Loading…
Tenderkart now works inside Claude and ChatGPT: search and analyse tenders right from your chat
Loading…
Tender ID
Eligibility, documents, scope and key termsEligibility, required documents, scope of work and key terms of this tender, in one click.
Tender Value
₹18.3 L
EMD Value
₹43,500
Closing Date
3 Oct 2024, 9:58 pmClosed
Eligibility, documents, scope and key termsEligibility, required documents, scope of work and key terms of this tender, in one click.
Directorate of Municipal Administration
EXECUTIVE ENGINEER
Installation of UG Cable and RMU for the Electrical connection network required for the project of upgradation of IBPS Plant in Pinjarapole Kabini water supply scheme
DMA/2024-25/WS/WORK_INDENT20144/CALL-3
DMA/2024-25/WS/WORK_INDENT20144/CALL-3
Open
Water supply/sewage lines
Electronic Documents, First(One Cover)
DMA City Corporation Mysuru
3 documents required · 3 mandatory
₹500
₹43,500
17 Sept 2024
17 Sept 2024
1 Oct 2024
Installation of UG Cable and RMU for the Electrical connection network required for the project of upgradation of IBPS Plant in Pinjarapole Kabini water supply scheme
11 kV, 400 Amps Double Break GOS
Pre-Stressed Tubular Spun Pole 11 Mtr Long, 500 Kg WL
For Three H Frame without Transformer Seating and Seating angle support cross arm for 11 Mtr Spun Pole up to and including 250 kVA (UG Cable) (excluding erection of Pole
11 kV, 3 Core, XPLE HTUG Cable with pressure extruded inner sheeth, ROUND WIRE ARMOURED as per IS-7098 (Part-2) Armouring wires dia and Resistivity as per IS-3975 240 Sqmm, (55 GI Wires - 3.15 mm Dia
Cable Covering Tile 125x250x40 mm
11 kV, Jointing & Cable Termination Kit as per IS-13573 Heat Shrinkable Type Transition Jointing Kit for XLPE Cable 3x240 Sqmm
12 kV, Jointing & Cable Termination Kit as per IS-13573 Heat Shrinkable Indoor Type Cable Termination Kit for XLPE Cable 3x240 Sqmm
13 kV, Jointing & Cable Termination Kit as per IS-13573 Heat Shrinkable Outdoor Type Cable Termination Kit for XLPE Cable 3x240 Sqmm
Fixing of pot heads for HT cable only Heat shrinkable/Cold
shrinkable/Pushon
Caution/Danger Board
Route & Joint indicating slab with MS Anchor rod
Supplying, fixing, wiring, earth electrode for grounding conduits, I.C. cutouts and othere equipment's on the meter board using 40 mm dia 2.90 mm thick GI pipe 2.5 m long buriedinapit. The pit should ...
Supplying fixing and wiring earth electrode for grounding of lifts, transformers, DG sets etc. using 40 mm dia 2.9mm thick 2.5m long GI pipe with GI funnel with mesh and suitable size reducer fixed on...
GI pipe 100 mm (Nominal bore), medium class
(including accessories)
Aluminium End Terminal (Lug) 240 Sqmm
Compact RMU (VCB/SF6 Type) with Copper Busbar, 350 MVA, 630 Amps as per IEC-62271/IS-3427 3 Way RMU, 2 OD + 1 VL (One Incomer + One Breaker + One Outgoing)
11KV CT (Secondary - 1A) for 3 Phase 4 Wire Metering, Burden: 2.5 VA, 0.2 Accuracy Class Ratio: 5/1A to 100/1A
GSM modem with connecting cable for remote communicating capabilities
Digging of Pit 2.5 Mtr depth for erection of 11 Mtr long Tubular Spun Pole as per approved Drawing. Ordinary Soil
Fixing of GOS including wiring (11 kV Double Break 400 Amps)
Erection of H-Frame.
Laying and Jointing: Joining with mud mortor complete Covering cable with Tiles
Laying and Jointing: Joining with mud mortor complete Fixing of Route Joint Indicating Slab
Spreading and forming with sand all round the cable to a depth of 75 mm and width of 500 mm. (Does not include cost of sand).
Laying the GI Pipe 80 mm to 150 mm dia at Drainage Water Supply Crossing including fixing collars elbows, bends, Tees and other fitting with Cuts and Threads wherever necessary complete.
Laying of cable in Existing Trench/GI pipe/Stone Ware/RCC Hume pipe using Wooden/Aluminum Rollers as directed by the departmental staff HT Cable 3x185 to 240 Sqmm
Fixing of GPRS Modems with Accessories
Transporting RMU (Compact) unit from store to work spot including loading, unloading. (No separate crane charges) 5 Panel
Fixing foundation frame of channels and angle iron welding fixing in concrete aligning the RMU on foundation bed, assembly of units, connecting Bus Bars from panel to panel initial filling of oil etc....
Lettering the RMU with enamel paint and also writing single line diagram of each panel, caution Board, Danger Board etc., including cost of Paint, Brush etc.,
Earth work excavation by manual means for drains, canals, waste weir, draft, approach channels, key trenches, foundation of Buildings & bridges and such simillar works in all kinds of soils, as per dr...
Providing and laying in position Cement Concrete for levelling course for all works in foundation. The granite/trap/basalt crushed graded coarse aggregates and fine aggregates as per relevant IS Codes...
Providing and laying in Cement Concrete for all Basement & surface level works, return walls, retaining walls, sunken floors etc. The granite/trap/ basalt crushed graded coarse aggregates and fine agg...
Providing Brick work with common burnt clay Non Modular bricks of
class designation 3.5 in foundation and plinth in Cement mortar 1:4 (1
cement : 4 coarse sand) including cost of all materials, labour...
Providing 18 mm cement plaster in two coats under layer 12 mm thick
cement plaster with cement mortar 1:5 (1 cement : 5 coarse sand) finished with a top layer 6 mm thick cement plaster with cement mor...
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
20144 KW 2 (2).docx
Tender Document • 0.29 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .