| 1 | SITC of Iron Removal Filter | Supply, Assembly, Erection, Testing and Commissioning of 12.5 CUM per HR new generation Iron Remover Filter, Vertical cylindrical type, FRP composite vessel complete with UPVC frontal piping with suitable number of valves and pressure gauges for Service, Backwash, Rinse etc. along with initial charge of iron remover filter media and underbed supporting bed media (as per OEM design) and other accessories including suitable RCC platform complete as required and as per the direction of Engineer-in-charge (Maximum operating pressure of 10 kg per sq.cm). | 1 | Job | buycon147.aai.mn | 150 |
| 2 | | Supply, Assembly, Erection, Testing and Commissioning of 12.5 CUM per HR new generation Activated Carbon Filter, Vertical cylindrical type, FRP composite vessel complete with UPVC frontal piping with suitable number of valves and pressure gauges for Service, Backwash, Rinse etc. along with initial charge of activated carbon filter media and underbed supporting bed media (as per OEM design) and other accessories including suitable RCC platform complete as required and as per the direction of Engineer-in-Charge (Maximum operating pressure of 10 kg per sq.cm). | 1 | Job | buycon147.aai.mn | 150 |
| 3 | SITC of Multigrade Filter | Supply, Assembly, Erection, Testing and Commissioning of 12.5 CUM per HR new generation Multigrade Filter, vertical cylindrical type, FRP composite vessel complete with UPVC frontal piping with suitable number of valves and pressure gauges for Service, Backwash, Rinse etc. along with initial charge of coarse and fine sand filter media and underbed supporting bed media (as per OEM design) and other accessories including suitable RCC platform complete as required and as per the direction of Engineer-in-Charge (Maximum operating pressure of 10 kg. per sq.cm). | 1 | Job | buycon147.aai.mn | 150 |
| 4 | SITC of Sodium Hypochlorite metering Dosing System | Supplying, installing, testing and commissioning of Sodium Hypochlorite metering dosing system consisting of one HDPE tank with lid of 500 litres capacity with positive displacement diaphragm dosing pumps (One Main and One Standby) having variable flow rate of 0-15 lph along with initial filling of Hypochlorite solution and necessary electrical connections. The motor shall be suitable for operation at 240 V, single phase, 50Hz Supply. The pumps shall be supplied complete with necessary polypropylene piping, valves, strainers, low level switch and injection fittings. The pump shall be speed and stroke control Motors shall be of energy efficient type meeting the latest BIS or ECBC guidelines compete as per site requirement. | 1 | Job | buycon147.aai.mn | 150 |
| 5 | Supply and Laying of 80 mm dia UPVC Pipeline | Supplying and laying of following dia UPVC pipeline along with UPVC plumbing fittings such as Tees, crosses, plugs, sockets, elbows, reducers, Union, sleeve pieces, checknuts, gaskets, nuts, bolts and other accessories etc. including cutting of pipe, fixing of UPVC plumbing fittings using UPVC adhesives etc. as required for making necessary connections as follows- (Note- All UPVC fittings for necessary pipeline connections are to be arranged by the Contractor and Linear measurement will be carried out considering pipe and other pipeline accessories).
a) 80 mm dia. | 60 | Mtr | buycon147.aai.mn | 150 |
| 6 | Supply and Laying of 65 mm dia UPVC Pipeline | Supplying and laying of following dia UPVC pipeline along with UPVC plumbing fittings such as Tees, crosses, plugs, sockets, elbows, reducers, Union, sleeve pieces, checknuts, gaskets, nuts, bolts and other accessories etc. including cutting of pipe, fixing of UPVC plumbing fittings using UPVC adhesives etc. as required for making necessary connections as follows- (Note- All UPVC fittings for necessary pipeline connections are to be arranged by the Contractor and Linear measurement will be carried out considering pipe and other pipeline accessories).
b) 65 mm dia. | 20 | Mtr | buycon147.aai.mn | 150 |
| 7 | Making Core Cutting in Cement Concrete | Making Core cutting of diameter upto 3 inch in the cement concrete of the underground sump of thickness 20 cm and making necessary finishing after laying the pipe. | 2 | Job | buycon147.aai.mn | 150 |
| 8 | | Supply of non-clogging self-priming centrifugal monoblock pump having CI casing and impeller suitable for operation on 415V, 50Hz AC supply with discharge capacity of minimum 12.5 cum per hr and head of minimum 15 Mtr, motor of required capacity, non-sealed construction, insulation Class H complete as required and as per direction of Engineer-in-Charge. | 3 | Each | buycon147.aai.mn | 150 |
| 9 | Supply of MS Stand for Monoblock Pump | Supply of MS stand for monoblock pump set supplied by OEM or Fabricated as per OEM recommendation for fixed floor mounting, painting with approved primer and two coat enamel paints as per the specification complete as required. | 50 | Kg | buycon147.aai.mn | 150 |
| 10 | | Installation, Testing and commissioning of monoblock pump set along with suitable stand including Grouting, fixing of MS Stand and pump set in position using all fasteners, clamps, nut, bolts etc. complete as required. | 3 | Job | buycon147.aai.mn | 150 |