indications for breaker ON, OFF, EARTH, TRIP, Spring Charged-Discharged (xvi) Right angle boots (push on type) (xvii) Protection CT - 40-80/1A, Cl- 5P10, 2.5VA burden
(c) One No. Operation Handle for Motorized Operation (d) One No. Manometer. (h) Safety Interlocks Shall be provided as per relevant IEC/IS Standards and Manufacturers directions. (j) Above switchgear shall confirm to all relevant IEC/IS Standards. (e) Operation and instruction mannual with drawings - 01 Set. (f) All cable bushing should be replaceable type. (g) Module should be accommodated as per manufacture's design. (i) Necessary interlocking arrangement for safety and operations Vacuum Interrupter should be of make as below. Cable box should be arc proof with bolted door and interlocked with respective earthing switches. Doors should be removable for the ease access to terminate cables.
Note :- Rate Quoted by the firm for this item should include the cost of the following:-
(i) PCC work/ any civil work for foundation required for errection of VCB and other accessories all as standard norms. (MAKE: L&T/ABB/ Siemens/ Schnieder)
Supply, install, testing and commissioning of 11 KV Outdoor type RMU, one-side extensible IP67 type with internal copper bus bars, consisting of fixed type Motorized operated Load Break Switch-02 No as incomer and fixed type Motorized operated Vacuum Circuit Breaker-01 Nos as outgoing (CCV). All live parts, bus bars of RMU should be enclosed in tank to avoid multiple inter connections & sealed for life robotically for three sides and one side Motorized welded non magnetic / non ferrite / stainless steel tank Grade 304 of minimum 2.5 mm thick having IP 67 degree of protection filled with SF6 gas to fulfill the requirement as per IEC 60376, 60376 & 603760 B as insulation with leakage rate less than 0.1% per year tested as per IEC 62271-200. The unit shall have front cable entry for ease of installation. RMU should be complete with all accessories such as Terminal boots, VPIS, cable supports, all front cable terminations, mechanical indications ON/OFF, Manometer as per with IEC standards 62271-200, 60056, 60129, 60265, 60298, 60420, 60529 and 60694. Altitude of installation up to 2000 as per IEC 60120. The unit shall include the following with all necessary standard fitting required at site. RMU should be tested for an internal arc fault of 21kA for 1 sec for tank as per IEC62271-200 and paint shade and thickness should be 70-80 microns, complete all as specified and as directed. The outer enclosure shall cover the full length of the switch gear, to ensure IP55 protection for full door covering of complete switchgear. (Srl item No 10.00 is hereby continued as Srl item No 10.01 to 10.07)
RMU should be provided with maintenance free battery, charger (24V DC), mechanical Interlocking for Incomers and capacitor bank for emergency delivering for trip system complete with suitable capacity of ammeter and voltmeter incoming connections with 2.5 sqmm FRLS insulated copper conductor cable as required.
The unit shall include the following with all necessary standard fittings as required at site and incorporatingthe following accessories :
(a) 2 No. Incomer - LBS : (i) 630A Load Break Switch module for making of fault current alongwith Earth Switch of full making capacity. (ii) Short time breaking current - 21KA/ 3 sec. Making Capacity - 52.5KA (iii) Internal Arc - 21kA/1 sec for tank (iv) Nominal operating gas pressure - 1.3(minimum) Bar abs. (v) Power frequency withstand voltage - 28KV (vi) Impulse withstand voltage - 75KV (vii) Outdoor Enclosure - IP54 (viii) Front cover mechanism - IP2X (ix) Cable covers - 3X (x) Gas pressure manometer (with red & green zones) (xi) Cable box for front termination of the cable suitable upto 3 core 120 Sqmm, 11 KV XLPE cable (xii) Operation Counter (xiii) Fault Passage Indicator (Short circuit + Earth Fault) (xiv) Capacitive voltage indication fixed type system (xv) Stored Energy mechanism for Motorized operation (xvi) Ronis Key Interlock (if required) (xvii) Suitable site replaceable Cable bushings (xviii) Arc proof cable covers with self Interlocking mechanism between doors, earth switch, disconnector & VCB (xix) Right angle boots (push on type)
(xx) Micropressor based numerical relay with O/L, E/F and S/C protection. (b) 1 no. Outgoing - VCB: (i) 630A Vacuum Circuit Breaker module (ii) Short time current - 21KA/ 3 sec (iii) Internal Arc - 21kA/1 sec for tank (iv) Nominal operating gas pressure - 1.3(minimum) Bar abs. (v) Power frequency withstand voltage - 30KV (vi) Impulse withstand voltage - 81KV (vii) Outdoor Enclosure - IP67 (viii) Front cover mechanism - IP 5X (ix) Cable covers - 3X (x) Stored Energy mechanism for Motorized operation (xi) Cable box for front termination of the cable suitable upto 3 core 120 Sqmm, 11 KV XLPE cable (xii) Suitable site replaceable Cable bushings (xiii) Arc proof cable covers with self-Interlocking mechanism between doors, earth switch, disconnector & VCB (xiv) Capacitive voltage indication fixed type system (xv) Digital Indications for breaker ON, OFF, EARTH, TRIP, Spring Charged-Discharged (xvi) Right angle boots (push on type) (xvii) Protection CT - 40-80/1A, Cl- 5P10, 2.5VA burden
(c) One No. Operation Handle for Motorized Operation (d) One No. Manometer. (e) Operation and instruction manual with drawings - 01 Set. (f) All cable bushing should be replaceable type. (g) Module should be accommodated as per manufacture's design. (h) Safety Interlocks Shall be provided as per relevant IEC/IS Standards and Manufacturer’s directions. (j) Above switchgear shall confirm to all relevant IEC/IS Standards. (k) Necessary interlocking arrangement for safety and operations Vacuum Interrupter should be of make as below. Cable box should be arc proof with bolted door and interlocked with respective earthing switches. Doors should be removable for the ease access to terminate cables.
Note :- Rate Quoted by the firm for this item should include the cost of the following:-
(i) PCC work/ any civil work for foundation required for errection of VCB and other accessories all as standard norms. (MAKE: L&T/ABB/ Siemens/ Schnieder)
Supply , installation, testing and commissioning of indoor non-sealed type oil immersed distribution transformer ISI marked (IS-1180:2014) Level 2 step down transformer complete with standard fittings and accessories, HT 11 kV 3 phase, LT 433 volt, 3 phase 4 wire, 50 Hz frequency, on load tap changer on primary side to carry secondary voltage +7.5% to -7.5% in step of 2.5 % of capacity 500 KVA , copper wound, oil cooling with fins vector group : DYn 11, including initial oil filling complete all as specified including the following accessories:-
a. No load voltage ratio : 11000 / 433 - 250 volts b. No of phase - 03 c. Type of cooling - ONAN d. Vector Group - Dyn11 e. Cable end box - HV & LV side (both with brass cable glands) f. Percentage Impedance - 4.5% g. Oil temperature indicator and winding temperature indicator h. Inspection Hole
j . Buchholz relay k. First filling of transformer oil of specification as per IS - 3335 l. Basic insulation level : 75 kV m. No of Tap position on HV side (Off load & manual operated) - 07 nos n. HT bushing with brass nuts and brass washers etc. - 03 nos o. LT bushing with brass nuts and brass washers etc. - 04 nos p. Rating and diagram plate - 01 nos. q. Earthing terminal with lugs for body - 02 nos. r. Lifting lugs - 06 nos. (4 nos for tank and 2 nos for top plate of the transformer)
l. Oil conservator with drain valve and oil level gauge - 01 nos. u. Drain valve (It shall be covered with metallic box spot welded to tank) - 01 nos. v. Thermometer pocket - 01 nos. x. Explosion vent - 01 nos. y. Silica gel breather - 01 nos z. Platform mounting channel (with hole suitable for axle of rollers) - 02 nosRollers (Dia 150 mm & width - 50 mm) - 04 nos. aa. Filter Valve - 01 nos
Note: (Altitude of installation - 2000 m above MSL) (i) The transformer shall be ISI marked with energy efficiency level-2 category and having BEE certification for which necessary test certificate to be produced by contractor from manufacturer of the transformer. (ii) Pre commissioning test of transformer shall be carried out by Rep of Aceepting Officer / SEI from HQCESZ. (iii) Before procurement of transformer, contractor shall furnish certificate that manufacturer has obtained licence from Bureau of Indian Standards. (iv) Factory test of transformer will be carried out in presence of Rep of Accepting Officer and necessary arrangement for visit and testing will be provided by contractor without any extra cost (v) Cost of all arangements , machinery and labour for fixing and installation of transformer on specified site is included in quoted rates. (vi) Contractor has to produce OEM test certificate.
Supply, laying & testing cable XLPE insulated, screened, PVC bedded, galvanized steel strip or wire armoured, electric power cables (heavy duty)with stranded aluminium conductor, 11000 volts Earthed, grade of size 3 core, cross sectional area 95 sq.mm including dismantling of old ACSR Conductor for the same complete all as specified and directed.
Supply and fix cable jointing kit for 11 KV (Earthed) grade cable for indoor termination cold shrink type joint complete with jointing material and accessories suitable for 3 core XLPE armoured aluminium conductor cable of size 50 sqmm to 95 sqmm complete all as specified and directed.
Supply and fix cable jointing kit for 11 KV (Earthed) grade cable for outdoor termination cold shrink type joint complete with jointing material and accessories suitable for 3 core XLPE armoured aluminium conductor cable of size 50 sqmm to 95 sqmm complete all as specified and directed.
Supply, install, testing and commissioning of approved OEM factory assembled diesel generator set of totally enclosed and sound proof (with acoustic enclosure) of capacity 125 KVA, 3 phase, 4 wire, 415 volts, 1500 RPM, AC power supply with power factor 0.8, coupled directly to alternator mounted on common base plate complete with fuel tank, battery and standard accessories and fittings, vibration pads, PCC foundation complete all as specified and directed. The genset shall conform to CPCB norms for noise and emission limits and including the following : (a) Alternator :- Standard design alternator rated at 125 KVA net output at site after considering all derating factors, site conditions and at power factor 0.8, AC 3 phase, 4 wire 415 volts, 50 cycles, 1500 RPM, self excited, self regulated, screen protected, drip proof IP-23 enclosure, brushless design, insulating class H, voltage regulation +/- 1% operated voltage from no load to full load complete all as specified and directed. (Srl item No 15.00 is hereby continued as Srl item No 15.01 to 15.04)
(b) DIESEL ENGINE: Adequate capacity diesel engine suitable to above alternator, radiator water cooled, to drive independently above alternator and after considering derating as per site conditions directly coupled to alternator multicylinder, multistroke, direct injection, cold starting, 1500 RPM, with an overload cap of 10% for 1 hour in any 12 hours continuous running complete with standard accessories all as specified and required for safe running and operation with accessories shall be as under:- (i) Flywheel (ii)Air cleaner wet/dry type (iii) fuel Filter (iv) Fuel Injection system incl.injection pump, solenoid switch, nozzle as per manufacturer's specifications (v) Lubricating oil filter (vi) Lubricating oil pump (vii) Turbocharger (viii) Radiator (ix) 12/24 volts starting system consisting of batteries of capacity as recommended by manufacturer, battery connections with copper leads and with lugs of adequate size, initial charging of batteries, battery charger/ generator with regulator, starter motor, starter gear (x) Exhaust silencer complete with exhaust pipe of suitable dia. (xi) Microprocessor control electronic metering and module for indication of battery voltage, oil pressure, engine RPM, hour meter and protection against low oil pressure and over speed of engine including electronic governing.
(q) Supply and lay Control cable LT 1100 Volt PVC insulated armoured heavy duty copper conductor of suitable size multicore from DG Set to AMF panel (g) Any other components/parts as per manufacturer instructions and as directed by GE required for entire completion of the item. (e) Acoustic Enclosure - Composite type made of CRCA sheet and structural/sheet metal base frame duly painted with air inlet louvers, including noise absorbent and fire-retardant grade acoustic insulation material, including removable gland plate at lower level of canopy for cable entry. Note :- (i) Necessary PCC foundation as per manufacturer recommendations is deemed to be included in the quoted rate. (ii) The drg and specifications of the DG set & AMF Panel shall be got approved by the contractor from the Engineer in Charge before procurement. (iii) The DG set after installation shall be got tested at site by the rep nominated by the Accepting Officer and the records of the testing shall be signed by the rep of accepting officer, GE, Engr-in-Charge and the Contractor. (iv) Diesel, grease, engine oil, load bank and testing equipments required for testing shall be provided by the contractor and cost of the same shall be deemed to be included in the contractor's quoted rates.
(Make for Diesel Engine Generating Set: Kirloskar Green, Cummins, Ashok Leyland, Greavs Cotton, M/s Sterling Generators Pvt Ltd) Notes : (i) Testing of DG set shall be carried out on artificial load of heating element only as specified in PS Sec-II. Heating element, power cable etc and Initial filling of lubricating oil/ coolant and fuel required for testing as per clause will be provided by the contractor. (ii) PCC and earth work for DG set foundation shall be deemed to be included in quoted rates
Supply, installing, testing and commissioning of silent Diesel Engine Drives Generating Set, 415 Volts, 20 KVA, 3 Phase, 4 wire, 0.8 Power Factor, 50 Hz, 1500 RPM MoEF certified power 25.2 bhp, 2 cylinder in line 4 stroke radiator cooled engine, self excited, self regulated brushless AC generator suitable for ambient conditions complete with sound proof canopy as per CPCB norms, 12 Volts 88 Ah battery, Control panel for automatic starting on main failure installed on cement concrete foundation as per recommendation of manufacturer and 60 cm above ground level complete all as specified in description given below and directed. (a) Diesel Engine : Diesel engine suitable BHP at 1500 RPM multi cylinder 4 stroke, water cooled, Electrical starter motor with soft start engagement feature, Coolant heater, Oil drain pump, Heavy duty air cleaner, Electronic Governing, Optimised turbocharger for increased altitude capabilities, Standard integral set-mounted radiator system, designed and tested for 50°C ambient temperature etc and conforming too ISO 3046 / BS 5514 capable of taking 10% over loading for one hour after 12 hour of continuous operation. The engine shall be fitted complete with all the required accessories. (Make for Diesel Engine Drives Generating Set: Kirloskar Green, Cummins, Ashok Leyland, Greavs Cotton, M/s Sterling Generators Pvt Ltd) (Srl item No 16.00 is hereby continued as Srl item No 16.01 to 16.03)
(b) Control panel shall be manufactured with 14/16 gauge CRCA sheet and powder coated for weather-proof and long lasting finish. The control panel consists of the following parts :- (i) Microprocessor based generator set monitoring and control system. This control includes an intuitive operator interface that allows for complete generator set control as well as system metering, fault annunciation, configuration and diagnostics.ƒIntuitive operator interface which includes LED backlit LCD display with tactile feel soft-switches and generator set status LED lamps, Remote Start-Stop, Engine Metering : Oil pressure, Engine temperature, Starting battery voltage, Engine running hours, AC Alternator Metering : L-L Voltage and L-N Voltage, Current (phase and total), kVA (phase and total) and Frequency. Engine Protection : Low lube oil pressure, High/Low coolant temperature, Battery Over/Under/Weak Volts, Fail to Crank/ Start, Sensor failure, Cranking lockout, Low fuel level. AC Alternator Protection : Over/Under Voltage, Over/Under Frequency, Loss of AC Sensing. Data Logging : Engine Hours, Control Hours and upto 5 recent fault codes Configurable glow plug control, 12 Volt DC operation, Sleep mode, Modbus interface (RS485 RTU), InPower compatible (PC based service tool). (ii) Automatic starting on main failure as per the manufacturer standard practice and specification complete with Aluminum bus bars with suitable capacity with incoming/outgoing terminals Indicating lamps for ‘Load ON’ and ‘Set Running’.
(iii) Instrument fuses duly wired and ferruled. (iv) Circuit breakers of suitable rating with overload and short circuit protections. (c) Alternator : Synchronous alternator rated at 20 KVA, 415 Volts at 1500 RPM 3 phase 50 Hz, AC supply, Brushless type, Screen protected, Revolving field, Self excited alternator conforming to IS/IEC 60034-1, Compact design with sealed bearings and ƒImpregnation on all wound components suitable for tropical conditions and with class F/H insulations. (d) Mounting Arrangement : Engine and alternator shall be mounted on a common MS fabricated base frame with AVM pads. Base frame with integral fuel tank shall be provided with drain plug, air vent, inlet and outlet connection, level indicator and provision for cleaning. (e) Fuel Tank : Daily service fuel tank of capacity as per manufacturer standard specification fabricated out of MS sheet complete with all standard accessories and fuel piping between fuel tank and diesel engine with MS class C pipe of suitable dia complete with valves. (f) Exhaust System : Dry exhaust manifold with hospital exhaust silencer and catalytic converter. (g) Starting System : 12 V/24 V starting system comprising of starter motors, voltage regulator and arrangement for initial excitation complete with suitable Nos of batteries (88 Amp hour capacity lead acid type) as required as per specification.
(h) Acoustic Enclosure : Specially designed to meet stringent CPCB norms of 75 dBA @ 1mtr at 75% load under free field conditions. The acoustic enclosure is made of CRCA sheets and a structural/ sheet metal base frame painted in black, High quality noise absorbent and fire-retardant grade acoustic Insulation material (Foam) complying to IS 8183, Two point lifting for easy handling, Air inlet louvers specially designed to operate at rated load, 11 tank pretreatment process and UV resistant powder coating of all parts to withstand extreme environment, Flush styling - no projections, Fluid drains for lube oil and fuel, Fuel filling arrangement inside the enclosure etc. Notes : (i) Testing of DG set shall be carried out on artificial load of heating element only as specified in PS Sec-II. Heating element, power cable etc and Initial filling of lubricating oil/ coolant and fuel required for testing as per clause will be provided by the contractor. (ii) PCC and earth work for DG set foundation shall be deemed to be included in quoted rates
Supply and fixing Servo controlled Voltage stabilizer 3 Phase 4 wire of Capacity 100 KVA for automatic operation, naturally oil cooled, indoor type & designed Input Volatge range 340 V to 460 V 3 Phase, Output voltage range 415 V ± 1 % 3 Phase, Operating frequency 47 to 53 Hz, suitable for working on unbalanced load with regulation of ± 1 %, correction speed of 60 V/sec, efficiency 97 % having following features :- (a) 45 degree C ambient temperature (b) AC servo motor with continues duty cycle (c) Indications for Main on, output on, Low Cut off, high cut off (d) Digital display to read voltage, current, frequency, status indications and parameters with soft touch buttons for ease of operations (e) Programmable Low voltage cut off upto 200 V AC (f) Programmable high voltage cut off from 220V to 250 V AC (g) Inbuilt phase reversal protection (h) Class F insulation (j) Protections for High Voltage cut off, Low voltage Cut off, overload protection, short circuit protection, single phase preventer, MCCB protection. (k) As per IS 9815 (Make: Voltamp, APLAB, Andrew Yule, Brentford, AE, Vinitec(Brand Name-Volina), Live line Electronics, M/s Instruments & Equipment Co) Note:- The registered factory trained sales/service office should be located within Eastern India Region for providing adequate prompt services.
Supply and fixing Servo controlled Voltage stabilizer 3 Phase 4 wire of Capacity 75 KVA for automatic operation, naturally oil cooled, indoor type & designed Input Volatge range 340 V to 460 V 3 Phase, Output voltage range 415 V ± 1 % 3 Phase, Operating frequency 47 to 53 Hz, suitable for working on unbalanced load with regulation of ± 1 %, correction speed of 60 V/sec, efficiency 97 % having following features :- (a) 45 degree C ambient temperature (b) AC servo motor with continues duty cycle (c) Indications for Main on, output on, Low Cut off, high cut off (d) Digital display to read voltage, current, frequency, status indications and parameters with soft touch buttons for ease of operations (e) Programmable Low voltage cut off upto 200 V AC (f) Programmable high voltage cut off from 220V to 250 V AC (g) Inbuilt phase reversal protection (h) Class F insulation (j) Protections for High Voltage cut off, Low voltage Cut off, overload protection, short circuit protection, single phase preventer, MCCB protection. (k) As per IS 9815 (Make: Voltamp, APLAB, Andrew Yule, Brentford, AE, Vinitec(Brand Name-Volina), Live line Electronics, M/s Instruments & Equipment Co) Note:- The registered factory trained sales/service office should be located within Eastern India Region for providing adequate prompt services.
Supply,install,testing and commissioning of Dehumidfier desiccant type capacity 900 CFM, Eco Dry rotor and totally self -contained having differential air pressure switch to control reactivation air flow along with Humidistat with Digital Display complete all as specified and directed. (Srl item No 19.00 is hereby continued as Srl item No 19.01 to 19.02)
Type of Dehumidifier: Desiccant type table top, Power – 415 V / 3 PH /50 Hz, Dehumidifier equipped with Microprocessor based controlling system having LED Display indicating the status of input, Humidistat with digital display, CNC fabricated unit with pre-coated MS sheet, The desiccant rotor is manufactured in-house (Made in India), Process & reactivation air flow sectors insulated with Aluminum Foils, The desiccant rotor is made of fluted honeycomb type with stainless steel perimeter flange to incorporate robust internal structure required for industrial quality, durability and easy serviceability and also to extend media and seal life. No wastage of active desiccant wheel media. The desiccant rotor is non-flammable and its media shall have high Performance metal silicates synthesized in situ, Differential air pressure switch to control reactivation air flow and indicating clogging of filters, High temperature thermostat cutout to economize the power consumption, Additional cooling thermostat as a safety measure, Electrical interlocking of fan motor, heaters and rotor drive as a safety measure, PTFE bonded silicon bulb seal designed to minimize air leakage, Dehumidifier has an option to control Reactivation temperature, system parameters, Dehumidifier is CE Certified with ISO 9001:2015 and ISO14001:2015 certifications, Dimension of Dehumidifier: 1208 mm (L) X 890 mm (D) X 584 mm (H). (Make-: Bry Air(asia) Pvt Ltd, Model-: FFB -1500 or equivalent Model of Make Munters /Seibu Giken DST.)
Note:- The registered factory trained sales/service office should be located within Eastern India Region for providing adequate prompt services.
Supply,install,testing and commissioning of three phase Monoblock Pump Set, pipe Suction x Delivery 65mm x 50mm, power rating 10HP (7.5 kW), Speed 3000 RPM, Head Range (40 to 68m) Flow range (468-180) suitable for 415 V, 3phase of capacity 10 HP, ) Insulation : F Class Protection : IP 55 Impeller : Cast Iron Delivery Casing : Cast Iron Motor Body : Cast Iron Pump Shaft : Carbon Steel Sealing : Gland Packed complete all as specified and directed. Note: The testing required to be done in presence of IEM. (Make :Crompton Greaves, Kirloskar, KSB)
Supply, install, testing and commissioning of Automatic Power Factor correction (APFC) Panel 100 KVAR with auto/Manual option, factory made, indoor type, slopy canopy, fabricated out of 3.15mm thick CRCA sheet with angle iron base frame made of 50x50x6mm, 45cm height, dust and vermin proof, suitable for voltage 415V 3 phase 4 wire weather proof with IP-54 protection, with compartment for incoming and outgoing switchgear/MCCB etc with locking arrangement, with back door openable (Screwed), legs grouted in PCC including painting with two coats of epoxy powder paint over a coat of primer after undergoing a rigorous metal treatment process involving alkaline degreasing, descaling in dilute sulphuric acid or any other acid and phosphate, suitable double compression copper cable glands compete in all respects for main panel for transformer and including provn of the following : - Note : The panel shall be of CPRI Approved, PCC will be deemed to be included in above rate. (a) No of steps- 03 steps and 1 fixed step of capacity 5 KVAR (Srl item No 22.00 is hereby continued as Srl item No 22.01 to 22.03)
k. 25 Amp capacitor switching TP contractor for 10 KVAR, - 05 Nos l. Auxiliary Contactor - 05 Nos m. 3 Stage APFC Relay, intelegent - 01 No n. On Delay Timer, 0-180 Sec, - 01 No o. MDXL capacitors (10+15+25+25+25=100 KVAR), p. Flush type Start Push Button with 1 No, -05 Nos q. Flush type Stop Push Button with 2 NC, -05 Nos r. LED Type On Indicating Lamp - RED , -05 Nos
Note :- (i)The capacitors shall be housed in self extinguishing insulation material operated on 3 phase, 415 Volts AC, frequency 50 Hz. The dielectric should be mixed dielectric type (MD XL), with built in over pressure safety device, tolerance 0% to 10% protection degree IP 30 and maximum temperature 55o C. (ii) Rate shall be deemed to include provision of suitable size of aluminium bus bar three phase 4 wire.
Supply and fix single door refrigerator, electric driven (single phase), capacity 195 Litres (BEE 5 star rated) all as specified and directed. (Make : LG, Samsung, Godgrej)
Supply and fix double door refrigerator, electric driven (single phase), capacity 310 Litres (BEE 3 star rated) all as specified and directed. (Make : LG, Samsung, Godgrej)
S&F Voltage stablizer for automatic operation single phase naturally cooled indoor type & designed for input variation between 160 V to 250 V with output voltage stabilized at 230 V with accuracy of +/- 2.5% and of capacity 3 KVA with high Voltage Cut off Protection all as specified and directed. (Make: Voltamp, APLAB, Brentford, Vinitec(Brand Name-Volina))
Supply and fix lightning arrestor HT 11 KV 10 KA station class all as specified and directed.
M & L of earthing complete with galvanized steel earth plate electrode 60 cm x 60 cm x 6.00 mm thick buried directly in ground [earth pit not less than 2.25 metre deep below normal ground level] with top edge of the plate electrode not less than 1.5 m below normal ground level, connected to including galvanised iron strip size 32 x 6 mm by means of bolts, nuts, and washers of galvanized iron or steel all as shown in electrical plate No. 3 of SSR Part I connected to earth test point including provision of earth strip protected by 40 mm dia light grade GI pipe & watering pipe shall be 20 mm bore medium grade GI pipe including all excavation and earth work in any type of strata, PCC pit with RCC cover, CI frame, char coal, salt & funnel etc complete all as specified or indicated including testing on completion all as specified and directed. (Rate to be considered for earth strip to be fixed 7.5m long)
Supply, Installation, Testing and Commissioning of ongrid Solar Photovoltaic Power Plant 25 KWP conforming to MNRE specifications as amended, consisting of Mono/Poly Crystalline silicon solar cells, net metering facility, necessary protections, earthing, mounted on Aluminium/GI structure of suitable strength with following components complete as required:- (Srl item No 28.00 is hereby continued as Srl item No 28.01 to 28.02)
a) Solar Photovoltaic Module of capacity 445 Wp or above, manufactured in India, conforming to IS 14286/IEC 61215, IS/IEC 61730-Part-1, IS/IEC 61730-Part-2. Solar Photovoltaic Module conversion efficiency shall not be less than 16.5%. PV modules used in solar power plants/ systems must be warranted for their output peak watt capacity, which should not be less than 90% at the end of 10 years and 80% at the end of 25 years. b) Power Conditioning Unit (PCU) of 350-800 V DC Input voltage range and 400 V AC, three phase, 4 wire, 50Hz +/- 2.5 Hz, output voltage suitable to generate AC Power with efficiency not less than 97%, total harmonic distortion less than 3% and suitable for ambient temperature from 0 to 50 degree C. The PCU shall adjust the voltage and frequency level to suit the Grid Voltage Frequency.
c) Data Monitoring System complete with accessories. d) Fixing of Array junction box & Main junction box with IP 65 protection and termination arrangement for incoming and outgoing cable along with glands, lugs and other accessories etc. as required. e) Lightning and surge voltage protection. f) Connections & Interconnections by supplying & fixing required size XLPE insulated copper conductor 1.1 kV grade armoured power and control cables between solar modules, main power cable to grid supply PCU unit along with supplying & fixing of necessary channel/conduit lugs and other accessories etc. as required
Supply, install, testing & commissioning of Microprocessor based single phase tamper proof electronic static pre paid cum postpaid GPRS base energy meter rating 240 Volts, 50 HZ, of range 5-30 Amps, confirming to IS 13779 & IS15884 / IS 16444 with LED display and parameters like Voltage, Current, Frequency, Power, Power factor, KWH/KVA, default /in built dual source, compatible for Prepaid and Postpaid online energy monitoring billing system, with disconnection /reconnection through remote software / data export to ERP complete all as specified and as directed by Engr-in-Charge. Taking download energy meter fixed in panels of any capacity any type after carefully disconnecting electrical connections all as specified and as directed by Engr-in-Charge. Note: - Quoted rate shall have deemed to be inclusive of following parameters: - (a) Meter reading record shall be submitted before and after replacement duly signed by the contractor rep and MES rep. (b) Old meters should be handed over to MES store. (c) Any rejoining of wires /cables shall be done using suitable ferrule /cable connectors after removal of meter. (d) The cost of making good disturbed surfaces & matching to the existing surface is deemed to be included in the unit quoted rates e)Taking down old Single phase Energy Meter from the Shops/ houses and deposited to MES yards all as specified and directed F)Hosting, GPRS charges for 2 years warranty period. (Make : Siemens, L&T, HPL, Schinder, Secure)
Supply, install, testing & commissioning of Microprocessor based three phase tamper proof electronic static pre paid cum postpaid GPRS base Energy Meter rating 240 Volts, 50 HZ, of range 5-30 Amps, confirming to IS 13779 & IS15884 / IS 16444 with LED display and parameters like Voltage, Current, Frequency, Power, Power factor, KWH/KVA, default /in built dual source, compatible for Prepaid and Postpaid online energy monitoring billing system, with disconnection /reconnection through remote software / data export to ERP complete all as specified and as directed by Engr-in-Charge. Taking download energy meter fixed in panels of any capacity any type after carefully disconnecting electrical connections all as specified and as directed by Engr-in-Charge. Note: - Quoted rate shall have deemed to be inclusive of following parameters: - (a) Meter reading record shall be submitted before and after replacement duly signed by the contractor rep and MES rep. (b) Old meters should be handed over to MES store. (c) Any rejoining of wires /cables shall be done using suitable ferrule /cable connectors after removal of meter. (d) The cost of making good disturbed surfaces & matching to the existing surface is deemed to be included in the unit quoted rates. e)Taking down old Three phase Energy Meter from the Shops/ houses and deposited to MES yards all as specified and directed F)Hosting, GPRS charges for 2 years warranty period. (Make : Siemens, L&T, HPL, Schinder, Secure)
Supply fixing testing & commissioning of configuration of cloud Hosted multi user web based software with following modules : (i) Meter data management Modules : The meter data management module would be responsible for collecting the data from the concentrator and make the data available to their billing system . The billing system wold support offline meter data entry. the meter data management system would capture and provide the following data. (a) 30min instantaneous data from all the meters for seven parameters - cumulative energy , Power, Current , Voltage, Power factor and frequency. (b) Monthly and quarterly billing survey data for cumulative energy and max demand. (ii) Billing Module : The billing module would collect the dat from the meter data management module , calculate billing determinant and make energy data / billing data available to admin and end user. (iii) Occupation and Vacation module : The system would support occupation/vacation based on the unit categories The system would support automatic data capture on occupation and vacation events. (iv) Customer Module : The system would include a customer portal for the resident/occupants to log in /out in and view their own energy/billing data. (Srl item No 31.00 is hereby continued as Srl item No 31.01)
(v) Energy Accounting module : The system would include features of energy accounting , the system would to able to account for total energy block wise, facility wise and would also allow calculations of the unaccounted energy in case total energy meter is also available. (iv) Communication Module : The system would provide communication of energy data and bills via print, email and sms methods. (vii) Meter Master Data : The system would support meter days repository. The system would support meter replacement process. (viii) Excel Export : the system would support export of metering and filling data in excel format.
Supply, install, testing & commissioning of Microprocessor based single phase tamper proof electronic static pre paid / postpaid energy meter rating 240 Volts, 50 HZ, of range 10-60 Amps, confirming to IS 13779 & IS 16444 with LED display and parameters like Voltage, Current, Frequency, Power, Power factor, KWh/KVA, default /in built dual source, inbuilt long range (LORAWAN) Communication suitable for outdoor LoRa data accumulatorand also compatible for Prepaid and Postpaid online energy monitoring billing system, with disconnection /reconnection through remote software / data export to ERPcomplete all as specified and as directed. (Make : Siemens, L&T, HPL, Schinder, Secure)
Supply, installation, testing & commissioning of single phase Meter box compatible for meters to be installed as per item 32.00 here-in-above, complete all as specified and directed. (Make :Syntex, Model SPGSMB2525(Single Phase) or equivalent model of make- Hensel, C&S)
Supply,and install, testing & commissioning of Microprocessor based three phase tamper proof electronic static prepaid / postpaid Energy Meter rating 415 Volts, 50 HZ, CT OPERATED, confirming to IS 13779 / IS 16444 with LED display and parameters like Voltage, Current, Frequency, Power, Power factor, KWh/KVA, default /in built dual source, inbuilt long range (LORAWAN) Communication suitable for outdoor LoRa data accumulator and also compatible for Prepaid/ Postpaid online energy monitoring / billing system, with disconnection /reconnection through remote software / data export to ERP complete all as specified and as directed. (Make : Siemens, L&T, HPL, Schinder, Secure)
Supply, installation, testing & commissioning of three phase Meter box compatible for meters to be installed as per item 34.00 here-in-above, complete all as specified and directed. (Make: Sintex, Model: SPGSMB3527(Three Phase) or equivalent model of make- Hensel, C&S)
Note for S. No 29.00 to 35.00 above: Taking down of old Energy Meter fixed in panels of any capacity/ any type after carefully disconnecting electrical connections all as specified and asdirected. Note: - Quoted rate shall have deemed to be inclusive of following parameters: - (a) Meter reading record shall be submitted before and after replacement duly signed by the contractor rep and MES rep. (b) Old meters should be handed over to MES store. (c) Any rejoining of wires /cables shall be done using suitable ferrule /cable connectors after removal of meter. (d) The cost of making good disturbed surfaces & matching to the existing surface is deemed to be included in the unit quoted rates.
Supply, installation, testing and commissioning of Outdoor LoRa accumulator for long range communication up to 1.00 KM suitable for communicating with Prepaid come postpaid meter with LoRa communication protocol and the data transfer to the existing Elnet V5 Software complete all as specified and as directed byEngr-in-Charge. Note: The cost of pole /fixing /mounting arrangement on which the accumulator to be installed and SMPS power supply with UPS backup (300VA) is deemed to be included in theunit quoted rates. (Make: Siemens, L&T, HPL, Schinder, Secure)
Description: Supply and Installation of Network Server, MQTT based intelligent network server for bridging between gateway and end application. Eliminate duplicatepackets, schedule acknowledgement, and adapts data rates, (Make: Siemens, L&T, HPL, Schinder, Secure)
Hosting, GPRS charges for 3 years warranty period,Make:AIRTEL/JIO
Supplying, Fixing, Commissioning and testing of configuration of server Hosted multi user web based software with following modules: (i) Meter Data Management Module: The meter data management module would be responsible for collecting the data from the data concentrator and make the data available to the billing system. The system would support offline meter data entry. The meter data management system would capture and provide the following data: (a) 30min instantaneous data from all the meters for seven parameters- Cumulative Energy, Power, Current, Voltage, Power factor and Frequency. (b) Monthly and quarterly billing survey data for cumulative energy and max demand (ii) Billing Module: The billing module would collect the data from the meter data management module, calculate billing determinant and make energy data/ billing data available to admin and end users. (iii) Occupation and vacation Module: The System would support occupation/ vacation based on the unit categories. The system would support automatic data capture on occupation and vacation events. (Srl item No 39.00 is hereby continued as Srl item No 39.01)
(a) Bidder/OEM shall make arrangement (available a standby on site) for disaster management server make available a standby at site (secondary server) in case of breakdown of parent server without any extra cost to the department for complete period of two years. (b) Bidder/OEM will arrange static IP and will provide internet infrastructure at GE/BSO office for servers having minimum speed of 10-20 MBPS without any extra cost to the department for the period of two years. (c) Contractor will be fully responsible for server connectivity and also functioning of complete system comprising of server for data base, App, web, standby data base, monitoring/management including desktop for monitoring/management primary and secondary firewall, switch duly installed and suitable size computer table, Chair and racks as per requirement. No extra payment will be provided for the infrastructure. (Make: Siemens, L&T, HPL, Schinder, Secure)
Supply of all in one PC (Personal Computer) complete in all respect similar to Lenovo idea Centre AIO 330 19.5'' All-in-One Desktop (Intel Pentium Silver J5040 Quad Core - 2GHz Base Speed/4GB/1TB HDD/Windows 10/MS Office 2019/Intel UHD Graphics/HD 720p Camera), Black (FoD7008KIN) (Make - HP/Lenovo/Dell) to be employed for both prepaid and AMR based Energy Meters all as specified and directed. (Make: HP, Dell, Acer)
Supply for desktop type Point of Sale Printer complete in all respect similar to HP Deskjet 2331 colour Printer, Scanner and Copier for Home/Small Office, Compact Size, Reliable, and Affordable Printing, Easy Set-up Through HP Smart App on Your PC Connected Through USB/equivalent (Make- Epson/HP/Canon) to be employed for both prepaid and AMR based Energy Meters (Make: HP, Canon, Epson, Brother)
Complete design, Engineering, Manufacturing, Supply, storage, Civil works, Erection, Testing, Commissioning as per the sikkim state policies of ground mounted On Grid Solar tree of aggregate capacity 5 kWp with Battery backup including operation & Maintenance for a period of 5 years all as specified and directed.
Complete design, Engineering, Manufacturing, Supply, storage, Civil works, Erection, Testing, Commissioning as per the sikkim state policies of ground mounted On Grid Solar tree of aggregate capacity 10 kWp with Battery backup including operation & maintenance for a period of 5 years all as specified and directed.
Note 1:- (Applicable for all parts/items) : The biidders/contractors are advised to read tender document, all drawings & all corrigendum/ amendments and general condition of contracts before entry/quoting the rates. Note 2:-The contract sum shall be arrived at after deducting amount of schedule of credit from the total quoted amount.
SAGGI ELECTRIC COMPANY
M/s BHAGWATI CONSTRUCTION
AVINASH ENTERPRISES
GEPS PROJECTS
BHARAT MULTITECH INDUSTRIES PVT LTD
HAMTECH ENGINEERING PRIVATE LIMITED
M/S R. K. INDUSTRIES
Mars Developments
stage.html
html • 0.07 MB
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.04 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .