Loading…
Loading…
| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | L1₹6.0 LAccepted-AOC | L1 | Accepted-AOC Bid accepted by the Government | |
| 2 | L2₹6.9 L+₹90,235 (15.2%)Rejected-Finance HNO 1131 TIVIM BARDEZ GOA | TIVIM | BARDEZ | GOA | 403507 | L2 | Rejected-Finance REJECTED | |
| 3 | Rejected-Technical | - | Rejected-Technical Not Qualified |
Tender Value
₹6.6 L
EMD Value
₹13,187
Closing Date
20 Dec 2021, 5:30 pmClosed
Executive Engineer
Office of the Executive Engineer Division XVII Mapusa Goa
Work of erection of 100KVA Distribution Transfomer Centre alongwith 3 phase 5 wire LT line inorder to release 1 no. of LTD Service connection to Shri. Ankush Arjun Gawas at survey No. 87/0, Nadora, Bardez-Goa for a total load of 6940W under the juris
2021_ED_1757_1
12(2021-22)
Open Tender
Electrical Works
Item Rate
90 days
Nadora Bardez
Please refer Tender documents.
2 documents required · 2 mandatory
₹1,000
₹13,187
Yes
Office of the Executive Engineer Division XVII
17 Oct 2022
2 Dec 2021
22 Dec 2021
3 Dec 2021
20 Dec 2021
10 Dec 2021
9 Dec 2021
Amount
COST OF MATERIAL
11 KV, 200A Horn gap fuse unit (Set of three) shall be as per enclosed drg No. CEE/E-786. Revision 3 and detailed specifications enclosed herewith.
9KV, 5KA nominal discharge current metal oxide gapless distribution class Lightning arrestor conforming to IEC-600994-4 and IS: 3070 part 3 1993 as amended upto date.
HDGI structure material. Consisting of Channels, angles, clamps, etc as per requirement of work, NIT, drawings, etc.
Turnbuckle with eye bolt for LT/11KV stay set
HDGI Top Insulator fitting Cross arm ISMC channel 75 x 40 mm, 0.7 mtr with nut bolts long for 11 mts long RCC pole
HDG cut point crosss arm channel ISMC 75 X40 X 6mm of 1.3 mts long with clamps and nuts & bolts for 11 mts RCC pole
11KV Guard Cross arm 1.5Mts long with clamps & nut bolt for 11mtr RCC pole
11 KV Disc Insulators 70 KN with metal parts 3 bolted type
11 KV Pin Insulator
LT shackle Insulator
Earthing complete with chamber as per drg/ No. CEE/E-830. Each earthing should consist as follows a) 40 mm. Dia 2.5 mtr long, class B GI pipe 1 No. b)HDGI nut bolts, clamps 1 set, c)Brick masonary-0.108 Cu.mts d) PVC pipe 50mm dia- 0.2mtr e) Salt-20 Kgs f) Charcoal-20 Kgs g) Excavation-0.864 Cu. Mtr h) refilling-0.74 Cu.mtr as per drg. No.CEE/E-830.
XPLE insulated single core unarmoured cable 50 mm2 for DP earthing.
AA"ANT" conductor
AA"GNAT" conductor
MS Distribution box as per drg No. CEE/E-689 Revision No. 3 along with MCCB 400 A, Bus bar made out of Aluminium strips 40 x 10 mm, kit kat fuses for 4 feeder arrangement
XLPE 1.1KV Armored single core unarmoured cable 300 mm²
XLPE 1.1KV Armored single core unarmoured cable 120 mm²
Distribution Transformer Metering unit as per T.S.
Enamelled danger boards 11000 Volts ,250mm x 200mmm as per drg no. CEE/E-490
Anti climbing device alongwith suitable two stay clamps & two pairs of H.D.G.I nuts bolts as per drg No. CEE/E-478
Aluminium crimping Lugs 300 Sq.mm.
Cement concreting 1 : 2:4
FRP Fencing complete with Gate as per specification for Distribution Transformer (Size 4Mx3Mx2M) with Concreting for FRP Fencing supports with plinth (0.3x0.3x0.5) Cu.m. x 12 nos. Each ratio 1:3:6
COST OF ERECTION
RCC pole 11 mtr long
RCC pole 9 mtr long
100 KVA 11KV/.43 KV Distribution transfromers
11 KV rated voltange GOAB switches 200 A
11 KV, 200 A Horn gap fuse unit (Set of three)
9 KV, 5 KA Lightning arrestor.
HDGI structure material. Consisting of Channels, angles, clamps, etc as per requirement of work, NIT, drawings, etc.
LT/11KV Stay set complete for 11Mts long RCC pole with Stay rod with plate , Stay wire 7/10SWG,Break insulator 8KV, Stay clamps ; G.I. Nuts & Bolts
Turnbuckle with eye bolt for LT/11KV stay set
LT/11KV Stay set complete for 9Mts long RCC pole with Stay rod with plate , Stay wire 7/10SWG,Break insulator 8KV, Stay clamps ; G.I. Nuts & Bolts
HDGI Top Insulator fitting Cross arm ISMC channel 75 x 40 mm, 0.7 mtr with nut bolts long for 11 mts long RCC pole
HDG 11 KV 'V' Shape cross arm of channel ISMC 75 x 40 x 7.3 mm. with HDG Clamp & HDG nut bolts etc. for 11 Mtr. long RCC Pole as pet drg no. CEE/E - 408-R1
HDG cut point crosss arm channel ISMC 75 X40 X 6mm of 1.3 mts long with clamps and nuts & bolts for 11 mts RCC pole
11KV Guard Cross arm 1.5Mts long with clamps & nut bolt for 11mtr RCC pole
HDG L.T. 4 pin cross arm Channel type as above with HDG clamps & HDG nut bolts etc for 9mts long RCC pole as per drg No.CEE/E-491 and drg no. CEE/E-524
HDG L.T. 2 pin cross arm Channel type as above with HDG clamps & HDG nut bolts etc for 9 mts long RCC pole as per drg No.CEE/E-491 and drg no. CEE/E-524
11 KV Disc Insulators 70 KN with metal parts 3 bolted type
11 KV Pin Insulator
GI pin for 11 KV pin insulators
LT shackle Insulator
Metal parts for LT Shackle insulator
ACSR WEASEL Conductor
Earthing complete with chamber as per drg/ No. CEE/E-830. Each earthing should consist as follows a) 40 mm. Dia 2.5 mtr long, class B GI pipe 1 No. b)HDGI nut bolts, clamps 1 set, c)Brick masonary-0.108 Cu.mts d) PVC pipe 50mm dia- 0.2mtr e) Salt-20 Kgs f) Charcoal-20 Kgs g) Excavation-0.864 Cu. Mtr h) refilling-0.74 Cu.mtr as per drg. No.CEE/E-830.
XPLE insulated single core unarmoured cable 50 mm2 for DP earthing.
AA"ANT" conductor
AA"GNAT" conductor
MS Distribution box as per drg No. CEE/E-689 Revision No. 3 along with MCCB 400 A, Bus bar made out of Aluminium strips 40 x 10 mm, kit kat fuses for 4 feeder arrangement
XLPE 1.1KV Armored single core unarmoured cable 300 mm²
XLPE 1.1KV Armored single core unarmoured cable 120 mm²
Distribution Transformer Metering unit with DLMS/COSEM protocol energy meter with modem
Enamelled danger boards 11000 Volts ,250mm x 200mmm as per drg no. CEE/E-490
Anti climbing device alongwith suitable two stay clamps & two pairs of H.D.G.I nuts bolts as per drg No. CEE/E-478
Aluminium crimping Lugs 300 Sq.mm.
Aluminium crimping Lugs 120 Sq.mm.
Aluminium crimping Lugs 50 Sq.mm.
FRP Fencing complete with Gate as per specification for Distribution Transformer (Size 4Mx3Mx2M) with Concreting for FRP Fencing supports with plinth (0.3x0.3x0.5) Cu.m. x 12 nos. Each ratio 1:3:6
Painting of Pole Numbers (including paint, etc charges)
Deepti Enterprises
stage.html
html • 0.05 MB
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .