Loading…
Loading…
| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | L1₹26.4 LAccepted-AOC 203 1 THIRUMATHI SUNDARI ILLAM CHINNAMMEN KOIL STREET AVADI CHENNAI 600 054 | CHENNAI | THIRUVALLUR | TAMIL NADU | 600054 | L1 | Accepted-AOC Being L1 | |
| 2 | L2₹29.1 L+₹1.8 L (6.61%)Rejected-Finance NO 229 ANGAPPAN STREET MITTANAMALAI AVADI IAF CHENNAI 600 055 | CHENNAI | CHENNAI | TAMIL NADU | 600055 | L2 | Rejected-Finance Not Being Lowest |
| Sl No | Description | Qty | Unit | pmv.enterprises L1 | muthu constructions L2 |
|---|---|---|---|---|---|
| 1.00 | Excavation in trenches not exceeding 1.5 m wide and not exceeding 1.5 m depth and getting out any type of soil for laying cables / pipes / erection of poles etc all as specified and as directed. | 864 | Cum | 171 ₹1,47,744 | 170 ₹1,46,880 Lowest |
| 2.00 | Removing excavated material(soil)not exceeding 50 m and depositing where directed at a level not exceeding 1.5 m above the starting point all as specified and as directed. | 364 | Cum | 81 ₹29,484 | 80 ₹29,120 Lowest |
| 3.00 | Returning filling in soil including spreading leveling watering well ramming in layers not exceeding 25 cm each all as specified and as directed. | 500 | Cum | 81 ₹40,500 | 80 ₹40,000 Lowest |
| 4.00 | Laying in trenches fine sieved excavated dry soil including spreading/leveling, cushioning for underground cables all as specified and as directed. | 259 | Cum | 98 ₹25,382 | 80 ₹20,720 Lowest |
| 5.00 | Supply and laying of common burnt clay building bricks, sub class B size for cable protection all as specified and as directed. | 25,600 | Each | 4.5 ₹1,15,200 Lowest | 5 ₹1,28,000 |
| 6.00 | Material and labour for XLPE insulated, armoured, heavy duty electric cable with aluminum conductor, 1100 volts grade, 3.5/4 in replacement of the following sizes cross-sectionl area including taking down of old unserviceable cable/OH line ACSR conductor of any type complete all as specified and as directed:-
10 sq mm 2 core
(Note: Earth work and connected items will be measured and paid separately under respective items of schedule) | 380 | RM | 90 ₹34,200 | 83 ₹31,540 Lowest |
| 7.00 | All as per item No 6.00 here in before but for 16 sq mm 4 core | 450 | RM | 154 ₹69,300 | 110 ₹49,500 Lowest |
| 8.00 | All as per item No 6.00 here in before but for 25 sq mm 3.5/4 core | 650 | RM | 171 ₹1,11,150 | 155 ₹1,00,750 Lowest |
| 9.00 | All as per item No 6.00 here in before but for 35 sq mm 3.5 Core | 460 | RM | 198 ₹91,080 | 190 ₹87,400 Lowest |
| 10.00 | All as per item No 6.00 here in before but for 50 sq mm 3.5 Core | 330 | RM | 243 ₹80,190 | 220 ₹72,600 Lowest |
Tender Value
₹46 L
EMD Value
₹92,000
Closing Date
26 Aug 2025, 6:00 pmClosed
Garrison Engineer, Avadi
Garrison Engineer , Muthapudupet, Air Force Area, Avadi, Chennai-55
REPAIR/REPLACEMENT OF LT SWITCH GEAR SYSTEM (MCCB AND CHANGE OVER SWITCH) INCL EXTERNAL LIGHT FITTING SYSTEM AND ALLIED WORKS AT AF STN UNDER GE AVADI.
2025_MES_723972_1
8313/E8
Open Tender
Electrical and Maintenance Works
Item Rate
260 days
GE Avadi
As per Tender document
7 documents required · 7 mandatory
₹500
GE Avadi
₹92,000
Yes
7 Oct 2025
1 Aug 2025
28 Aug 2025
1 Aug 2025
26 Aug 2025
9 Aug 2025
1 Aug 2025 - 6 Aug 2025
Amount
Excavation in trenches not exceeding 1.5 m wide and not exceeding 1.5 m depth and getting out any type of soil for laying cables / pipes / erection of poles etc all as specified and as directed.
Removing excavated material(soil)not exceeding 50 m and depositing where directed at a level not exceeding 1.5 m above the starting point all as specified and as directed.
Returning filling in soil including spreading leveling watering well ramming in layers not exceeding 25 cm each all as specified and as directed.
Laying in trenches fine sieved excavated dry soil including spreading/leveling, cushioning for underground cables all as specified and as directed.
Supply and laying of common burnt clay building bricks, sub class B size for cable protection all as specified and as directed.
Material and labour for XLPE insulated, armoured, heavy duty electric cable with aluminum conductor, 1100 volts grade, 3.5/4 in replacement of the following sizes cross-sectionl area including taking down of old unserviceable cable/OH line ACSR conductor of any type complete all as specified and as directed:- 10 sq mm 2 core (Note: Earth work and connected items will be measured and paid separately under respective items of schedule)
All as per item No 6.00 here in before but for 16 sq mm 4 core
All as per item No 6.00 here in before but for 25 sq mm 3.5/4 core
All as per item No 6.00 here in before but for 35 sq mm 3.5 Core
All as per item No 6.00 here in before but for 50 sq mm 3.5 Core
All as per item No 6.00 here in before but for 70 sq mm 3.5 Core
All as per item No 6.00 here in before but for 95 sq mm 3.5 Core
All as per item No 6.00 here in before but for 120 sq mm 3.5 Core
All as per item No 6.00 here in before but for 185 sq mm 3.5 Core
Taking out from trenches/poles/wall etc LT XLPE UG Cable /PVC Sheathed aluminium conductor armoured and relaying after fault rectification duly tested in trenches/Poles/Wall of following sizes : LT UG Cable 4 core 16 Sqmm (Note: Earth work and connected items will be measured and paid separately under respective items of schedule)
All as per item No 15.00 here in before but for LT UG Cable 3.5/ 4 core 25 Sqmm to 3.5 core 50 Sqmm
All as per item No 15.00 here in before but for LT UG Cable 3.5 core 70 Sqmm to 3.5 core 120 Sqmm
All as per item No 15.00 here in before but for LT UG Cable 3.5 core 150 Sqmm to 3.5 core 185 Sqmm
Testing the cables with high voltage DC testing machine and locating the fault in the cables by fault locating machine to pin point exact position of fault, disconnecting faulty 1.1 KV LT cables of different sizes from both ends, removal of Fault, Re-connections and testing of cables after removal of fault complete all as specified and directed. Note: (a) Excavation,earth work,cable & joints shall be measured and paid for seperately under respective items of schedule. (b) Material and labour for emergency maintenance work of LT cable line during breakdown by deploying skilled electricians at faulty site including transportation and other tools and plant required at site for fault rectification.(c) Contractor or his rep shall come to the site of breakdown within two hours of notification of breakdown. In case the contractor or his rep shall not come to the site of breakdown and start attending breakdown within two hours, a penalty of Rs 600 per fault per hour shall be imposed over contractor and shall be deduct from his dues.
Supply and Fixing of Straight through joints heat shrink type for underground cable suitable for LT XLPE/ PVC sheathed/ armoured heavy duty cables with aluminium conductor all as specified and as directed for 3.5/ 4 core, 16 sqmm to 50 sqmm
All as per item No 20.00 here in before but for 3.5/ 4 core, 70 sqmm to 120 sqmm
All as per item No 20.00 here in before but for 3.5/ 4 core, 150 sqmm to 185 sqmm
Material and labour for GI tubing light grade for cable protection laid in trenches in road crossing or fixed to wall/Pole of following sizes including taking down old unserviceable one complete all as specified and as directed for Bore of tube 40mm
All as per item No 23.00 here in before but for Bore of 50mm
All as per item No 23.00 here in before but for Bore of 80mm
Supply ,Fabricate, install, connect, test and commissioning Busbar chamber, powder coated, outdoor weather proof type, compartmentalised fabricated with 3 mm thick CRCA steel and suitable sized pressed steel frame work, top with sloping canopy, bottom with detachable plates, front and rear with hinged type door and locking arrangements, chamber for cable entry and exit , chamber for aluminium busbars, separate compartment for switch gear, louvers and air vent for natural air flow, holes drilled for connection including suitable angle iron/flat iron frame work/ supports, excavation, earth work, PCC foundation etc., as required with and including following switch gear items internally connected with suitable capacity aluminium strip/ rods insulated, complete mounted on PCC pillars including taking down the old busbar chamber and demolition of old plain cement concrete complete all as specified and comprising of the followings:- (i) 4 Nos busbar of equal size of Aluminium conductor with PVC coloured heat shrinkable type sleeves continuous rating of 400 Amps mounted on fibre reinforced insulator.(1set), with LED indication lamps-03 Nos for RYB phases on incoming side. (ii) MCCB fixed thermal magnetic release type of capacity 200 amps, 4 pole, 36 kA.- 1 No. (i) 4 Nos busbar of equal size of Aluminium conductor with PVC coloured heat shrinkable type sleeves continuous rating of 400 Amps mounted on fibre reinforced insulator.(1set), with LED indication lamps-03 Nos for RYB phases on incoming side. (ii) MCCB fixed thermal magnetic release type of capacity 200 amps, 4 pole, 36 kA.- 1 No. (iii) On load change over switch 200 Amps ,4 pole 415 volts ,3 phase , 50 Hz AC - 01 No Note : MCCB shall be front handle operated.
Supply ,Fabricate, install, connect, test and commissioning Busbar chamber, powder coated, outdoor weather proof type, compartmentalised fabricated with 3 mm thick CRCA steel and suitable sized pressed steel frame work, top with sloping canopy, bottom with detachable plates, front and rear with hinged type door and locking arrangements, chamber for cable entry and exit , chamber for aluminium busbars, separate compartment for switch gear, louvers and air vent for natural air flow, holes drilled for connection including suitable angle iron/flat iron frame work/ supports, excavation, earth work, PCC foundation etc., as required with and including following switch gear items internally connected with suitable capacity aluminium strip/ rods insulated, complete mounted on PCC pillars including taking down the old busbar chamber and demolition of old plain cement concrete complete all as specified and comprising of the followings:- (i) 4 Nos busbar of equal size of Aluminium conductor with PVC coloured heat shrinkable type sleeves continuous rating of 400 Amps mounted on fibre reinforced insulator.(1set), with LED indication lamps-03 Nos for RYB phases on incoming side. (ii) MCCB fixed thermal magnetic release type of capacity 200 amps, 4 pole, 36 kA.- 1 Nos. (iii) On load change over siwtch 200 Amps ,4 pole 415 volts ,3 phase , 50 Hz AC - 01 No Note : MCCB shall be front handle operated.
Supply ,Fabricate, install, connect, test and commissioning Busbar chamber, powder coated, outdoor weather proof type, compartmentalised fabricated with 3 mm thick CRCA steel and suitable sized pressed steel frame work, top with sloping canopy, bottom with detachable plates, front and rear with hinged type door and locking arrangements, chamber for cable entry and exit , chamber for aluminium busbars, separate compartment for switch gear, louvers and air vent for natural air flow, holes drilled for connection including suitable angle iron/flat iron frame work/ supports, excavation, earth work, PCC foundation etc., as required with and including following switch gear items internally connected with suitable capacity aluminium strip/ rods insulated, complete mounted on PCC pillars including taking down the old busbar chamber and demolition of old plain cement concrete complete all as specified and comprising of the followings:- (i) 4 Nos busbar of equal size of Aluminium conductor with PVC coloured heat shrinkable type sleeves continuous rating of 600 Amps mounted on fibre reinforced insulator.(1set), with LED indication lamps-03 Nos for RYB phases on incoming side. (ii) MCCB fixed thermal magnetic release type of capacity 400 amps, 4 pole, 36 kA.- 1 Nos. (iii) On load change over siwtch 400 Amps ,4 pole 415 volts ,3 phase , 50 Hz AC - 01 No Note : MCCB shall be front handle operated.
Boring under roads without disturbing the top surface of the road for passing through the cables with using of 75 mm dia HDPE pipe. (Note : 1. Necessary infrastructure(Tools, Plants,Machinery and any eqpts) reqd for boring shall be arranged by the Contractor and rates deemed to be included for quoted rate. 2. HDPE pipe shall be measured and paid separately under relevant items) complete all as specified and directed.
M&L for 75 mm dia HDPE pipe PN-10 with fittings laid in trenches/wall for protection of underground cable when crossing the road/fixing on wall as in repair and all as specified and directed.
M & L for Cutting of road/path for laying of GI tubing and making the good to disturbed road/ path including provision of PCC 1:2:4 type B-1 using 20mm graded stone aggregate all as specified and directed.
S&F in replacement of LED energy saving High bay light fitting for capacity 150 watt, IP65 with high efficancy integrated electronic drivers fixed at hangers/sheds complete including connection to light fitting with suitable size of connection cable complete with suitbale fixing arrangements of trusses controlled complete all as specified and directed.
Supply and Fixing of LED flood light fitting,230 V,AC, 50 W, LED, outdoor type,heat resistance toughened glass with frame IP 65/ 66 protection with driver, complete fixed on existing / New bracket and making connections including taking down the old one complete all as specified and as directed .
Supply and Fixing of LED flood light fitting,230 V,AC, 100 W, LED, outdoor type,heat resistance toughened glass with frame IP 65/ 66 protection with driver, complete fixed on existing / New bracket and making connections including taking down the old one complete all as specified and as directed .
Material and labour for 1100 volts grade heavy duty cable PVC insulated , PVC sheathed,fire resistant, round ,copper conductor, 3 core industrial cable of size 1.50 sqmm including taking down the old one complete all as specified and as directed.
All as per item No 35.00 here in before but for size of 2.50 sqmm including taking down the old one complete all as specified and as directed.
Material and Labour for MCCB 63 amps ,4 pole 415 volts ,3 phase ,50 Hz AC, 16 KA breaking capacity. The MCCBs shall have spreader links and barriers as standard feature of manufacturer including taking down old unserviceable one complete all as specified and as directed.
All as per item No 37.00 here in before but for of capacity 100/125 amps, 25 KA including taking down old unserviceable one complete all as specified and as directed.
All as per item No 37.00 here in before but for of capacity 160 amps, 36 KA including taking down old unserviceable one complete all as specified and as directed.
All as per item No 37.00 here in before but for of capacity 200 amps, 36 KA including taking down old unserviceable one complete all as specified and as directed.
All as per item No 37.00 here in before but forof capacity 250 amps, 36 kA including taking down old unserviceable one complete all as specified and as directed.
All as per item No 37.00 here in before but for of capacity 400 amps, 26 ka including taking down old unserviceable one complete all as specified and as directed.
M&L for open enclosure type, on load change over siwtch 200 Amps ,4 pole 415 volts ,3 phase ,50 Hz AC suitable for fixing in Panels incl taking down old unsv complete all as specified and as directed.
M&L for earthing complete with galvanised steel earth plate electrode of size 60cm x 60cm x 6mm thick burried directly in ground vertically at a depth not less than 2.25 metre deep below normal ground level with top edge of the plate not less than 1.5 metre below normal ground level surrounded from all sides by 15 cm thick packed layer of charcoal dust and common salt, filling in alternate layer and electrode connections by using galvanised iron strip 25×4mm dia by means of bolts, nuts, check nuts and washers made of copper or brass and protected by light grade 15 mm dia GI pipe connected to main switch board or main control board, and GI pipe light grade 20 mm bore for watering and including funnel, wire mesh, RCC pit cover and PCC chamber pit with PCC 1: 2: 4 type C2 including excavation and earth work, disposal of surplus soil to a distance not exc. 50 mtr all as specified and as shown on Plate No 5 of SSR Part I (2009) all as specified and directed.
Material and labour, Earth continuity conductor or main earthing conductor 25mmx4mm galvanised iron strip, fixed to wall on batten with saddles and fixing screws or PVC/ Porcelain insulators etc. or recessed or chases or burried in ground or drawn in conduit/pipe or fixed to poles or any other indicated situation for loop earthing etc. as required, including brazing on both sides (over lapping) at all joints complete all as specified and directed.
Repair of earth pit incl required exacavation, earth work and PCC work to make good damaged/disturbed surfaces of earth pit chamber & making new pit cover of RCC 1:2:4 type B-1 using 20mm graded stone aggregate reinforced and lifting handle on RCC cover with 8 mm MS bars at 150 mm centre to centre both ways incl supply & fixing of wire mesh and funnel including re-connection of earth wire/strip with panel/eqpts using GI nut, bolts & washer complete all as specified & directed
muthu constructions (BID ID -3392234)
stage.html
html • 0.04 MB
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .