Loading…
Loading…
| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | L1₹2.4 CrAccepted-AOC 2 1433 D 6 KAMAL COLONY SAHARANPUR UP PIN 247001 | SAHARANPUR | UTTAR PRADESH | 247001 | ₹2.4 Cr | L1 | Accepted-AOC Found 1st lowest |
| 2 | L2₹2.4 Cr+₹6.9 L (2.94%)Rejected-AOC | ₹2.4 Cr+₹6.9 L (2.94%) | L2 | Rejected-AOC Found 2nd lowest |
| 3 | L3₹2.4 Cr+₹8.3 L (3.53%)Rejected-AOC | ₹2.4 Cr+₹8.3 L (3.53%) | L3 | Rejected-AOC Found 3rd lowest |
| 4 | L4₹2.4 Cr+₹9.3 L (3.96%)Rejected-AOC | ₹2.4 Cr+₹9.3 L (3.96%) | L4 | Rejected-AOC Found 4th lowest |
| 5 | L5₹2.5 Cr+₹13.8 L (5.87%)Rejected-AOC | ₹2.5 Cr+₹13.8 L (5.87%) | L5 | Rejected-AOC Found 5th lowest |
Tender Value
₹2.8 Cr
EMD Value
₹6.5 L
Closing Date
2 Jun 2026, 5:00 pmClosed
Senior Manager (E) HQ
A-1/4 Lakhanpur, Kanpur
Up-gradation of 33/11 KV Sub-Station (1x5 MVA) to 15 MVA, 33/11 KV Sub-Station at I.A. Khimsepur Distt. Farrukhabad.
2026_SIDC_1147999_1
ED_I_447_05032026
Open Tender
Electrical Works
Percentage
365 days
Khimsepur Farrukhbad
Please refer Tender documents.
3 documents required · 3 mandatory
₹6,806
UPSIDA
₹6.5 L
10 Sept 2026
13 May 2026
3 Jun 2026
13 May 2026
2 Jun 2026
13 May 2026
This is a percentage-rate BOQ. The schedule below shows estimated quantities and rates. Bidders quote a single percentage above or below the total estimated cost.
| Sl No | Description | Qty | Unit | Est. Rate | Est. Amount |
|---|---|---|---|---|---|
| 1 | S/E of Terminal Gantry of R.S. Joist-175x85 mm 19.5 Kg/Mtr. 6.1 Mtr. above the ground and 1:3:6 cement concrete foundation mounted on a stone pad of 300x300x75 mm complete in all respect as per latest technical specification of DVVNL approved by Engineer in charge. | 1 | Nos | 88,718 | ₹88,718 |
| 2 | S/E of erection of 33 KV line Isolator suitable 1250 Amp. with structure & foundation complete in all respect as per latest technical specification of DVVNL approved by Engineer in charge. | 1 | Nos. | 79,731 | ₹79,731 |
| 3 | S/E of erection of 33 KV Bus Isolator suitable 1250 Amp. with structure & foundation complete in all respect as per latest technical specification of DVVNL approved by Engineer in charge. | 2 | Nos. | 64,363 | ₹1,28,726 |
| 4 | Supply, Errection, testing & Commissioning of 33 KV VCB,1250A 750 MVA Motorized auto spring charge system complete with Mounting structure,Outdoor CT-400/200/100/1A, 0.2 Class with structure and foundation , 33 KV Outdoor PT 33KV/11V with structure and foundation work complete in all respect as per latest technical specification of DVVNL approved by Engineer in charge. | 1 | Set | 10,56,944 | ₹10,56,944 |
| 5 | S/E of Bus Bar gantry structure of 105 Lbs/Rail Pole 6.5 Meter long 5.2 Meter above in ground level including cost of material, foundation etc. complete in all respect as per latest technical specification of DVVNL approved by Engineer in charge. (All drawing preparation & approval shall be done by Contractors at its own cost from DVVNL/Electrical saftey of U.P | 1 | Nos. | 54,669 | ₹54,669 |
| 6 | S/E of 33 KV lighting arrestors set with structure made of MS channel 125x65 mm 3.1 Kg./M top of MS angle 50x50x6 mm, 4.5 Kg/M Lighting Arrestor (one set of lighting arrestor shall be installed on gantry) complete in all respect as per latest technical specification of DVVNL approved by Engineer in charge. | 2 | Set | 48,148 | ₹96,296 |
| 7 | Supply, Errection, testing & Commissioning of outdoor type with copper wound 33/11KV , 10 MVA Transformer with off load tap changer as per DVVNL with following provisions.(a) Cable termination box with disconnecting facility for 33 KV XLPE cable outdoor arrangement with 33 KV bushings at 33 KV side. (b) Cable termination box with disconnecting facility with 11 KV bushings for 11 KV XLPE cable at 11 KV side. (c) Off load tap changer +5% to -15% @ 2.5% (d) Bi directional roller (e) Conservator with drain valve & sump value. (f) Earthing terminals (Two) (g) Double diaphram explosion vent (h) Radiator with top & bottom shut of valve (i) First filling of oil including makeup fill (j) Silica gel breather with oil seal (k) Rating and Diagram plate (l) Air release plug (m) Buchholz relay with shut off valves on both sides.(n) Winding temperature Indicator (WTI) (o) Oil Temperature indicator (OTI) (p) Magnetic oil level gauge (q) Pressure relief device (r) Marshalling Box (s) Tap position indicator (t) Marking plate for OLTC (u) Terminal marking plate (v) Drain valve with plug & locking arrangement (w) Filter valve (x) Oil sampling Valves (03 nos) as per latest technical specification of DVVNL approved by Engineer in charge. | 1 | No. | 1,20,10,125 | ₹1,20,10,125 |
| 8 | Supply & fixing 33 KV Pin Insulator with pin on main terminal gantry including cost of material, men and T&P. | 3 | Nos. | 668 | ₹2,004 |
| 9 | S/F of 33 KV insulator string having 4 nos of 11 KV B&S type strain disc insulators 120 KN E&M strength & 33 KV tension fitting complete in all respects as per latest technical specification of DVVNL approved by Engineer in charge. | 12 | Set | 2,706 | ₹32,472 |
| 10 | S/F of P.G. Clamp suitable for panther conductor for jumpring complete in all respect as per latest technical specification of DVVNL approved by Engineer in charge. | 36 | Nos. | 223 | ₹8,028 |
stage.html
html • 0.07 MB
tech_eval.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Tendernotice_1.pdf
PDF • 0.09 MB
FEEFORMAT.xls
Tender Documents • 0.03 MB
etenderdocuments.pdf
Tender Documents • 0.44 MB
BOQ_2148393.xls
BOQ • 0.39 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .