Loading…
Loading…
| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | L1₹1.3 LAccepted-Finance 2ND FLOOR SHOP NO 303 MARUTI PLAZA RONCHI BANGAR TOWNSHIP MATHURA | MATHURA | UTTAR PRADESH | 281001 | L1 | Accepted-Finance Accept | |
| 2 | L2₹1.3 L+₹1,093 (0.85%)Accepted-Finance 58 KAILASHPURAM GOVINDPURAM GAZIABAD | GHAZIABAD | UTTAR PRADESH | L2 | Accepted-Finance Accept | |
| 3 | L3₹1.4 L+₹7,520 (5.86%)Accepted-Finance | L3 | Accepted-Finance Accept |
Tender Value
₹1.3 L
EMD Value
₹2,600
Closing Date
30 Sept 2024, 11:00 amClosed
Executive Engineer ETD Etawah
Executive Engineer ETD Etawah
WORKS FOR PROVIDING AND FIXING OF VACUUM INTERRUPTER AND OVERHAULING OF DIFFERENT 33KV VCB AND REPLACEMENT OF DIFFECTIVE 33KV VCB AT DIFFERENT SUBSTATIONS UNDER ELECTRICITY TRANSMISSION DIVISION, ETAWAH
2024_UPTCL_958661_1
T-05/ETD(E)/2024-25
Open Tender
Electrical Works
Item Rate
15 days
Etawah
Please refer Tender documents.
2 documents required · 2 mandatory
₹590
Yes
Executive Engineer ETD Etawah
₹2,600
Yes
30 Sept 2024
23 Sept 2024
30 Sept 2024
23 Sept 2024
30 Sept 2024
23 Sept 2024
Amount
Providing & fixing of vacuum interrupter in defective 33kv VCB Siemens make of Dakatal feeder of Y Phase which megger value is found less than 100M-ohm at 132kv s/s Chakarnagar .
Providing & fixing of vacuum interrupter in defective 33kv VCB CGL make of jack bus feeder of B Phase which megger value is found less than 100M-ohm at 132kv s/s Etawah.
After replacement of vacuum interrupter following test & overhauling to be carried out - (a). Checking & adjustment of snatch gap, travel of drive insulator rod & tie rod of each pole. (b). Opening & closing time of breaker of each pole . ( c). Carrying out contact resistance measurement (CRM test) of each pole. (d). Checking of megger values of breaker poles. (e). Checking tripping of breaker at 70% DC voltage (f) Checking the close / open operation of breaker from remote & local and ratification of fault , if any
Dismantling the damaged / defective 36 KV vacuum circuit breaker of 33kv feeder Mahewa by opening, jumper, cable termations, nut and bolts etc. from plinth, and remove earthing by cutting and shifting it to store .
Making the frame of galvanized structure suitable to fixing it on plinth with proper matching of new breaker structure holes. Erection of 36 KV VCB circuit breaker with proper jumper tightening, earthing and leveling including all work for proper erection including shfting of VCB from store to site.
Termination at VCB of following sizes of control cable as laid already including making necessary holes in gland plates or box wherever required, providing and fixing of cable glands of appropriate size, supply and providing ferrules and Nos. for each core of cable and its termination with crimping type lugs of Dowell/Tension make and all other associated work to complete the jobs satisfactorily as per technical specification.
2Cx2.5 Sq. mm. Unarmoured
4Cx2.5 Sq. mm. Unarmoured
6Cx2.5 Sq. mm. Unarmoured
SARASWAT ELECTRICALS
TIRUPATI ELECTRICALS
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .