Loading…
Loading…
| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | L1₹9.7 LAccepted-AOC | L1 | Accepted-AOC L1 | |
| 2 | L2₹14.0 L+₹3.5 L (33.5%)Rejected-AOC | L2 | Rejected-AOC L2 | |
| 3 | L3₹14.2 L+₹3.8 L (36.1%)Rejected-AOC | L3 | Rejected-AOC L3 | |
| 4 | L4₹15.5 L+₹5.0 L (48.0%)Rejected-AOC I 910 JAHANGIR PURI NEAR BY ANAND MAYA HOSPITAL NORTH WEST DELHI DELHI 110033 UDYAM DL 06 0040830 | NORTH DELHI | DELHI | 110033 | L4 | Rejected-AOC L4 | |
| 5 | L5₹15.8 L+₹5.3 L (50.7%)Rejected-AOC | L5 | Rejected-AOC L5 |
Tender Value
₹18 L
EMD Value
₹36,000
Closing Date
11 Jul 2020, 6:00 pmClosed
GE JAMMU
GE JAMMU PIN-180003 C/O 56APO
REPAIR AND MAINTENANCE OF UG CABLES, ACSR CONDUCTOR, POLES AND OTHER CONNECTED WORKS AND LT DISTRIBUTION SYSTEM AND ALLIED WORKS AT DAMANA UNDER GE JAMMU
2020_MES_353114_1
GEJC-21/2020-21
Open Tender
Electrical and Maintenance Works
Item Rate
180 days
GE JAMMU
Class E
Category b(i)
8 documents required · 8 mandatory
₹500
GE JAMMU
₹36,000
Yes
24 Aug 2020
20 Jun 2020
13 Jul 2020
20 Jun 2020
11 Jul 2020
4 Jul 2020
Amount
Excavation in trenches not exc 1.5 Mtr wide and not exc 1.5 Mtr deep any type of soil getting out and levelling of bottom surface to required level for poles/stay assembly/cable all as specified and as directed.
M&L for road cutting, PCC hard standing with width 0.4 & depth 0.9 mtr including excavation for laying of GI pipe and making good the disturbed surfaces all as per existing surface all as specified and as directed.
All as per above item No. 1 here in before but for each additional 1.5 mtr or part thereof in depth beyond the first 1.50 mtr all as specified and as directed.
Returning filling in, including spreading, leveling, watering and well ramming in layers not exc 25m thick all as specified and directed.
Removing excavated material from site to a distance not exc 50mtr away and depositing where directed not exc 1.5mtr from the starting point all as specified and as directed.
M&L in replacement of GI Pipe light grade 80 mm bore for cable protection as a guard pipe complete all as specified and as directed.
M&L in replacment of GI Pipe light grade 50 mm bore for cable protection as a guard pipe complete all as specified and as directed.
M&L Sub class 'B' bricks well burnt laid with length perpendicular to the axis of the cable in trenches for protection to cable complete all as specified and as directed.
Supplying & Laying in trenches Clear Sand for cushioning under ground cable 8 cm below and 15 cm above complete in level all as specified and as directed.
M&L for PCC 1:3:6 (40 mm graded aggregate) Type C2 for foundation of pole, stay incl frame work where required all as specified and directed.
PCC (1:2:4) type B-I coping with 20 mm graded aggregate for poles complete all as specified and directed.
Taking out/down unserviceable, defective cable any Type/size including disconnecting all the electrical connections all as required at site and all as directed.
M&L for XLPE insulated, armoured heavy duty electric cable with aluminium conductor, 1100 volts grade, cross-sectional area 10 Sq mm, 2 core, complete all as specified and directed by Engr-in-Charge. Note: Wherever cable fixing/connection, suitable thimble should be used as per site situation AND Excavation and earth work, sand cushioning, brick work and GI pipe shall be measured and paid separately.
All as per item No. 13 here in before but cross sectional area 16 sq mm 2 core complete all as specified and directed by Engr-in-Charge.
All as per item No. 13 here in before but cross sectional area 25 sq mm 3.5 core complete all as specified and directed by Engr-in-Charge.
All as per item No. 13 here in before but cross sectional area 35 sq mm 3.5 core complete all as specified and directed by Engr-in-Charge.
All as per item No. 13 here in before but cross sectional area 50 sq mm 3.5 core complete all as specified and directed by Engr-in-Charge.
M&L in replacement of ACSR conductor any size/any type drawn on fixed to insulator on the pole complete as with permissible sags for OH Conductor all as specified and directed.
M&L in replacement of Galvanised steel wire 4.0 mm dia for continuous earth wire and Cradles hexagonal/rectangular shall be provided and securely fastened to each pole and connected with earth ordinarily and cradle guarding where required complete all as specified and directed.
M&L in replacement of Stay assembly complete with all accessories as shown in electrical plate No 1, including loop type insulator and stay clamps, Diameter of stay rod 20 mm complete all as specified and as directed. Note:- Excavation and Concrete work will be measured and paid separately.
M&L for Pre stressed concrete pole 9.0 meter long 102mmX172 mm at Top and 12 mm and 279 mm at bottom class 10 all as specified and directed.
M&L in replacement of Cross arms, bracings, supports, clamps and back plates fabricated from structural steel sections i.e M.S. channel or angle sections etc. including new nuts, bolts, washers as reqd dia/length in size, welding, bending cold or hot, drilling holes for bolts, in any shape or size as indicated or directed and inclusive one primer coat of red oxide, one under coat and one finishing coat of silver paint (1st quality ) as required complete all as specified and as directed.
M&L in replacement of Insulator Shackle type, porcelain, vitreous, white,brown or green , shall be in one piece and shall have a groove on the side and a hole for a cotter pin and two galvanised bolts 12 mm dia and nuts with or without a pair of straps in size 31 x 3 mm as indicated size height 75 mm and dia 90 mm, for working pressure 1100 volts complete all as specified and as directed.
M&L in replacement of Insulator Pin type, porcelain, vitreous, white,brown or green including one galvanised mild steel spindle, two galvanised iron washers and one galvanised iron nut, 100 mm height, 65 mm dia for 1100 volts grade, shall be in one piece and have a top groove and shall be threaded to take galvanised mild steel pin complete as specified and as directed.
Labour for Cutting of tree branches 2 mtr above the conductor which are touching to the 11/9 mtr Over Head Lines in vertically & horizontally conductor and poles etc, complete clear in a standard Span in between two poles as per SSR Part-I, 19.59 and removing cutting material not exc 50 mtr and depositing where directed at a distance level not exc 3 mtr from starting point, minimum 04 Nos of Mazdoor-man with ropes/cutting tools complete will be engaged for a standard one span at a forest/high gradient/any type of surfaces, follows safety measures as per IE Rules, all as specified and as directed. Note: Cutting of tree will be measured in unit mtr from pole to pole.
Material and labour for preparation of old painted / rusted surfaces of steel tubular poles 11/9 mtrs long type 410 SP-31,55 and applying one coat of synthetic enamel paint up to 1.2 mtr height as per exising pattern above the P.C.C coping and two coat of aluminum paint (1st quality) beyond 1.2 mtr height (for the rest of portion) incl cross arms and channel, angle fitted on the pole incl wiriting pole numbers and cutting vegetation growth all arond and on the poles up to 1 mtr radius complete all as specified and directed.
Material and labour for preparation of old painted surfaces of PCC poles 11/9 mtrs long type 410 SP-31,55 and applying two coats of synthetic enamel paint up to 1.2 mtr height as per exising pattern above the P.C.C coping and two coats of aluminium paint to cross arms and channel, angle fitted on the pole incl wiriting pole numbers and cutting vegetation growth all arond and on the poles up to 1 mtr radius complete all as specified and directed.
Supply and fix in replacement unserviceable aluminium lugs/thimble of size 240 sqmm complete all as specified and directed.
Supply and fix in replacement unserviceable aluminium lugs/thimble of size 185/120 sqmm complete all as specified and directed.
Supply and fix in replacement unserviceable aluminium lugs/thimble of size 70/95 sqmm complete all as specified and directed.
Supply and fix in replacement unserviceable aluminium lugs/thimble of size 25/35/50 sqmm complete all as specified and directed.
Supply, installation, testing and commissioning replacement of LT panel of suitable size for 3 Phase 415 volt , outdoor weather proof vermin proof duly powder coated double door with back and front opening made out from 3.0 mm thick CRCA sheet with angle iron base frame of size 50x50 x6 mm cubical type complete with aluminium bus bar 400 Amp 4 way with proper color coding complete with PVC insulator, with IP 54 as per IS 13947 protection, fault rating 50 KA/1Sec, complete with following items including :-
MCCB 4 Pole, current rating 400 Amp, with adjustable thermal magnetic setting 70%-100% breaking capacity 36KA at 415V,50Hz, - 01 No as incomer
MCCB 4 Pole, current rating 250 Amp, with adjustable thermal magnetic setting 70%-100% breaking capacity 25kA at 415V,50Hz, - 02 No as outgoing
MCCB 4 Pole, current rating 100 Amp, with adjustable thermal magnetic setting 70%-100% breaking capacity 25kA at 415V,50Hz, - 03 No as outgoing (one spare)
MCB SPN 40 amps 'C' series 10 KA -2 No
Digital Ammeter 0-315 Amp with suitable CTs and selctor switch-01 No
Indicator lamps (LED type) showing R,Y,B phases - 01 Set
Internal panel wiring with suitable multistranded copper conductor PVC insulted and seathed FRLSH complete with copper thimble/lugs
Angle iron base frame as reqd size as per above panel, total leg height 600 mm and grouting in side PCC 150 mm legs and made out of ISA5050, 50 x 50 x 6 mm thick angle iron duly painted - 01 No.
Necessary foundation in PCC 1:3:6 (40 mm graded aggregate) Type C2 for foundation of angle iron legs frame work complete - 01 Job
Supply, installation, testing and commissioning replacement of LT panel of suitable size for 3 Phase 415 volt , outdoor weather proof vermin proof duly powder coated double door with back and front opening made out from 3.0 mm thick CRCA sheet with angle iron base frame of size 50x50 x6 mm cubical type complete with aluminium bus bar 800 Amp 4 way with proper color coding complete with PVC insulator, with IP 54 as per IS 13947 protection, fault rating 50 KA/1Sec, complete with following items including :-
MCCB 4 Pole, current rating 630 Amp, thermal setting adjustable 70%-100% breaking capacity 50kA at 415V,50Hz, 01 No as incomer
MCCB 4 Pole, current rating 250 Amp, thermal setting adjustable 70%-100% breaking capacity 36kA at 415V,50Hz, 02 No as out going
MCCB 4 Pole, current rating 100 Amp, thermal setting adjustable 70%-100% breaking capacity 16kA at 415V,50Hz, 02 No as out going(one spare)
On load change over switch 400Amps,4pole,415V front operatred rotary type-01No
Indicator lamps (LED type) showing R,Y,B phases - 01 Set
Angle iron base frame as reqd size as per above panel, total leg height 600 mm and grouting in side PCC 150 mm legs and made out of ISA5050, 50 x 50 x 6 mm thick angle iron duly painted - 01 No.
Necessary excavation and as reqd PCC 1:3:6 (40 mm graded aggregate) Type C2 for foundation of angle iron legs frame work complete - 01 Job
Internal panel wiring with suitable multistranded copper conductor PVC insulted and seathed FRLSH complete with copper thimble/lugs
M&L for welding to damaged/broken hinges of unsv LT panel board shutters complete with painting and matching with existing colour all as specified and as directed. Note:- Welding of two no hinges considered as one Job.
M&L for replacement of old unsv/broken shutter of LT panel with 3 mm thick CRCA sheet as per exisitng size to match with the existing panel duly powder coated and welding hinges and fixing complete all as specified and as directed by Engr-in-Charge.
M&L for painting of existing LT panel board with spray gun with synthetic enamel paint to match with the existing surface internally and externally incl prepration of old rusted surface after taking proper shut down complete all as specified and directed by Engr-in-Charge.
M&L for replacment of old burnt out aluminium bus bar and connected link bar with proper colour coading with insulation tape of current rating 630/400 Amps incl replacement of old rusted nut & bolts, washers complete all as specified and as directed by Engr-in-Charge.
M&L for XLPE insulated, armoured heavy duty electric cable with aluminium conductor, 1100 volts grade, cross-sectional area 70 Sq mm, 3.5 core, complete all as specified and directed by Engr-in-Charge. Note:- Excavation and earth work, sand cushioning, brick work and GI pipe shall be measured and paid separately.
All as per item No. 38.00 here in before but cross sectional area 95 sq mm 3.5 core complete all as specified and directed by Engr-in-Charge.
All as per item No. 38.00 here in before but cross sectional area 120 sq mm 3.5 core complete all as specified and directed by Engr-in-Charge.
All as per item No. 38.00 here in before but cross sectional area 185 sq mm 3.5 core complete all as specified and directed by Engr-in-Charge.
All as per item No. 38.00 here in before but cross sectional area 240 sq mm 3.5 core complete all as specified and directed by Engr-in-Charge.
S&F in replacement unsv indicators LED set of three pieces as per existing size and samplecompleted all as directed by Engr-in-Charge.
S&F in replacement Ampere meter analog type 0-200/ 0 to 400, 0 to 600 96 sqmm square type flush panel mounted complete all as specified and as directed by Engr-in-Charge.
S&F Volt meter analog type 0-500 Volt 96 sqmm square type flush panel mounted complete all as specified and as directed by Engr-in-Charge.
M&L for replacement of MCCB 4 Pole, current rating 630 Amp, thermal setting adjustable 70%-100% rapturring capacity 50kA at 415V,50Hz all as specified and as directed.
M&L in replacement of MCCB 4 Pole, current rating 400 Amp, thermal setting adjustable 70%-100% rapturring breaking capacity 50kA at 415V,50Hz all as specified and as directed.
M&L for in replacement of MCCB 4 Pole, current rating 250 Amp, thermal setting adjustable 70%-100% breaking capacity 36kA at 415V,50Hz all as specified and as directed.
M&L for in replacement of MCCB 4 Pole, current rating 200 Amp, thermal setting adjustable 70%-100% breaking capacity 25kA at 415V,50Hz all as specified and as directed.
M&L in replacement of MCCB 4 Pole, current rating 160 Amp, thermal setting adjustable 70%-100% breaking capacity 25kA at 415V,50Hz, all as specified and as directed.
Supply and Fix in replacement of onload changeover switch AC-23 (side handle) in sheet metal enclosure of capacity 100 Amp, 415 volts 3 phase , four pole all as specified and as directed.
M/S Bali Agencies
M/S GAGAN ENGINEERS AND CONTRACTORS
SATISH AND CO
Vishesh Engineers
Kay Bee Traders
R K BUILDERS
M/S S K Electricals Regd
Bidder Name
Vishesh Engineers
M/S S K Electricals Regd
SATISH AND CO
Sarbat Construction Co
Kay Bee Traders
M/S Bali Agencies
R K BUILDERS
M/S GAGAN ENGINEERS AND CONTRACTORS
stage.html
html • 0.06 MB
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .