Loading…
Loading…
| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | L1₹36.1 LAccepted-AOC | L1 | Accepted-AOC Being L1 | |
| 2 | L2₹39.4 L+₹1.6 L (4.31%)Rejected-Finance | L2 | Rejected-Finance Being L2 | |
| 3 | L3₹40.2 L+₹2.4 L (6.47%)Rejected-Finance | L3 | Rejected-Finance Being L3 | |
| 4 | L4₹41.6 L+₹3.9 L (10.2%)Rejected-Finance | L4 | Rejected-Finance Being L4 | |
| 5 | L5₹43.3 L+₹5.5 L (14.6%)Rejected-Finance | L5 | Rejected-Finance Being L5 |
Tender Value
₹38.5 L
EMD Value
₹76,960
Closing Date
9 Feb 2022, 6:00 pmClosed
HQ CWE Hisar
Hisar Military Station Hisar-125006
CWE/HSR-25 OF 2021-22 SPL REPAIR TO VCBS, RMUS, LT PANELS AND ALLIED WORKS AT HISAR MIL STN UNDER GE HISAR
2021_MES_497705_2
CWE/HSR-25 OF 2021-22
Open Tender
Civil Works
Item Rate
180 days
Hisar Military Station
As per tender documents
9 documents required · 9 mandatory
₹500
GE Hisar
₹76,960
24 Feb 2022
29 Jan 2022
11 Feb 2022
29 Jan 2022
9 Feb 2022
2 Feb 2022
Amount
Disconnecting and taking out non functional VCB of any make of rating 11 KV, 630 Amp/ 800 Amps dismantling / opening of the VCB for servicing / overhauling taking out and removing unserviceable/ defective parts including cleaning and servicing, greasing , oiling of the parts etc and replacement of unserviceable parts with new one, reassembling the VCB after overhuling / servicing and its testing complete all as specified and directed. Note :- The quoted rate of the contractor includes for fixing the serviceable parts in position and replacement of unserviceable parts with new parts. The new replaced parts shall be measured and paid separately under appropriate item of Sch 'A' as supply only. Make : CG, Areva & Simens
Supply only spring charging motor & gear assembly 110V AC/DC
Supply only push botton bracket assembly
Supply only Big gear assembly . Make -CG
Supply only small gear half girari, assembly with motor shaft ,11 KV breaker .
Supply only Closing coil assembly 24 Volt
Supply only Tripping coil assembly, 24 volt
Supply only Closing coil assembly, 110 Volt
Supply only Tripping coil assembly, 110 volt
Supply only TNC Switch
Supply only Anti pumping device
Supply only Motor cut off switch KC
Supply only Pulg & Socket Assembly
Supply only Auxillary switch (7 NO + 7NC) model 33 PO24
Supply onlyNumerical relay CGI-14 CGL
Supply only breaker operatiing mechanism of VCB, moter wound spring oprated, moter operatubg vitage 110/220 V AC and charging motor powr 80-150W etc Make- CG
Supply only breaker operatiing mechanism of VCB Make- Areva
Supply only Potential transformer (PT) , three phase ,drow out type, indoor type,110 V, 12 KV ration 11000/110V
Supply only tranformer of Current transformer ration (CT) 100-50/5,5A
Disconnection & repairs to vaccum circuit breaker panel incl replacement of Indicating lamps LED,24V,2 Watt with holder,any type ( Red/ Green/ White/ Amber /blue)
Disconnection & repairs to vaccum circuit breaker panel incl replacement ofPhase indicating lamps 110V AC with holder (Red/ Yellow / Blue)
Disconnection & repairs to vaccum circuit breaker panel incl replacement of Push button actuator 1 No element, 22.5mm dia (TCH).
Disconnection & repairs to vaccum circuit breaker panel incl replacement of Thermostat range 30-90 deg celcius.
Disconnection & repairs to vaccum circuit breaker panel incl replacement of Bakelite HRC fuse base with carrier 2A, 4A,6A & 10A
Disconnection & repairs to vaccum circuit breaker panel incl replacement of Power factor meter 3 phase, 2 element dynamometer type.
Disconnection & repairs to vaccum circuit breaker panel incl replacement of Digital Ammeter 96mm x 96mm , three phase, range 100/1600 AC, input 5A AC, accuracy class-0.5, Auxillary supply 110V AC, 50Hz . Make AE
Disconnection & repairs to vaccum circuit breaker panel incl replacement of Digital AC voltmeter 96mm x 96mm , three phase, 30 V to 600V AC, Range O-15KV, Accuracy class 0.5 PTR 11KV/110V, Auxillary supply 110V AC 50Hz, Make AE
Calibration of relays, 11 KV of any description through primary and secodary injection method and testing complete re-setting where required and ensuring proper functioning of earth fault and over current relays complete all as specified and directed. Make : CG, Areva & Simens.
Disconnecting electric supply and earthed the Ring Main Unit (RMU) of cap upto 800 Amps of any make of rating 11 KV, opening of the RMU for servicing / overhauling the mechanism including cleaning and servicing, greasing, oiling of the parts etc reassembling the RMU after overhuling / servicing and its testing complete all as specified and directed. Make -ABB & C&S
Supply and fixing in replacement indication lamps (set of three) suitble for RMU, 11 KV complete all as specified and directed.
Excavation in trenches not exceeding 1.5 m wide and not exc. 1.5 m depth for laying cables, foundation for pole etc and getting out in soft/loose soil etc complete all as specified and as directed.
All as per Serial item No 35.00 (here-in-before) but hard/dense soil.
Removing excavated material to distance n. exc 50m and depositing where directed at a level n. exc 1.5m above the starting point etc complete all as specified and as directed. .
Returning filling in incl spreading leveling watering and well ramming in layers n. exc 25cm thick etc complete all as specified and as directed.
M&L for Sand cushioning 230mm thickness with dry sand (one layer of 80mm thickness before laying of cable and other layer of 150mm thickness after laying of cable) and punned down to 180mm after laying of cable in trenches for protection of cable complete all as directed. Note :- For the purpose of payment only punned thickness shall be measured.
Taking up bricks laid as stacking serviceable brick for reuse at site etc complete all as specified and directed.
Laying only old bricks retrieved from item Srl Item No. 40.00 (here-in-before) as cable covers in trenches etc complete all as specified and directed.
M&L for brick covering to underground electric cable using sub class ‘B’ bricks, laid dry, flat, perpendicular to the direction of cable etc complete all as specified and directed. .
Taking up precast concrete laid as cable covers for reuse at site etc complete all as specified and directed.
Laying only old reinforced precast concrete cable cover retrieved from item Srl Item No. 43.00 (here-in-before) as cable covers in trenches etc complete all as specified and directed.
Supplying and laying reinforced precast concrete cable cover class HV type 1 flat size 300mm x 180mm x 40mm (ISI Marked) complete all as specified and directed.
Taking out the old unserviceable HT underground cable 120/150 sqmm 3core 11000 volts grade, XLPE insulated and PVC sheathed, armoured heavy duty with multistrand aluminium conductors from trenches/wall/floor/road/ culverts or pole etc complete all as specified and directed .
Supplying, laying jointing testing and commissioning of HT underground XLPE insulated, screened PVC bedded galvanized steel strip or wire armoured electric power cable (heavy duty) with aluminium conductor 11KV grade (Earthed) of size 120 sqmm 3 core confirming to IS-7098 Pt-II cable laid in trenches/walls/ducts/poles etc. complete all as specified and directed.
Supplying, laying jointing testing and commissioning of HT underground XLPE insulated, screened PVC bedded galvanized steel strip or wire armoured electric power cable (heavy duty) with aluminium conductor 11KV grade (Earthed) of size 150 sqmm 3 core confirming to IS-7098 Pt-II cable laid in trenches/walls/ducts/poles etc. complete all as specified and directed.
Supply and fix cable jointing kit for 11 KV grade cable for outdoor termination, heat shrink type, joint complete with jointing material and accessories suitable for3 core XLPE, armoured, Al conductor cable of size 120 sqmm
Supply and fix cable jointing kit for 11 KV grade cable for outdoor termination, heat shrink type, joint complete with jointing material and accessories suitable for3 core XLPE, armoured, Al conductor cable of size 150 sqmm
Supply and fix cable jointing kit for 11 KV grade cable for in staight termination, heat shrink type, joint complete with jointing material and accessories suitable for3 core XLPE, armoured, Al conductor cable of size 120 sqmm
Supply and fix cable jointing kit for 11 KV grade cable for in staight termination, heat shrink type, joint complete with jointing material and accessories suitable for3 core XLPE, armoured, Al conductor cable of size 150 sqmm
Taking out the old unserviceable LT underground cable any size, XLPE insulated and PVC sheathed, armoured heavy duty with multistrand aluminium conductors from trenches/wall/floor/road/ culverts or pole etc complete all as specified and directed .
Supply, laying and testing cable XLPE Insulated ,screened, PVC bedded, galvanized steel strip or wire armoured, electric power cables (heavy duty) 1100 Volts grade with stranded aluminium conductor of size 150 sq mm 3.5 core
Supply, laying and testing cable XLPE Insulated ,screened, PVC bedded, galvanized steel strip or wire armoured, electric power cables (heavy duty) 1100 Volts grade with stranded aluminium conductor of size 120 sq mm 3.5 core
Supply, laying and testing cable XLPE Insulated ,screened, PVC bedded, galvanized steel strip or wire armoured, electric power cables (heavy duty) 1100 Volts grade with stranded aluminium conductor of size 70 sq mm 3.5 core
Supply, laying and testing cable XLPE Insulated ,screened, PVC bedded, galvanized steel strip or wire armoured, electric power cables (heavy duty) 1100 Volts grade with stranded aluminium conductor of size 35 sq mm 3.5 core
M&L for earthing complete with galvanized steel earth plate electrode size 600 mm x 600 mm x 6.3 mm thick buried directly in ground vertically in a pit of depth not less than 2.25 mtr below ground levels with top edge of the earth plate not less than 1.5 mtr below normal ground level surrounded from all sides by mixture of charcoal and common salt and electrode connected to and including galvanized earth iron strip 24x4mm by means of bolts, nuts, check nuts and washers of galvanized including GI protection pipe medium grade 40mm dia connected to main earth wire on pole or control board and GI pipe medium grade 20 mm dia bore for watering funnel with wire mesh. RCC cover with frame, PCC chamber pit with PCC 1:3:6 type C-2 excavation and earth work all as shown in electrical plate No 3 connected to earthing test point all as specified or indicated including testing on completion
MAHI PALL CONSTRUCTION COMPANY
fauji electric works
malik constructions
S K CONTRACTOR
stage.html
html • 0.06 MB
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .