Loading…
Tenderkart now works inside Claude and ChatGPT: search and analyse tenders right from your chat
Loading…
Tender ID
Eligibility, documents, scope, Go/No-Go checksEligibility, required documents, scope of work and Go/No-Go checks for this tender, in one click.
Tender Value
Refer Docs
EMD Value
₹3.1 L
Closing Date
7 Dec 2026, 3:00 pm
Eligibility, documents, scope, Go/No-Go checksEligibility, required documents, scope of work and Go/No-Go checks for this tender, in one click.
Karnataka Power Corporation Limited
Kantharaja
Design, engineering, manufacturing, quality surveillance, shop testing Inspection before dispatch, packing and forwarding, arranging for transit insurance on FOR destination basis. 02(two) sets of Static Excitation equipments each comprising the following. i.100 percent redundant two independent thyristor convertors of suitable capacity to cater to the maximum continuous and ceiling current requirements. ii.Digital automatic voltage regulator with dual auto and dual manual channels as redundancy, provided with all standard limiter functions, PSS facility parameter tuning and testing facilities, as per latest IEGC/SRPC stipulations on both Auto channels with required no. of Digital Input, Digital Output, Analog Input, Analog Output, 100 percent redundant power supply units, HMI & pushbuttons along with standard protections to provide total Excitation system functionality. iii.Field flashing (both AC & DC) for excitation start up. iv.Field breaker and field discharge & suppression equipments. One set of Essential spares (Mandatary spares. ERECTION, TESTING & COMMISSIONING Dismantling of existing system, erection, testing & commissioning of the above new equipments in complete to provide complete functionality of static excitation system.
KPCL/2026-27/PS/WORK_INDENT5016
KPCL/2026-27/PS/WORK_INDENT5016
Open
Power stations
Two Tender Document System(Two Cover)
KPCL Chief Engineer ED office Bengaluru
10 documents required · 9 mandatory · 1 optional
List of existing commitments and ongoing works
List of works for which tenders already submitted
Reports on the financial standing of the tenderer, such as profit and loss statements and auditor’s reports for the last five years
The bidder shall be a regular manufacturer of Static Excitation system and shall have manufacturing facility in India and shall have supplied, installed and commissioned Static Excitation system for a Generating Unit of minimum capacity of 50 MW or higher and the same is performing satisfactorily in India for at least One year in the preceding five years from the date of NIT.
The Bidder shall have achieved a minimum annual turnover of Rs.414 Lakhs in any two years of preceding five financial years i.e. from 2020-21 to 2024-25. Annual financial statements and reports duly audit & certified by the chartered accountant for at least two financial years in the last five years to establish the minimum financial annual turnover requirement stipulated.
The intending bidder shall not have been subject to forfeiture of EMD/foreclosure/termination of their Contract in KPCL or Government or any other utility or shall not have been blacklisted for participating in tender by KPCL or Government or any other utility in India during the past three years.Bidder shall furnish the notarized declaration as specified in Schedule-11 of the bid. (Declaration by the bidder shall be on Rs.200/- non-judicial stamp paper purchased in Karnataka and duly signed by the Notary).
Not applicable
Not applicable
Not applicable
Not applicable
Not applicable
Not applicable
Not applicable
Not applicable
Not applicable
Not applicable
₹5,000
₹3.1 L
6 Nov 2026
6 Nov 2026
9 Dec 2026
21 Nov 2026
23 Nov 2026
GUARANTEED TECHNICAL PARTICULARS FOR STATIC EXCITATION EQUIPMENT
Sl No. DETAILS Guaranteed technical Particulars to be furnished by the Bidder
I STATIC EXCITATION EQUIPMENT
a Overall Dimension in mm.
(length x breadth x height)
1. Regulation panel
2. Thyristor panel
4. Field flashing Panel
b Degree of protection
1. Regulation panel
2. Thyristor panel
4. Field flashing Panel
c Thickness of sheet steel
1. front and rear
2. sides and top
d Power cable exit from the cubicle (Top/Bottom)
e control cable exit from the cubicle (Top/Bottom)
f Material and thickness of gland plate
g Lables for each equipment (yes/No)
h Whether Following accessories provided
1. space heater (Yes/No)
2. lighting fixture (Yes/No)
3. plug point (Yes/No)
4. Earthing Bus bar (Yes/No)
i Weight of panel
1. Regulation panel in Kgs.
2. Thyristor panel in Kgs.
3. FCB panel in Kgs.
4. Field flashing Panel in Kgs
II EXCITER (THYRISTOR CONVERTOR)
b Rated exciter output voltage in volts
(corresponding to generator rated output)
c Rated DC output in Amps
d Maximum continuous DC output rating in Amps
e Short time rating in Amps (specify time)
f Ceiling voltage in Volts
g Ceiling current and duration (Amps/Sec)
h Ability of the excitation system to operate under all conditions of duty cycle
I Type of converter
j No. of converters
k Rating of each converter bridge
l Power for the excitation equipment
1. Required supply voltage in Volts
2. No. of phases
3. Rated frequency in Hz
m Type and make of Thyristor
n Rated PIV of thyristor
o Rated current of thyristor
p Maximum current rating of thyristor
q Thyristor element cooling method
1.Natural/Forced
2. No of Cubicle fans/Bridge
3. Rating of Cubicle fans (KW,A,V)
4. Monitoring of air flow
a. Air Flow sensors or Junction Temperature
b. Make & Type of air flow sensor
r No. of bridges per cubicle
s No. of thyristors per converter bridge
t Thyristor junction temperature at rated current
u Whether each thyristor bridge is provided with Main and standby fans
v Thyristor fuses:
a.Rating: type & and make
b. No of fuses /Thyristor
c. Whether fuses are supervised
w Maxiumum ripple content at rated current
x Whether supply Change over links provided for connecting Test transformer.
3.Details of Micro Switch Provided
4.Type of switch as ON Load or OFF Load
3.Details of Micro Switch Provided
4.Type of switch as ON Load or OFF Load
III FIELD FLASHING
b AC field flashing details
1) Required power source
2) Rating of transformer used in KVA
3) Details of Diode Bridge
c DC field flashing details
1) Required power source
2) Ratings of diodes used
d DC Out put voltage in Volts.
IV AUTOMATIC/ DIGITAL VOLTAGE REGULATOR
b No of channels Provided
c Whether Auto/manual mode of operation possible in both the channels
d Whether each CPU (AUTO / MANUAL- Channel 1 and 2) shall be able to control all the thyristor bridges (thyristor converter).
e Range of voltage setting in %
f Response time
g Excitation response ratio
h Operating frequency range
j Steady state accuracy
k Limiters provided ( List to be furnished separately)
l Alarms provided ( List to be furnished separately)
m Protections provided ( List to be furnished separately)
n Provision for PSS module/scheme
o Whether redundancy in power supply
p No of Input And Output Modules
q Type of Input/Out put
I Total No. of Binary Inputs and Outputs
Whether Binary inputs provided for:
1. Field breaker/ Excitation Open & Close.
2. Selection of Auto/manual mode
3. Selection of channel in operation
4. MVAR Regulator On/Off.
5. Set Point Raise/Lower
6. MVAR raise/lower
7. Master trip relay healthy
8. Unit lock out relay operated
9. Generator Off line & On line.
10.Speed interlock
11. Auto synchronising
12. AC/DC isolator open
13. Loss of Cooling/Junction temp high
14. AVR in test
15. Other inputs
16. Thyristor Fuse Fail
17. PSS ON and OFF
18. Over excitation Limitor in action
19. Under excitation Limitor in action
Whether Binary outputs provided for:
1. Loss of converter
3.Warning alarms
4. Auto to Manual mode change over
5.Channel Changeover
6. Limiters in action
7.Status indications for Field breaker.
8. Status indications for Excitation.
9. Status indication for channel selection
10. Status indication for mode selection
11. Status indication for MVAR mode selection.
12.Other out puts (Details to be furnished)
II Total No. of Analog Inputs And Outputs
Whether provision of taking following
Analog inputs provided :
1. Generator Voltage from PT's (110V ) for all
the three phases
2. Generator current from CT's ( 5A and 1A) for all the
3. Other inputs (Details to be furnished)
4. Excitation Transformer CT secondary current.
Whether Analog outputs provided for:
1.Field current, if yes signal range
2.Field voltage, if yes signal range
3.Rotor Temperature, if yes signal range
4.Other Outputs (Details to be furnished)
(Write up of each module to be furnished
o Local MMI (Micro Terminal) and other Details:
1.Display and no. of characters
2.Parameters Displayed
3.Whether all settings can be viewed & modified
4.Whether Self Diagnostic Feature Provided
p POWER SUPPLY TO REGULATOR:
1. Rating & No. of Power Supply Modiles (DC-DC)
2. Rating & no. of Power Supply Modules(AC-DC)
3.Whether separate power supplies are
provided for each channel
4. type of source: separate or integrated type
V DETAILS OF FIELD CIRCUIT BREAKER
c Rated voltage
d Rated current
e Rated short time current for 0.2sec
f Rated breaking capacity at rated short time voltage
g Rated maximum breaking current
h Rated breaking current at rated max.breaking voltage
I Rated number of operations
l Field discharge resistor rating (KW, Amps,Ohms to be specified)
m Close & trip coil voltage
n whether manual closing is provided
o Whether Polarity change over links provided
p Opening time of Discharge contact
q No of NO and NC contacts.
r FCB Trip coil monitoring
s Whether FCB having two main contacts and one discharge contact with arc chutes is provided
VI REQUIRED POWER SOURCE
b Field flashing
c Lighting & testing Regulation panel
d Thyristor cooling
VII DETAILS OF ROTOR TEMPERATURE MEASUREMENT
1 Whether rotor temperature measurement is a part of soft ware or separate maths module provided
2 Signal range for inputs
a. Field voltage
b. Field current
3 Out put Signal range
4 No of output signals
VIII DETAILS OF ROTOR OVER VOLTAGE PROTECTION:
2 No. & rating of thyristers used
3 Pickup over voltage
4 No. of output contracts provided
IX DETAILS OF EXCITATION TRANSFORMER PROTECTION:
I OVER TEMPERATURE:
1 Details of temperature protection relay
i) Warning set temperature
ii)Trip set temperature
iii) Details of display unit.
iv) Type of Thermistors and RTDs
II OVER CURRENT:
OVER CURRENT RELAY
iii)Delayed Setting
iv) Instantaneous setting
X DETAILS OF MCB'S, TIMERS,AUXILIARY CONTACTORS AND RELAYS
A Miniature Circuit Breaker:
1. Make and rating
2. Quantity used
1. Make and rating
2. Quantity used.
C Auxiliary relays:
1. Make and rating
2. Quantity used.
D Auxiliary Contactors
1. Make and rating
2. Quantity used
XI Details of Networking system
1 Make and type of the Ethernet switches
2 Details of Optical fibre cable
3 Details of application software proposed for server PC
4 Details of application software proposed for engineer's laptop
5 Details of any other accessories proposed for networking.
Seal & Signature of the Bidder
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
3 e-nit SECTION-I - GENERAL CONDITIONS-FINAL.pdf
Tender Document • 0.42 MB
4 e-nit-SECTION II - Brief Description.pdf
Tender Document • 0.26 MB
Schedule 15-GTP-SUPA-FINAL.xlsx
Others - Guaranteed Technical Particulars • 0.02 MB
5 e-nit SECTION-III -SCC.pdf
Tender Document • 0.29 MB
1 e-nit detailed.pdf
Others - e-NIT detailed • 0.24 MB
6 e-nit SECTION-IV- ERECTION CONDITIONS.pdf
Tender Document • 0.34 MB
1 e-nit notice.pdf
Others - e-NIT • 0.12 MB
2 e-nit INSTRUCTION TO BIDDERSFINAL.pdf
Instructions to Tenderers • 0.34 MB
Annexure - A and B.doc
Others - Annexure - A&B • 0.18 MB
Schedules 1-14-FINAL.doc
Others - Schedule 1 to 14 • 0.13 MB
7 SECTION- V -Tech spec -FINAL.pdf
Tender Document • 0.47 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .