| Sl No | Description | Qty | Unit | Est. Rate | Est. Amount |
|---|---|---|---|---|---|
| 1FIRE DETECTION AND ALRAM SYSTEM | |||||
| 1.01 | Supply, Installation, Testing & Commissioning of Analogue Addressable 100% Hot Redundant (Display, Mother Board, Loop Card, PSU, Battery, Network Card and all other components) with inbuilt Automatic switcher of 2 Loop Fire Alarm Control Panel expandable via plug-in loop driver boards, loop current 500mA maximum per loop, dual flash based microprocessor, supports to connect 20% spare detector in Each loop via fully digital communication protocol, equipped with a white backlit display (600 Character/240x64 pixel resolution/10" Touchscreen) graphical LCD Display with at least 6 lines of information, 400 fire zones (soft zones), fully programmable via alphanumeric keypad or configuration software without using any king of DONGLE/LICENCE/SPECIAL CABLE, dedicated USB and RS-232 serial port for direct or PC connection, 5000 events storage, loop current 500 mA, panel shall be equipped with inbuilt multi-meter for live monitoring of loop current, earth voltage, loop voltage etc., installer's logo application, inbuilt fault-tolerant network card to network with compatible addressable panel(s) and repeater panel(s), capable to connect maximum 200 network nodes on a standard network, features battery charger status and temperature, supports programmable cause / effect on outputs, panel housing meets min IP30 ingress protection classification finished in RAL 7035, The panel shall support more than one OEM protocol to allow user of using other make detector & devices at later stage. (The System cost shall be included of all necessary cards, modules, Panel enclosure, CPU and associated accessories to complete the system design). Approved by: International Independently certified as complying with requirements of BS EN 54 Part 2, 4, and 13. Note: The FACP shall communicate over peer-to-peer communication network complete all as specified and directed by Engineer-in-Charge. | 5 | Each | - | - |
| 1.02 | MAIN FIRE ALARM CONTROL PANEL OR NETWORK NODE: 1. Main FACP or network node shall contain a microprocessor based central processing unit (CPU) and power supply. The CPU shall communicate with and control the following types of equipment used to make up the system: intelligent addressable smoke and thermal (heat) detectors, addressable modules, printer and other system control device. 2. In conjunction with intelligent loop control modules and loop expander, the main FACP shall perform the following function: supervise and monitor all intelligent addressable detectors and monitor modules connected to the system for normal, trouble and alarm conditions, supervise all initiating signalling and notification circuits throughout the facility by way of connection to addressable monitor and control modules, detect the activation of any initiating device and the location of the alarm condition, Operate all notification appliances and auxiliary device as programmed complete all as specified and directed by Engineer-in-Charge. | - | - | - | - |
| 1.03 | NETWORK COMMUNICATION: The FACP shall communicate over a peer-to-peer communication network, inherently over a regenerative communication format and protocol. The network shall support communication speed up to 100 mbps and support up to 200 control panels/network nodes over a single medium (copper conductor/fibre optics), redundant ring, communication channel for fire alarm, voice evacuation and telephone talk back system. The system shall support up to 200 such networks in a single system. The network card shall have inbuilt fibre port for terminating fibre optic cable without any third-party convertors. | - | - | - | - |
| 1.04 | DIGITAL VOICE COMMAND CENTRE: 1. The digital voice command centre located with the FACP, shall contain all equipment required for all audio control, emergency telephone system control, signalling and supervisory functions. This shall include speaker zone indication and control, telephone circuit indication and control, digital voice units, microphone and main telephone handset. 2.Function: The voice command centre equipment shall perform the following function: a. operates as supervised multi-channel emergency voice communication system. Operate as a two-way emergency telephone system control centre. b. Audibly and visually annunciate the active or trouble condition of every speaker circuit and emergency telephone circuit. c. Audibly and visually annunciate any trouble condition for digital tone and voice units required for normal operation of the system. d. provides all call emergency paging activities through activation of a single control switch. | - | - | - | - |
| 2 | Supply, Installation, Testing & Commissioning of Active Repeater Panel (Remote Control Panel) with white backlit (240x64) graphical LCD display, incorporates function buttons for Silence, Mute, Resound, Reset and Disable/Enable, flash memory and advanced graphical display allows it to be easily configured to operate in virtually any language, with any character set and allows for the installer’s logo and company details to be displayed on the LCD display during normal operation. Networked for system display and control, in-built fault-tolerant network card to network with compatible addressable panel(s) and repeater panel(s), fully on-site programmable via alphanumeric keypad or configuration software, panel housing meets min IP30 ingress protection classification finished in RAL 7035. Approved by: International Independently certified as complying with requirements of BS EN 54 Part 2 & 4 complete all as specified and directed by Engineer-in-Charge. | 6 | Each | - | - |
| 3 | Supply, Installation, Testing & Commissioning of analogue addressable Multisensor with inbuilt isolator having three sensors (OH2) i.e. one optical and dual heat sensor (Static and ROR both), It shall have multiple modes with min five different optical sensitivity adjustment from 1.1%/m to 4.2%/m and to be possible to configure the detector to work in any of the modes such as only optical type or only heat type or combined type. 360° Visible Tri-coloured led for Normal, Fault and alarm condition, addressing shall be by means of soft addressing or dip switches or decade switches, or suitable punched cards. It shall have Compensation to drift and transient rejection and complies with the essential requirement of the EMC Directive, designed for IP54 requirements and approved to operate in –10°C to +55°C temperature, It shall be possible to insert and remove detectors by a single push twist movement, base shall have special locking tool feature to prevent loosening of detector on its own. (For Detectors/Device without inbuilt isolator, Fault Isolator or Isolator base to be provided with Each detector/device). Approved by LPCB for EN 54-5, EN 54-7, & EN 54-17 standard complete all as specified and directed by Engineer-in-Charge. | 865 | Each | - | - |
| 4 | Supplying, installing, testing and commissioning approved make Addressable Loop Powered Auto aligned Beam Detector. The beam detector shall be used for High Ceiling application with a detection range from 5 up to 100 mtrs and highly resistant to building movement; tolerates +/- 1° movement, Resistant to solid object intrusion, , Built-in imager heater, Resistant to strong light sources; does not alarm when saturated by sunlight, Automatic sensitivity threshold level settings and drift compensation. The detector shall be IP-55 compliant complete all as specified and directed by Engineer-in-Charge. | 14 | Each | - | - |
| 5 | Supply, Installation, Testing & commissioning of Response Indicator. The RI Shall be IP-55 compliant complete all as specified and directed by Engineer-in-Charge. | 134 | Each | - | - |
| 6 | Supply, Installation, Testing & Commissioning of Analogue addressable Manual Call Point (Resettable Type) with inbuilt isolator and LED indicator, designed for IP44 requirements and approved to operate in –10°C to +55°C temperature, complies with the essential requirement of the EMC Directive to be supplied with Barriers, Junction Box, Glands and other mounting accessories for proper installation. (For Detectors/Device without inbuilt isolator, Fault Isolator or Isolator base to be provided with Each detector/device). Approved by LPCB for EN 54-11 & EN 54-17 standard complete all as specified and directed by Engineer-in-Charge. | 230 | Each | - | - |
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Tendernotice_1.pdf
PDF • 0.21 MB
87985TenderPages.pdf
Tender Documents • 1.75 MB
87985Drawings_1.pdf
Additional Documents • 5.05 MB
87985Drawing_2.pdf
Additional Documents • 20.51 MB
BOQ_871208.xls
BOQ • 2.22 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at [email protected].