Loading…
Loading…
| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | L1₹7.9 LAccepted-AOC | L1 | Accepted-AOC Being L1 | |
| 2 | L2₹8.8 L+₹84,248 (10.5%)Rejected-Finance | L2 | Rejected-Finance Being L2 | |
| 3 | L3₹9.2 L+₹1.2 L (15.2%)Rejected-Finance | L3 | Rejected-Finance Being L3 | |
| 4 | L4₹11.6 L+₹3.6 L (45.5%)Rejected-Finance BHU | L4 | Rejected-Finance Being L4 | |
| 5 | L5₹12.1 L+₹4.1 L (51.9%)Rejected-Finance | L5 | Rejected-Finance Being L5 |
Tender Value
₹15 L
EMD Value
₹30,000
Closing Date
2 Nov 2019, 6:00 pmClosed
GE I R and D Kanpur
GE I R and D Kanpur DMSRDE Complex, GT Road Kanpur 208013
REPAIR, REPLACEMENT, MAINTENANCE OF INTERNAL WIRING, DISTRIBUTION BOARDS, SUB MAIN WIRING, AC BOXES, SERVICE CONNECTIONS, THREE PHASE CONNECTION FOR MACHINES AND OTHER CONNECTING ITEMS ETC IN TECHNICAL AREA UNDER GE (I) R and D KANPUR
2019_MES_287458_1
8166/E8
Open Tender
Electrical and Maintenance Works
Item Rate
180 days
Tech Area GE(I) R and D Kanpur
As Per NIT
8 documents required · 8 mandatory
₹500
Yes
GE I R and D Kanpur
₹30,000
Yes
14 Mar 2020
5 Oct 2019
4 Nov 2019
5 Oct 2019
2 Nov 2019
19 Oct 2019
Amount
Supply and fixing in replacement Cirrus surface mounted which is and energy efficent luminarire suitable for 2 x2 grid of 36 W ceiling including control driver and other accessories complete all as specified and directed. Make: Cat part of Philips: SM365C LED33-6500 PSU-OD GR/ Cat part of Crompton: LCTRP-36-CDL.
Supply & Fixing in replacement of Kit Kat DB by SPN Distribution Box, double door of protection grade IP 43 in fine powder coated, matt finish with best CRCA sheet, fitted with shrouded neutral, insulated pin type copper bus bar, Din rail, earth bar of 8 way, confirming to IS 13032 & 8623 complete all as specified and directed. Make:- Schneider (Electric)/Legrand/L & T /Indoaisa
Supply & Fixing MCB TPN, 100 Amps 415 volts, AC , 10 KA breaking capacity 'C' Series,"ISI marked and conforming to IS 8828/IEC 60898-1 complete all as specified and directed. Make:-Schneider Electric/L&T/Legrand.
Supply & Fixing MCB SPN, 32 Amps 240 volts, AC , 10 KA breaking capacity 'C' Series,"ISI marked and conforming to IS 8828/IEC 60898-1 complete all as specified and directed. Make:- Schneider Electric/Legrand/L & T
Supply & Fixing MCB SP, 06 to 32 Amps 240 volts, AC , 10 KA breaking capacity 'C' Series,"ISI marked and conforming to IS 8828/IEC 60898-1 complete all as specified and directed. Make:- Schneider Electric/Legrand/L & T.
Supply only MCB TPN, 63 Amps 240 volts, AC , 10 KA breaking capacity 'C' Series,"ISI marked and conforming to IS 8828/IEC 60898-1 complete all as specified and directed. Make:-Schneider Electric/Legrand/L & T/Indoasian
Supply only MCB SPN, 63 Amps 240 volts, AC , 10 KA breaking capacity 'C' Series,"ISI marked and conforming to IS 8828/IEC 60898-1 complete all as specified and directed. Make:-Schneider Electric/Legrand/L & T.
Supply only MCB TP, 63 Amps 240 volts, AC , 10 KA breaking capacity 'C' Series,"ISI marked and conforming to IS 8828/IEC 60898-1 complete all as specified and directed. Make:-Schneider Electric/Legrand/L & T.
Supply & fixing in replacement of AC/Geyser box by sheet steel enclosure in single pole and neutral fitted with two pin and earth plug and socket complete with one single pole MCB, 240 volt, 20 Amps , 'C' series of suitable rating complete all as specified and directed . Make:-Schneider Electric/Legrand/L & T/Havells/Indoasian
Supply & Fixing in replacement of Kit Kat DB by SPN Distribution Box, double door of protection grade IP 43 in fine powder coated, matt finish with best CRCA sheet, fitted with shrouded neutral, insulated pin type copper bus bar, Din rail, earth bar of 4 way, confirming to IS 13032 & 8623 complete all as specified and directed. Make:-Schneider Electric/Legrand/L & T..
Supply & Fixing in replacement of Kit Kat DB by TPN Distribution Box vertical, double door of protection grade IP 43 provn for 4 Pole MCCB frame F2+24 modules upto 250 Amps , upto 50 KA breaking capacity as incomer in fine powder coated, matt finish with best CRCA sheet, fitted with shrouded neutral, insulated pin type copper bus bar, Din rail, earth bar of 8 way, confirming to IS 13032 & 8623 including chasing/cutting of wall and concealed and making good as existing surface complete all as specified and directed. Make:-Schneider Electric/Legrand/L & T/Indoasian
Supply and fixing in replacement of Kit Kat DB by TPN Distribution Box double door of protection grade IP 43, in fine powder coated, matt finish with best CRCA sheet, fitted with shrouded neutral, insulated pin type copper bus bar, Din rail, earth bar of 8 way, confirming to IS 13032 & 8623 including chasing/cutting of wall and concealed and making good as existing surface complete all as specified and directed. Make:-Schneider Electric/Legrand/L & T/Indoasian
supply and fixing of MCCB 200 Amps 25 KA with fixed thermal magnetic release frame F2 optim 1.0 , 4pole all as specified and directed. Make:-Schneider Electric/Legrand/L & T/Indoasian
S & F service connection with twin core 10 Sqmm 240 volt heavy duty un armured PVC insulated stranded aluminium conductor cable with GI supporting wire of suitable size in replacement of old unseriveable conductor cable complete. Make : Plaza /Poly cab/Havells/fenolex
S & F service connection with twin core 6 Sqmm 240 volt heavy duty un armured PVC insulated stranded aluminium conductor cable with GI supporting wire of suitable size in replacement of old unseriveable conductor cable complete. Make : Plaza/Poly cab/Havells/fenolex
M&L in replacement of worn out sub main of worn out aluminium conductor by sub main wiring with four run of FR PVC insulated unsheathed flexible copper conductor (multistrands) single core of size 10.0 Sqmm 1100 volts grade and two run of 6.0 Sqmm FR PVC insulated unsheathed (in green colour) flexible copper conductor (multistrands) for continuous earthing conforming to IS 694 with latest amendments and ISI marked drawing in PVC rigid conduit and providing flexible conduit at each end point connecting incoming/out going electric connection by using required size copper lugs/thimbles and making good the disturbed surface to match with existing surface complete. Note :- 1. four run of single core cable with two run of contineous earth wire of copper conductor wire flexible (Multistrand) of FR PVC insulated shall be measured and paid as one unit length 2. PVC conduit pipe with fitting shall be measured and paid separately . Make of Wire: Polycab, KEI,Plaza
M&L in replacement of worn out sub main of worn out aluminium conductor by sub main wiring with four run of FR PVC insulated unsheathed flexible copper conductor (multistrands) single core of size 16.0 Sqmm 1100 volts grade and two run of 10.0 Sqmm FR PVC insulated unsheathed (in green colour) flexible copper conductor (multistrands) for continuous earthing conforming to IS 694 with latest amendments and ISI marked drawing in PVC rigid conduit and providing flexible conduit at each end point connecting incoming/out going electric connection by using required size copper lugs/thimbles and making good the disturbed surface to match with existing surface complete. Note :- 1. four run of single core cable with two run of contineous earth wire of copper conductor wire flexible (Multistrand) of FR PVC insulated shall be measured and paid as one unit length 2. PVC conduit pipe with fitting shall be measured and paid separately . Make of Wire: Polycab, KEI,Plaza
Supplied and fixing in replacement PVC conduit by Non Metallic Rigid PVC conduit, ISI Marked, conforming to IS 9537, medium grade of size 32 mm dia including all fittings like bends, elbow reducer, junction boxes, tee bell mouth all fixing accessories such as coupler lock, nuts, saddles, pipe hooks etc complete all as specified and directed.
M & L for sub main wiring in replacement of worn out aluminium conductor wire with two run of FR PVC insulated unsheathed flexible copper conductor (Multistrands), single core of size 4.0 Sqmm, 1100 Volts grade and one run of 2.5 Sqmm FR PVC insulated unsheathed as earth (In Green Colour), flexible copper conductor (Multistrands) for continuous earthing conforming to IS 694 with latest amendments and including draw in PVC rigid conduit 25 mm dia , connecting incoming / outgoing electric connections by using required size copper lugs / thimbles and making good the disturbed surface to match with existing colour (distumber, Oil bound, Samosem etc ) complete in all respect all as specified and directed. Note :- 1. Two run of single core cable with one run of contineous earth wire of copper conductor wire flexible (Multistrand) of FR PVC insulated shall be measured and paid as one unit length 2. PVC conduit pipe with fitting shall be measured and paid separately .
M & L for sub main wiring in replacement of worn out aluminium conductor wire with two run of FR PVC insulated unsheathed flexible copper conductor (Multistrands), single core of size 6.0 Sqmm, 1100 Volts grade and one run of 4.00 Sqmm FR PVC insulated unsheathed as earth (In Green Colour), flexible copper conductor (Multistrands) for continuous earthing conforming to IS 694 with latest amendments and drawing in PVC rigid conduit , connecting incoming / outgoing electric connections by using required size copper lugs / thimbles and making good the disturbed surface to match with existing complete in all respect all as specified and directed. Note :- 1. Two run of single core cable with one run of contineous earth wire of copper conductor wire Flexible (Multistrand) of FR PVC insulated shall be measured and paid as one unit length. 2. PVC conduit pipe with fitting shall be measured and paid separately .
Supplied and fixing in replacement PVC conduit by Non Metallic Rigid PVC conduit, ISI Marked, conforming to IS 9537, medium grade of size 25 mm dia including all fittings like bends, elbow reducer, junction boxes, tee bell mouth all fixing accessories such as coupler lock, nuts, saddles pipe hooks etc complete including Cutting & Chasing required on brick wall not exceeding 10 CM girth for concealed conduit wiring and making good to disturbed surface with cement mortar 1:3 and distemper / colour wash etc to match with existing surfaces including facing / finishing complete all as specified and directed.
Supply and fixing in replacement of LED bay Light of 90 Watt, with pressure die-cast aluminium housing with sealed toughened glass cover , light source SMD LED array with proper fixing arrangemetns as sepcified and directed by E-in-C. Make:- Cat Part of CROMPTON LHB-90-CDL/60, Cat part of Philips: BY400V LED72S CW SY60 PSU S2 FG WH or equivalent of wipro/bajaj
42. S & F in replacement of MCCB with continuously adjustable electronic release ,4 Pole, 415 VAC, Current rating- 400 Amps, Breaking capacity ( Icu ) - 36 KA with thermal setting between 70% to 100% and Ics is equal to 100% of Icu as per the Table- 1, page 13 of IS 13947 (Part-2) /1989, having over current/load protection setting O/L (lr) : 0.7 - 1 In & Short Circuit setting S/C : 2 -10 lr with Rotary Controls/Handle, conforming to IS 13947-II / IEC 60947 - II complete all as specified and directed . Make:- Legrand / Schenider(Electric) /HPL/Indoasian
43. S&F in replacement of MCCB with continuously adjustable electronic release ,4 Pole, 415 VAC, Current rating- 250 Amps, Breaking capacity ( Icu ) - 25 KA with thermal setting between 70% to 100% and Ics is equal to 100% of Icu as per the Table- 1, page 13 of IS 13947 (Part-2) /1989, having over current/load protection setting O/L (lr) : 0.7 - 1 In & Short Circuit setting S/C : 2 -10 lr with Rotary Controls/Handle, conforming to IS 13947-II / IEC 60947 - II complete all as specified and directed . Make:- Legrand / Schenider(Electric) /L&T/Indoasian
44. S&F in replacement of MCCB with continuously adjustable electronic release ,4 Pole, 415 VAC, Current rating- 100 Amps, Breaking capacity ( Icu ) - 25 KA with thermal setting between 70% to 100% and Ics is equal to 100% of Icu as per the Table- 1, page 13 of IS 13947 (Part-2) /1989, having over current/load protection setting O/L (lr) : 0.7 - 1 In & Short Circuit setting S/C : 2 -10 lr with Rotary Controls/Handle, conforming to IS 13947-II / IEC 60947 - II complete all as specified and directed . Make:- Legrand / Schenider(Electric) /L&T/Indoasian
Supply, fixing and testing in replacement of Old unserviceable/ worn out LED T8 Retrofit Tube light:Tara Series.LED T8 retrofit light 20 watt 240 volt,Light source SMD LED array having IP 6X protection complete, all as specified and directed including all accessories complete all as specified and directed . Cat part no. of Crompton: LTT8-20 or equivalent model in Phillips.
Supply only LED lamp retrofit 12 Watt, 230 volts,50 HZ,AC supply with base holder B22 white colour with polycarbonate body and aluminium heat sink complet all as specified and directed . Make:- Philips/Crompton/C&S.
Supply, fixing and testing in replacement of Old unserviceable/ worn out Gate light LED Post Top Lantern housing material is pressure die cast aluminium alloy with UV stablised clear one piece PMMA diffuser,indculding mounting arrangements having pipe dia 60 MM O.D. LED street light 30 watt 240 volt Mains current 0.145 Amps,Light source SMD LED array having IP 66 protection complete all as specified and directed including all accessories complete . Cat part No of Crompton:LPTO-40-CDL or equivalent model in Phillips.
Supply, fixing and testing in replacement of Old unserviceable/ worn out building secutiy light fitting by pressure die cast powder coated LED street light 30 watt 240 volt Mains current 0.140 Amps,suitable for mounting OD 40 mm,Light source SMD LED array having IP 66 protection complete all as specified and directed including all accessories complete all as specified and directed. Cat Part No of Crompton :LSTS-30-CDL or equivalent model in Phillips.
Supply and fixing in replacement of flood light fitting by LED flood light 120 Watt aluminium die cast powder coated housing and frame , high efficiency long life LEDs, high purity PMMA lenses for superior performance , toughened glass with EPDM gaskets for IP 65 protection ,loop in loop out connector, complete assembly with LED driver and accessories pre wired up to terminal block in control gear compartment , intergal covered control gear compartment with connector 240 volt AC, complete with all acessories as specified and directed . Make of wipro Cat No LF07-122-XXX-50-V5 ,Cat part of C & S : Orion-2.0/120W(LTEFI120WHPLED, Cat part of Bajaj: Turbo led flood light Cat part(BARFEG 120W LED) or equivalent philips.
Supply, fixing and testing in replacement of Old unserviceable/ worn out street light fitting by pressure die cast powder coated LED street light 90 watt 240 volt Mains current 0.39 Amps, in built integrated electronic LED driver toughened glass with silicon gaskets for IP 65 protection complete all as specified and directed including all accessories complete . Cat part no. LR02-102-XXX-57-XX of make Wipro or equivalent model in Phillips
S&F in replacement of LED surface mounted backlit panle: CYGNUS-CS SERIES recess/surface mounted poweder coated white CRCA full glow LED panle 36 watt LED fitting with proper fixing arrangemetns with LED complete as sepcified and directed. Make:- Crompton Cat No. LCLP54-36-CDL / Philips Cat No RC380B LED32S-6500 L120W30 PSU OD/Havells.
NOTE FOR LED LAMP AND LED LIGHT FITTINGS :- GUARANTEE FOR LED LIGHT FITTING AND LED LAMPS :- Contractor shall submit a guarantee of LED lamp and LED light fittings for a period of 02 (Two) years from the date of completion of work. In case any LED lamp and LED light fittings are not found functioning during this period, the same shall be replaced by the contractor without any extra cost to the department. The contractor should furnish a written guarantee for the satisfactory performance of LED lamp and LED light fittings for period of 02 years in favour of GE. The department may hold guarantee money equal to 2.5% of amount quoted against respective items.The contractor shall furnish FDR for said amount in favour of GE (I) R&D Kanpur.
SAKSHAM SUPPLIERS BUILDERS
VEE KAY ENTERPRISES
Lalta Prasad vijay kumar Forwarding Agency
G S SANDHU & CO.
stage.html
html • 0.05 MB
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.04 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .