| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | L-1₹19.1 LAccepted-AOC SHIVAJI NAGAR GALI NO 1 DHANGU ROAD MODEL TOWN PATHANKOT 145001 PB | PATHANKOT | PATHANKOT | PUNJAB | 145001 | L-1 | Accepted-AOC Lowest Bidder | |
| 2 | L-2₹21.1 L+₹1.4 L (7.36%)Rejected-AOC H NO 309 REHARI COLONY JAMMU DISTT JAMMU J K 180005 | JAMMU | JAMMU AND KASHMIR | 180005 | L-2 | Rejected-AOC Other than lowest bidder | |
| 3 | L-3₹21.2 L+₹1.6 L (7.98%)Rejected-AOC | L-3 | Rejected-AOC Other than lowest bidder | |
| 4 | L-4₹21.6 L+₹2.0 L (10.1%)Rejected-AOC | L-4 | Rejected-AOC Other than lowest bidder | |
| 5 | L-5₹22.6 L+₹2.9 L (14.9%)Rejected-AOC | L-5 | Rejected-AOC Other than lowest bidder |
Tender Value
Refer Docs
EMD Value
₹59,000
Closing Date
5 Oct 2021, 6:00 pmClosed
Lt Col Ram G
GE Kaluchak Pin-900673 C/O 56 APO
SPECIAL REPAIRS TO LIGHTEING CONDUCTOR EARTH PITS AND PROVISION OF INVERTER TUBELIGHTS AND CEILING FANS AT RATNUCHAK MIL STN UNDER GE KALUCHAK
2021_MES_473695_1
GE/KC/NIT-33/2021-22
Open Tender
Electrical and Maintenance Works
Item Rate
180 days
Kaluchak
Please refer Tender documents.
9 documents required · 9 mandatory
₹500
GE Kaluchak
₹59,000
Yes
26 Nov 2021
8 Sept 2021
14 Oct 2021
8 Sept 2021
5 Oct 2021
22 Sept 2021
8 Sept 2021 - 17 Sept 2021
Amount
Air termination single pointed copper rod 12mm dia and 300mm long including necessary fixing arrangements using MS clamps, nuts, bolts etc, complete all as specified & directed.
Earthing complete with copper earth plate of 600x600mm 3mm thick electrode buried directly in ground (preferably in vertical position) earth pit not less than 2.25 metre below normal ground level with top edge of the earth plate not less 1.5 metre (BGL), connected to copper earthing strip of 32mm x 6mm upto 7.5m connected with by means of tinted copper bolt, nuts, check nuts and washers besides braising at all joints all as directed and connected to earth test point with and including necessary earth work in any type of soil, returning filling in, removal of surplus soil etc, filling adequate qty of charcoal dust, common salt, PCC pit in RCC 1:2:4 type B-1, precast RCC cover with suitable handle, 20mm bore 'medium grade' galvanized iron water tubing fixed with funnel and wire mesh and 40 mm bore “light grade” galvanized iron protection pipe for copper earthing strip 32mm x 6mm upto 7.5m length,
complete all as shown in electrical plate No 3 of SSR 2009 Part-I, connected to test point, complete all as specified and testing on completion. Notes : (i) The excess requirement (if more than 7.5 Mtr) of copper strip as for connecting upto the test point will be measured and paid separately. (ii) The excess requirement (if more than 7.5 Mtr) of GI protection pipe will be measured and paid separately. (iii).Testing of earthing is to be carried out by using earth tester & test result shall be submited duly signed by contractor. (iv) Earth resistance value shall be less than 1.0 ohm.
Earth continuity conductor or main earthing lead fixed to wall on batten or recess or chases or buried in ground or drawn in conduit/pipe or fixed to poles or any other indicated situation for loop earthing etc as required of copper strip of 25 x 3mm to connect earthpit to electrical equipment room, complete all as specified & directed.
Galvanized iron water tubing, medium grade, 25mm bore for installation of air termination rod, complete all as specified and directed.
Test point terminal block made of gun metal or phosphorus bronze size 75x75x25mm, drilled and screwed including 3 Nos. 8mm dia 25mm long hex head screw, complete all as specified & directed.
PCC 1:2:4, nominal mix, type B-1, using 20mm graded crushed stone aggregate as in coping, bed plates and the like including weathering, slightly rounded or chamfered angles and throating including necessary form work, complete all as specified & directed.
Supply, hanging and testing of 1200mm sweep, 230 volts, AC ceiling fans, BEE rated energy efficient ceiling fan conforming to IS:374-2019, having 3 blades alongwith copper wound stator (capacitor start) with minimum air delivery 210 cubic metre per minute, power consumption not more than 50 watt, top speed minimum 370 RPM or higher, speed control by 5 step electronic regulator including fan regulator two module 100 watt ISI marked five step, capacitor, down rod, canopy, making connection with three core flexiable copper cable of 1.50 Sqmm upto ceiling rose, complete all as specified & directed.
M/S A K ENGINEERS & CO.
Warne Builders
LAIQ RAM VERMA
Pyramid constructions
M/S GRD ENGINEERS
vishesh engineers
Sarbat Construction Co
Azurite Engineering
Prakash Trading Corporation
M/S Sudagar Mal
stage.html
html • 0.07 MB
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.04 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .