| 1 | | Sub Head I Supply of Precision PAC units Supply of microprocessor based air cooled type super low noise 7 TR sensible cooling capacity Top or bottom discharge type as per requirement Precision Air conditioning unit working on R407C/R410A refrigerant and capable of delivering minimum 3850 CFM comprising of indoor and outdoor units as detailed below with all components i/c humidifier and heater controls provided with BMS connectivity and interlocking electrical accessories refrigerant piping within unit initial charge of refrigerant and oil Serrated rubber pads filters having 95 percentage efficiency down to 5 microns including sequential control and Run hour equalization etc. as per detailed specifications attached. Note Rates of refrigerant pipe to be quoted separately in SH III | 13 | Nos | Ramesh Chand Yadav 226001,O/o CE(Electrical)First Floor, Bhopal House, Lalbagh, Lucknow-226001 | 90 |
| 2 | ITC package AC unit and condensers | Sub Head II ITC of Precision PAC units Installation testing and commissioning of the above package AC unit and condensers including providing powder coated MS stand for Indoor unit and corrosion treated and painted frame for condensers minor civil works like cutting/grouting making good the damages 25mmX5mm GI earth strip between indoor and outdoor unit providing necessary scaffolding pressure testing vaccumising gas charging etc. complete as required. | 13 | Job | Ramesh Chand Yadav 226001,O/o CE(Electrical)First Floor, Bhopal House, Lalbagh, Lucknow-226001 | 90 |
| 3 | Providing and fixing 40mm dia CPVS Pipe | Sub Head III Miscellaneous items Providing and fixing 40 mm dia. nominal bore FRLS HMS High Mechanical Stress CPVC pipe from outlet socket of HPAC unit complete with CPVC fittings and clamps including cutting and making good the walls etc. complete as required. | 130 | Mtr | Ramesh Chand Yadav 226001,O/o CE(Electrical)First Floor, Bhopal House, Lalbagh, Lucknow-226001 | 90 |
| 4 | SITC of 19 mm dia OD Hard drawn | Supply Installation testing and commissioning including vaccumization and Nitrogen testing of following nominal sizes of hard drawn copper refrigerant piping for PAC system complete with fittings with suitable adjustable ring type hanger supports jointing/brazing including accessories insulated with XPLE Class O tubular insulation/with Class O closed cell elastometric nitrile rubber tubular sleeves sections of specified thickness as given below for Suction and Liquid lines all accessories as per specifications complete as required The item shall be measured from outside connection of indoor unit to outside of condensor unit. a. 19 mm dia. OD Hard drawn with tube thickness 1.2 mm with 19 mm thick insulation | 182 | Mtr | Ramesh Chand Yadav 226001,O/o CE(Electrical)First Floor, Bhopal House, Lalbagh, Lucknow-226001 | 90 |
| 5 | SITC of 22.2 mm dia OD Hard drawn | Supply, Installation, testing and commissioning including vaccumization and Nitrogen testing of following nominal sizes of hard drawn copper refrigerant piping for PAC system, complete with fittings, with suitable adjustable ring type hanger supports, jointing/brazing including accessories, insulated with XPLE Class-O tubular insulation/with Class-O closed cell elastometric nitrile rubber tubular sleeves sections of specified thickness as given below for Suction and Liquid lines, all accessories as per specifications complete as required (The item shall be measured from outside connection of indoor unit to outside of condensor unit). b. 22.2 mm dia. OD Hard drawn with tube thickness 1.2 mm with 19 mm thick insulation | 182 | Mtr | Ramesh Chand Yadav 226001,O/o CE(Electrical)First Floor, Bhopal House, Lalbagh, Lucknow-226001 | 90 |
| 6 | SITC of GI 150x50 mm depth X 1.6 mm thickness | Supplying and installing following size of perforated Hot Dipped Galvanised Iron cable tray Galvanisation thickness not less than 50 microns with perforation not more than 17.5 percentage in convenient sections joined with connectors suspended from the ceiling with G.I. suspenders including G.I. bolts and nuts etc. as required. a. 150 mm width X 50 mm depth X 1.6 mm thickness | 182 | Mtr | Ramesh Chand Yadav 226001,O/o CE(Electrical)First Floor, Bhopal House, Lalbagh, Lucknow-226001 | 90 |
| 7 | SITC of GI 300x50 mm depth X 1.6 mm thickness | Supplying and installing following size of perforated Hot Dipped Galvanised Iron cable tray (Galvanisation thickness not less than 50 microns) with perforation not more than 17.5%, in convenient sections, joined with connectors, suspended from the ceiling with G.I. suspenders including G.I. bolts & nuts, etc. as required. b. 300 mm width X 50 mm depth X 1.6 mm thickness | 182 | Mtr | Ramesh Chand Yadav 226001,O/o CE(Electrical)First Floor, Bhopal House, Lalbagh, Lucknow-226001 | 90 |
| 8 | Supplying and laying of 1.1 KV Grade XLPE copper conductor | Supplying and laying of 1.1 KV grade XLPE insulated armoured and sheathed copper conductor cables confirming to IS 1554 Part I 1964 of 2 X 2.5 sq. mm size including providing and making cable termination by crimping joints as required for interconnecting between the outdoor and indoor units as required at site. Suitable clamping arrangement shall be provided for cables to be fixed on walls/Cable trays/racks where necessary. Suitable cable glands shall also be provided for all cable terminations. | 325 | Mtr | Ramesh Chand 226001,O/o CE(Electrical)First Floor, Bhopal House, Lalbagh | 90 |
| 9 | CM of HPAC PKG During first year of operation after warranty period C1 | Sub Head IV MAINTENANCE ITEMS Comprehensive maintenance of 7 TR HPAC PKG units which include routine preventive and breakdown maintenance for a period of 4 years i/c supply of refrigerant gas and other consumables repair/replacement of worn out items with minimum down time and warranty/guarantee of repaired/replaced items after completion of one year of guarantee period. Rates to be quoted year wise as per following. a. During first year of operation after warranty period C1 | 13 | Each Pkg per year | Ramesh Chand Yadav 226001,O/o CE(Electrical)First Floor, Bhopal House, Lalbagh, Lucknow-226001 | 365 |
| 10 | CM of HPAC PKG During 2nd year of operation after warranty period. C2 | Comprehensive maintenance of 7 TR HPAC PKG units which include routine preventive and breakdown maintenance for a period of 4 years i/c supply of refrigerant gas and other consumables repair/replacement of worn out items with minimum down time and warranty/guarantee of repaired/replaced items after completion of one year of guarantee period. Rates to be quoted year wise as per following.b. During 2nd year of operation after warranty period. C2 | 13 | Each Pkg per year | Ramesh Chand Yadav 226001,O/o CE(Electrical)First Floor, Bhopal House, Lalbagh, Lucknow-226001 | 365 |