Loading…
Tenderkart now works inside Claude and ChatGPT: search and analyse tenders right from your chat
Loading…
Tender ID
Eligibility, documents, scope, Go/No-Go checksEligibility, required documents, scope of work and Go/No-Go checks for this tender, in one click.
Tender Value
₹43.6 L
EMD Value
₹87,200
Closing Date
26 Nov 2026, 6:00 pm4d left
Eligibility, documents, scope, Go/No-Go checksEligibility, required documents, scope of work and Go/No-Go checks for this tender, in one click.
Jitender Singh, IDSE, EE
GE (N) Bathinda
PROVISION OF AIR DUCT COOLING SYSTEM FOR TROOPS UNDER AGE EM-V OF GE (NORTH) BATHINDA AT BATHINDA MIL STN
2026_MES_798456_1
8941/NIT-57/26-27/E8
Open Tender
Electrical and Maintenance Works
Item Rate
180 days
Bathinda
Class D Category c(i)
8 documents required · 8 mandatory
₹500
GE (N) Bathinda
₹87,200
Yes
12 Nov 2026
12 Nov 2026
28 Nov 2026
12 Nov 2026
26 Nov 2026
19 Nov 2026
12 Nov 2026 - 18 Nov 2026
| Sl No | Description | Qty | Unit | Est. Rate | Est. Amount |
|---|---|---|---|---|---|
| 1 | Supply, installation, testing and commissioning (SITC) of industrial ductable evaporative super cooler, having cabinet fabricated from 100% virgin, UV-stabilized, industrial-grade engineering polymer/plastic, corrosion-resistant, rust-free, shock-resistant and suitable for outdoor/industrial applications, complete with cool-flow water dispenser and universal body design. The unit shall be provided with high-efficiency rigid cooling media pads, offering cooling efficiency up to 85%, complete with heavy-duty, three-phase, single-speed fan motor with 100% copper winding, manufactured in India, suitable for delivering an air volume of 25,000 CMH, and turbo axial fan designed for low-noise operation and air throw up to 100 feet. The unit shall also be complete with motor protection device, automatic water-level sensor, built-in electrical protection devices including phase failure/single-phase preventer and voltage surge protector, suitable motor starter and intelligent centralised digital controller, including all necessary duct connections, supports, mounting arrangements, electrical wiring and connections, water supply connections, drainage arrangements, testing and commissioning, ensuring satisfactory operation of the complete system. The unit shall be suitable for operation through a generator supply also.
Discharge arrangement shall be top discharge or down discharge, as per approved site engineering design complete all as specified, as per manufacturer's recommendations and as directed by the Engineer-in-Charge.
Important technical points for tender finalisation:
Capacity: 25,000 CMH.
Fan motor: Three-phase, single-speed, 100% copper winding.
Cooling efficiency: Up to 85%.
Air throw: Up to 100 feet.
Cooling media: Rigid cooling pads.
Electrical protection: Phase failure and voltage surge protection.
Discharge: Top/Down, as per site requirement. | 12 | Each | - | - |
| 3 | Material and labour for fabrication, installation, balancing and commissioning of site-fabricated rectangular air-distribution ducts made out of 24 SWG galvanised steel (GI) sheets, conforming to IS 655:2010, for air discharge from ductable air cooler, including cutting, bending, folding, joining and fabrication of GI sheets to the required sizes and configurations, complete with neoprene rubber gaskets, elbows, splitter dampers, turning vanes, hangers, supports, brackets, mounting arrangements, flanges, cleats, nuts and bolts, joint gaskets and all necessary accessories, including connecting the cooler unit to the duct system, fixing of controller and associated components, proper sealing of joints, alignment, air balancing, testing and commissioning of the complete ducting system, complete all as specified and directed by the Engineer-in-Charge.
Note:
(i) Any concealed wall ducting disturbed or damaged during installation shall be properly repaired and reinstated by the contractor at no extra cost. All necessary plastering, civil repairs and finishing of affected surfaces shall be carried out to restore them to their original condition, including application of matching paint/colour and texture, complete at the contractor's own cost. No extra payment shall be admissible on this account. | 625 | Square Metre | - | - |
| 4 | Material and labour for fabrication, installation, balancing and commissioning of site-fabricated rectangular air-distribution ducts made out of 22 SWG galvanised steel (GI) sheets, conforming to IS 655:2010, for air discharge from ductable air cooler, including cutting, bending, folding, joining and fabrication of GI sheets to the required sizes and configurations, complete with neoprene rubber gaskets, elbows, splitter dampers, turning vanes, hangers, supports, brackets, mounting arrangements, flanges, cleats, nuts and bolts, joint gaskets and other necessary accessories, including connecting the cooler unit to the duct system, fixing of controller and associated components, proper sealing of joints, alignment, air balancing, testing and commissioning of the complete ducting system, complete all as specified and directed by the Engineer-in-Charge.
Note:
(i) Any concealed wall ducting disturbed or damaged during installation shall be properly repaired and reinstated by the contractor at no extra cost. All necessary plastering, civil repairs and finishing of affected surfaces shall be carried out to restore them to their original condition, including application of matching paint/colour and texture, complete at the contractor's own cost. No extra payment shall be admissible on this account. | 375 | Square Metre | - | - |
| 5 | Material and labour for providing and fixing 9 mm thick, high-quality cross-linked polyethylene (XLPE) thermal insulation to external surfaces of GI air-distribution ducts exposed to direct sunlight, including cleaning and preparation of duct surfaces, cutting, fitting, jointing, sealing of all joints and overlaps with suitable approved adhesive/tape, and providing necessary fixing accessories to ensure continuous, uniform and effective thermal insulation, complete in all respects, as specified and directed by the Engineer-in-Charge.
Note: Insulation shall be suitable for outdoor exposure and provided with a UV-resistant protective finish/cladding to prevent deterioration due to sunlight and weathering. | 875 | Square Metre | - | - |
| 6 | Supply and fixing of air-discharge grills, specially designed for ductable air cooler, with automatic swing mechanism, manufactured from high-quality corrosion-resistant and rust-proof material, suitable for long-term operation, providing wider air-distribution angle and extended air throw up to twice the normal range, with low-noise operation, offering up to 50% noise reduction, including all necessary mounting arrangements, frames, nuts, bolts, screws, rubber gaskets, fasteners and accessories, complete with proper alignment, fixing, adjustment, testing and commissioning for satisfactory operation of the air-distribution system, complete all as specified and directed by the Engineer-in-Charge.
Note: Size, material, finish, air-discharge capacity and compatibility of grills with the duct system shall be as per approved shop drawings and site requirements. | 20 | Square Metre | - | - |
| 7 | Material and labour for providing, fabricating and fixing structural framework using mild steel angle iron sections for frame supports, conforming to Fe-290 Grade E-165, including cutting, shaping, bending, welding, joining, drilling of holes, notching, providing and fixing flat iron fillets for securing wire mesh or other components, and all necessary bolting, riveting, grinding and finishing of joints, including all required fittings, fasteners, tools and accessories, complete in all respects as specified and directed by the Engineer-in-Charge.
Note: All steel sections and flats shall be of approved quality and sizes as per drawings or as directed by the Engineer-in-Charge. Painting/anti-corrosive treatment, if required, shall be as specified separately. | 500 | Kilogram | - | - |
| 8 | Material and labour for drilling/cutting holes of required size and shape in existing brickwork/stone masonry walls for passage and installation of GI ducts of ductable air coolers/exhaust fans, including careful removal of masonry without damaging adjoining structures, making good the disturbed facings and surrounding surfaces, filling gaps around duct openings and pointing the edges/ends in cement mortar 1:3, finished neatly with white cement wherever required, including all necessary tools, plant, scaffolding and accessories, removal of debris from the site and disposal as directed, complete all as specified and directed by the Engineer-in-Charge. | 144 | Each Job | - | - |
| 9 | Supply and fixing of exhaust fan set, 300 mm sweep, suitable for 230 Volts AC, 50 Hz supply, operating at 1300 RPM, manufactured from mild steel, complete with suitable automatic/manual louver, fan blades, motor, mounting frame, protective grill, necessary fasteners, electrical connections and all required accessories, including removal of the existing unserviceable exhaust fan, installation of the new fan, testing and commissioning for satisfactory operation, complete all as specified and directed by the Engineer-in-Charge.
Note:
(i) The dismantled unserviceable exhaust fan shall be deposited by the contractor at AGE E/M-V Store, in safe custody, as directed by the Engineer-in-Charge. The cost of dismantling, handling, transportation and depositing the unserviceable fan shall be deemed to be included in the quoted rates. No extra payment shall be admissible on this account. | 48 | Each | - | - |
| 10 | Supply and installation of polyethylene water storage tank of 1000 litres capacity, ISI marked conforming to IS 12701, suitable for installation at terrace level of G+2 building, complete with properly fitted cover and suitable locking arrangement, including making necessary holes and providing suitable connections for inlet, outlet, overflow and washout pipes, complete with all necessary fittings, washers, sealing arrangements, supports/base preparation, lifting, shifting and positioning at the required location, testing for leakage and satisfactory operation, complete all as specified and directed by the Engineer-in-Charge.
Note: All necessary T&P, labour, scaffolding, lifting arrangements and safety provisions required for installation at terrace level of G+2 building shall be deemed to be included in the quoted rates. No extra payment shall be admissible on this account. | 4 | Each | - | - |
| 11 | Material and labour for providing and fixing Chlorinated Polyvinyl Chloride (CPVC) pipes, suitable for hot and cold water supply and having adequate thermal stability, of nominal diameter 20 mm, including all necessary CPVC plain and brass threaded fittings, bends, tees, elbows, sockets, unions and other accessories, jointing with approved one-step CPVC solvent cement, fixing the pipes on walls/roof with suitable clamps at 1.00 m centre-to-centre spacing, including cutting, threading wherever required, making connections, pressure testing of completed pipework and ensuring leak-proof joints, complete all as specified and directed by the Engineer-in-Charge.
Note: All CPVC fittings and accessories required for proper installation and fixing of the pipework shall be deemed to be included in the quoted rates. No extra payment shall be admissible on this account. | 85 | Running Metre | - | - |
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Tendernotice_1.pdf
PDF • 3.67 MB
tenderdocuments571.pdf
Tender Documents • 0.39 MB
tenderdocuments572.pdf
Tender Documents • 0.99 MB
BOQ_895712.xls
BOQ • 0.58 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .