Loading…
Loading…
Tender ID
Eligibility, documents, scope and key termsEligibility, required documents, scope of work and key terms of this tender, in one click.
| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | L1₹1 LAccepted-Finance | L1 | Accepted-Finance lowest | |
| 2 | L2₹1.0 L+₹1,000 (1.00%)Rejected-Finance BHAGWATI NAGAR JAMMU | L2 | Rejected-Finance not lowest | |
| 3 | L3₹1.0 L+₹1,500 (1.50%)Rejected-Finance BYE PASS N H NEAR STATE BANK OF INDIA SIDHRA JAMMU | L3 | Rejected-Finance not lowest |
| Sl No | Description | Qty | Unit | GS ENGG WORKS L3 | M/S RAGHUNATH MECHANICAL AND ELECTRICAL ENGINEERING WORKS L1 | PERFECT ELECTRICAL WORKS L2 |
|---|---|---|---|---|---|---|
| 1.00Repairs to 5 cusec x 15mtr head Horizontal split casing pumping unit-III along with allied mechanical works at LIS Dulmachak-I. | ||||||
| 1.01 | Decoupling of 5 cusec x 15 meter head discharge pump unit no III from 50 hp motor and then dismantling the pump from the base frame. Carriage & shifting of dismantled pump on head load to roadside using manual labour and then to workshop by carriage vehicle.
Repair to 5 cusec x 15 meter head discharge split casing pump of pumping unit no III of Lift irrigation station, Dulmachak–I at workshop by dismantling and extraction of all worn out/damaged parts i.e. pump shaft, impeller, bearings, sleeves, bush, check nuts, nuts & bolts, gland plate, gland studs. Properly cleaning the internal surface of pump casing. Repairing of pump shaft by balancing ,brazing and turning to bearing size and threading at position of check nuts. Repairs to impeller by filling cavities, cracks and finishing to original size. Providing and fitting 2 no’s of new bearing on driving and non-driving end of the pump, 1 no’s check nuts, nuts & bolts, fabrication of 2 no’s new gland plate with providing and fitting of 2 no’s new gland studs on ends of pump. Repair to bearing housing on driving and non-driving end of pumping unit by providing and fitting of bush, turning and fitting of bush to make inner diameter of bearing housing suitable for fitment of bearing. Reassembling all parts of pump with proper greasing of bearings and providing and fitting of gasket sheet between upper and lower part of the pump. Providing and fitting of graphite packing of suitable size on both ends of pump. Job also includes providing of 2 kg Graphite packing spare at site for routine use.
Shifting of repaired pumping unit on site and fitting of pumping unit on base frame. Alignment of the pumping unit.
Repair to 200 mm dia sluice valve of unit no. III, installed at Lift irrigation station Dulmachak - I, by way of cutting of nuts and bolts around the sluice valve with gas cutter. Completely dismantling all the internal parts of valve. Fabrication/Replacement of new stem rod with square threads. Providing and replacement of new wedge nut, repair to wedge shape disc with seat ring. Providing and replacement of new gland packing, gland plate with gland nuts. Properly checking inner body of sluice valve for any cavitations voids or corrosion repairing of the same. Complete assembling of valve with providing of graphite packing. Providing and fitting of rubber sheet between the flanges on both side of valve with providing of new nuts and bolts.
Repairs to 50 HP starter of pumping unit no- III by way of extracting the damaged worn out parts. Repair to Tripping system by brazing and finishing required size, Providing and fitting of no voltage coil, overload relay, moving and fixed contact point. Replacement of worn out thimbles nuts-bolts and internal leads duly soldered properly. Providing and filling of starter with 8 litres of fresh transformer oil.
Repair to 200 mm dia Non return valve by way of dismantling reflux valve from delivery side of unit no. III. The job involves extraction of broken flap of reflux valve. Providing and fitting of new flap with locking sheet. Replacement of hinge and hinge pin of the valve. Fitting of the valve on the delivery line with providing and fitting of new nuts and bolts along with rubber sheet.
The job also includes Electrification of pump room building by using standard quality materials as per site requirement for lightening and power circuits by supply and fixing of surface PVC conduit of 20 mm size for wiring of approximately 70 m length for various light and power points, P/f of 4 no. Led light points/lights (15 watts) along with switches inside pump room. The job also includes p/f of 16 amp power socket and 6 ampere charging sockets. The scope also includes p/f of 1 no. ceiling fan. Job includes fitting of 2 no. flood light of 50 watts of reputed make outside pump room for illumination of approach path and LIS area. P/F of 32 ampere main switch/MCCB for lightening and power circuit.
The complete job includes the cost of material, loading, un-loading, manual labour, carriage charges of vehicle (to &fro), tools & tackles, installation& testing charges at site etc. Complete Job.
Note: The tenderers are requested to visit the site and quote the rate as per site conditions. Any modifications/alterations of the job felt necessary if required at the time of actual execution may be done as per actual site conditions. | 1 | Job | 1,01,500 ₹1,01,500 | 1,00,000 ₹1,00,000 Lowest | 1,01,000 ₹1,01,000 |
| 1.02 | Rebate on Old Parts | 1 | Job | -2,030 ₹-2,030 | -2,000 ₹-2,000 | -2,020 ₹-2,020 |
Tender Value
₹1.0 L
EMD Value
₹2,040
Closing Date
6 Dec 2025, 12:00 pmClosed
Eligibility, documents, scope and key termsEligibility, required documents, scope of work and key terms of this tender, in one click.
XEN MID JAMMU
MID JAMMU
MID/J/129
2025_IFC_296714_1
MID/J/e-NIT/2025-26/129
Open Tender
Repair and Maintenance Works
Item Wise
7 days
Dulmachak
as per tender notice
8 documents required · 8 mandatory
₹200
Executive Engineer MID JAMMU
₹2,040
10 Dec 2025
28 Nov 2025
6 Dec 2025
28 Nov 2025
6 Dec 2025
28 Nov 2025
Repairs to 5 cusec x 15mtr head Horizontal split casing pumping unit-III along with allied mechanical works at LIS Dulmachak-I.
Decoupling of 5 cusec x 15 meter head discharge pump unit no III from 50 hp motor and then dismantling the pump from the base frame. Carriage & shifting of dismantled pump on head load to roadside using manual labour and then to workshop by carriage vehicle. Repair to 5 cusec x 15 meter head discharge split casing pump of pumping unit no III of Lift irrigation station, Dulmachak–I at workshop by dismantling and extraction of all worn out/damaged parts i.e. pump shaft, impeller, bearings, sleeves, bush, check nuts, nuts & bolts, gland plate, gland studs. Properly cleaning the internal surface of pump casing. Repairing of pump shaft by balancing ,brazing and turning to bearing size and threading at position of check nuts. Repairs to impeller by filling cavities, cracks and finishing to original size. Providing and fitting 2 no’s of new bearing on driving and non-driving end of the pump, 1 no’s check nuts, nuts & bolts, fabrication of 2 no’s new gland plate with providing and fitting of 2 no’s new gland studs on ends of pump. Repair to bearing housing on driving and non-driving end of pumping unit by providing and fitting of bush, turning and fitting of bush to make inner diameter of bearing housing suitable for fitment of bearing. Reassembling all parts of pump with proper greasing of bearings and providing and fitting of gasket sheet between upper and lower part of the pump. Providing and fitting of graphite packing of suitable size on both ends of pump. Job also includes providing of 2 kg Graphite packing spare at site for routine use. Shifting of repaired pumping unit on site and fitting of pumping unit on base frame. Alignment of the pumping unit. Repair to 200 mm dia sluice valve of unit no. III, installed at Lift irrigation station Dulmachak - I, by way of cutting of nuts and bolts around the sluice valve with gas cutter. Completely dismantling all the internal parts of valve. Fabrication/Replacement of new stem rod with square threads. Providing and replacement of new wedge nut, repair to wedge shape disc with seat ring. Providing and replacement of new gland packing, gland plate with gland nuts. Properly checking inner body of sluice valve for any cavitations voids or corrosion repairing of the same. Complete assembling of valve with providing of graphite packing. Providing and fitting of rubber sheet between the flanges on both side of valve with providing of new nuts and bolts. Repairs to 50 HP starter of pumping unit no- III by way of extracting the damaged worn out parts. Repair to Tripping system by brazing and finishing required size, Providing and fitting of no voltage coil, overload relay, moving and fixed contact point. Replacement of worn out thimbles nuts-bolts and internal leads duly soldered properly. Providing and filling of starter with 8 litres of fresh transformer oil. Repair to 200 mm dia Non return valve by way of dismantling reflux valve from delivery side of unit no. III. The job involves extraction of broken flap of reflux valve. Providing and fitting of new flap with locking sheet. Replacement of hinge and hinge pin of the valve. Fitting of the valve on the delivery line with providing and fitting of new nuts and bolts along with rubber sheet. The job also includes Electrification of pump room building by using standard quality materials as per site requirement for lightening and power circuits by supply and fixing of surface PVC conduit of 20 mm size for wiring of approximately 70 m length for various light and power points, P/f of 4 no. Led light points/lights (15 watts) along with switches inside pump room. The job also includes p/f of 16 amp power socket and 6 ampere charging sockets. The scope also includes p/f of 1 no. ceiling fan. Job includes fitting of 2 no. flood light of 50 watts of reputed make outside pump room for illumination of approach path and LIS area. P/F of 32 ampere main switch/MCCB for lightening and power circuit. The complete job includes the cost of material, loading, un-loading, manual labour, carriage charges of vehicle (to &fro), tools & tackles, installation& testing charges at site etc. Complete Job. Note: The tenderers are requested to visit the site and quote the rate as per site conditions. Any modifications/alterations of the job felt necessary if required at the time of actual execution may be done as per actual site conditions.
Rebate on Old Parts
PERFECT ELECTRICAL WORKS (BID ID -2661497)
GS ENGG WORKS (BID ID -2661368)
GS ENGG WORKS
stage.html
html • 0.04 MB
tech_eval.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Tendernotice_1.pdf
PDF • 0.42 MB
BOQ_961441.xls
BOQ • 0.28 MB
SBD129.pdf
Additional Documents • 0.63 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .