Loading…
Loading…
| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | 1₹42.9 LAccepted-AOC 1 225 5 6 SADAR BAZAR DELHI CANTT 110010 | NEW DELHI | DELHI | 110010 | 1 | Accepted-AOC being L1 | |
| 2 | 2₹44.2 L+₹1.3 L (3.06%)Rejected-Finance | 2 | Rejected-Finance Rejected being not L1 | |
| 3 | 3₹45.9 L+₹3.0 L (6.90%)Rejected-Finance | 3 | Rejected-Finance Rejected being not L1 | |
| 4 | 4₹49.5 L+₹6.6 L (15.4%)Rejected-Finance NO 9 BYRAVESHWARA INDUSTRIAL ESTATE ANDRAHALLI MAIN ROAD NEAR PEENYA 2ND STAGE BENGALURU 560 091 | BENGALURU URBAN | KARNATAKA | 560091 | 4 | Rejected-Finance Rejected being not L1 | |
| 5 | 5₹59.3 L+₹16.4 L (38.2%)Rejected-Finance 12 BHARTI AARTIST COLONY VIKAS MARG NEW DELHI 110092 | EAST | DELHI | 110092 | 5 | Rejected-Finance Rejected being not L1 |
| Sl No | Description | Qty | Unit | Rajindera Enterprises L2 | Vijaypower Generators Limited L5 | ALLIED CONSTRUCTION L3 | Vijay Electricals L4 | SAGGI ELECTRIC COMPANY L6 | M P TYAGI ENGINEERS AND CONTRACTORS L1 |
|---|---|---|---|---|---|---|---|---|---|
| 1.00 | Supply, installation, testing and commissioning of transformer as per IS: 1180 part - I (latest edition), level - II, step down, copper wound 11KV/433 Volts (at no load) AC 3 phase 50 Hz 500 KVA capacity, core type, oil immersed naturally air cooled, oil natural air natural (ON/AN), with external cooling tubes, delta connected on primary side (HV) and star connected on secondary side (LV) in accordance with vector group DYn-11 with neutral brought out on secondry side (LV) and having taping at +5% to +10% in steps of 2.5% on HV side to be changed by means of hand operated off load tap changergear. The maximum temperature rise should not exceed 50 degree celsius in oil and 55 degree celsius in HV/LV winding when measured by resistance method after continuous full load run on an ambient temp of 40 degree celsius transformer shall be of BOLTLESS core design. Transformer shall be double wound, core type with low loss, non ageing, high permeability prime grade crgo with M4 grade or better, perfectly insulated and clamped to minimize noise and vibrations. The transformer shall be IS/IEC 60076and as per IS-1180 part - I of 2014 (latest edition) marked and shall comprise of the following :- | 1 | Each Job | 10,00,000 ₹10,00,000 Lowest | 11,56,000 ₹11,56,000 | 12,75,000 ₹12,75,000 | 12,00,000 ₹12,00,000 | 13,22,400 ₹13,22,400 | 12,99,999 ₹12,99,999 |
| 1.01(a) One cable box on HT side (Primary side) consisting of three nos porcelain bushing with copper rods, complete with nuts and washer, with cable glands suitable for reception/taking out 3 core 120 Sqmm, HT 11000 volts grade, XLPE insulated and PVC sheathed, heavy duty, armoured cables including jointing materials complete. (b) One cable box on LT side(secondary side) consisting of four nos porcelain bushing with copper rods, complete with nuts and washers, with cable glands suitable for reception/taking out single core 630 sqmm, LT 1100 volts grade, PVC/XLPE insulated and PVC sheathed, heavy duty, armoured cables including jointing materials complete. (c) conservator with filter type drain valve and oil level guage. (d) De-hydrating breather with first fill of dehydrating agent (Silica Gel). (e) Explosive vent, Thermometer pocket on tank cover, oil level guage, Oil drain filter valve, at bottom of the tank Lifting ligs, oil filling hole with cap/plug with connection plate complete, Air release valve plug and four nos plain solid cast steel detachable rollers. (f) One No 100 mm dia, dial type thermometer, vapour pressure type, having range 0-120 degree celsius with metal guard having maximum perimeter temperature reading indicator with re-setting device. (g) Two earthing terminals on tank cover to facilitate fixing of 50x6mm galvanised iron earth strip for earthing of body. (h) Rating plate and terminal marking plate. (j) Extra bushing for neutral in the LT cable box for providing independent set of earthing for neutral. First fill of new and unused transformer oil, IS-335 of 1986 marked, filtered and tested upto 50 KV dielectric strength at 2.5 mm air gap between testing electrodes, specific resistance at 27 Degree celsius Ohm-om 500 x 10 the power12, water content 50 PPM, Dielectric dissipation factor (tan Deta at 90 degree celsius) 0.005, Neutralisation value mg of KOH/gm of oil 0.03, Inter facial tension N/M at 27 Degree celsius -0.04, flash point 140 Degree celsius and sluge 0.1% by weight. (l) Providing adequate size and nos of channels, embeded in floor, for movement of transformer. (m ) Tranformer losses shall not exceed the loses mentioned in Table 6 of IS: 1180 of 2014 Part - I (latest edition) with energy Effeciency level - III. (n) Oil temperator indicator, winding temperature indicator, marshlig box single window, double flit buchoiz relay with alarm and trip contact including connection to existing RMU/VCB relay with PVC insulated PVC sheathed cable galvanized steel strip or wire armoured electric control cables (Heavy duty) with stranded copper conductor of size 1.5 sq mm 10 core 1100 volts grade. NOTE:- (i) Rate quoted includes the cost of making and Testing of controll wiring connection at the Transformer and RMU/VCB for the Temperature alarm/Trip, Gas alarm/Trip. (ii) Controll cable shall be measured and paid seperately. | |||||||||
| 2.00 | Supplying, installation, testing and commissioning of 11 KV, 630 Amps having short circuit capacity 20kA/3-sec, Outdoor (IP54), RMU (Ring main unit) 3-way comprising of 01 Nos motorized operated Load Break Switch and 02 Nos 630 Amp Fixed-Type motorized spring-charging VCB electrolytic grade copper busbars all inside single, gas-filled, robotically welded stainless steel 304 (Non Ferrite Non Magnetic Grade) tank with min. thickness 3+0.5 mm, IP 67 Degree of Protection, internal-arc classified 20kA/1sec, on-site-repairable with site replaceable bushing/coupling/mechanism, gas refilling etc. The enclosure shall have padlockable double-door access with anti-theft higes, fully covering the front facia and cable boxes to ensure fail-safe anti-theft protection. The unit alongwith Bus-connected, fixed-type Auxiliary transformer shall include the following along with all necessary accessories and fittings as required at site.
(a) 01 Nos. Incoming Load Break Switch module each consisting of following accessories :-
(i) Each switching-unit is designed as a three position switch. This three function switch combines the functions of switch-disconnector and earthing switch.
(ii) 11kV, 630A Load Break Switch with interlocked line-earthing scheme both short circuit current 20kA/3-sec, Making Capacity 50kAp-01 No
(iii) Auxiliary contacts-1NO+1NC-01 No
(iv) Spring-assisted snap-action motorized mechanism with un-inhibited operating shaft for emergency manual operation with integrated earthing switch -01 No
(v) Cable terminals (site replacable Cable bushings situated not beyond 300mm from cable-cover to allow ease of access for installation/testing/replacement purposes) with double-door arrangement for enhanced safety (IP54+IP3X) interlocked to prevent access upto 11 KV, 300 Sqmm, 3 Core, XLPE AL cable termination in live-condition. Each Set of 03
(vi) Right angle boots (push on type)-Each Set of 03
(vii) Arc proof cable covers having cable entry from bottom, front with Interlocking mechanism including earth switch -01 No
(viii) Capacitive voltage indication fixed type system as per IEC61243 with LED-01 Set
(ix) Fault Passage Indicator It is to be provided for each incomer load break unit, FPI with LED/digital display to be added for detection of cable fault-01 No
(x) ON, OFF, EARTH mechanical indication on the front mimic of the panel - 01 No | 1 | Each Job | 9,00,000 ₹9,00,000 | 10,50,000 ₹10,50,000 | 9,25,000 ₹9,25,000 | 9,00,000 ₹9,00,000 | 9,95,600 ₹9,95,600 | 6,99,999 ₹6,99,999 Lowest |
| 2.01(b) 02 Nos. Outgoing VCB module each consisting of following accessories :- (i) Each function-unit consists of a vacuum-circuit breaker in combination with a three position-switch. The three-position-switch fulfills the operation of the disconnector-function and earthing function. (ii) 11kV, 630A Fixed-Type VCB module with series disconnector cum earthing switch of short circuit breaking current/withstand 20kA/3-sec, Making Capacity - 50kAp-01 No (iii) Aux. contacts - 1NO+1NC-01 No (iv) Stored-energy motorized high-endurance spring charging mechanism (M1+), with inbuilt spring-charging lever and mechanically latched ON/OFF push-buttons to allow handle-less and un-inhibited operation -01 No (v) Cable terminals (site replacable Cable bushings situated not beyond 300mm from cable-cover to allow ease of access for installation/testing/replacement purposes) with double-door arrangement for enhanced safety (IP54+IP3X) interlocked to prevent access upto 11 KV, 185 Sqmm, 3 Core, XLPE AL cable termination in live-condition. Each Set of 3 (vi) Right angle boots (push on type)-Each set of 3 (vii) 30/C + 1E/F self powered numerical protection relay with Low and High set for Over current and Earth Fault. Relay should have facility to display the maximum loaded phase current also. Relay shall record minimum 5 fault records with time stamping. Relay shall be communicable with RS 485 Port on MODBUS Protocol-01 No (viii) Associated ring-core cast-resin insulated CTs 100/50/1 Amp, 2.5 VA, 10P10 for protection - Each Set of 3 (ix) Arc proof cable covers with self Interlocking mechanism with earth switch -01 No (x) Capacitive voltage indication fixed type system as per IEC61243 with LED-01 No (xi) Push button for breaker trip (xii) Shunt trip coil 24V DC-01 (xiii) ON, OFF, TRIP mechanical indication on the front mimic of the panel-01. (xiv) Emergency Trip Push Button - 01. | |||||||||
| 2.02(c) 01 No. Bus-connected, fixed-type Auxiliary transformer With positioned along-side RMU or on the top of the RMU to provide required aux. supply and metering consisting of following accessories :- (i) 1-Ph (11kV/rt3):230VAC, 500VA Auxiliary transformer-01 No (ii) 2x12 Volt DC battery-01 Set (iii) Battery charger-01 No (iv) HRC fuse-links for primary side isolation and AC/DC MCBs for secondary isolation-01 Set (v) Voltmeter & RYB LED Indications to confirm AC/DC supply availability-01 Set (vi) Anti-condensation space-heater-01 No (vii) CFL lamp for illumination and 3-pin socket with switch -01 No (d) Additional equipment delivered separately or mounted separately :- (i) Operating Handle for Manual Isolator/Disconnector/Earthing Operation-02 Nos (ii) Standard Manometer -01 No (iii) Operation and Maintenance Manual -01 No (iv) Installation & Commissioning Manual -01 No (v) Cable clamming provision (standard) 01 No Note:- (i) It is preferable to have all feeder-switches inside single stainless steel compartment with incomer feeders at the extremities to prevent chances of failure due to plug-in coupling arrangement. (ii) Necessary interlocking arrangement shall be provided for safety and operations (iii) Above switchgear shall confirm to relevant IEC (62271-200) for design, manufacturing and internal arc compliance. Any claims towards internal arc compliance, number of mechanical/electrical/short-circuit operations, gas-leakage rates etc. shall not be accepted unless proven via type-test reports of model being offered. | |||||||||
| 3.00 | Supply, installation, testing and commissioning of factory made and tested (including CPRI type tested certified panel) LT Panel board, cubical compartmentalized, out door type double door, plate form mounted, suitable for 415 volts, 3 phase, 4 wire, 50 HZ AC supply system having bus bar chamber with insulated aluminium bus bars four pole installed on porcelain/SMC insulator. The panel shall be dust and vermin proof. IP-65 class protection and shell be made of 3.15 mm CRCA MS sheet, and 50x50x6mm thick MS angle iron frame work, powder coated finish over one coat of red oxide primer on outside surface and painted inside with two coats of red oxide primer, front and rear opening type, with apron for cable entry closing locking arrangement including internal wiring with PVC insulated solid, copper conductor FRLS cable, IS-694 marked, 1100 volts grade of appropriate size (but not less than 2.5 Sqmm) and comprising of the following :-
(a) Incoming :-
(i) ACB 4 pole, 800 Amp, 50 KA, 415 Volt AC Horizontal draw out type motorized, front operated with Micro processor based LCD protection release for adjustable over current, short circuit and earth fault protection-01 No
(ii) Voltmeter digital type with 4 way rotary selector switch -01 No.
(iii) Ammeter digital type with 4 way rotary selector switch-01 No.
(iv) CTs ratio 800/5 A, class 1, ISI marked -01 sets of three
(v) Indicating lamp-01 set of three
(vi) Aluminium bus bar of rating 1600 Amp-set of four
(vii) Onload changeover switch 630 Amps four pole -01 No
(b) Outgoing:-
(i) MCCB 4 pole, 400 Amps, 50 Hz,415 Volts, 50 KA with microprocessor release - 01 Nos
(ii) MCCB 4 pole, 250 Amps,50 Hz,415 Volts, 36 KA with microprocessor release - 01 Nos
(iii) MCCB 4 pole, 200 Amps, 50 Hz,415 Volts, 36 KA with microprocessor release - 01 Nos
(iii) MCCB 4 pole, 160 Amps,50 Hz,415 Volts, 36 KA with microprocessor release - 02 Nos
(c) Platform of Panel :- Platform for the panel with PCC 1:4:8 type D-2 with 40 mm graded crushed stone, 15 cm thick in foundation, brick work in CM 1:6 with sub class 'B', old size bricks, rendering 15 mm thick in CM 1:6 on exposed surfaces and 100 mm thick PCC padding 1:3:6, type C-1 using 20 mm graded crushed stone aggregate on top and grouting bolts etc for panel. The platform shall be such that it is of a height 45 cm above the nearest road level.
Note:-
(i) All out going feeder shall be connected by cable through suitable size gland plate/glands.
(ii) The various feeders shall be indicated by 50 mm size letters in synthetic enamel white paint.
The MCCB should have Ics=100%icu. The MCCBs shall have spreader links and barriers as standard feature of manufacturer
(iii) All MCCB with adjustable protection for over load and short circuit and conforming to IEC60947-II/IS 13947-II (Latest Version | 1 | Each Job | 3,00,000 ₹3,00,000 | 5,66,000 ₹5,66,000 | 3,55,000 ₹3,55,000 | 2,80,000 ₹2,80,000 Lowest | 5,30,480 ₹5,30,480 | 2,99,999 ₹2,99,999 |
| 4.00 | Supply, laying, jointing, testing and commissioning of 11 KV (earth) grade of size 120 Sqmm 3 Core (Heavy duty) with straded compacted circular aluminium conductor screened with extruded semi- conducting compound in combination with copper tape, cores laid up, inner sheeath of thermoplastic tape, PVC bedded galvanised steel strip, armoured and overall FRLS PVC sheathed confirming to IS-70298, Part-II with latest amendments laid in cable Ducts/Trays/Tranches/Encased in GI pipe/RCC/DWC HDPE pipes complete all as specified and directed by Engr-in-Charge. | 800 | RM | 1,000 ₹8,00,000 | 1,220 ₹9,76,000 | 830 ₹6,64,000 Lowest | 1,200 ₹9,60,000 | 1,262 ₹10,09,600 | 1,199 ₹9,59,200 |
| 5.00 | Supply, laying, connecting, testing and commissioning of LT XLPE cable of PVC Sheathed armoured aluminium conductor 1100 V graded 630 Sqmm single core complete all as specified and directed by Engr-in-Charge. | 100 | RM | 1,000 ₹1,00,000 | 1,224 ₹1,22,400 | 810 ₹81,000 | 900 ₹90,000 | 973 ₹97,300 | 99 ₹9,900 Lowest |
| 6.00 | Material and labour for excavation in trenches not exceeding 1.5m wide & not exceeding 1.5m in depth and n.exc 10 sqm on plan for foundations, laying of HT under ground cables/ GI pipes and steel tubular poles etc. and getting out as in soft / loose soil complete all as specified and directed by Engr-in-Charge. | 542.7 | Cum | 100 ₹54,270 | 300 ₹1,62,810 | 180 ₹97,686 | 99 ₹53,727.3 Lowest | 122 ₹66,209.4 | 149 ₹80,862.3 |
| 7.00 | Material and labour for returning, filling in, including spreading, levelling, watering and well ramming in layers not exc. 25 cm deep as in soil complete all as specified and directed by Engr-in-Charge. | 345.56 | Cum | 30 ₹10,366.8 | 21 ₹7,256.76 | 40 ₹13,822.4 | 29 ₹10,021.24 | 61 ₹21,079.16 | 19 ₹6,565.64 Lowest |
Tender Value
₹5.0 Cr
EMD Value
₹99,500
Closing Date
11 Sept 2025, 6:00 pmClosed
GE UTILITY ELECTRIC SUPPLY
GE UTILITY ELECTRIC SUPPLY
PROVISION OF 500 KVA TRANSFORMER ALONGWITH CONNECTED ITEMS FOR KALPATARU AND GIRLS CADETS AREA AT DGNCC CAMP UNDER GE U ELECT SUPPLY DELHI CANTT 10
2025_MES_710228_2
GE ELECT/D-24/2025-26
Open Tender
Electrical and Maintenance Works
Item Rate
180 days
GE UTILITY ELECTRIC SUPPLY
AS PER DOCUMENTS
7 documents required · 7 mandatory
₹500
Yes
GE UTILITY ELECTRIC SUPPLY
₹99,500
Yes
24 Nov 2025
14 Aug 2025
15 Sept 2025
14 Aug 2025
11 Sept 2025
28 Aug 2025
stage.html
html • 0.06 MB
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .