| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | L1₹63.4 LAccepted-AOC 2ND FLOOR 39 4166 SHEMA BUILDING M G ROAD RAVIPURAM KOCHI ERNAKULAM KERALA 682016 | KOCHI | ERNAKULAM | KERALA | 682016 | L1 | Accepted-AOC WO issued to L1 bidder | |
| 2 | L2₹63.7 L+₹33,701 (0.53%)Rejected-AOC | L2 | Rejected-AOC WO issued to L1 bidder | |
| 3 | L3₹67.4 L+₹4.1 L (6.40%)Rejected-AOC 90 MYLAPORE CHENNAI TAMIL NADU 600004 | CHENNAI | TAMIL NADU | 600004 | L3 | Rejected-AOC WO issued to L1 bidder | |
| 4 | Not Admitted-Fee/PreQual/Technical | - | Not Admitted-Fee/PreQual/Technical Not Complied with technical specification | |
| 5 | Not Admitted-Fee/PreQual/Technical COIMBATORE COIMBATORE TAMIL NADU | - | Not Admitted-Fee/PreQual/Technical Others-Others |
Tender Value
₹64.0 L
EMD Value
₹1.3 L
Closing Date
27 Oct 2022, 3:00 pmClosed
Eligibility, documents, scope and key termsEligibility, required documents, scope of work and key terms of this tender, in one click.
Executive Engineer (Electrical)
Engineering Unit, Admin Block 3rd Floor, IIT Madras CHENNAI-600036
Provision of AC Facility to GF and FF of Campus Cafe in IIT Madras
2022_IITM_132186_1
20/2022-23/ELDB
Open Tender
Electrical Works
Item Rate
30 days
IIT MADRAS CHENNAI
All required documents as specified in the tender
2 documents required · 2 mandatory
₹0
₹1.3 L
6 Dec 2022
15 Oct 2022
28 Oct 2022
15 Oct 2022
27 Oct 2022
18 Oct 2022
16 Oct 2022 - 17 Oct 2022
Amount
AIR HANDLING UNITS
Supply, Delivery, Installation, testing & commissioning of Floor mounted Air handling units in Re-circulatory configuration with 24G (0.64mm) pre-plasticised G.I. outer skin and 22G (0.8mm) plain G.I. inner skin with 40kg/m3 density Polyurethen Foam/PIR insulation having thickness 43±2mm in double skin construction as per air flow diagrams & specifications with following accessories. AHU cost will be inclusive of lifting & putting inplace.
Thermal break profile at corners and at joints for double skin air handling units along with internal covings.
AHU frame shall be made of non corrosive extruded aluminum profile fitted together with polyamide corner pieces.
Flange type filters with extruded aluminum flanges along with quick filter fixing arrangement with SS 304 wing nuts.
Chilled water cooling coil shall be of copper tubes with aluminum fins and 6 rows deep suitable for chilled water operation.
Drain pan in 16G SS 304 construction along with 25mm nitrile rubber insulation with smooth finish and slope should be provided to have zero retention of water in drain pan. The insulation shall be sandwiched between to sheets of SS 304.
Inlet and outlet connection of chilled water shall be on same side.
AHU shall be with blower shall be DIDW Centrifugal fans low aerodynamic losses, silent operation & high efficiency with class IE3 suitable for operation on 415 volts ± 10%, 50 Hz ± 5% AC supply,
AHU shall be along with VFD & Electrical cable connection from panel consisting with stand alone controller to AHU shall be done by HVAC contractor.
All AHU's will be supplied with two sets of filters. One set will be for Pre commissioning & one original set of post commissioning Filters shall be EU-4
Fire retardant flexible canvas connection and cushy foot mounting for fan
AHU will be mounting on 25 mm neoprene rubber for anti vibration
Unit shall be provided with flanges and low leakage extruded motorised aluminum volume control dampers with positive locking arrangement and percent opening gradations on supply side, return side, fresh air side and purge side in loose condition.
AHU shall be with Wall mounted type VFD Starter Panels located in respective AHU Rooms. The panel enclosure shall be same as for MCCs. (The VFD Starter Panel shall consist of MCCB Auto Manual Switch, Luminous ON/OFF Push Buttons, Internal Wiring, Connectors for power & Control cables & Other panel accessories to make the panel complete.) Panel Should be compatible with BMS System. All internal wiring in the AHU should be as per Firenorms
AHU shall be supplied with Stand-alone operation controller with built in applications inclusive of sensors, sensor cables & DP transmitter complete with DDC controller, It Should be compatible with BMS System as per technical specification
Horizontal Floor Mounted AHU
Capacity: 44.0 TR, Dehumidified Air: 17600 CFM, AHU with 65mm Static Pressure (Valve Sizes 50 MM)
Capacity: 50.0 TR, Dehumidified Air: 20000 CFM, AHU with 65mm Static Pressure (Valve Sizes 65 MM)
PIPES AND VALVES
Supply, erection, testing and commissioning of chilled water circulation pipes. Pipes will be of Mild Steel - Class C and insulation material shall be PUF. The insulation material shall be covered with 24G Aluminium cladding for outdoor application
80 NB pipe with 30mm thick PUF insulation
65 NB pipe with 30mm thick PUF insulation
25 NB pipe with 30mm thick PUF insulation
Supply and erection of the following UPVC pipe with all joints, reducer, necessary elbows and tees, supporting arrangements, etc. Rate shall be inclusive of 19mm thick FM approved closed cell nitrile rubber insulation covering with fire resistant fibre cloth fabric as a resistant to Scratch & Mechanical Impact.
50mm Dia
Supply and erection of Butterfly valves(PN 16) as per specification complete with end flanges / matching flanges, additional supports, fixing accessories, thermal insulation, etc. The valve shall be gear operated for 200NB and above.
Supply and erection of ‘Y’ type strainer with removable stainless steel screen with 3mm perforation and permanent magnet, drain piping. Rate shall inclusive of matching flanges, additional supports, fixing accessories, thermal insulation, etc.
Supply, Installation, testing and commissioning of Flow Control Valve - Pressure independent type with Dynamic Balancing Cum 2 Way modulating valves (PN-20) for AHUs with actuator in a single Unit of Valve provided with spring return function. The valve shall be suitable for standalone operation. Valve shall be of PN16 Rating. The BMS compatible actuator shall be supplied by the valve manufacturer and capable of accepting 2-10VDC / 4- 20 mA electric signal and shall provide similar transduced feedback output signal to control system. The minimum close off Pressure of actuator must be 1.5 times shut off head of pump as per specifications. Rate shall be inclusive of stepdown transformer, digital thermostat (modulation type) suitable for the given actuator, required length of 2Cx1.5Sqmm shielded communication cable, end flanges/matching flanges, additional supports, fixing accessories, dismantling the existing valves, thermal insulation, etc
COOLING THERMOSTAT :
Supply, installation, testing and commissioning of COOLING THERMOSTAT with Power / Control Cabling for various air handling units and fan coil units as described in specifications. The thermostat shall be proportionately type for modulating control valve with digital temperature indicator. Receiving at site the imported equipment, unloading, storing, handling hoisting, installing in position, effecting connections, anchoring, grouting testing and commissioning the equipment including supplying & installing all necessary indigenous accessories as required to complete the installation.
Proportional cooling thermostat at AHU.
Supply and erection of SS Glycerine filled Pressure gauges complete with ball valve, mounting well, fittings and copper tubing extension where required
Supply and erection of SS Glycerine filled Thermometers with copper separable well complete with guard mounted on water lines, etc.
Supply and erection of 25 NB Automatic Air Vents along with ball valve
AIR DISTRIBUTION SYSTEM
Note: The colour shade for the air distribution equipments like ducts, diffusers, grilles, etc shall be approved by the Client / Architects before procurement and execution. The powder coating shall be 50 to 40 microns
The air distribution system comprises with all supports like anchor fasteners and tie-rods, cradles, angle iron supports, bolts and nuts, 4mm thick self-adhesive neoprene rubber gasket, stiffeners, zinc chromate painted angle iron flanges, chipping and plastering of openings made for duct supports etc., filling the gap with fibre glass wool and with fire sealant complete as per specification. The rates quoted shall include turning vanes, straightening vanes, splitters, inspection doors probe, provisions for BAS sensors, inlets with test openings enclosures complete with locking caps, chain, gaskets, insulating plugs, and extension for insulated ductwork etc.
Supply, installation, testing and balancing of Air Distribution System consists of factory fabricated Rectangular duct Galvanized Iron sheet metal ducting (Zinc coating 120GSM) with TDF/TDC flanges
1.0mm thick GSS ducting (20G) – factory fabricated
0.8mm thick GSS ducting (22G) – factory fabricated
Supply, fabrication, erection, testing and commissioning of factory fabricated powder coated GI flat Oval ducts. The price shall include associated coupling, bends, transformation pieces, collars, turning vanes( if any), ' GRIPPLE' supports/hanging system. All the duct joints shall be sealed with silicon sealant. The joints shall be with least leak. No additional payment will be made for insulating couplings,joints etc., The quoted rate shall be inclusive of loading, transportation, unloding, shifting & conduciting the pressure test as per the techical spcification & drawing details.
0.8mm thick GSS ducting (22G) – factory fabricated
Supply and fixing of Acoustic lining of wall and ceiling of AHU rooms with 50mm thick density 32Kg/Cu.m resin bonded glass fibber insulation friction fixed in 610mm X 610mm frame work made of 25X50mm made out of 0.6mm thick G.I Sheet U shaped channel and covered with reinforced fibre glass tissue and finished with .80mm perforated aluminium sheet etc. Complete as per Specifications.
Supply and fixing of Acoustic insulation - Material shall be FM approved, open cell Nitrile Rubber foam. The density of the same shall be within 140-180 Kg/m3. The maximum surface temperature the material should withstand is 105º C and minimum temperature should be -20ºC. The material should conform to Class 1 rating for surface spread of Flame as per BS 476 Part 7. The Thickness of the insulation material shall be as follows
10 mm thick
Supply and installing of Thermal insulation, Material shall be processed FM approved Crosslinked polyolefin foam with factory applied reinforced aluminium foil. The material should be fibre free. The Thickness of the material shall be as follows.
13mm thick
SUPPLY AIR GRILLES :
Supply, installation, testing and balancing of powder coated Extruded Aluminium supply air Grilles/diffusers with volume control dampers in accordance with the approved shop drawings and specifications. Collar are to be fixed properly to the Grilles without any gap for leakages with adjustable double louvers powder coated extruded aluminium.
Return Air Grilles
Supply and installation of Powder coated extruded aluminium continuous linear grilles/diffusers without volume control damper for exhaust /Return air Grille.
VOLUME CONTROL DAMPER :
Supplying & fixing of opposed blade volume control dampers in supply air duct collars as per approved drawings and specifications. Damper shall be with 18G GSS body and blades shall be with aluminium airfoil construction.
LOUVERS :
Supply, installation, testing and balancing of weather proof louvers with bird screen for fresh air / exhaust air as per specifications and approved drawings.
Powder coated/Anodized extruded aluminium construction.
Design, Supply, installation, testing and commissioning of motorized Fire damper in supply air/return air/exhaust air streams. The damper shall be made out of 16G thick galvanized sheet steel frame and blades of 16G galvanized steel with air tight arrangement. The damper shall be provided with control panel, BMS compatible actuator of the motorized Damper shall have required torque to ON / OFF the actuator with 220 V / 24 V transformer duly encased and wired, combined smoke and heat sensor and transmitters, control / communication cables, etc. The control panel shall be suitable for receive/send signal from the Fire Alarm System and status shall be monitored thru BMS.
Smoke & Fire Dampers.
BMS compatible Actuators with Control Panel & Wiring
HVAC - ELECTRICAL WORKS
Supply and laying of following size XLPE / PVC (FRLS) insulated armoured cables with aluminium / copper conductors partly laid in existing cable tray and partly laid in wall/ ceiling with suitbale clamps for working voltages up to and including 1100V conforming to IS 1554 part I 1988 for PVC and IS 7098 Part I for XLPE. Rate shall inclusive of single compression / double compression (weather proof glands-Only for outdoor termination) with suitable size PVC boot and suitable crimping socket, gland earthing by using copper flexible and all other necessary accessories. (copper sockets for copper cables and aluminium sockets for aluminium cables)
3 Core 10 Sq.mm XLPE Copper conductor armoured Cable
4 Core 10 Sq.mm PVC Copper conductor armoured Cable
6 Core 1.5 Sq.mm PVC Copper conductor armoured Cable
3.5 core 35 sq.mm XLPE alu.conductor armoured cable
Supply and Installation of the following Cable Trays / Accessories Prefabricated hot dip galvanized 1.6mm thick sheet perforated / Ladder type cable tray including all necessary curved bends-tees-reducers, coupler plates, fasteners etc.,for the following sizes. Inclusive necessary fixing arrangement etc.
200 mm x 100mm Perforated type cable tray along with top cover
150 mm x 50mm Perforated type cable tray along with top cover
Supplying and fixing following ways surface/ recess mounting, vertical type, 415 volts, 4 way TPN MCCB distribution board of sheet steel, dust protected, duly powder painted, inclusive of 200 amps tinned copper bus bar, common neutral link, earth bar, din bar for mounting MCB's, with provision of TP/4P 16 KA MCCB as incomer, interconnection between incomer MCCB and bus bars as required . (Note : Vertical type MCCB TPDB is normally used where 3 phase outlets are required.)
Incomer: 100 amps, 16 kA 4 pole MCCB- 1 No.
Outgoings: 32 amps, 10 kA TP MCB, C Curve-3 Nos. & 6- 10 amps SP MCB- 3 Nos.
EARTHING
Supply and laying of 6 sq.mm single core copper FRLS unarmoured cables for equipments earthing including termination with copper lugs in both ends
Vertical Inline pumps
Supply, Installation, Testing & commissioning of Single stage centrifugal coupled type pump set with axial suction port and radial discharge port, bronze impeller, mechanical seal, three phase TEFC squirrel cage motor with IP 55 protection, Class F insulation having a speed of 1450 rpm for chilled water circulation having the following duty conditions as per specifications along with vibration Isolators/rubber bellows /MS supports arrangements. Motor shall be suitable for VFD operation. (Vertical Inline pump with suction guide and other accessories). The pump shall be supplied with VFD drive with control panel as required. The accepted make shall be Amstrong/Xylem/Grunfos.
Variable vertical inline Pump with Head of 15m and flow rate of 100 Cu. Per hour.
Supply and installation of following sizes/ratings of industrial range air curtains of high velocity with low noise aluminium impeller of forward curved SS blades,pre lubricated sealed ball bearing type,easily mountable, vibration free complete set to operate 230V,50 Hz power supply. The accepted make will be ALMONARD/AIRCON.
285(W) x 285(H) x 1525(L) with effective air throw upto 2.5 mts.
360(W) x 365(H) x 2000(L) with effective air throw upto 3.5 mts.
THIRUMALAYA ENTERPRISES
GEMINI COOLING SYSTEMS PROJECTS PRIVATE LIMITED
stage.html
html • 0.05 MB
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .