Sl. No. DSR-2023 DESCRIPTION DSR Amount MR Amount
B 4.0 CONCRETE WORKS ₹ 3,077,639.00 ₹ 0.00
C 5.0 REINFORCED CEMENT CONCRETE WORKS ₹ 93,484,749.00 ₹ 0.00
E 8.0 MARBLE & GRANITE WORKS ₹ 2,678,403.00 ₹ 339,921.00
K 21.0 ALUMINIUM & STRUCTURAL GLAZING WORK ₹ 3,757,904.00 ₹ 5,214,830.00
L 22.0 WATER PROOFING WORKS ₹ 353,810.00 ₹ 0.00
Add: Impact of Multiplying factor on DSR 2023 ₹ 191,961,952.78
GRAND TOTAL ₹ 220,879,129.78
GRAND TOTAL ₹ 220,879,129.78
ADMIN CUM ACADEMIC BLOCK COLLEGE OF HORTICULTURE, MORENA
Name of Project: Development of Administrative-cum-Academic Block for the College of Horticulture at Morena (M.P.), under RLBCAU.
ESTIMATE CIVIL WORKS_ADMIN CUM ACADEMIC BUILDING
Sl. No. DSR-2023 DESCRIPTION UNIT Admin, Qty. RATE DSR Amount NDSR Amount
A 2.0 EARTH WORKS
Earth work in excavation by mechanical means (Hydraulic
excavator)/manual means over areas (exceeding 30 cm in depth, 1.5 m
1 2.6 in width as well as 10 sqm on plan) including getting out and disposal of
excavated earth lead upto 50 m and for all lift, as directed by Engineer-
Earth work in excavation by mechanical means (Hydraulic
excavator)/manual means over areas (exceeding 30 cm in depth, 1.5 m
3 2.7 in width as well as 10 sqm on plan) including getting out and disposal of ₹ 0.00
excavated earth lead upto 50 m and lift upto 1.5 m, as directed by
Engineer-incharge.
Extra for every additional lift of 1.5 m or part thereof in excavation /
banking excavated or stacked materials.
ii 2.26.2 Ordinary or hard rock Cum 2739.15 ₹ 227.40 ₹ 622,883.00
Excavating trenches by mechanical / manual means of required width
for pipes, cables, etc including excavation for sockets, and dressing of
sides, ramming of bottoms, for all depth, including getting out the
excavated soil, and then returning the soil as required, in layers not
exceeding 20 cm in depth, including consolidating each deposited layer
by ramming, watering, etc. and disposing of surplus excavated soil as
directed, within a lead of 50 m :
a) 2.10.1 All kinds of soil ₹ 0.00
Pipes, cables etc. exceeding 80 mm dia. But not exceeding 300 mm dia
Filling available excavated earth (excluding rock) in trenches, plinth,
sides of foundations etc. in layers not exceeding 20cm in depth,
consolidating each deposited layer by ramming and watering, lead up
to 50 m and lift upto 1.5 m.
Carriage of Earth by mechanical transport including loading, unloading
8 1.1.2 and Stacking including royalty & carriage up to 5 KM complete. Cum 312.86 ₹ 326.68 ₹ 102,205.00
Carriage of Excavated rock by mechanical transport including loading,
9 1.1.4 unloading and Stacking including royalty & carriage up to 5 KM Cum 2739.15 ₹ 522.70 ₹ 1,431,754.00
Supplying and filling in plinth with sand under floors including, watering,
ramming consolidating and dressing complete.
Surface dressing of the ground including removing vegetation and
11 2.28.1 inequalities not exceeding 15 cm deep and disposal of rubbish, lead up Sqm 2904.93 ₹ 34.15 ₹ 99,203.00
to 50 m and lift up to 1.5 m. All kinds of soil.
Digitally signed by VARUN
ADMIN CUM ACADEMIC BLOCK COLLEGE OF HORTICULTURE, MORENA
Sl. No. DSR-2023 DESCRIPTION UNIT Admin, Qty. RATE DSR Amount NDSR Amount
Supplying chemical emulsion in sealed containers including delivery as
i 2.34.1 Chlorpyriphos/ Lindane emulsifiable concentrate of 20% litre 309.41 ₹ 234.75 ₹ 72,634.00
Anti termite treatment ₹ 0.00
Diluting and injecting chemical emulsion for POST-CONSTRUCTIONAL
14 2.35 anti-termite treatment (excluding the cost of chemical emulsion) : ₹ 0.00
Treatment of soil under existing floors using chemical emulsion @ one
litre per hole, 300 mm apart including drilling 12 mm diameter holes
and plugging with cement mortar 1 :2 (1 cement : 2 Coarse sand) to
match the existing floor :
i 2.35.3.1 With Chlorpyriphos/Lindane E.C. 20% with 1% concentration. Sqm 2320.57 ₹ 310.05 ₹ 719,494.00
TOTAL (Carried Over to Summary of Civil Works) ₹ 6,563,657.00 ₹ 0.00
B 4.0 CONCRETE WORKS
Providing and laying in position cement concrete of specified grade
1 4.1 excluding the cost of centering and shuttering - All work up to plinth
1:3:6 (1 Cement : 3 coarse sand (zone-III) derived from natural sources :
i 4.1.5 6 graded stone aggregate 20 mm nominal size derived from natural Cum 4.60 ₹ 7,294.70 ₹ 33,545.00
1:4:8 (1 Cement : 4 coarse sand (zone-III) derived from natural sources :
ii 4.1.8 8 graded stone aggregate 40 mm nominal size derived from natural Cum 369.18 ₹ 6,812.00 ₹ 2,514,836.00
Centering and shuttering including strutting, propping etc. and removal
of form work for :
i 4.3.1 Foundations, footings, bases for columns Cum 426.35 ₹ 392.15 ₹ 167,195.00
Providing and laying damp-proof course 50mm thick with cement
concrete 1:2:4 (1 cement : 2 coarse sand (zone-III) derived from natural
sources : 4 graded stone aggregate 20mm nominal size derived from
natural sources).
Extra for providing and mixing water proofing material in cement
4 4.12 concrete work in doses by weight of cement as per manufacturer's per 50 kg cement 29.69 ₹ 18.15 ₹ 539.00
Providing & applying a coat of residual petroleum bitumen of grade of
VG-10 of approved quality using 1.7kg per square metre on damp proof
course after cleaning the surface with brushes and finally with apiece of
cloth lightly soaked in kerosene oil.
Digitally signed by VARUN
ADMIN CUM ACADEMIC BLOCK COLLEGE OF HORTICULTURE, MORENA
Sl. No. DSR-2023 DESCRIPTION UNIT Admin, Qty. RATE DSR Amount NDSR Amount
Making plinth protection 50mm thick of cement concrete 1:3:6 (1
cement : 3 coarse sand (zone-III) derived from natural sources : 6
graded stone aggregate 20 mm nominal size derived from natural
6 4.17 sources) over 75mm thick bed of dry brick ballast 40 mm nominal size, Sqm 383.13 ₹ 749.30 ₹ 287,079.00
well rammed and consolidated and grouted with fine sand, including
necessary excavation, levelling & dressing & finishing the top smooth.
TOTAL (Carried Over to Summary of Civil Works) ₹ 3,077,639.00 ₹ 0.00
C 5.0 REINFORCED CEMENT CONCRETE WORK
Centering and shuttering including strutting, propping etc. and removal
a 5.9.1 Foundations, footings, bases of columns, etc. for mass concrete Sqm 769.08 ₹ 392.15 ₹ 301,595.00
Walls (any thickness) including attached pilasters, butteresses, plinth
and string courses etc.
c 5.9.3 Suspended floors, roofs, landings, balconies and access platform. Sqm 8157.41 ₹ 927.25 ₹ 7,563,959.00
d 5.9.4 Shelves (Cast in situ) Sqm 65.13 ₹ 927.25 ₹ 60,390.00
e 5.9.5 Lintels, beams, plinth beams, girders, bressumers and cantilevers Sqm 6882.72 ₹ 736.40 ₹ 5,068,437.00
f 5.9.6 Columns, Pillars, Piers, Abutments, Posts and Struts. Sqm 4963.95 ₹ 961.30 ₹ 4,771,845.00
g 5.9.7 Stairs, (excluding landings) except spiral-staircases. Sqm 432.44 ₹ 764.95 ₹ 330,793.00
Small lintels not exceeding 1.5m clear span, moulding as in cornices,
i 5.9.15 window sills, string courses, bands, copings, bed plates, anchor blocks Sqm 110.82 ₹ 392.15 ₹ 43,459.00
j 5.9.16 Edges of slabs and breaks in floors and walls ₹ 0.00
k 5.9.19 Weather shade, Chajjas, corbels etc., including edges. Sqm 50.00 ₹ 951.10 ₹ 47,555.00
Extra for additional height in centering, shuttering where ever required
with adequate bracing, propping etc., including cost of de-shuttering
2 5.11 and decentering at all levels, over a height of 3.5 m, for every additional ₹ 0.00
height of 1 metre or part thereof (Plan area to be measured).
Suspended floors, roofs, landing, beams and balconies (Plan area to be
Steel reinforcement for R.C.C. work including straightening, cutting,
3 5.22 bending, placing in position and binding all complete upto plinth level. ₹ 0.00
i 5.22.6 Thermo-Mechanically Treated bars of grade Fe-500D or more. kg 96250.72 ₹ 107.85 ₹ 10,380,640.00
Steel reinforcement for R.C.C. work including straightening, cutting,
4 5.22A bending, placing in position and binding all complete above plinth level. ₹ 0.00
i 5.22A.6 Thermo-Mechanically Treated bars of grade Fe-500D or more. kg 277025.10 ₹ 107.85 ₹ 29,877,157.00
Digitally signed by VARUN
ADMIN CUM ACADEMIC BLOCK COLLEGE OF HORTICULTURE, MORENA
Sl. No. DSR-2023 DESCRIPTION UNIT Admin, Qty. RATE DSR Amount NDSR Amount
Providing and laying in position ready mixed or site batched design mix
cement concrete for reinforced cement concrete work; using coarse
aggregate and fine aggregate derived from natural sources, Portland
Pozzolana / Ordinary Portland /Portland Slag cement, admixtures in
recommended proportions as per IS: 9103 to accelerate / retard setting
of concrete, to improve durability and workability without impairing
strength; including pumping of concrete to site of laying, curing,
carriage for all leads; but excluding the cost of centering, shuttering,
finishing and reinforcement as per direction of the engineer-in-charge;
for the following grades of concrete. Note: Extra cement up to 10% of
the minimum specified cement content in design mix shall be payable
separately. In case the cement content in design mix is more than 110%
of the specified minimum cement content, the contractor shall have
discretion to either re-design the mix or bear the cost of extra cement.
a) 5.33.1 All works upto plinth level ₹ 0.00
Concrete of M25 grade with minimum cement content of 330 kg /cum
Concrete of M30 grade with minimum cement content of 350 kg /cum
b) 5.33.2 All works above plinth level upto floor V level ₹ 0.00
Concrete of M25 grade with minimum cement content of 330 kg /cum
Concrete of M30 grade with minimum cement content of 350 kg /cum
Add for using extra cement in the items of design mix over and above
the specified cement content therein.
Extra for R.C.C./ B.M.C/ R.M.C. work above floor V level for each four
floors or part thereof.
Providing and fixing of expansion joint system related with floor
location as per drawings and direction of Engineer-In-Charge. The joints
system will be of extruded aluminum base members, self aligning / self
centering arrangement and support plates etc. as per ASTM B221-02.
The system shall be such that it provides floor to floor /floor to wall
expansion control system for various vertical localtion in load
application areas that accommodates multi directional seismic
movement without stress to it's components. System shall consist of
metal profiles with a universal aluminum base member designed to
accommodate various project conditions and finish floor treatments.
The cover plate shall be designed of width and
Digitally signed by VARUN
ADMIN CUM ACADEMIC BLOCK COLLEGE OF HORTICULTURE, MORENA
Sl. No. DSR-2023 DESCRIPTION UNIT Admin, Qty. RATE DSR Amount NDSR Amount
thickness required to satisfy projects movement and loading
requirements and secured to base members by utilizing manufacturer’s
pre-engineered self-centering arrangement that freely rotates / moves
in all directions. The Self – centering arrangement shall exhibit circular
sphere ends that lock and slide inside the corresponding aluminum
extrusion cavity to allow freedom of movement and flexure in all ₹ 0.00
directions including vertical displacement. Provision of Moisture Barrier
Membrane in the Joint System to have watertight joint is mandatory
requirement all as per the manufactures design and as approved by
Engineer -in- Charge . (Material shall confirm to ASTM 6063.)
Providing and fixing of expansion joint system related with wall joint
(internal/external) location as per drawings and direction of Engineer-In-
Charge. The joints shall be of extruded aluminum base members, self
aligning / centering arrangement and support plates as per ASTM B221-
02. The material shall be such that it provides an Expansion Joints
System suitable for vertical wall to wall/ wall to corner application, both
9 5.45 new and existing construction in office Buildings & complexes with no ₹ 0.00
slipping down tendency amongst the components of the Joint System.
The Joint System shall utilize light weight aluminum profiles exhibiting
minimal exposed aluminum surfaces mechanically snap locking the
multicellular to facilitate movement. (Material shall confirm to ASTM
Providing and fixing of expansion joint system of approved make and
manufactures for various roof locations as per approved drawings and
direction of Engineer-In-Charge. The joints shall be of extruded
aluminum base members with, self aligning and self centering
arragement support plates asper ASTM B221-02. The system shall be
10 5.46 such that it provides watertight roof to roof/roof to corner joint cover ₹ 0.00
expansion control system that is capable of accommodating
multidirectional seismic movement without stress to its components.
System shall consist of metal profile that incorporates a universal
aluminum base member designed to accommodate various project
conditions and roof treatments.
Digitally signed by VARUN
ADMIN CUM ACADEMIC BLOCK COLLEGE OF HORTICULTURE, MORENA
Sl. No. DSR-2023 DESCRIPTION UNIT Admin, Qty. RATE DSR Amount NDSR Amount
The cover plate shall be designed of width and thickness required to
satisfy movement and loading requirements and secured to base
members by utilizing manufacturer’s pre-engineered self-centering
arrangement that freely rotates / moves in all directions. The Self
centering arrangement shall exhibit circular sphere ends that lock and
slide inside the corresponding aluminum extrusion cavity to allow
freedom of movement and flexure in all directions including vertical ₹ 0.00
displacement. The Joint System shall resists damage or deterioration
from the impact of falling ice, exposure to UV, airborne contaminants
and occasional foot traffic from maintenance personnel. Provision of
Moisture Barrier Membrane in the Joint System to have water tight
joint is mandatory requirement. Material shall confirm to ASTM 6063.
TOTAL (Carried Over to Summary of Civil Works) ₹ 93,484,749.00 ₹ 0.00
D 6.0 BRICK WORK ₹ 0.00
Brick work with common burnt clay F.P.S. (non modular) bricks of class
designation 7.5 in foundation and plinth in:
i 6.1.2 Cement mortar 1:6 (1 cement : 6 coarse sand) Cum 4.03 ₹ 7,132.25 ₹ 28,757.00
Providing and laying autoclaved aerated cement blocks masonry with
150mm/230mm/300 mm thick AAC blocks in super structure above
plinth level up to floor V level with RCC band at sill level and lintel level
2 6.47 with approved block laying polymer modified adhesive mortar all Cum 1468.43 ₹ 8,333.65 ₹ 12,237,374.00
complete as per direction of Engineer-in-Charge. (The payment of RCC
band and reinforcement shall be made for seperately).
Extra for brick work / AAC block masonry / Tile brick masonry in
3 6.5 superstructure above floor V level, for each four floors or part thereof Cum 40.01 ₹ 169.45 ₹ 6,779.00
by mechanical means.
Extra for half brick masonry in superstructure, above floor V level for
every four floors or part thereof by mechanical means.
Providing and laying autoclaved aerated cement blocks masonry with
100 mm thick AAC blocks in super structure above plinth level up to
5 6.38 floor V level in cement mortar 1:4 (1 cement : 4 coarse sand ). The rate Cum 400.45 ₹ 10,195.45 ₹ 4,082,806.00
includes providing and placing in position 2 Nos 6 mm dia M.S. bars at
every third course of masonry work.
TOTAL (Carried Over to Summary of Civil Works) ₹ 16,355,785.00 ₹ 0.00
E 8.0 MARBLE & GRANITE WORK
Digitally signed by VARUN
ADMIN CUM ACADEMIC BLOCK COLLEGE OF HORTICULTURE, MORENA
Sl. No. DSR-2023 DESCRIPTION UNIT Admin, Qty. RATE DSR Amount NDSR Amount
Providing and fixing 18 mm thick gang saw cut, mirror polished,
premoulded and prepolished, machine cut for kitchen platforms, vanity
counters, window sills, facias and similar locations of required size,
approved shade, colour and texture laid over 20 mm thick base cement
mortar 1:4 (1 cement : 4 coarse sand), joints treated with white cement,
mixed with matching pigment, epoxy touch ups, including rubbing,
curing, moulding and polishing to edges to give high gloss finish etc.
complete at all levels.
a) 8.2.2 Granite stone slab colour black, Cherry/Ruby red
Providing edge moulding to 18 mm thick marble stone counters,
Vanities etc., including machine polishing to edge to give high gloss
finish etc. complete as per design approved by Engineer-in-Charge.
Extra for providing opening of required size & shape for wash basins/
kitchen sink in kitchen platform, vanity counters and similar location in
3 8.5 marble/Granite/Stone work including necessary holes for pillar taps etc. Each 99.00 ₹ 978.70 ₹ 96,891.00
including rubbing and polishing of cut edge etc. complete.
Providing and fixing stone slab with table rubbed, edges rounded and
polished, of size 75x50 cm deep and 1.8 cm thick, fixed in urinal
partitions by cutting a chase of appropriate width with chase cutter and
4 8.10 embedding the stone in the chase with epoxy grout or with cement ₹ 0.00
concrete 1:2:4 (1 cement : 2 coarse sand : 4 graded stone aggregate 6
mm nominal size) as per direction of Engineer-in-charge and finished
i 8.10.2 Granite Stone of approved shade Sqm 15.30 ₹ 4,051.85 ₹ 61,993.00
Providing and fixing machine cut, mirror/ eggshell polished, Granite
stone work for wall lining (veneer work) including dado, skirting, risers
of steps etc., in required design and pattern wherever required, stones
of different finished surface texture, on 12mm (average) thick cement
mortar 1:3 (1 cement : 3 coarse sand) laid and jointed with white
5 cement slurry @ 3.3 kg/sqm including pointing with white cement slurry Sqm 40.50 ₹ 8,393.10 ₹ 339,921.00
admixed with pigment of matching shade, including rubbing, curing,
polishing etc. all complete as per Architectural drawings, and as
directed by the Engineer-in-Charge. Granite of colour black,
cherry/ruby red 18-20mm thick (slab area above 0.50 sqm)
Digitally signed by VARUN
ADMIN CUM ACADEMIC BLOCK COLLEGE OF HORTICULTURE, MORENA
Sl. No. DSR-2023 DESCRIPTION UNIT Admin, Qty. RATE DSR Amount NDSR Amount
Providing and fixing Ist quality ceramic glazed wall tiles conforming to
IS: 15622 (thickness to be specified by the manufacturer), of approved
make, in all colours, shades except burgundy, bottle green, black of any
size as approved by Engineer-in-Charge, in skirting, risers of steps and
dados, over 12 mm thick bed of cement mortar 1:3 (1 cement : 3 coarse
sand) and jointing with grey cement slurry @ 3.3kg per sqm, including
pointing in white cement mixed with pigment of matching shade
Designing, fabricating, testing, installing and fixing in position Curtain
Wall with Aluminium Composite Panel Cladding, with open grooves for
linear as well as curvilinear portions of the building , for all heights and
all levels etc. including: (a) Structural analysis & design and preparation
of shop drawings for pressure equalisation or rain screen principle as
required, proper drainage of water to make it watertight including
checking of all the structural and functional design. (b) Providing,
fabricating and supplying and fixing panels of aluminium composite
panel cladding in pan shape in metalic colour of approved shades made
out of 4mm thick aluminium composite panel material consisting of
3mm thick FR grade mineral core sandwiched between two Aluminium
sheets (each 0.5mm thick). The aluminium composite panel cladding
sheet shall be coil coated, with Kynar 500 based PVDF / Lumiflon based
fluoropolymer resin coating of approved colour and shade on face # 1
and polymer (Service) coating on face # 2 as specified using stainless
steel screws, nuts, bolts, washers, cleats, weather silicone sealant,
backer rods etc.
Digitally signed by VARUN
ADMIN CUM ACADEMIC BLOCK COLLEGE OF HORTICULTURE, MORENA
Sl. No. DSR-2023 DESCRIPTION UNIT Admin, Qty. RATE DSR Amount NDSR Amount
(c) The fastening brackets of Aluminium alloy 6005 T5 / MS with Hot Dip
Galvanised with serrations and serrated washers to arrest the wind load
movement, fasteners, SS 316 Pins and anchor bolts of approved make in
SS 316, Nylon separators to prevent bi-metallic contacts all complete
required to perform as per specification and drawing The item includes
cost of all material & labour component, the cost of all mock ups at site,
cost of all samples of the individual components for testing in an
approved laboratory, field tests on the assembled working curtain wall
with aluminium composite panel cladding, cleaning and protection of
the curtain wall with aluminium composite panel cladding till the
i i handing over of the building for occupation. The Contractor shall Sqm. 50.00 ₹ 5,015.05 ₹ 250,753.00
provide curtain wall with aluminium composite panel cladding,and
including base frame work for ACP having all the performance
characteristics all complete , as per the Architectural drawings, as per
item description, as specified, as per the approved shop drawings and
as directed by the Engineer-in-Charge. However, for the purpose of
payment, only the actual area on the external face of the curtain wall
with Aluminum Composite Panel Cladding (including width of groove)
shall be measured in sqm. up to two decimal places.
TOTAL (Carried Over to Summary of Civil Works) ₹ 2,678,403.00 ₹ 339,921.00
F 9.0 WOOD & PVC WORK ₹ 0.00
Providing wood work in frames of doors, windows, clerestory windows
and other frames, wrought framed and fixed in position with hold fast
lugs or with dash fasteners of required dia & length ( hold fast lugs or
dash fastener shall be paid for separately).
i 9.1.1 Second class teak wood Cum 3.15 ₹ 142,949.70 ₹ 450,347.00
Providing and fixing ISI marked flush door shutters conforming to IS :
2202 (Part I) non-decorative type, core of block board construction with
2 9.21 frame of 1st class hard wood and well matched commercial 3 ply ₹ 0.00
veneering with vertical grains or cross bands and face veneers on both
faces of shutters:
35 mm thick including ISI marked Stainless Steel butt hinges with
necessary screws
Extra for providing lipping with 2nd class teak wood battens 25 mm
3 9.23 minimum depth on all edges of flush door shutters (over all area of door Sqm 112.17 ₹ 462.35 ₹ 51,862.00
shutter to be measured).
Providing and fixing wooden moulded beading to door and window
4 9.40.1 frames with iron screws, plugs and priming coat on unexposed surface ₹ 0.00
etc. complete : 2nd class teak wood
Digitally signed by VARUN
ADMIN CUM ACADEMIC BLOCK COLLEGE OF HORTICULTURE, MORENA
Sl. No. DSR-2023 DESCRIPTION UNIT Admin, Qty. RATE DSR Amount NDSR Amount
Providing and fixing M.S. grills of required pattern in frames of windows
5 9.48 etc. with M.S. flats, square or round bars etc. including priming coat ₹ 0.00
with approved steel primer all complete.
i 9.48.2 Fixed to openings /wooden frames with rawl plugs screws etc. kg 6847.74 ₹ 238.35 ₹ 1,632,159.00
Providing and fixing curtain rods of 1.25 mm thick chromium plated
brass plate, with two chromium plated brass brackets fixed with C.P.
brass screws and wooden plugs, etc., wherever necessary complete :
Providing 40x5 mm flat iron hold fast 40 cm long including fixing to
frame with 10 mm diameter bolts, nuts and wooden plugs and
7 9.53 embedding in cement concrete block 30x10x15cm 1:3:6 mix (1 cement : Each 978.00 ₹ 228.85 ₹ 223,815.00
3 coarse sand : 6 graded stone aggregate 20mm nominal size).
Providing and fixing aluminium tower bolts ISI marked anodised (anodic
coating not less than grade AC 10 as per IS : 1868 ) transparent or dyed
to required colour or shade with necessary screws etc. complete :
Providing and fixing aluminium pull bolt lock, ISI marked, anodised
(anodic coating not less than grade AC 10 as per IS : 1868) transparent
or dyed to required colour and shade, with necessary screws bolts, nut
and washers etc. complete.
Providing and fixing aluminium handles of approved make anodized
(anodic coating not less than grade AC 10 as per IS : 1868) transparent
or dyed to required colour or shade with necessry screws etc. complete.
Providing & Fixing decorative high pressure laminated sheet of plain /
wood grain in gloss / matt / suede finish with high density protective
14 9.127 surface layer and reverse side of adhesive bonding quality conforming ₹ 0.00
to IS : 2046 Type S, including cost of adhesive of approved quality.
Providing and fixing factory made uPVC door frame made of uPVC
extruded sections having an overall dimension as below (tolerance
±1mm), with wall thickness 2.0 mm (± 0.2 mm), corners of the door
frame to be Jointed with galvanized brackets and stainless steel screws,
15 9.117 joints mitred and Plastic welded. The hinge side vertical of the frames ₹ 0.00
reinforced by galvanized M.S. tube of size 19 X 19 mm and 1mm (± 0.1
mm) wall thickness and 3 nos. stainless steel hinges fixed to the frame
complete as per manufacturer’s specification and direction of
Engineerin-charge
i 9.117.2 Extruded section profile size 42x50 mm Rmt 574.20 ₹ 331.35 ₹ 190,261.00
16 9.118 Providing and fixing to existing door frames. ₹ 0.00
Digitally signed by VARUN
ADMIN CUM ACADEMIC BLOCK COLLEGE OF HORTICULTURE, MORENA
Sl. No. DSR-2023 DESCRIPTION UNIT Admin, Qty. RATE DSR Amount NDSR Amount
30 mm thick factory made Polyvinyl Chloride (PVC) door shutter made
of styles and rails of a uPVC hollow section of size 60x30 mm and wall
thickness 2 mm (± 0.2 mm), with inbuilt decorative moulding edging on
one side. The styles and rails mitred and joint at the corners by means
of M.S. galvanised/ plastic brackets of size 75x220 mm having wall
thickness 1.0 mm and stainless steel screws. The styles of the shutter
reinforced by inserting galvanised M.S. tube of size 25x20 mm and 1
mm (± 0.1 mm) wall thickness. The lock rail made up of 'H' section, a
uPVC hollow section of size 100x30 mm and 2 mm (± 0.2 mm) wall
thickness fixed to the shutter styles by means of plastic/ galvanised M.S.
'U' cleats. The shutter frame filled with a uPVC multi-chambered single
panel of size not less than 620 mm, having over all thickness of 20 mm
and 1 mm (± 0.1 mm) wall thickness . The panels filled vertically and tie
bar at two places by inserting horizontally 6 mm galvanised M.S. rod
and fastened with nuts and washers, complete as per manufacturer's
specification and direction of Engineer-in-charge.
Providing and fixing partition upto ceiling height consisting of G.I. frame
and required board, including providing and fixing of frame work made
of special section power pressed/ roll form G.I. sheet with zinc coating
of 120 gms/sqm(both side inclusive), consisting of floor and ceiling
channel 50mm wide having equal flanges of 32 mm and 0.50 mm thick,
fixed to the floor and ceiling at the spacing of 610 mm centre to centre
with dash fastener of 12.5 mm dia meter 50 mm length or suitable
anchor fastener or metal screws with nylon plugs and the studs 48 mm
wide having one flange of 34 mm and other flange 36 mm and 0.50 mm
17 9.105 thick fixed vertically within flanges of floor and ceiling channel and ₹ 0.00
placed at a spacing of 610 mm centre to centre by 6 mm dia bolts and
nuts, including fixing of studs along both ends of partition fixed flush to
wall with suitable anchor fastener or metal screws with nylon plugs at
spacing of 450 mm centre to centre, and fixing of boards to both side of
frame work by 25 mm long dry wall screws on studs, floor and ceiling
channels at the spacing of 300 mm centre to centre. The boards are to
be fixed to the frame work with joints staggered to avoid through
M.S. fixing channel of 99 mm width (0.9 mm thick having two flanges of
9.5 mm each) to be provided at the horizontal joints of two boards,
fixed to the studs using metal to metal flat head screws, including
jointing and finishing to a flush finish with recommended jointing
compound, jointing tape, angle beads at corners (25 mm x 25 mm x 0.5
mm), joint finisher and two coats of primer suitable for board as per
manufacture’s specification and direction of engineer in charge all
Digitally signed by VARUN
ADMIN CUM ACADEMIC BLOCK COLLEGE OF HORTICULTURE, MORENA
Sl. No. DSR-2023 DESCRIPTION UNIT Admin, Qty. RATE DSR Amount NDSR Amount
75 mm overall thickness partition with 12.5 mm thick double skin fire
i 9.105.1 rated Glass Reinforced Gypsum (GRG) plaster board conforming to IS: Sqm 314.34 ₹ 2,131.10 ₹ 669,892.00
2095: part 3 (Board with BIS certification marks)
Providing and fixing factory made uPVC glazed/ wire mesh
windows/ doors comprising of lead free uPVC multichambered frame,
sash and mullion/ coupler (wherever required) extruded profiles having
minimum wall thickness of 1.70 mm for Series R1 and R2 profiles and
2.10 mm for Series R3 and R4 profiles conforming to EN: 12608 in any
shape, colour and design duly reinforced with galvanized mild steel
section made of required shape & size as per CPWD Specification, uPVC
extruded glazing beads, interlocks and Inline sash adaptor (whereever
required) of appropriate dimension, EPDM gasket, hardware, SS 304
grade fasteners of minimum 8 mm dia. with countersunk head,
comprising of matching polyamide PA6 grade sleeve for fixing frame to
18 9.147.a finished wall as per IS 1367 : Part 1 to 14, plastic packers, plastic caps ₹ 0.00
and necessary stainless steel screws etc. Profile of frame, sash &
mullion (if required) shall be mitred cut and fusion
welded/mechanically jointed duly sealed at all corners, including drilling
of holes for fixing hardware and drainage of water etc. After fixing
frame the gap between frame and adjacent finished wall shall be filled
with weather proof silicon sealant over backer rod of approved size and
quality, all complete as per approved drawing conforming to CPWD
specification & direction of Engineer-in-Charge. Section of steel
reinforcement and cross sections of uPVC profiles to be as per design
approved by Engineer-in-Charge.
Wire mesh/ Glazing of plain/ toughened/ laminated/ double glass unit
with/ without high performance coatings as per design requirements
and conforming to IS: 3548 & IS: 16231 shall be paid separately. Note:-
Structural design proof checked from a Government Engineering
Institute, to be provided by the manufacturer for : (iii) Sites with basic
wind speed > 45 m/sec as per IS 875 –Part 3 (iv) Sites with structure
height more than 20m for all wind speeds
Two and half track three panels sliding window with two glazed & one
a) 9.147.A3 wire mesh panels with Aluminium channel for roller track, wool pile, ₹ 0.00
nylon rollers with SS 304 body.
Using R3 series with frame (85mm & above) x (40mm & above) & glazed
sash (30mm & above) x (55mm & above) & fly screen sash (20mm &
i 9.147.A3.2 above) x (50mm & above) with zinc alloy (zamak) powder coated Sqm 33.25 ₹ 9,968.70 ₹ 331,464.00
handle on every glazed panel along with multi-point locking system.
(Height upto 1.8 meter).
Digitally signed by VARUN
ADMIN CUM ACADEMIC BLOCK COLLEGE OF HORTICULTURE, MORENA
Sl. No. DSR-2023 DESCRIPTION UNIT Admin, Qty. RATE DSR Amount NDSR Amount
Three track three panels sliding window with two glazed & one wire
b) 9.147.A4 mesh panels with Aluminium channel for roller track, wool pile, nylon ₹ 0.00
rollers with SS 304 body.
Using R4 series with frame (115mm & above) x (45mm & above) & both
glazed and fly screen sash (44mm & above) x (55mm & above) with zinc
alloy (zamak) powder coated touch locks with hook. (Height upto 1.8
c) 9.147.C1 Fixed window / ventilator without mullion / transom. ₹ 0.00
Using R1 series with frame (33mm & above ) x (35mm & above). (Height
upto 0.90 metre)
Providing and fixing factory made single extruded WPC (Wood Polymer
Composite) solid door/ window/ Ceosetory windows & other Frames/
Chowkhat comprising of virgin PVC polymer of K value 58-60
(Suspension Grade), calcium carbonate and natural fibers (wood
powder/ rice husk/ wheat husk) and non toxic additives (maximum
toxicity index of 12 for 100 gms) fabricated with miter joints after
applying PVC solvent cement and screwed with full body threaded star
headed SS screws having minimum frame density of 750 kg/cum, screw
withdrawal strength of 2200 N (Face) & 1100 N (Edge), minimum
compressive strength of 58 N/mm2, modulus of elasticity 900 N/mm2
and resistance to spread of flame of Class A category with property of
being termite/ borer proof, water/ moisture proof and fire retardant
and fixed in position with M.S hold fast/ lugs/ SS dash fasteners of
required dia and length complete as per direction of Engineer-In-
(M.S hold fast/ lugs or SS dash fasteners shall be paid for separately).
Note: For WPC solid door/ window frames, minus 5mm tolerance in
dimensions i.e depth and width of profile shall be acceptable.
Variationin profile dimensions on plus side shall be acceptable but no
extra payment on this account shall be made.
Digitally signed by VARUN
ADMIN CUM ACADEMIC BLOCK COLLEGE OF HORTICULTURE, MORENA
Sl. No. DSR-2023 DESCRIPTION UNIT Admin, Qty. RATE DSR Amount NDSR Amount
Providing and fixing factory made single extruded WPC (Wood Polymer
Composite) solid decorative type flush door shutter of required size
comprising of virgin polymer of K value 58-60 (Suspension Grade),
calcium carbonate and natural fibers (wood powder/ rice husk/wheat
husk) and non toxic additives (maximum toxicity index of 12 for 100
gms) having minimum density of 650 kg/cum and screw withdrawal
strength of 1800 N (Face) & 900 N (Edge), minimum compressive
strength 50 N/mm2, modulus of elasticity 850 N/mm2 and resistance to
20 26.88 spread of flame of Class A category with property of being ₹ 0.00
termite/borer proof, water/moisture proof and fire retardant. WPC to
be laminated with PVC foil of minimum 14 microns thick of approved
design pasted with hot melt adhesive on both faces of shutter and fixing
with stainless steel butt hinges of required size with necessary full body
threaded star headed counter sunk S.S screws, all as per direction of
Engineer-In- Charge. (Note: stainless steel butt hinges and necessary S.S
screws shall be paid separately)
Providing and fixing IS : 12817 marked stainless steel butt hinges with
stainless steel screws etc. complete :
SS Hardware ₹ 0.00
Providing and fixing bright /matt finished Stainless Steel handles of
22 9.165 approved quality & make with necessary screws etc all complete. ₹ 0.00
Providing and fixing Stainless Steel tower bolts of approved make with
necessary screws etc. complete :
Providing and fixing Stainless Steel hanging floor door stopper of
approved make with necessary screws etc. complete.
i i Single rubber stopper Each 275.00 ₹ 219.30 ₹ 60,308.00
Providing and fixing Concealed Door Closer With Track Arm (SS Finish),
Slide in SS Cover Stainless Steel door closer, door weight upto 80 kg and
25 MR-3 door width from 701 mm to 1000 mm), with double speed adjustment Each 275.00 ₹ 2,626.15 ₹ 722,191.00
with necessary accessories and screws etc. complete.
Providing and fixing of Mortise Lock with Handles Stainless Steel Finish
26 MR-4 (Solid Casted) with necessary screws etc. complete as per design & Each 158.00 ₹ 5,070.35 ₹ 801,115.00
approved by Engineer in Charge.
Providing and fixing stainless steel sliding door bolts, ISI marked
anodised (anodic coating not less than grade AC 10 as per IS : 1868),
transparent or dyed to required colour or shade, with nuts and screws
etc. complete : 300x16 mm
Digitally signed by VARUN
ADMIN CUM ACADEMIC BLOCK COLLEGE OF HORTICULTURE, MORENA
Sl. No. DSR-2023 DESCRIPTION UNIT Admin, Qty. RATE DSR Amount NDSR Amount
28 MR-6 Providing and fixing Stainless steel Al-drop Each 116.00 ₹ 363.80 ₹ 42,201.00
Providing and fixing fire resistant door frame of section 50 x 60 mm on
horizontal side & 35 x 60 mm on vertical sides having built in rebate
made out of 1.6 mm thick GI sheet ( Zinc coating not less than
120gm/m²) suitable for mounting 120 min Fire Rated Glazed Door
Shutters. The frame shall be filled with Mineral wool Insulation having
density min 96Kg/m³ . The frame will have a provision of G.I. Anchor
fastners 14 nos ( 5 each on vertical style & 4 on horizontal style of size
M10 x 80 ) suitable for fixing in the opening along with Factory made
Template for SS Ball Bearing Hinges of Size 100x89x3mm for fixing of
fire rated glazed shutter . The frame shall be finished with a approved
fire resistant primer or Powder coating of not less than 30 micron in
desired shade as per the directions of Engineer - in- charge . (Cost of SS
ball bearing hinges is excluded).
Providing and fixing 60 mm thick glazed fire resistant door shutters of
120 min Fire Rating confirming to IS:3614 (Part II) or EN1634-1:1999,
tested and certified as per laboratory approved by Engineer-in-charge,
with suitable mounting on door frame, consisting of vertical styles, top
rail & side rail 60 mm x 60 mm wide and bottom rail of 110 mm x 60mm
made out of 1.6mm thick G.I. sheet (zinc coating not less than
120gm/m²) duly filled mineral wool insulation having density min 96 kg/
m³ and fixing with necessary stainless steel ball bearing hinges of size
100x89x3mm of approved make, including applying a coat of approved
fire resistant primer or powder coating not less than 30 micron etc all
complete as per direction of Engineer-in-charge (panelling to be paid for
Digitally signed by VARUN
ADMIN CUM ACADEMIC BLOCK COLLEGE OF HORTICULTURE, MORENA
Sl. No. DSR-2023 DESCRIPTION UNIT Admin, Qty. RATE DSR Amount NDSR Amount
Providing and fixing glazing in fire resistant door shutters, fixed panels &
partitions etc., with G.I. beading made out of 1.6 mm thick G.I. sheet
(zinc coating not less than 120 gm/m²) of size 20 x 33 mm screwed with
M4 x 38 mm SS screws at distance 75 mm from the edges and 150 mm
c/c , including applying a coat of approved fire resistant primer/powder
coating of not less than 30 micron on G.I. beading, & special ceramic
tape of 5 x 20 mm size etc complete in all respect as per NBC 2016, IS
16231 (Part 3):2016 and as per direction of Engineer-in-charge with
glass of required thickness having 120 minutes of fire resistance both
31 9.164 integrity & radiation control (EW120) and minimum 20 minutes of Sqm 11.88 ₹ 43,677.65 ₹ 518,890.00
insulation (EI20). The manufacturer have to give test
report/certification of fire glass and the glass should have the stamp
showing the value of E, EW & EI. The glass shall be tested in approved
NABL accredited lab or by any other accreditation body which operates
in accordance with ISO/IEC 17011 and accredits labs as per ISO/IEC
17025 for testing and calibration scopes shall be eligible. The maximum
glazing size shall not be more than 1100x2200 mm (w x h) or 2.42 sqm.
Providing and fixing panic bar / latch (Double point) fitted with a single
body, Trim Latch & Lock on back side of the Panic Latch of reputed
brand and manufacture to be approved by the Engineer- in- charge, all
Providing and fixing certified restroom cubicle system of approved
make comprising of green guard certified solid compact laminated
water proof board, minimum 18 mm thick made as per IS: 2046
(phenolic core board) and as per BS-476/97 for fire retardant for toilet
showers, water closet etc . The board shall be manufactured under high
pressure and temperature by impregnating kraft papers and outer
decorative papers with thermosetting phenolic/ melamine resins (low
VOC). The cubicle system shall be resistant towards water, chemical,
33 MR-7 scratch, impact and heat and shall be anti bacterial, colour fast and shall ₹ 0.00
have accessories like door knob, Gravity/ auto return hinges, privacy
thumb turn with occupancy indicator, coat Hook, etc all in SS 304. The
hardware and fixings includes anchoring of all fixed front panel to floor
with SS 316 L brackets/ base plates with a clearance height upto 110
mm, and covered with SS 316 Shoe box plates, wall and corner joineries
(brackets and channels) shall be SS 304 grade, SS 304 sr ISO/IEC 17025
for testing and calib
Digitally signed by VARUN
ADMIN CUM ACADEMIC BLOCK COLLEGE OF HORTICULTURE, MORENA
Sl. No. DSR-2023 DESCRIPTION UNIT Admin, Qty. RATE DSR Amount NDSR Amount
The cubicle unit shall be installed in approved finish, shades and colours
as per specifications and directions of Engineer-In-Charge, including
minimum 5 (five) years warranty against any moisture related damages
to all intermediate panels, doors, hardqwares etc. Standard dimension ₹ 0.00
of the cubicle system shall be of approx. 2100 mm Height(overall) x
1500mm Depth and 1200 mm Width which includes 600mm door size
I shaped Cubicle System consisting of front face panel including door
and all necessary accessories, fittings and hardware etc.
L shaped Cubicle System consisting of front face panel including door,
ii ii intermediate panel and all necessary accessories, fittings and hardware Each 72.00 ₹ 48,468.85 ₹ 3,489,757.00
TOTAL (Carried Over to Summary of Civil Works) ₹ 16,170,871.00 ₹ 6,413,816.00
G 10.0 STEEL WORK ₹ 0.00
Structural steel work riveted, bolted or welded in built up sections,
1 10.2 trusses and framed work, including cutting, hoisting, fixing in position Kg 250.00 ₹ 133.70 ₹ 33,425.00
and applying a priming coat of approved steel primer all complete.
Providing and fixing 1mm thick M.S. sheet door with frame of
40x40x6mm angle iron and 3 mm M.S. gusset plates at the junctions
2 10.5 and corners, all necessary fittings complete, including applying a ₹ 0.00
priming coat of approved steel primer.
i 10.5.1 Using M.S. angels 40x40x6 mm for diagonal braces Sqm 5.04 ₹ 5,804.35 ₹ 29,254.00
Steel work in built up tubular ( round, square or rectangular hollow
tubes etc.) trusses etc., including cutting, hoisting, fixing in position and
4 10.16 applying a priming coat of approved steel primer, including welding and ₹ 0.00
bolted with special shaped washers etc. complete.
i 10.16.2 Hot finished seamless type tubes Kg 16849.00 ₹ 206.35 ₹ 3,476,791.00
5 10.20 Providing and fixing bolts including nuts and washers complete kg 842.45 ₹ 159.35 ₹ 134,244.00
Providing and fixing circular/ Hexagonal cast iron or M.S. sheet box for
ceiling fan clamp, of internal dia 140 mm, 73 mm height, top lid of 1.5
mm thick M.S. sheet with its top surface hacked for proper bonding, top
6 10.18 lid shall be screwed into the cast iron/ M.S. sheet box by means of 3.3 each 200.00 ₹ 220.65 ₹ 44,130.00
mm dia round headed screws, one lock at the corners. Clamp shall be
made of 12 mm dia M.S. bar bent to shape as per standard drawing.
Steel work welded in built up sections/ framed work including cutting,
7 10.25 hoisting, fixing in position and applying a priming coat of approved steel ₹ 0.00
primer using structural steel etc. as required
In stringers, treads, landings etc. of stair cases including use of
chequered plate wherever required, all complete.
Digitally signed by VARUN
ADMIN CUM ACADEMIC BLOCK COLLEGE OF HORTICULTURE, MORENA
Sl. No. DSR-2023 DESCRIPTION UNIT Admin, Qty. RATE DSR Amount NDSR Amount
In gratings, frames, guard bar, ladder, railings, brackets, gates and
Providing and fixing carbon steel galvanised ( minimum coating 5
micron) dash fastener of 10 mm dia double threaded 6.8 grade (yield
strength 480 N/mm2), counter sunk head, comprising of 10 m dia
polyamide PA 6 grade sleeve, including drilling of hole in frame ,
concrete/ masonry, etc. as per direction of Engineer-in-charge.
Providing and fixing stainless steel ( Grade 304) railing made of Hollow
tubes, channels, plates etc., including welding, grinding, buffing,
polishing and making curvature (wherever required) and fitting the
same with necessary stainless steel nuts and bolts complete, i/c fixing
the railing with necessary accessories & stainless steel dash fasteners ,
9 10.28 stainless steel bolts etc., of required size, on the top of the floor or the kg 3983.25 ₹ 772.40 ₹ 3,076,662.00
side of waist slab with suitable arrangement as per approval of Engineer-
in-charge, (for payment purpose only weight of stainless steel members
shall be considered excluding fixing accessories such as nuts, bolts,
fasteners etc.).
TOTAL (Carried Over to Summary of Civil Works) ₹ 7,646,207.00 ₹ 0.00
H 11.0 FLOORING WORK ₹ 0.00
Cement concrete flooring 1:2:4 (1 cement : 2 coarse sand : 4 graded
stone aggregate) finished with a floating coat of neat cement, including
cement slurry, but excluding the cost of nosing of steps etc. complete.
i 11.3.1 40 mm thick with 20 mm nominal size stone aggregate Sqm 58.26 ₹ 614.20 ₹ 35,781.00
Chequerred precast cement concrete tiles 22 mm thick in footpath
&courtyard, jointed with neat cement slurry mixed with pigment to
2 11.20 match the shade of tiles, including rubbing and cleaning etc. complete, ₹ 0.00
on 20mm thick bed of cement mortar 1:4 (1 cement: 4 coarse sand).
i 11.20.1 Light shade pigment using white cement. Sqm 25.00 ₹ 1,402.00 ₹ 35,050.00
Kota stone slab flooring over 20 mm (average) thick base laid over and
jointed with grey cement slurry mixed with pigment to match the shade
3 11.26 of the slab including rubbing and polishing complete with base of ₹ 0.00
cement mortar 1 : 4 (1 cement : 4 coarse sand) :
Digitally signed by VARUN
ADMIN CUM ACADEMIC BLOCK COLLEGE OF HORTICULTURE, MORENA
Sl. No. DSR-2023 DESCRIPTION UNIT Admin, Qty. RATE DSR Amount NDSR Amount
Kota stone slabs 20 mm thick in risers of steps, skirting, dado and pillars
laid on 12 mm (average) thick cement mortar 1:3 (1 cement 3 coarse
4 11.27 sand) and jointed with grey cement slurry mixed with pigment to match Sqm 24.17 ₹ 2,354.70 ₹ 56,904.00
the shade of the slabs, including rubbing and polishing complete.
Extra for pre finished nosing to treads of steps of marble / granite stone.
Extra for marble / granite stone flooring in treads of steps and risers
using single length up to 2.00 metre.
Providing and laying Ceramic glazed floor tiles of size 300x300 mm
(thickness to be specified by the manufacturer), of 1st quality
conforming to IS : 15622, of approved make, in all colours, shades,
except White, Ivory, Grey, Fume Red Brown, laid on 20 mm thick bed of
cement mortar 1:4 (1 Cement : 4 Coarse sand), jointing with grey
cement slurry @ 3.3 kg/ sq.m including pointing the joints with white
cement and matching pigments etc., complete.
Providing & Laying vitrified floor tiles in different sizes ( thickness to be
specified by the manufacturer) with water absorption's less than 0.08%
and confirming to IS : 15622 of approved make in all colours and
shades, laid on 20mm thick cement mortar 1:4 (1 cement : 4 coarse
sand) including grouting the joints with white cement and matching
pigments etc, complete.
Providing and laying Vitrified tiles in different sizes (thickness to be
specified by manufacturer), with water absorption less than 0.08 % and
conforming to I.S. 15622, of approved make, in all colours & shade, in
11 11.46 skirting, riser of steps, over 12 mm thick bed of cement mortar 1:3 (1 ₹ 0.00
cement: 3 coarse sand), jointing with grey cement slurry @ 3.3 kg/ sqm
including grouting the joint with white cement & matching pigments
Providing and laying Polished Granite stone flooring in required design
and patterns, in linear as well as curvilinear portions of the building all
complete as per the architectural drawings with 18 mm thick stone slab
over 20 mm (average) thick base of cement mortar 1:4 (1 cement : 4
12 11.56 coarse sand) laid and jointed with cement slurry and pointing with ₹ 0.00
white cement slurry admixed with pigment of matching shade including
rubbing, curing and polishing etc. all complete as specified and as
directed by the Engineer-in-Charge.
Polished Granite stone slab colour of Black, Cherry/Ruby Red or
Digitally signed by VARUN
ADMIN CUM ACADEMIC BLOCK COLLEGE OF HORTICULTURE, MORENA
Sl. No. DSR-2023 DESCRIPTION UNIT Admin, Qty. RATE DSR Amount NDSR Amount
Providing and laying Laminate wooden
flooring (Grade AC6 or AC6+ laminates) 6 mm to 12 mm thick, having a
good backing layer made up of plastic laminate or melamine, core
made up of medium-density fibreboard (MDF),which is less resistant to
impact damage and less resistant to being dented by heavy furniture,
having a décor layer to give each floor its appearance and consisting of
13 MR-8 one or more sheets of paper impregnated with melamine resin and Sqm 61.00 ₹ 2,619.50 ₹ 159,792.00
top wear layer having clear aluminium oxide finish that protects
the decorative layer & imparts the desired level of sheen, from full
gloss to low gloss, duly fixed to the base floor using adhesive as
approved by the manufacturer.
Providing and fixing Engineered Wooden finish flooring designed to be
installed as a floating floor not nailed or glued to the subfloor. planks
are fastened together utilizing unique tongues and grooves to create a
durable, easy-to-maintain floor surface. 1⁄4" be left around the floor’s
perimeter shall be left as expansion space.before installing a sound
underlayment and/or 6-mil(.15mm) non-recycled (100% virgin) resin
polyethylene film as a moisture barrier beneath the wooden floor.
Providing & fixing High Definition Chromo- Jet printed carpet tufted,
1/10 gauge, 100% type 6 nylon cut pile roll type carpet, which is
suitable & recommended to be used in an Auditorium application.. It
should have a standard length & width of 25m and 3.66m or4m
respectively. The carpet should have a minimum pile height of 6mm,
with a total height of 8mm, and it should also have a minimum pile
13 MR-10 weight of 800g/m² and a minimum total weight of 1810 g/m², to ensure Sqm 310.04 ₹ 3,267.60 ₹ 1,013,070.00
adequate quality for the said usage. The carpet should ensure good
density to perform under heavy traffic usage. Primary backing should be
P.P. woven cloth and action back second backing. The carpet must
have green label CRI+PLUS—GLP 1350. The color fastness standard of
minimum 4 or more for rubbing (wet or dry), water or light. Equivalent
to CCIL carpet.
TOTAL (Carried Over to Summary of Civil Works) ₹ 19,856,780.00 ₹ 1,448,827.00
I 12.0 ROOFING ₹ 0.00
Providing gola 75x75 mm in cement concrete 1:2:4 (1 cement : 2 coarse
sand : 4 stone aggregate 10 mm and down gauge), including finishing
with cement mortar 1:3 (1 cement : 3 fine sand) as per standard design :
In 75x75 mm deep chase
Digitally signed by VARUN
ADMIN CUM ACADEMIC BLOCK COLLEGE OF HORTICULTURE, MORENA
Sl. No. DSR-2023 DESCRIPTION UNIT Admin, Qty. RATE DSR Amount NDSR Amount
Making khurras 45x45 cm with average minimum thickness of 5 cm
cement concrete 1:2:4 (1 cement : 2 coarse sand : 4 graded stone
aggregate of 20 mm nominal size) over P.V.C. sheet 1 m x1 m x 400
micron, finished with 12 mm cement plaster 1:3 (1 cement : 3 coarse
sand) and a coat of neat cement, rounding the edges and making and
finishing the outlet complete.
Providing and fixing false ceiling at all height including providing and
fixing of frame work made of special sections, power pressed from M.S.
sheets and galvanized with zinc coating of 120 gms/sqm (both side
inclusive) as per IS : 277 and consisting of angle cleats of size 25 mm
wide x 1.6 mm thick with flanges of 27 mm and 37mm, at 1200 mm
centre to centre, one flange fixed to the ceiling with dash fastener 12.5
mm dia x 50mm long with 6mm dia bolts, other flange of cleat fixed to
the angle hangers of 25x10x0.50 mm of required length with nuts &
bolts of required size and other end of angle hanger fixed with
intermediate G.I. channels 45x15x0.9 mm running at the spacing of
3 12.45 1200 mm centre to centre, to which the ceiling section 0.5 mm thick ₹ 0.00
bottom wedge of 80 mm with tapered flanges of 26 mm each having
lips of 10.5 mm, at 450 mm centre to centre, shall be fixed in a direction
perpendicular to G.I. intermediate channel with connecting clips made
out of 2.64 mm dia x 230 mm long G.I. wire at every junction, including
fixing perimeter channels 0.5 mm thick 27 mm high having flanges of 20
mm and 30 mm long, the perimeter of ceiling fixed to wall/partition
with the help of rawl plugs at 450 mm centre, with 25mm long dry wall
screws @ 230 mm interval,
including fixing of gypsum board to ceiling section and perimeter
channel with the help of dry wall screws of size 3.5 x 25 mm edges of
the board with recommended jointing compound , jointing tapes ,
finishing with jointing compound in 3 layers covering upto 150 mm on
both sides of joint and two coats of primer suitable for board, all as per
manufacturer's specification and also including the cost of making
openings for light fittings, grills, diffusers, cutouts made with frame of
perimeter channels suitably fixed, all complete as per drawings,
specification and direction of the Engineer in Charge but excluding the
cost of painting with : at 230 mm c/c, including jointing and finishing to
a flush finish of tapered and square
i 12.45.3 12.5 mm thick tapered edge gypsum moisture resistant board. Sqm 1853.80 ₹ 1,529.10 ₹ 2,834,645.00
Digitally signed by VARUN
ADMIN CUM ACADEMIC BLOCK COLLEGE OF HORTICULTURE, MORENA
Sl. No. DSR-2023 DESCRIPTION UNIT Admin, Qty. RATE DSR Amount NDSR Amount
Supply of 80/115 mm PUF insulated thick roof panel with 0.5 mm PGPI
sheet both sides in 40+_2 kg/m3 density. The PU panel shall be CFC free
and Zero Ozone depleting panel made out of continous line running on
uninterrupted power supply.Panel shall have pre coated GI sheet on
both side of Polyurethane Foam confirming to IS 12436:1988. The pre
coated sheet shall be of minimum 240 Mpa steel grade confirming to
4 MR-11 IS:277:1992, 5_7 microns epoxy primer on both sides of the sheet and Sqm 481.40 ₹ 2,838.00 ₹ 1,366,213.00
polyester top coat 15_18 micron. The PPGL sheet shall have plastic
protective gaurd film of minimum 25 Microns to avoid scratches during
transportation. The panels shall be vertically joined together by tongue
and groove joints. The PU Foam shall be self extinguishing having
standard density of 40 kg/m3 with thermal conductivity K value
Providing and fixing tiled false ceiling of specified materials of size
595x595 mm in true horizontal level, suspended on inter locking metal
grid of hot dipped galvanized steel sections ( galvanized @ 120 grams/
sqm, both side inclusive) consisting of main "T" runner with suitably
spaced joints to get required length and of size 24x38 mm made from
0.30 mm thick (minimum) sheet, spaced at 1200 mm center to center
and cross "T" of size 24x25 mm made of 0.30 mm thick (minimum)
sheet, 1200 mm long spaced between main "T" at 600 mm center to
center to form a grid of 1200x600 mm and secondary cross "T" of length
600 mm and size 24x25 mm made of 0.30 mm thick (minimum) sheet to
be interlocked at middle of the 1200x600 mm panel to form grids of
600x600 mm and wall angle of size 24x24x0.3 mm and laying false
ceiling tiles of approved texture in the grid including, required
cutting/making, opening for services like diffusers, grills, light fittings,
fixtures, smoke detectors etc. Main "T" runners to be suspended from
ceiling using GI slotted cleats of size 27 x 37 x 25 x1.6 mm fixed to
ceiling with 12.5 mm dia and 50 mm long dash fasteners, 4 mm GI
adjustable rods with galvanised butterfly level clips of size 85 x 30 x 0.8
mm spaced at 1200 mm center to center along main T, bottom exposed
width of 24 mm of all T-sections shall be pre-painted with polyester
paint, all complete for all heights as per specifications, drawings and as
directed by Engineer-in-charge.
Digitally signed by VARUN
ADMIN CUM ACADEMIC BLOCK COLLEGE OF HORTICULTURE, MORENA
Sl. No. DSR-2023 DESCRIPTION UNIT Admin, Qty. RATE DSR Amount NDSR Amount
GI Metal Ceiling Lay in perforated Tegular edge global white color tiles
of size 595x595 mm and 0.5 mm thick with 8 mm drop; made of GI
sheet having galvanizing of 100 gms/sqm (both sides inclusive) and 20%
perforation area with 1.8 mm dia holes and having NRC (Noise
Reduction Coefficient ) of 0.5, electro statically polyester powder
coated of thickness 60 microns (minimum), including factory painted
after bending and perforation, and backed with a black Glass fiber
acoustical fleece.
Providing and fixing Heat Resistant Terrace Tiles (300 mm x 300mm x 20
mm) with SRI (solar refractive index) > 78, solar reflection > 0.70 and
initial emittance > 0.75 on waterproof and sloped surface of terrace,
laid on 20 mm thick cement sand mortar in the ratio of 1:4 (1 cement : 4
6 12.55 coarse sand) and grouting the joints with mix of white cement & marble Sq.Mt. 1731.28 ₹ 1,703.95 ₹ 2,950,015.00
powder in ratio of 1:1, including rubbing and polishing of the surface
upto 3 cuts complete, including providing skirting upto 150 mm height
along the parapet walls in the same manner.
Acostical False Ceiling ₹ 0.00
Providing & Fixing of BOLLARD PHONIC SOFT FIBRE Ceiling Tiles With
15mm GRID. The tiles should have NRC 0.9, Light Reflectance ≥88%,
Thermal Conductivity k = 0.052 - 0.057 w/m K, Colour White, in module
size of 600 x 600 x 15mm. The tile shall be installed with 15*35(web
hight) wide T - section flanges colour white having rotary stitching on all
T sections i.e. the Main Runner, 1200 mm & 600 mm Cross Tees with a
web height of 35mm and need to be installed with Suspension system
of manufacturer. The Tile & Grid system used together should carry a 10
year warranty.INSTALLATION: The grid should be of “BOLLARD” make
with 15mm wide T - section flanges color white. The main T runner with
7 MR-12 length and size of 15X38mm made from .30mm thick sheet spaced at ₹ 0.00
1200mm Centre to Centre and cross T of size 15X38mm made of .3mm
thick of 1200mm long spaced between main T at 600mm center to
centre to form a grid of 1200X600mm and second cross T of length
600mm and size 15X38mm made of 0.30mm sheet to be interlocked at
middle of the 1200X600 mm panel to form grid of 600X600mm and wall
angle of size 19X19 Installation should be carried out as per Bollard
recommended procedure. The grid frame should be suspended from
ceiling using M-6 fastener, L Cleat, 4mm GI wire with Stainless steel
level adjustible clip which will be attached to Main Runner at spaced of
Digitally signed by VARUN
ADMIN CUM ACADEMIC BLOCK COLLEGE OF HORTICULTURE, MORENA
Sl. No. DSR-2023 DESCRIPTION UNIT Admin, Qty. RATE DSR Amount NDSR Amount
INSTALLATION: To comprise main runner spaced at 1200mm centres
securely fixed to the structural soffit using Armstrong suspension
system (specifications below) at 1200mm maximum centre. The
First/Last Armstrong suspension system at the end of each main runner
should not be greater than 450mm from the adjacent wall. The
orientation of the first tile should be such that the tegular edge side of
the plank should be placed on the wall angle and the flange of the
1200mm long special cross tees to be inserted in the grooved edge side
of the plank. The groove will occupy only half of the T section but would
cover the face of the flange. On the other half of the T section the
tegular edge of the subsequent plank would rest and the special cross
tee would be placed in grooved edge and this would be repeated thus
forming a semi concealed system. A stabilizer bar of 1200 mm to be
placed on the bulb of the main
Providing and Fixing 15 mm thick densified tegular edged eco friendly
light weight calcium silicate false ceiling tiles of approved texture of size
595 x 595 mm in true horizontal level, suspended on inter locking metal
grid of hot dipped galvanised steel sections (galvanising @ 120 grams
per sqm including both side) consisting of main ‘T’ runner suitably
spaced at joints to get required length and of size 24x38 mm made from
0.33 mm thick (minimum) sheet, spaced 1200 mm centre to centre, and
cross “T” of size 24x28 mm made out of 0.33 mm (Minimum) sheet,
1200 mm long spaced between main’T’ at 600 mm centre to centre to
form a grid of 1200x600 mm and secondary cross ‘T’ of length 600 mm
and size 24 x28 mm made of 0.33 mm thick (Minimum) sheet to be inter
locked at middle of the 1200x 600 mm panel to from grid of size
8 12.53 600x600 mm, resting on periphery walls /partitions on a Perimeter wall Sq.Mt. 10.00 ₹ 2,158.15 ₹ 21,582.00
angle pre-coated steel of size(24x24X3000 mm made of 0.40 mm thick
(minimum) sheet with the help of rawl plugs at 450 mm centre to
centre with 25 mm long dry wall screws @ 230 mm interval and laying
15 mm thick densified edges calicum silicate ceiling tiles of approved
texture in the grid, including, cutting/ making opening for services like
diffusers, grills, light fittings, fixtures, smoke detectors etc., wherever
required. Main ‘T’ runners to be suspended from ceiling using G.I.
slotted cleats of size 25x35x1.6 mm fixed to ceiling with 12.5 mm dia
and 50 mm long dash fasteners, 4 mm G.I. adjustable rods with
galvanised steel level clips of size 85 x 30 x 0.8 mm, spaced at 1200 mm
centre to centre along main ‘T’, bottom exposed with 24 mm of all
Tsections shall be pre-painted with polyster baked paint, for all heights,
as per specifications, drawings and as directed by Engineer-in-Charge.
Digitally signed by VARUN
ADMIN CUM ACADEMIC BLOCK COLLEGE OF HORTICULTURE, MORENA
Sl. No. DSR-2023 DESCRIPTION UNIT Admin, Qty. RATE DSR Amount NDSR Amount
Providing and Fixing of 16mm Thick sky lights consisting of Multi
cell/tight cell Polycarbonate Panel System of approved colour, 16 mm
thick (minimum) having uniform in color with an integral Tight-Cell core
constructed not to exceed 4mmx4mm in a cross section, Vertical
Standing Seam manufactured at both sides of the panel. Snap-on
connector to interlock the panels shall have a grip-lock double tooth
locking mechanism to ensure maximum uplift capability and shall be of
9 MR-13 same color as that of panel. Panel shall be factory sealed/end welded Sq.Mt. 10.00 ₹ 2,780.00 ₹ 27,800.00
panels with additional End-cap/Aluminium U-Profile (mill finish) for
ends. Panel shall be co-extruded with special anti glare compound and
UV protected. The full system shall be fitted on MS purlins
perpendicular to direction of sheeting with purlin spacing as specified
by Manufacturer. The rate includes cost of all the operations, labour
and all materials and tests (as applicable) involved such as bolts nuts
and screws etc. and labour for cutting bending to required profile,
Providing and fixing stretch ceiling at all heights and levels and of any
shape including wall coveing wherever shown on dawing as pe detailed
specifications: Detailed Description Features: System comprises of two
components - A perimeter track and lightweight fabric membrane.
Ceiling manufactured from roll material bespoke to ceilings height and
shape. it shall have povision of multiple ceiling removal and re-
installation for access. it shall include Incorporatiing of all types of light
10 MR-14 fixtures, grilles and fixing points including Transmittance for Light Sq.Mt. 10.00 ₹ 16,768.00 ₹ 167,680.00
Diffusion, Backlighting (LED) and projection. System shall be entirely
waterproof, washable. membane shall be 0.2mm thick PVC (Polyvinyl
Chloride) based membrane and shall be connected through Membranes
by Micro-Seams (Factory Welded). Semi-Concealed Perimeter Track
Matt White/Black PVC mateial fo fixing or Anodised Aluminium as per
Acostical Wall Paneling ₹ 0.00
Digitally signed by VARUN
ADMIN CUM ACADEMIC BLOCK COLLEGE OF HORTICULTURE, MORENA
Sl. No. DSR-2023 DESCRIPTION UNIT Admin, Qty. RATE DSR Amount NDSR Amount
Providing and Fixing of Channeled Woodworks perforated panels
Custom Perforated of width 192mm, thickness of 17mm and length
2440 mm , made of a HDHMR FR Grade board with minimum 860
Kg/M3 density substrate with a laminated facing as per the approved
shade & finish (Khaya Mahagony/Fusion Mapple/ Bavarian Beech) and
a melamine balancing layer on the reverse side. The boards shall have a
special perforation pattern of 3mm width Custom Perforaton of visible
panel each. The edges of the panels shall be “tongue-and-grooved” to
receive special clips for installation. The back of the perforated panel
shall have sound absorbing non-woven acoustical fleece having NRC of
11 MR-15 0.60. The panels shall be mounted on special aluminium splines (keel) Sq.Mt. 351.21 ₹ 5,326.40 ₹ 1,870,685.00
using clips provided by manufacturer.INSTALLATION: Screw the
aluminium extruded keel for channelled woodworks provided by
manufacturer over the solid wall/ surface an on-centre distance of
600mm. Place the inside clip on the groove end of the panel along the
Al keel and then place the tongue end of the next panel. Continue
installing rows of panels by inserting the tongue into the groove of the
earlier inserted panel and progressively installing inside clips into the
next keel till the actual height is achieved. Installation to be carried out
by Trained Installation team & Installation should be carried out as per
manufacturer recommended procedure.
TOTAL (Carried Over to Summary of Civil Works) ₹ 7,242,808.00 ₹ 5,235,009.00
J 13.0 FINISHING WORK
1 13.4 12 mm cement plaster of mix :
15 mm cement plaster on rough side of single or half brick wall of mix :
3 13.6 20 mm cement plaster of mix : ₹ 0.00
4 13.16 6 mm cement plaster of mix : ₹ 0.00
Extra for providing and mixing water proofing material in cement per bag of 50KG
5 13.21 plaster work in proportion recommended by the manufacturers. Cement Used in 3863.30 ₹ 22.10 ₹ 85,379.00
Extra for plastering exterior walls of height more than 10 m from
ground level for every additional height of 3 m or part thereof.
Digitally signed by VARUN
ADMIN CUM ACADEMIC BLOCK COLLEGE OF HORTICULTURE, MORENA
Sl. No. DSR-2023 DESCRIPTION UNIT Admin, Qty. RATE DSR Amount NDSR Amount
Providing and applying plaster of paris putty of 2 mm thickness over
7 13.26 plastered surface to prepare the surface even and smooth complete. Sqm 5281.53 ₹ 262.70 ₹ 1,387,457.00
Distempering with 1st quality acrylic distemper, having VOC (Volatile
Organic Compound ) content less than 50 grams/ litre, of approved
brand and manufacture, including applying additional coats wherever
required, to achieve even shade and colour.
New work (two or more coats) over and including water
i 13.41.1 thinnable priming coat with cement primer having VOC content Sqm 7135.33 ₹ 185.65 ₹ 1,324,674.00
less than 50 gram/litre
Applying one coat of water thinnable cement primer of approved brand
and manufacture on wall surface :
With water thinnable cement primer on wall surface having
VOC content less than 50 grams/litre
Wall painting with acrylic emulsion paint of approved brand and
manufacture to give an even shade :
i 13.82.2 Two or more coats on new work Sqm 12427.01 ₹ 137.45 ₹ 1,708,093.00
Finishing walls with water proofing cement paint of required shade :
i 13.44.1 New work (Two or more coats applied @ 3.84 kg/10 sqm) Sqm 50.00 ₹ 116.90 ₹ 5,845.00
13 13.45 Finishing walls with textured exterior paint of required shade : ₹ 0.00
New work (Two or more coats applied @ 3.28 ltr/10 sqm) over and
i 13.45.1 including priming coat of exterior primer applied @ 2.20kg/10 sqm Sqm 1840.38 ₹ 223.60 ₹ 411,508.00
Finishing exterior walls with Ceramic textured finish with protection
coating by Texture Paints Natural - Ceramic/ Stony of approved shade
or approved equivalent make) to external wall surfaces comprising of
water-borne, penetrating, water repellent EM- primer & super durable
water based acrylic silicon resin clear and super durable dirt and dust
resistant protection coat of FSI Clear coat, which shall be highly water
repellant, Anti-algae & anti-fungal in nature. The coating shall also
cover hairline cracks with application method which includes 2 coats of
14 MR-16 E M Primer, 2 coats (Silmultaneouly) of 100% natural Ceramic & granite Sqm 2605.00 ₹ 2,831.00 ₹ 7,374,755.00
crushed stone , all in approved colour and texture including preparation
of surface, appropriate primer coat etc. applied as per manufacturer's
instructions complete & project consultant instructions, allow for
scaffolding, staging as required. The finish shall be natural colour/ non
pigmented, water repellant, resistant to condensate formation, cover
hairline cracks/ crazing, UV & alkali resistant & ensure good
breathability for the substrate all to complete as per direction of
Engineer-in-charge.
Finishing walls with Multi surface paint system for interiors and
15 13.48 exteriors using Primer as per manufacturers specifications : ₹ 0.00
Digitally signed by VARUN
ADMIN CUM ACADEMIC BLOCK COLLEGE OF HORTICULTURE, MORENA
Sl. No. DSR-2023 DESCRIPTION UNIT Admin, Qty. RATE DSR Amount NDSR Amount
Painting wood work with Multi Surface Paint of required shade. Two or
more coat applied @0.90 ltr/10 sqm over an under coat of primer
applied @0.75 ltr/ 10 sqm of approved brand or manufacture
Applying priming coat : Applying priming coats with primer of approved
16 13.85 brand and manufacture, ₹ 0.00
having low VOC (Volatile Organic Compound ) content.
With ready mixed pink or Grey primer of approved brand and
manufacture on wood work (hard and soft wood)
With ready mixed red oxide zinc chromate primer of approved brand
and manufacture on steel galvanised iron/ steel works
Painting with synthetic enamel paint of approved brand and
manufacture to give an even shade :
i 13.62.1 Two or more coats on new work Sqm 2929.91 ₹ 226.25 ₹ 662,892.00
Add for plaster drip course/ groove in plastered surface or moulding to
R.C.C. projections.
Providing and applying white cement based putty of average thickness
1 mm, of approved brand and manufacturer, over the plastered wall
surface to prepare the surface even and smooth complete
(Providing and fixing Glass Reinforced Concrete (G.R.C) Jali in approved
size, pattern, design, thickness and color. The Screens should be made
from ‘53 grade’White Portland Cement manufactured by ‘JK Cement’ or
equivalent, Quartz, Fine Silica Sand, Alkali Resistant Glass Fiber
manufactured by ‘Saint Gobain’ or equivalent, Super Plasticizers
manufactured by ‘BASF’ or equivalent, Polymers manufactured by
20 MR-17 ‘BASF’ or equivalent and U.V resistant Synthetic inorganic pigments Sqm 374.22 ₹ 6,208.00 ₹ 2,323,158.00
should be used for pigmentation manufactured by ‘BAYFERROX
(Germany)’ or equivalent. The material casting should take place in
Synthetic Rubber / FRP Mould manufactured by ‘Reckli’ or equivalent.
The fixing of Jali should be ‘Dry fixing’ i.e. to be done with MS/SS ‘L’
shaped Clamps, dash fasteners and pins etc as per site requirment.)
Digitally signed by VARUN
ADMIN CUM ACADEMIC BLOCK COLLEGE OF HORTICULTURE, MORENA
Sl. No. DSR-2023 DESCRIPTION UNIT Admin, Qty. RATE DSR Amount NDSR Amount
Supply and Installation of 6mm thick FR Grade Aluminium Composite
HPL Composite Panel Cladding of approved color, made out of 5.5mm
thick FR grade mineral core sandwiched between two aluminium sheets
(each 0.25mm thick). The Aluminium HPL Composite Panel Cladding
shall be coil coated with High Durable resin coating of approved colour
with 10 years exterior warranty and shade on face #1 and polymer
(service) coating on face #2. Installation of panels will be done by MBE
Rivets (with Fixed and Sliding Points) with recommended Aluminum T
section of 75x37x2.8 mm thick and L section 38x38x2.8mm thick held by
Aluminum Wall Bracket with Wind load and Dead load slot, anchored
by standard anchor fasteners along with Thermal Separator. Installation
of Panels will be done using Rear Ventilated Principles only, which is
ensured by providing ventilation gap minimum 200 cm2/ per Meter (for
free flow of air behind the façade) for the façade and using the
framework with no horizontal section. (for all levels and all height e
tongue end of the next panel. Cont
TOTAL (Carried Over to Summary of Civil Works) ₹ 20,100,136.00 ₹ 10,264,774.00
M 21.0 ALUMINIUM & STRUCTURAL GLAZING WORK
Providing and fixing aluminium work for doors, windows, ventilators
and partitions with extruded built up standard tubular
sections/appropriate Z sections and other sections of approved make
conforming to IS: 733 and IS : 1285, fixed with rawl plugs and screws or
with fixing clips, or with expansion hold fasteners including necessary
filling up of gaps at junctions, at top, bottom and sides with required
PVC/neoprene felt etc. Aluminium sections shall be smooth, rust free,
straight, mitred and jointed echanically wherever required including
cleat angle, Aluminium snap beading for glazing / paneling, C.P. brass /
stainless steel screws, all complete as per architectural drawings and
the directions of Engineer-in-charge. Glazing and paneling to be paid
for separately) :
a) 21.1.1 For fixed portion.
Powder coated aluminium (minimum thickness of powder coating 50
For shutters of doors, windows & ventilators including providing and
fixing hinges/ pivots and making provision for fixing of fittings wherever
required including the cost of EPDM rubber / neoprene gasket required
(Fittings shall be paid for separately)
Powder coated aluminium (minimum thickness of powder coating 50
Digitally signed by VARUN
ADMIN CUM ACADEMIC BLOCK COLLEGE OF HORTICULTURE, MORENA
Sl. No. DSR-2023 DESCRIPTION UNIT Admin, Qty. RATE DSR Amount NDSR Amount
Providing and fixing 12 mm thick prelaminated particle board flat
pressed three layer or graded wood particle board conforming to IS:
12823 Grade l Type ll, in panelling fixed in aluminum doors, windows
shutters and partition frames with C.P. brass / stainless steel screws etc.
complete as per architectural drawings and directions of engineerin-
Pre-laminated particle board with decorative lamination on both sides
Providing and fixing glazing in aluminium door, window, ventilator
shutters and partitions etc. with EPDM rubber / neoprene gasket etc.
3 21.3 complete as per the architectural drawings and the directions of ₹ 0.00
engineer-in-charge . (Cost of aluminium snap beading shall be paid in
With float glass panes of 5 mm thickness (weight not less than 12.50
With float glass panes of 8 mm thickness (weight not less than 20
Filling the gap in between aluminium frame and adjacent
RCC/Brickwork/ Stone Work by providing weather silicon sealant over
backer rod of approved quality as per architectural drawings and
direction of Engineer-in-charge
i 21.8.1 Upto 5mm depth and 5mm width metre 2094.14 ₹ 96.75 ₹ 202,608.00
Providing and supplying aluminium extruded tubular and other
aluminium sections as per the architectural drawings and approved
shop drawings , the aluminium quality as per grade 6063 T5 or T6 as per
BS 1474,including super durable powder coating of 60-80 microns
conforming to AAMA 2604 of required colour and shade as approved by
5 25.1 the Engineer-in-Charge. ( The item includes cost of material such as kg 1094.00 ₹ 414.30 ₹ 453,244.00
cleats, sleeves, screws etc. necessary for fabrication of extruded
aluminium frame work. Nothing extra shall be paid on this account).
The weight of aluminium extruded section shall be taken for purpose of
Designing, fabricating, testing, protection, installing and fixing in
position semi (grid) unitized system of structural/ curtain wall glazing
(with open joints) for linear as well as curvilinear portions of the
building for all heights and all levels, including :
Digitally signed by VARUN
ADMIN CUM ACADEMIC BLOCK COLLEGE OF HORTICULTURE, MORENA
Sl. No. DSR-2023 DESCRIPTION UNIT Admin, Qty. RATE DSR Amount NDSR Amount
a) Structural analysis & design and preparation of shop drawings for the
specified design loads conforming to IS 875 part III (the system must
passed the proof test at 1.5 times design wind pressure without any
failure), including functional design of the aluminum sections for fixing
glazing panels of various thicknesses, aluminium cleats, sleeves and
splice plates etc. gaskets, screws, toggles, nuts, bolts, clamps etc., ₹ 0.00
structural and weather silicone sealants, flashings, fire stop (barrier)-
cum-smoke seals, microwave cured EPDM gaskets for water tightness,
pressure equalization & drainage and protection against fire hazard
b) Fabricating and supplying serrated M.S. hot dip galvanized /
Aluminium alloy of 6005 T5 brackets of required sizes, sections and
profiles etc. to accommodate 3 Dimensional movement for achieving
perfect verticality and fixing structural glazing system rigidly to the RCC/
masonry/structural steel framework of building structure using stainless ₹ 0.00
steel anchor fasteners/ bolts, nylon separator to prevent bimetallic
contacts with nuts and washers etc. of stainless steel grade 316, of the
required capacity and in required numbers..
c) Providing and filling, two part pump filled, structural silicone sealant
and one part weather silicone sealant compatible with the structural
silicone sealant of required bite size in a clean and controlled factory /
work shop environment , including double sided spacer tape, setting ₹ 0.00
blocks and backer rod, all of approved grade, brand and manufacture,
as per the approved sealant design, within and all around the perimeter
for holding glass
d) Providing and fixing in position flashings of solid aluminium sheet 1
mm thick and of sizes, shapes and profiles, as required as per the site
conditions, to seal the gap between the building structure and all its ₹ 0.00
interfaces with curtain glazing to make it watertight.
e) Making provision for drainage of moisture/ water that enters the
curtain glazing system to make it watertight, by incorporating principles
of pressure equalization, providing suitable gutter profiles at bottom (if
required), making necessary holes of required sizes and of required
numbers etc. complete. This item includes cost of all inputs of
designing, labour for fabricating and installation of aluminium grid,
installation of glazed units, T&P, scaffolding and other incidental ₹ 0.00
charges including wastages etc., enabling temporary structures and
services, cranes or cradles etc. as described above and as specified. The
item includes the cost of getting all the structural and functional design
including shop drawings checked by a structural designer, dully
approved by Engineer-in-charge.
Digitally signed by VARUN
ADMIN CUM ACADEMIC BLOCK COLLEGE OF HORTICULTURE, MORENA
Sl. No. DSR-2023 DESCRIPTION UNIT Admin, Qty. RATE DSR Amount NDSR Amount
The item also includes the cost of all mock ups at site, cost of all
samples of the individual components for testing in an approved
laboratory, field tests on the assembled working structural glazing as
specified, cleaning and protection till the handing over of the building
for occupation. In the end, the Contractor shall provide a water tight
structural glazing having all the performance characteristics etc. all
complete as required, as per the Architectural drawings, as per item
description, as specified, as per the approved shop drawings and as
directed by the Engineer in-Charge.
Note:- 1. The cost of providing extruded aluminium frames, shadow
boxes, extruded aluminium section capping for fixing in the grooves of
the curtain glazing and vermin proof stainless steel wire mesh shall be
paid for separately under relevant items under this subhead. However,
for the purpose of payment, only the actual area of structural/ curtain
wall glazing (including width of grooves ) on the external face shall be
measured in sqm. up to two decimal places.
Providing, assembling and supplying vision glass panels (IGUs)
comprising of hermetically-sealed 6-12- 6 mm insulated glass (double
glazed) vision panel units of size and shape as required and specified,
comprising of an outer heat strengthened (as approved) glass 6mm
thick, of approved colour and shade with reflective soft coating on
surface # 2 of approved colour and shade, an inner heat strengthened
(as approved) clear float glass 6mm thick, spacer tube 12mm wide,
desiccants, including primary seal and secondary seal (structural silicone
sealant) etc. all complete for the required performances, as per the
Architectural drawings, as per the approved shop drawings, as specified
and as directed by the Engineer-in-Charge. The IGUs shall be assembled
in the factory/ workshop of the glass processor. (Payment for fixing of
IGU Panels in the curtain glazing is included in cost of item No.1.8.16
above). For payment, only the actual area of glass on face # 1 of the
glass panels (excluding the areas of the grooves and weather silicone
sealant) provided and fixed in position, shall be measured in sqm. (To
be fixed on extruded aluminium sections. and cost of aluminium
sections to be paid in relevant item)
(i) Coloured tinted float glass 6mm thick Heat Strengthened substrate
with reflective soft coating on face # 2, + 12mm Airgap + 6mm Heat
Strengthened clear Glass of approved make having properties as visible
i i Light transmittance (VLT) of 25 to 35 %, Light reflection internal 10 to Sqm 59.40 ₹ 3,718.70 ₹ 220,891.00
15%, light reflection external 10 to 20 %, shading coefficient (0.25- 0.28)
and U value of 3.0 to 3.3 W/m2 degree K etc.
Digitally signed by VARUN
ADMIN CUM ACADEMIC BLOCK COLLEGE OF HORTICULTURE, MORENA
Sl. No. DSR-2023 DESCRIPTION UNIT Admin, Qty. RATE DSR Amount NDSR Amount
Extra for openable side / top hung vision glass panels (IGUs/laminated
glass) including providing and supplying at site all accessories and
hardware for the openable panels as specified and of the approved
make such as heavy duty stainless steel friction hinges, min 4 -point
cremone locking sets with stainless steel plates, handles, buffers etc.
including necessary stainless steel screws/ fasteners, nuts, bolts,
washers etc. all complete as per the Architectural drawings, as per the
approved shop drawings, as specified and as directed by the Engineer in-
Providing and fixing 12 mm thick frameless toughened glass door
shutter of approved brand and manufacture, including providing and
fixing top & bottom pivot & double acting hydraulic floor spring type
9 21.18 fixing arrangement and making necessary holes etc. for fixing required Sqm 136.32 ₹ 5,325.90 ₹ 726,027.00
door fittings, all complete as per direction of Engineer-in-charge (Door
handle, lock and stopper etc.to be paid separately).
Providing and fixing Pull Handle back to Back Approved makes of Fixing
10 MR-19 25mm dia x300mm c/c, SS Matt with necessary screws etc. complete as Each 114.00 ₹ 2,616.05 ₹ 298,230.00
per direction of Engineer-in-Charge.
Providing and fixing Corner Patch Lock With Cylinder Approved makes,
11 MR-20 SS Matt with necessary screws etc. complete as per direction of Each 57.00 ₹ 3,899.50 ₹ 222,272.00
Engineer-in-Charge.
Providing and fixing 12mm thk. Toughened float glass glazing cut and
fixed in openings of desired shape as per drawing with 3/4" beveling all
around, fixed with the help of SS patch fittings, with top and bottom 'C'
12 MR-21 channels, fixed firmly to the slab/ MS Structure ,as directed by Engineer Sqm 629.19 ₹ 5,804.95 ₹ 3,652,428.00
in Charge. Area of openings to be measured). Assume frameless glass.
Rate of above item to include P/F of : 20x20mm "C" channel SS patch
Aluminium Louver ₹ 0.00
Supply and installation of Exterior Aluminium Vertical Louvers ARF200
Vertical Fin System, in different sizes as per drawing. Louvers to be
made with Aluminium Box Tube sections and covered with Solid
Aluminium Sheet pre-coated on a continuous reverse roller colour
coating line with high durable paint in approved colour. The top coated
surface shall be pre coated. Post painting by way of powder coating or
11 MR-22 spray coating is not allowed. Colour consistency with pre coating is Rmt. 75.00 ₹ 13,892.00 ₹ 1,041,900.00
desired. Welding is not acceptable. Blades to be mechanically secured
to allow for replacement in case of damage. Fasteners to be hex head.
All the fasteners should be mechanically fastened. Louvers must be
factory fabricated and finished so that only assembly / installation will
be done at the site.
Digitally signed by VARUN
ADMIN CUM ACADEMIC BLOCK COLLEGE OF HORTICULTURE, MORENA
Sl. No. DSR-2023 DESCRIPTION UNIT Admin, Qty. RATE DSR Amount NDSR Amount
TOTAL (Carried Over to Summary of Civil Works) ₹ 3,757,904.00 ₹ 5,214,830.00
N 22.0 WATER PROOFING
Providing and laying water proofing treatment to vertical and horizontal
1 22.3 surfaces of depressed portions of W.C., kitchen and the like consisting
(i) Ist course of applying cement slurry @ 4.4 Kg/Sqm mixed with water
proofing compound conforming to IS 2645 in recommended
proportions including rounding off junction of vertical and horizontal
surface. (ii) IInd course of 20mm cement plaster 1:3 (1 cement : 3
coarse sand) mixed with water proofing compound in recommended
proportion including rounding off junction of vertical and horizontal sqm 459.73 ₹ 769.60 ₹ 353,810.00
surface. (iii) IIIrd course of applying blown or residual bitumen applied
hot at 1.7 Kg. per Sqm of area. (iv) IVth course of 400 micron thick PVC
sheet. (Overlaps at joints of PVC sheet should be 100 mm wide and
pasted to each other with bitumen @ 1.7 Kg/Sqm.)
TOTAL (Carried Over to Summary of Civil Works) ₹ 353,810.00 ₹ 0.00
Digitally signed by VARUN
ADMIN CUM ACADEMIC BLOCK COLLEGE OF HORTICULTURE, MORENA
Name of Project: Development of Administrative-cum-Academic Block for the College of Horticulture at Morena
(M.P.), under RLBCAU.
BUILDING NAME : ADMIN CUM ACDEMIC BLOCK
ELECTRICAL WORKS (AS PER DSR 2025)
S.NO NAME OF SUB-HEAD
DSR 2025 items Non Scheduled items
1 SUBHEAD- I: DISTRIBUTION BOARD ₹ 721,815.00 ₹ 0.00
2 SUB-HEAD - II : INTERNAL WIRING ₹ 14,921,160.00 ₹ 0.00
3 SUB-HEAD III - FANS & LIGHT FIXTURES: ₹ 2,167,989.00 ₹ 371,029.63
4 SUB HEAD - IV : LIGHTNING PROTECTION SYSTEM ₹ 413,490.00 ₹ 0.00
6 SUB HEAD -VI : RACEWAY AND CABLE TRAY ₹ 677,170.00 ₹ 1,567,250.23
7 SUB HEAD-VII : LIFT ₹ 3,368,451.44 ₹ 0.00
8 SUB HEAD-VIII :SOLAR DSR-2019 ₹ 2,171,200.00 ₹ 0.00
9 SUB HEAD-IX :Panels ₹ 0.00 ₹ 2,918,523.83
10 SUB HEAD-X :Earthing ₹ 1,007,691.00 ₹ 0.00
Digitally signed by VARUN
ADMIN CUM ACADEMIC BLOCK COLLEGE OF HORTICULTURE, MORENA
Name of Project: Development of Administrative-cum-Academic Block for the College of Horticulture at Morena (M.P.), under RLBCAU.
BUILDING NAME : ADMIN CUM ACDEMIC BLOCK
SCHEDULE OF QUANTITIES FOR SUPPLY, ERECTION, TESTING AND COMMISSIONING
ELECTRICAL WORKS (AS PER DSR 2025)
As Per DSR AS PER MARKET RATE
S.NO DSR ITEMS DESCRIPTION OF ITEM UNIT
Rate DSR 2025 AMOUNT (RS.) RATE (RS.) AMOUNT (RS.)
1 SUBHEAD- I: DISTRIBUTION BOARD
Supplying and fixing following way, single pole and neutral, sheet
steel, MCB distribution board, 240 V, on surface/ recess complete
1 2.3 with tinned copper bus bar, neutral bus bar, earth bar, din bar,
interconnections, powder painted including earthing etc. as required.
(But without MCB/RCCB/Isolator)
Supplying and fixing following way, horizontal type three pole and
neutral, sheet steel, MCB distribution board, 415 V, on surface/
recess, complete with tinned copper bus bar, neutral bus bar, earth
2 2.4 bar, din bar, interconnections, powder painted including earthing etc.
as required. (But without MCB/RCCB/ Isolator)
Supplying and fixing of following ways surface/ recess mounting,
vertical type, 415 V, TPN MCB distribution board of sheet steel, dust
protected, duly powder painted, inclusive of 200 A, tinned copper bus
bar, common neutral link, earth bar, din bar for mounting MCBs (but
3 2.5 without MCBs and incomer) as required.Make:BS,Havells,Legrand
(Note : Vertical type MCB TPDB is normally used where 3 phase
outlets are required.)
Supplying and fixing following rating, double pole, 240 volts, isolator
4 2.12 in the existing MCB DB complete with connections, testing and
commissioning etc. as required.
Supplying and fixing following rating, four pole, 415 volts, isolator in
5 2.13 the existing MCB DB complete with connections, testing and
commissioning etc. as required.
Supplying and fixing 5 amps to 32 amps rating, 240/415 volts, "C"
curve, miniature circuit breaker suitable for inductive load of
following poles in the existing MCB DB complete with connections,
testing and commissioning etc. as required.
Digitally signed by VARUN
ADMIN CUM ACADEMIC BLOCK COLLEGE OF HORTICULTURE, MORENA
As Per DSR AS PER MARKET RATE
S.NO DSR ITEMS DESCRIPTION OF ITEM UNIT
Rate DSR 2025 AMOUNT (RS.) RATE (RS.) AMOUNT (RS.)
Supplying and fixing single pole blanking plate in the existing MCB
e) DB complete etc. as required.
Supplying and fixing following rating, double pole, single phase and
neutral, 240 volts, residual current circuit breaker ( RCCB), having a
7 2.14 sensitivity current upto 30 milliamperes in the existing MCB DB
complete with connections, testing and commissioning etc as required.
Supplying and fixing following rating, four pole, three phase and
neutral, 415 volts, residual current circuit breaker ( RCCB), having a
8 2.15 sensitivity current upto 30 milliamperes in the existing MCB DB
complete with connections, testing and commissioning etc as required.
Total carried over to Summary 721,815.00 0.00
2 SUB-HEAD - II : INTERNAL WIRING
1 Wiring for light point/ fan point/ exhaust fan point/ call bell point
with 1.5 sq.mm FRLS PVC insulated copper conductor
single core cable in surface / recessed steel conduit, with modular
1.30 switch, modular plate, suitable GI box and earthing the
point with 1.5 sq.mm FRLS PVC insulated copper conductor single
core cable etc. as required.
Wiring for group controlled (looped) light point/fan point/exhaust fan
point/ call bell point (without independent
switch etc.) with 1.5 sq. mm FRLS PVC insulated copper conductor
2 1.54 single core cable in surface/ recessed steel conduit, and earthing the
point with 1.5 sq. mm FRLS PVC insulated copper conductor single
core cable etc. as required
3 Wiring for circuit/ submain wiring alongwith earth wire with the
following sizes of FRLS PVC insulated copper conductor, single core
cable in surface/ recessed steel conduit as required.
Digitally signed by VARUN
ADMIN CUM ACADEMIC BLOCK COLLEGE OF HORTICULTURE, MORENA
As Per DSR AS PER MARKET RATE
S.NO DSR ITEMS DESCRIPTION OF ITEM UNIT
Rate DSR 2025 AMOUNT (RS.) RATE (RS.) AMOUNT (RS.)
Supplying and fixing suitable size GI box with modular plate and
cover in front on surface or in recess, including providing and fixing
4 1.31 3 pin 5/6 amps modular socket outlet and 5/6 amps modular switch, Each 570.00 545.00 310,650.00
connection etc. as required. (For light plugs to be used in residential
Supplying and fixing suitable size GI box with modular plate and
cover in front on surface or in recess, including providing and fixing
6 pin 5/6 & 15/16 amps modular socket outlet and 15/16 amps
modular switch, connection etc. as required.
Supplying and fixing 20 amps, 240 volts, SPN industrial type, socket
outlet, with 2 pole and earth, metal enclosed plug top along with 20
amps "C" curve, SP, MCB, in sheet steel enclosure, on surface or in
6 2.18 recess, with chained metal cover for the socket out let and complete Each 25.00 1,806.00 45,150.00
with connections, testing and commissioning etc. as required.
3 SUB-HEAD III - FANS & LIGHT FIXTURES:
LED Down lighter (SMD Type) (System lumen efficacy ≥120 <135 lm/Watt )
Supplying, installation, Testing & Commissioning of LED Recessed /
surface Down lighter (Round / square/ Rectangular) SMD type of following
body material with PMMA and prismatic diffuser and construction as per IS :
10322 with driver as per the requirement with Driver efficiency >85%,
Operating voltage AC 140-270 Volt, freq 50/60 hz, Operating temp range
-15 deg to 40 deg centigrade, internal surge protection of 2.5 KV with
Short & Open circuit protection ,THD < 10% , P. F.≥0.95, IP20, CRI >80 ,
UGR (Unified Glare Rating) < 19, Flicker free (flicker should
be below 5 %), life time (LED,Driver & electrical circuitry), life time of
minimum 50000 Burning Hours with , 70% of initial Lumen maintained
till life ends , CCT 3000°K / 4000°K / 5700°K /6000°K/6500°K (As per
ANSI Bin), SDCM(Standard Deviation Color Matching) <3, Maximum
power consumption should not more than the specified rating and Fixture
shall be of relevant BIS standard and trade mark certificate ( T.C.).
Manufactures Word Mark/ Name Engraved/ Embossing/ Screen printing on
housing. OEM must have its own in house NABL lab setup for all
testing facilities for LED fixtures. "complete in all respect i/c
connections with 1.5 sq mm FRLS, PVC insulated copper conductor
single core cable and earthing etc. as required with Minimum 5 year OEM
warranty. System lumen efficacy ≥120 <135 lm/Watt output . LM79 & LM80
Test report from NABL lab for all testing required for LED fixtures as
per BIS shall be submitted. Shape size and CCT shall be as approved by
Engineer-in-Charge as per requirement. (Thermal management: heat sink
of aluminum housing such that LED junction temperature shall not rise
Digitally signed by VARUN
ADMIN CUM ACADEMIC BLOCK COLLEGE OF HORTICULTURE, MORENA
As Per DSR AS PER MARKET RATE
S.NO DSR ITEMS DESCRIPTION OF ITEM UNIT
Rate DSR 2025 AMOUNT (RS.) RATE (RS.) AMOUNT (RS.)
Powder coated die cast /Extruded aluminum Body including trim .
2 DSR2025-8.5 LED Down lighter (COB Type) (System lumen efficacy ≥120 lm/Watt )
Supplying, installation, Testing & Commissioning of LED Recessed /
surface Down lighter (Round / square/ Rectangular) COB Type of
following body material and construction as per IS : 10322 with driver as per
the requirement with Driver efficiency >85%, Operating voltage AC 140-
270 Volt, freq 50/60 hz, Operating temp range -15 deg to 40 deg
centigrade, internal surge protection of 2.5 KV with Short & Open
circuit protection ,THD < 10% , P. F.≥0.95, IP20, CRI >80 , UGR (Unified
Glare Rating) < 19, Flicker free (flicker should be below 5 %), life time
(LED,Driver & electrical circuitry), life time of minimum 50000 Burning Hours
with , 70% of initial Lumen maintained till life ends , CCT 3000°K /
4000°K / 5700°K /6000°K/6500°K (As per ANSI Bin), SDCM(Standard
Deviation Color Matching) <3, Maximum power consumption should not
more than the specified rating and Fixture shall be of relevant BIS standard
and trade mark certificate ( T.C.). Manufactures Word Mark/ Name
Engraved/ Embossing/ Screen printing on housing. OEM must have its
own in house NABL lab setup for all testing facilities for LED fixtures.
complete in all respect i/c connections with 1.5 sq mm FRLS, PVC
insulated copper conductor single core cable and earthing etc. as required
with Minimum 5 year OEM warranty. System lumen efficacy ≥120 <135
lm/Watt output . LM79 & LM80 Test report from NABL lab for all testing
required for LED fixtures as per BIS shall be submitted. Shape size and
CCT shall be as approved by Engineer-in-Charge as per requirement.
(Thermal management: heat sink of aluminum housing such that LED
junction temperature shall not rise above 90°C).
Powder coated die cast /Extruded aluminium Body including trim with
Aluminium Reflector
Supply, Installation, testing & commissioning of LED Bulkhead
Luminaries, made of high-pressure die-cast Aluminium body with
polycarbonate diffuser. Luminaries should be with minimum system
efficacy of 110Lumen/Watt and minimum system lumen output of
1100lm.LED used shall have life of 50000Hrs @ L70B50, CCT of
6500°K, SDCM≤5 & CRI≥80. The luminaire driver shall comply to
following parameters at 220V to 240V: PF≥0.90 (@full load), THD ≤
NDSR-1.1 10% (@full load) & in-built surge protection of 2.5KV. The input Each 24.00 1,386.63 33,279.10
voltage range shall be 140V to 270V. The fixture should comply with
the parameters as per IS10322. The luminaire shall have class C
serviceability. The luminaire shall be IP66 & IK09 compliant. The
luminaire brand name shall be embossed/engraved on the
luminaire/accessory/Endplate & not screen printed or put using
sticker. Luminaire manufacturer must have In-house NABL
accredited lab to conduct LM79 as per 2019 Standard, Type test as
Digitally signed by VARUN
ADMIN CUM ACADEMIC BLOCK COLLEGE OF HORTICULTURE, MORENA
As Per DSR AS PER MARKET RATE
S.NO DSR ITEMS DESCRIPTION OF ITEM UNIT
Rate DSR 2025 AMOUNT (RS.) RATE (RS.) AMOUNT (RS.)
4 DSR2025-9.2 Brush Less Direct Current (BLDC) Motor
Supply, Installation, Testing and Commissioning of ceiling fan with Brush
Less Direct Current (BLDC) Motor, class of insulation: B, 3 nos. metal
( Aluminum alloy) blades, 30 cm long down rod, 2 nos. canopies, shackle kit,
safety rope, copper winding, steel/Al body Power Factor not less than 0.9,
Service Value (CM/M/W) minimum as below, 350 RPM (tolerance as per IS :
374-2019), THD (Total Harmonic Distortion) less than 10%, suitable for
operation with regulator for speed control and all remaining accessories
including safety pin, nut bolts, washers, temperature rise=75 degree C
(max.), insulation resistance more than 2 mega ohm, suitable for 230 V, 50
Hz, single phase AC Ceiling Fan compliant to IS 374:2019 fan Supply,
earthing etc. complete as req
Brush Less Direct Current (BLDC) Motor, 1200mm, service value ≥
6.0 CM/Min/Watt, air delivery 210 CM/Min
5 Supply installation testing and comissioning 4ft LED (Light Emitting
Diode) tube light system power: 20W, luminous flux of luminaire
NDSR-1.2 2000lm or more, colour temperature of min 5700K , CRI>80, 230V Each 2 1145 2,289.04
constant current driver, luminaire profile powder coated in white.
Protection class I, L = 1175 mm (min),
6 Supply installation testing and comissioning LED Tube, Wall /
Surface / Celling Mounted, 10W(MIRROR LIGHT), luminous flux
of luminaire 900lm, IP 20,1200mm, Direct light emission, 230V,
NDSR-1.3 Electronic Control Gear, 5700K, Satin Diffuser, L=600mm (Min) Each 98 1321 129,418.70
7 DSR2025-8.7 LED Panel light 2x2 ft. (System lumen efficacy ≥120 <135 lm/Watt)
Supplying, installation, Testing & Commissioning of Panel light 2x2 ft., of
following body material and construction as per IS : 10322 with driver as per
the requirement with Driver efficiency >85%, Operating voltage AC 140-
270 Volt, freq 50/60 hz, Operating temp range -15 deg to 40 deg
centigrade, internal surge protection of 2.5 KV with Short & Open circuit
protection ,THD < 10% , P. F.≥0.95, IP20, CRI >80, UGR (Unified Glare
Rating) < 19, Flicker free, (flicker should be below 5 %), life time
(LED,Driver & electrical circuitry), of minimum 50000 Burning Hours with ,
70% of initial Lumen maintained till life ends,CCT 3000°K / 4000°K
/ 5700°K /6000°K/6500°K (As per ANSI Bin), SDCM(Standard
Deviation Color Matching) <3, Maximum power consumption should not
more than the specified rating and Fixture shall be of relevant BIS standard
and trade mark certificate ( T.C.). Manufactures Word Mark/ Name
Engraved/ Embossing/ Screen printing on housing. complete in all respect
i/c connections with 1.5 sq mm FRLS, PVC insulated copper conductor
single core cable and earthing etc. as required with Minimum 5 year OEM
warranty. System lumen efficacy ≥120 <135 lm/Watt output . LM79 & LM80
Test report from NABL lab for all testing required for LED fixtures as
per BIS shall be submitted. Shape size and CCT shall be as approved by
Engineer-in-Charge as per requirement. (Thermal management: heat sink
Digitally signed by VARUN
ADMIN CUM ACADEMIC BLOCK COLLEGE OF HORTICULTURE, MORENA
As Per DSR AS PER MARKET RATE
S.NO DSR ITEMS DESCRIPTION OF ITEM UNIT
Rate DSR 2025 AMOUNT (RS.) RATE (RS.) AMOUNT (RS.)
of aluminium housing such that LED junction temperature shall not rise
Powder coated die cast / Extruded aluminium Body (Thickness
LED Panel light 2x2 ft. (System lumen efficacy ≥120 <135
lm/Watt), 36 Watt
8 NDSR-1.4 SITC Fresh air exhaust fan with louvers 300 mm sweep Each 44 2,201.00 96,843.93
9 NDSR-1.5 SITC of wall fan Each 2 2,509.14 5,018.28
10 Supplying of MS Body Exhaust Fan heavy duty 230V A.C 50 cycles,
600 mm sweep, 900 rpm, energy efficient, complete erected in
NDSR-1.6 position with 16A 3 Pin Plug Top in the existing opening, including Each 4 13,205.99 52,823.96
making good the damage, connection, testing, commissioning etc. as
NDSR -1.7 SITC of Warm fight focus light, not less than 60W Each 10 5,135.66 51,356.63
LIGHT FIXTURES: to summary sheet 2,167,989.00 371,029.63
SUB HEAD - IV : LIGHTNING PROTECTION SYSTEM
1 Providing and fixing of lightning conductor finial, made of 25mm dia
300mm long, copper tube, having single prong at top, with 85mm dia
6 mm thick copper base plate including holes etc. complete as
2 Jointing copper / G.I. tape (with another copper/ G I tape, base of the
6.3 finial or any other metallic object) by riveting / nut bolting/ sweating Each 250.00 139.00 34,750.00
and soldering etc as required.
3 Providing and fixing GI tape 20mm x 3mm thick on parapet or
6.6 surface of wall for lightning conductor as required. (for horizontal Metre 550.00 148.00 81,400.00
6.7 Providing and fixing G.I. tape 20mm x 3mm thick on parapet or Metre 450.00 238.00 107,100.00
surface of wall for lightning conductor as required. (For vertical run.)
5 Providing and fixing testing joint, made of 20mm x 3mm thick G.I.
6.10 strip, 125mm long with 4 Nos. of G.I. bolts, nuts, check nuts and Each 20.0 140.00 2,800.00
spring washers etc. complete as required.
6 Providing and laying G.I. tape, 32mm x 6mm thick, from earth
electrode directly in ground as required.
Digitally signed by VARUN
ADMIN CUM ACADEMIC BLOCK COLLEGE OF HORTICULTURE, MORENA
As Per DSR AS PER MARKET RATE
S.NO DSR ITEMS DESCRIPTION OF ITEM UNIT
Rate DSR 2025 AMOUNT (RS.) RATE (RS.) AMOUNT (RS.)
7 Earthing with G.I. earth pipe 4.5 metre long, 40mm dia including
accessories, and providing masonry enclosure with cover plate having
locking arrangement etc. with charcoal or coke and salt complete as
Total of Sub-Head - IV 413490 0.00
SUB HEAD - V: UPS
26.2 Online UPS- Input supply: Three Phase, Output supply: Three
Supplying, installation, Testing & Commissioning of of following
full load (Unity Power Factor) at operating temperature 0 to 40 deg C,
Relative humidity 0 to 95%, Online double conversion true sine wave
Uninterrupted hot swappable (allow for the replacement or addition of
battery modules without shutting down the entire system) modular
Supply (UPS) system with N+1 modules (N denotes total number of
requird for rated capacity). The UPS shall include a Rectifier, inverter,
battery bank suitable for 30 minutes back up (Battery VAH capacity
be less than 1600 VAH per KVA of UPS rating per Hour backup
load (Battery shall be VRLA, SMF in ABS Container) and Static
switch alongwith provision for manual bypass, suitable isolation
for additional protection against neutral faults etc. UPS shall have
phase sequence correction. The UPS systems offered are to be of the
technology with Digital Control Microprocessor based for reliable
using Insulated Gate Bipolar Transistor (IGBT)'s both for the rectifier
inverter (3 Level) with PWM (Pulse Width Modulation). The quality
manufacturing and inspection process should confirm to the relevant
standards such as IEC/EN/VDE. The operating efficiency of the
UPS systems shall be >96% while operating on battery mode and
quality power to the 100% non-linear loads. Current total harmonic
effect(ITHD) on the input grid shall be < 5% at 50 %load. (The
inductor (L) and a capacitor (C)) filters shall be included in UPS cost),
extreme power factor kit to be included to limit the input power factor
0.99 and output power factor shall be unity (i.e. kw rating of the UPS
kva rating x 1 ), however UPS shall be suitable to take load at 0.7
leading power factor loads. UPS shall be suitable for incoming supply
3Phase 400V +/-20%, 50 Hz +/-5 Hz, AC Output voltage: 3Phase
50 Hz +/- 0.2Hz, Overload capacity of 120% for 10 mins, Sine wave
Non condensing, noise level less than 60db at 1 meter distance,
Input Under voltage over voltage, abnormal out voltage, battery over
charging, output over current, short circuit protection, battery deep
discharge protection, 10KV surge. UPS must comply with low voltage
electromagnetic compatibility (EMC) achieved as per EN 6204,
I and Part 2, it shall be a Voltage and Frequency Independent (VFI)-
UPS. Communication RS232/RS485/SNMP port open protocol for
integration, all hardware & software for iOT Communication as per
by Engineering in charge. Required battery racks and interconnecting
copper conductor cables of suitable size and connectors and all
accoseries are inclusive of the cost). This system must provide a
logging and alarming of all monitored points plus email notification.
air-cooling with integral inbuilt fans with redundancy (if one fan fail
should be able to handle at least 80% of the load, Noise Level 65 DB
meter distance. The system shall be in compliance IEC 62040- 1,2 &
16242 and CPWD Specification. Display Panel (minimum) (In-build
Digitally signed by VARUN
ADMIN CUM ACADEMIC BLOCK COLLEGE OF HORTICULTURE, MORENA
As Per DSR AS PER MARKET RATE
S.NO DSR ITEMS DESCRIPTION OF ITEM UNIT
Rate DSR 2025 AMOUNT (RS.) RATE (RS.) AMOUNT (RS.)
more LC Display / LED ) to display : a) Input: Voltage, current,
Bypass: Voltage, Frequency. c) Output: Voltage, frequency, Current.
d) Battery: Voltage, Capacity. e) Load: KVA, KW, Percentage.
f)Temperature: STS, Inverter, PFC. g) Event Logging & Statistical
LCD/LED): UPS should capture and display up to 3000 events like:
temperature / DC Bus Fail / Fan Fail / Fuse Fail / Overload / Short-
Device Fail / Inverter Fail / Rectifier Fail / Bypass Fail, etc. h)
No. of power failures / Transfers to Bypass / Total Running time, etc.
Mode of Operation /Battery Mode of Operation / Bypass feeding the
UPS Fault /Battery charging and discharging, overload, battery
battery capacity. j) Audible Alarms : Mains Failure, Battery Low
Overload, Fault, Shutdown, Input Over, Under Voltage, Output Over,
Voltage, Battery Over, Under Voltage, Over Load and short circuit,
Temperature. The UPS should have QR code which should contain
drawing, test report OEM manual,Geo- Tag of manufacturing
26.2.5 60KVA (Each Power module shall be < =10 KVA) Each 1 913,600.00 913,600.00
Total of Sub-Head - V 913,600.00 0.00
SUB HEAD -VI : RACEWAY AND CABLE TRAY
1 Metal Partition Raceways : Floors
Supply and fixing in position of following size of under floor GI
raceways [consists of body & cover] for distributing cabling in
screed floor installations. Raceway should be made up of Pre
galvanized sheet conforming to IS 277 with thickness of
1.6mm consists of Body and Openable cover with 275 GSM
coating. Raceway should be supplied with required
accessories such as fixing brackets and coupling plates as
required. Raceway should be confirmed with the standard EN
60-670 and EN 50085-2-2, IP 20 & IK08 in recess / on surface
including chasing the wall/floor complete as required of
following configurations:
Partition Metal Junction Box : Floors
Supply and fixing in position height adjustable under floor
crossover Junction box for Raceways for direct access to
cables at the intersection of Raceways supplied completely
with base and cover plate [lid]. Junction box should be made
of Pre galvanized sheet consist of body and cover. Height of
the junction box should be adjustable from minimum 65mm.
Junction box should be supplied with the metal cover for
protecting the junction box during constructions at site. It
should be confirmed with the standard EN 50085-2-2 including
all accessories complete as required of following sizes:
Digitally signed by VARUN
ADMIN CUM ACADEMIC BLOCK COLLEGE OF HORTICULTURE, MORENA
As Per DSR AS PER MARKET RATE
S.NO DSR ITEMS DESCRIPTION OF ITEM UNIT
Rate DSR 2025 AMOUNT (RS.) RATE (RS.) AMOUNT (RS.)
NDSR-10 Box : 400 x 400 x 65-90mm [1mm base & 3mm lid] Nos 1,556.84 0.00
Cover Plate : 400 x 400mm
Cover Plate : 300 x 300mm
NDSR-12 Box : 225 x 225 x 65-90mm [1mm base & 3mm lid] Nos 45 983.11 44,240.07
Cover Plate : 225 x 225mm
NDSR-13 Box : 150 x 150 x 65-90mm [1mm base & 3mm lid] Nos 80 783.56 62,684.43
Cover Plate : 150 x 150mm
3.0 Cable Tray
3.1 4.1 Supplying and installing following size of perforated pre-
painted M.S cable trays with perforation not more than 17.5%,
inconvenient sections, joined with connectors, suspended from
the ceiling with M.S. suspenders including bolts&nuts, painting
suspenders etc as required.
a 4.1.1 100 mm width X 50 mm depth X 1.6mm thickness Meter 350 623.00 218,050.00
b 4.1.2 150 mm width X 50 mm depth X 1.6mm thickness Meter 200 686.00 137,200.00
c 4.1.4 300 mm width X 50 mm depth X 1.6mm thickness Meter 100 866.00 86,600.00
3.2 4.2 Supplying and installing following size of perforated pre-
painted M.S cable trays bends with perforation not more than
17.5%, inconvenient sections, joined with connectors,
suspended from the ceiling with M.S. suspenders including
bolts&nuts, painting suspenders etc as required.
a 4.2.1 100 mm width X 50 mm depth X 1.6mm thickness Each 20 948.00 18,960.00
b 4.2.2 150 mm width X 50 mm depth X 1.6mm thickness Each 20 1,105.00 22,100.00
c 4.2.4 300 mm width X 50 mm depth X 1.6mm thickness Each 5 1,544.00 7,720.00
3.3 4.3 Supplying and installing following size of perforated pre-
painted M.S cable trays reducers with perforation not more
than 17.5%, inconvenient sections, joined with connectors,
suspended from the ceiling with M.S. suspenders including
bolts&nuts, painting suspenders etc as required.
a 4.3.1 100 mm width X 50 mm depth X 1.6mm thickness Each 15 1,089.00 16,335.00
b 4.3.2 150 mm width X 50 mm depth X 1.6mm thickness Each 10 1,281.00 12,810.00
c 4.3.4 300 mm width X 50 mm depth X 1.6mm thickness Each 5 1,826.00 9,130.00
Digitally signed by VARUN
ADMIN CUM ACADEMIC BLOCK COLLEGE OF HORTICULTURE, MORENA
As Per DSR AS PER MARKET RATE
S.NO DSR ITEMS DESCRIPTION OF ITEM UNIT
Rate DSR 2025 AMOUNT (RS.) RATE (RS.) AMOUNT (RS.)
3.4 4.4 Supplying and installing following size of perforated pre-
painted M.S cable trays Tee's with perforation not more than
a 4.4.1 100 mm width X 50 mm depth X 1.6mm thickness Each 5 1,231.00 6,155.00
b 4.4.2 150 mm width X 50 mm depth X 1.6mm thickness Each 5 1,498.00 7,490.00
c 4.4.4 300 mm width X 50 mm depth X 1.6mm thickness Each 2 2,110.00 4,220.00
3.5 4.5 Supplying and installing following size of perforated pre-
painted M.S cable trays Cross members with perforation not
more than 17.5%, inconvenient sections, joined with
connectors, suspended from the ceiling with M.S. suspenders
including bolts&nuts, painting suspenders etc as required.
a 4.5.1 100 mm width X 50 mm depth X 1.6mm thickness Each 50 1,089.00 54,450.00
b 4.5.2 150 mm width X 50 mm depth X 1.6mm thickness Each 30 1,281.00 38,430.00
c 4.5.4 300 mm width X 50 mm depth X 1.6mm thickness Each 20 1,876.00 37,520.00
Total of Sub-Head - VI 677,170.00 1,567,250.23
SUB HEAD-VII : LIFT
1 21.1 Passenger Lift
Supplying, Installation, Testing & Commissioning of
following capacity passenger Machine room less
(MRL) lift with regenerative drive as per CPWD
General Specification for Electrical Works (Part-III Lift
& Escalator) 2003, BIS Codes, NBC 2016 as
amended upto date having provision for barrier free
access as per Harmonised Guidelines & Standards for
Universal Accessibility in India - 2021 of MoHUA,
serving different floors in the lift shaft as per detailed
specifications enclosed and as under including all
other equipment and accessories complete as
(i) Speed-1 MPS
(ii) Floors-5 (G+4)
(iii) Travel -17 Meters (approx.)
(iv) Stops & opening- 5 stops and 5 openings
(v) Controller: A.C. variable voltage & variable
(vi) Automatic rescue device (ARD) complete with dry
maintenance free batteries as required.
vii) Operation: Microprocessor based single automatic
push button/simplex selective collective/duplex
collective selective with/without attendant
(viii) Power-415 Volts+10%, 3 phase, 50 Hz, 4 wires
(ix) Car Enclosure: Stainless steel scratch proof
Digitally signed by VARUN
ADMIN CUM ACADEMIC BLOCK COLLEGE OF HORTICULTURE, MORENA
As Per DSR AS PER MARKET RATE
S.NO DSR ITEMS DESCRIPTION OF ITEM UNIT
Rate DSR 2025 AMOUNT (RS.) RATE (RS.) AMOUNT (RS.)
(Moon Rock/Honeycomb/ Hairline Finish) on all sides
and stainless steel decorative ceiling with fans (indirect
throw) and LED fitting.
(x) The car flooring should be smooth and antiskid as
approved by engineer-in-charge.
(xi) Type of doors
(a) Car: Power operated, centre opening horizontal
sliding stainless steel scratch proof (Moon
Rock/Honeycomb/ Hairline Finish).
(b) Landing doors: stainless steel scratch proof .
(xii) A hand rail not less that 600mm long at 900mm
above floor level to be fixed adjacent to control panel
in the lift car.
(xiii)Voice announcement system in the car to
announce the position of the elevator in the hoist
way as the car passes or stops at floor served by the
(xiv) Closed loop Control System, protection against
power fluctuation, self diagnostic control, Landing
doors 2 hours Fire rated, Overload detection and
protection, Overspeed Governer, Dot Matrix LED D &
P Indicators In Car & Landings, BMS Compatibility,
tamper proof infrared curtain covering almost the entire
height of the lift car door, Alarm horn, Anti Nuisance
Operation, CCTV camera system with 4 MP IP
camera, suitable NVR and HDD for 30 days storage
backup , Firemen switch, 2/3 way intercom,
Emergency Stop Switch with battery backup for fan
and light fitting for 1 hour, pit ladder.
(xv) The lift doors shall have a vision panel to enable
persons with hearing impairment to
signal for help or assistance in the event of an
(xvi) An appropriate technological support be provided
emergency messaging |services or alarms etc.) to
respond to the emergency requirements of person with
hearing impairment or deafness.
(xvii) In case of failure of ARD or other electronic
devices, a provision of manual rescue be provided
Total of Sub-Head 3368451 0
SUB HEAD-VIII : SOLAR
17.1 Supplying Installation, Testing and Commissioning of
on-grid Solar Photovoltaic Power Plant conforming to
various applicable standards BIS, IEC, MNRE
Digitally signed by VARUN
ADMIN CUM ACADEMIC BLOCK COLLEGE OF HORTICULTURE, MORENA
As Per DSR AS PER MARKET RATE
S.NO DSR ITEMS DESCRIPTION OF ITEM UNIT
Rate DSR 2025 AMOUNT (RS.) RATE (RS.) AMOUNT (RS.)
guidelines, the Central Electricity Authority
Regulations and CPWD Specifications as amended up
to date, consisting of Mono/Poly Crystalline silicon
solar cells module, net metering facility, necessary
control, protections, earthing, cabling, mounting
structure, junction boxes, power conditioning units,
Real time online web interfaced Data Monitoring
System, Distribution panels, grid connecting
arrangement, conduits, pipes, cable trays and other
accessories etc. as required.
a) High Energy Efficiency Solar Photovoltaic Module of
capacity 330 Wp or above, manufactured in India,
conforming to IS 14286/IEC 61215, IS/IEC 61730-
Part-1, IS/IEC 61730-Part-2. Solar Photovoltaic
Module conversion efficiency shall not be less than
23% at STC with temperature coefficient of Pmax
better than -0.30% per 0C. PV modules used in solar
power plants/ systems must be warranted for their
output peak watt capacity, which should not be less
than 90% at the end of 10 years and 80% at the end of
25 years. Solar Modules shall be designed to operate
in relative humidity upto 100% with temperature
between -10 0C and +85 0C. Further, each PV module
used in any solar power project must have Radio
frequency identification tag with information such as
name of manufacturer, month and year of
manufacturing, country of origin (separately for Solar
cell and module), I-V curve, Unique Serial No and
Model No of the module, Wattage, Im, Vm and FF,
name of test lab issuing IEC certificate.
b)Power Conditioning Unit (PCU) of 350-800 V DC
Input voltage range and 415 V AC, three phase, 4
wire, 50Hz +/- 2.5 Hz, output voltage suitable to
generate AC with a variation of 10% at nominal
voltage. Power with efficiency not less than 97%, total
harmonic distortion less than 3% and suitable for
ambient temperature from 0 to 50 0C, Minimum IP-65
for outdoor and Minimum IP 21 for indoor, Built-in
meter and data logger, MPPT, switching devices
IGBT/MOSFETs and controller Microprocessor /DSP.
PCU/inverter shall be capable of complete automatic
operation including wake-up, synchronization &
shutdown. The PCU shall be able to withstand
unbalanced load conforming to IEC standard with
shutdown/standby mode. It must be provided with grid
islanding along with manual disconnect pole isolation
switch besides automatic disconnection. Minimum
protections: Mains Under / Over Voltage, Over current,
Over/Under grid frequency, Over temperature, Surge
voltage induced at output due to external source,
Digitally signed by VARUN
ADMIN CUM ACADEMIC BLOCK COLLEGE OF HORTICULTURE, MORENA
As Per DSR AS PER MARKET RATE
S.NO DSR ITEMS DESCRIPTION OF ITEM UNIT
Rate DSR 2025 AMOUNT (RS.) RATE (RS.) AMOUNT (RS.)
Short-circuit, Lightening, Anti Islanding (for grid synch.
Mode) and other protections as per applicable
standards. LCD/LED display of minimum parameters:
DC input voltage, DC current, AC Voltage and current
(all 3 phases, in case of 3 phase), Instantaneous &
cumulative AC output power, Daily DC energy
produced and other parameters applicable standard.
Communication interface RS 485 / RS 232.
c) Module mounting structure: The roof top solar plant
generation units shall be installed by using supporting
Aluminium/Galvanized MS structure (mass of zinc
coating shall be as per IS4759 ) having minimum head
room clearance of 2.4 meter above the terrace level /
ground level. The mounting structure would be
designed to sustain wind load and seismic parameter
of the site of installation. All the structure shall be
design as per applicable BIS code and the material
shall also confirm the applicable BIS Code. Structural
material shall be corrosion resistant and electrolytically
compatible with the materials used in the module
frame, its fasteners, nuts and bolts. The suitable
arrangements for maintenance and cleaning shall be
d) Real time online web interfaced Data Monitoring
System complete with accessories for various
parameters such as Solar Irradiance, temperature, AC
Output Voltage and current, Output Power, Power
factor, DC Input Voltage and Current, Time Active,
Time disabled, Time Idle, Power produced and other
parameters as per standard practices.
e) Array junction box & Main junction box with IP 65
protection and termination arrangement for incoming
and outgoing cable along with glands, lugs and other
accessories etc. as required. Each junction box shall
be made of GRP/FRP/Powder Coated Aluminium /cast
aluminium alloy with full dust, water & vermin proof
arrangement with High quality Suitable capacity Metal
Oxide Varistors(MOVs) (semiconductor diode with
resistant applied voltage)/ surge arrestors and suitable
Reverse Blocking Diodes, isolation switches isolate
the DC input to Inverter, copper bus bar etc.
f) Lightning, surge voltage protection, earthing
protection and grid islanding.
g) Cables: Connections & Interconnections by
required size IR/UV protected XLPE insulated copper
conductor 1.1 kV grade armored power and control
cables(ISI Marked) along with supplying & fixing of
necessary channel/conduit, GI cable trays, supports,
lugs, thimble and other accessories etc. as required.
h) DC Distribution Board And AC Distribution Panel
Digitally signed by VARUN
ADMIN CUM ACADEMIC BLOCK COLLEGE OF HORTICULTURE, MORENA
As Per DSR AS PER MARKET RATE
S.NO DSR ITEMS DESCRIPTION OF ITEM UNIT
Rate DSR 2025 AMOUNT (RS.) RATE (RS.) AMOUNT (RS.)
Board: IP65, free standing, metal cladded, having
copper bus bar, having required protection and control
gears, connection-interconnection, etc. as required.
Total of Sub-Head 2171200 0
SUB HEAD-IX : Panels
NDSR-14 LIFT PANEL
LIFT PANEL FOR ADMIN BUILDING
1 No. 100amps 4P MCCB(16KA) with thermal Magnetic release
(PRTM) with Class-C transient voltage surge suppression device
suitable for 3 phases as per specifications.
1 No.100 amps ATS
METERING & INDICATION for each Incomer
1 set of R,Y,B phase indicating lamps
Multifunction digital meter (consisting of Voltage, Current,
Frequency, PF, kWh, kVA, harmonics upto 15th order & %THD)
with RS-485 Port.
Sets of 100/5A, CL-1, 15VA CTs for measuring.
Sets of phase indicating lamp with 2A control MCBs.
150 A TPN Aluminium Bus Bar with colour coded PVC Sleeves
3 Nos. 63 Amp TP MPCB
3 Nos. 63 Amp TP MCB
1 Nos.40 Amp DP MCB
Lift Panel admin building as described above Set 1 165,074.88 165,074.88
NDSR-15 MAIN BUILDING PANEL FOR ADMIN BUILDING
1 No. 500amps 4P MCCB(25KA) with thermal Magnetic release
(PRTM) with Class-C transient voltage surge suppression device
suitable for 3 phases as per specifications.
METERING & INDICATION for each Incomer
1 set of R,Y,B phase indicating lamps
Multifunction digital meter (consisting of Voltage, Current,
Frequency, PF, kWh, kVA, harmonics upto 15th order & %THD)
with RS-485 Port.
Sets of 500/5A, CL-1, 15VA CTs for measuring.
Sets of phase indicating lamp with 2A control MCBs.
630A TPN Aluminium Bus Bar with colour coded PVC Sleeves
Digitally signed by VARUN
ADMIN CUM ACADEMIC BLOCK COLLEGE OF HORTICULTURE, MORENA
As Per DSR AS PER MARKET RATE
S.NO DSR ITEMS DESCRIPTION OF ITEM UNIT
Rate DSR 2025 AMOUNT (RS.) RATE (RS.) AMOUNT (RS.)
8 No. 100amps 4P MCCB
3No. 63amps 4P MCCB
1 No. 40amps 4P MCB
MAIN PANEL DESCRIVED ABOVE Set 1 469,913.15 469,913.15
NDSR-16 ADMIN BUILDING GROUND FLOOR PANEL
1 No. 100amps 4P ACB(16KA) with thermal Magnetic release
(PRTM) with Class-C transient voltage surge suppression device
suitable for 3 phases as per specifications.
METERING & INDICATION for each Incomer
1 set of R,Y,B phase indicating lamps
Multifunction digital meter (consisting of Voltage, Current,
Frequency, PF, kWh, kVA, harmonics upto 15th order & %THD)
with RS-485 Port.
Sets of 100/5A, CL-1, 15VA CTs for measuring.
Sets of phase indicating lamp with 2A control MCBs.
125A TPN Aluminium Bus Bar with colour coded PVC Sleeves
3 No. 63amps 4P MCB
3 No. 40amps 4P MCB
14 No. 32amps DP MCB
ADMIN BUILDING GROUND FLOOR PANEL DESCRIVED
NDSR-17 ADMIN BUILDING FIRST FLOOR PANEL
1 No. 100amps 4P MCCB(25KA) with thermal Magnetic release
(PRTM) with Class-C transient voltage surge suppression device
suitable for 3 phases as per specifications.
1 No.100amps ATS
METERING & INDICATION for each Incomer
1 set of R,Y,B phase indicating lamps
Multifunction digital meter (consisting of Voltage, Current,
Frequency, PF, kWh, kVA, harmonics upto 15th order & %THD)
with RS-485 Port.
Sets of 100/5A, CL-1, 15VA CTs for measuring.
Sets of phase indicating lamp with 2A control MCBs.
125A TPN Aluminium Bus Bar with colour coded PVC Sleeves
3 No. 63amps 4P MCB
3 No. 40amps 4P MCB
14 No. 32amps DP MCB
Digitally signed by VARUN
ADMIN CUM ACADEMIC BLOCK COLLEGE OF HORTICULTURE, MORENA
As Per DSR AS PER MARKET RATE
S.NO DSR ITEMS DESCRIPTION OF ITEM UNIT
Rate DSR 2025 AMOUNT (RS.) RATE (RS.) AMOUNT (RS.)
ADMIN BUILDING FIRST FLOOR PANEL DESCRIVED
NDSR-18 ADMIN BUILDING SECOND FLOOR PANEL
1 No. 100amps 4P ACB(16KA) with thermal Magnetic release
(PRTM) with Class-C transient voltage surge suppression device
suitable for 3 phases as per specifications.
METERING & INDICATION for each Incomer
1 set of R,Y,B phase indicating lamps
Multifunction digital meter (consisting of Voltage, Current,
Frequency, PF, kWh, kVA, harmonics upto 15th order & %THD)
with RS-485 Port.
Sets of 100/5A, CL-1, 15VA CTs for measuring.
Sets of phase indicating lamp with 2A control MCBs.
125A TPN Aluminium Bus Bar with colour coded PVC Sleeves
2 No. 63amps 4P MCB
3 No. 40amps 4P MCB
3 No. 32amps DP MCB
ADMIN BUILDING SECOND FLOOR PANEL DESCRIVED
ADMIN BUILDING THIRD FLOOR PANEL/Raw Power Panel
1 No. 100amps 4P MCCB(16KA) with thermal Magnetic release
(PRTM) with Class-C transient voltage surge suppression device
suitable for 3 phases as per specifications.
1 No.100amps ATS
METERING & INDICATION for each Incomer
1 set of R,Y,B phase indicating lamps
Multifunction digital meter (consisting of Voltage, Current,
Frequency, PF, kWh, kVA, harmonics upto 15th order & %THD)
with RS-485 Port.
Sets of 100/5A, CL-1, 15VA CTs for measuring.
Sets of phase indicating lamp with 2A control MCBs.
125A TPN Aluminium Bus Bar with colour coded PVC Sleeves
6 No. 63amps 4P MCB
5 No. 40amps 4P MCB
MAIN BUILDING THIRD FLOOR PANEL DESCRIVED
Digitally signed by VARUN
ADMIN CUM ACADEMIC BLOCK COLLEGE OF HORTICULTURE, MORENA
As Per DSR AS PER MARKET RATE
S.NO DSR ITEMS DESCRIPTION OF ITEM UNIT
Rate DSR 2025 AMOUNT (RS.) RATE (RS.) AMOUNT (RS.)
NDSR-20 ADMIN BUILDING FOURTH FLOOR PANEL
1 No. 100amps 4P MCCB(16KA) with thermal Magnetic release
(PRTM) with Class-C transient voltage surge suppression device
suitable for 3 phases as per specifications.
1 No.100amps ATS
METERING & INDICATION for each Incomer
1 set of R,Y,B phase indicating lamps
Multifunction digital meter (consisting of Voltage, Current,
Frequency, PF, kWh, kVA, harmonics upto 15th order & %THD)
with RS-485 Port.
Sets of 100/5A, CL-1, 15VA CTs for measuring.
Sets of phase indicating lamp with 2A control MCBs.
125A TPN Aluminium Bus Bar with colour coded PVC Sleeves
2 No. 63amps 4P MCB
2 No. 40amps 4P MCB
8 No. 32amps DP MCB
ADMIN BUILDING FOURTH FLOOR PANEL DESCRIVED
NDSR-21 HVAC MAIN PANEL ADMIN BUILDING
1 No. 500amps 4P MCCB(25KA) with thermal Magnetic release
(PRTM) with Class-C transient voltage surge suppression device
suitable for 3 phases as per specifications.
1 No.400amps ATS
METERING & INDICATION for each Incomer
1 set of R,Y,B phase indicating lamps
Multifunction digital meter (consisting of Voltage, Current,
Frequency, PF, kWh, kVA, harmonics upto 15th order & %THD)
with RS-485 Port.
Sets of 400/5A, CL-1, 15VA CTs for measuring.
Sets of phase indicating lamp with 2A control MCBs.
630A TPN Aluminium Bus Bar with colour coded PVC Sleeves
2 No. 200amps 4P MCCB
2 No. 125amps 4P MCCB
8 No. 100amps 4P MCCB
AHU MAIN PANEL DESCRIVED ABOVE Set 1 346,657.24 346,657.24
NDSR-22 VTPN DB ADMIN BUILDING
1 No.100amps 4P MCCB(25KA) with thermal Magnetic release
(PRTM) with Class-C transient voltage surge suppression device
suitable for 3 phases as per specifications.
Digitally signed by VARUN
ADMIN CUM ACADEMIC BLOCK COLLEGE OF HORTICULTURE, MORENA
As Per DSR AS PER MARKET RATE
S.NO DSR ITEMS DESCRIPTION OF ITEM UNIT
Rate DSR 2025 AMOUNT (RS.) RATE (RS.) AMOUNT (RS.)
1 No.100amps ATS
METERING & INDICATION for each Incomer
1 set of R,Y,B phase indicating lamps
Multifunction digital meter (consisting of Voltage, Current,
Frequency, PF, kWh, kVA, harmonics upto 15th order & %THD)
with RS-485 Port.
Sets of 100/5A, CL-1, 15VA CTs for measuring.
Sets of phase indicating lamp with 2A control MCBs.
125A TPN Aluminium Bus Bar with colour coded PVC Sleeves
7 No.32amps 4P MCB
AHU GR. FLOOR VTPN DB DESCRIVED ABOVE Set 5 55,024.96 275,124.80
NDSR-23 UPS PANEL
1 No. 125amps 4P MCCB(25KA) with thermal Magnetic release
(PRTM) with Class-C transient voltage surge suppression device
suitable for 3 phases as per specifications.
1 No.125amps ATS
METERING & INDICATION for each Incomer
1 set of R,Y,B phase indicating lamps
Multifunction digital meter (consisting of Voltage, Current,
Frequency, PF, kWh, kVA, harmonics upto 15th order & %THD)
with RS-485 Port.
Sets of 125/5A, CL-1, 15VA CTs for measuring.
Sets of phase indicating lamp with 2A control MCBs.
160A TPN Aluminium Bus Bar with colour coded PVC Sleeves
4 No.63amps 4P MCB
4 No.40amps 4P MCB
UPS PANEL DESCRIVED ABOVE Set 1 176,079.87 176,079.87
Subhead-IX Total 0.00 2,918,523.83
SUB HEAD X: Earthing
Earthing with G.I. earth pipe 4.5 metre long, 40 mm dia including Set
accessories, and providing masonry enclosure with cover plate having
locking arrangement and watering pipe etc. with charcoal/ coke and
salt as required.
5.4 Earthing with G.I. earth plate 600 mm X 600 mm X 6 mm thick Set 11
including accessories, and providing masonry enclosure with cover
plate having locking arrangement and watering pipe of 2.7 metre long
etc. with charcoal/ coke and salt as required.
Digitally signed by VARUN
ADMIN CUM ACADEMIC BLOCK COLLEGE OF HORTICULTURE, MORENA
As Per DSR AS PER MARKET RATE
S.NO DSR ITEMS DESCRIPTION OF ITEM UNIT
Rate DSR 2025 AMOUNT (RS.) RATE (RS.) AMOUNT (RS.)
5.6 Earthing with copper earth plate 600 mm X 600 mm X 3 mm thick Set 10
including accessories, and providing masonry enclosure with cover
plate having locking arrangement and watering pipe of 2.7 metre long
etc. with charcoal/ coke and salt as required.
5.7 Supplying and laying 6 SWG G.I. wire at 0.50 metre below ground Metre 100
level for conductor earth electrode, including connection/ termination 62.00 6,200.00
with GI thimble etc. as required.
5.10 Providing and fixing 25 mm X 5 mm copper strip in 40 mm dia G.I. Metre 100
pipe FRLSom earth electrode including connection with brass nut,
bolt, spring, washer excavation and re-filling etc. as required.
5.11 Providing and fixing 25 mm X 5 mm G.I. strip in 40 mm dia G.I. Metre 150
pipe from earth electrode including connection with G.I. nut, bolt,
spring, washer excavation and re-filling etc. as required.
5.12 Providing and laying earth connection from earth electrode with 6 Metre 150
SWG dia G.I. Wire in 15 mm dia G.I. pipe from earth electrode
including connection with G.I. thimble excavation and re-filling as
5.14 Providing and fixing 25 mm X 5 mm copper strip on surface or in Metre 200
recess for connections etc. as required.
5.15 Providing and fixing 25 mm X 5 mm G.I. strip on surface or in recess Metre 300
for connections etc. as required.
5.16 Providing and fixing 6 SWG dia G.I. wire on surface or in recess for Metre 130
loop earthing as required.
Sub Head X Total 1,007,691.00 0.00
Digitally signed by VARUN
ADMIN CUM ACADEMIC BLOCK COLLEGE OF HORTICULTURE, MORENA
Name of Project: Development of Administrative-cum-Academic Block for the College of Horticulture at
Morena (M.P.), under RLBCAU.
BUILDING NAME : ADMIN CUM ACADEMIC BUILDING
Detailed estimate of Internal & External Plumbing Services
S. No. Description
Amount (in Rs.)
1 SANITARY FIXTURES & FITTINGS ₹ 3,362,455.20 ₹ 3,597,170.00
2 INTERNAL & EXTERNAL WATER SUPPLY ₹ 2,110,335.00 ₹ 307,597.50
3 SOIL, WASTE, VENT PIPES, RAIN WATER PIPES & FITTINGS. ₹ 5,647.20 ₹ 1,440,782.70
4 EXTERNAL SEWERAGE AND STORM WATER DRAINAGE ₹ 22,508.50
Add: Impact of Multiplying factor on DSR 2023 ₹ 5,352,420.36
GRAND TOTAL (DSR +NSR) ₹ 10,697,970.56
GRAND TOTAL (DSR +NSR) ₹ 10,697,970.56
Digitally signed by VARUN
ADMIN CUM ACADEMIC BLOCK COLLEGE OF HORTICULTURE, MORENA
Name of Project: Development of Administrative-cum-Academic Block for the College of Horticulture at Morena (M.P.), under
BUILDING NAME : ADMIN CUM ACADEMIC BUILDING
Schedule Of Quantity
TOTAL DSR Amount (in MR Rate MR Amount
DSR 2023 Description Unit DSR Rate (in Rs.)
QUANTITY Rs.) (in Rs.) (in Rs.)
SANITARY FIXTURES & FITTINGS
Providing and fixing white vitreous china extended wall mounting water
closet of size 780x370x690mm of approved shape including providing and
17.78 fixing white vitreous china cistern with dual flushing fitting,of flushing Each 116 ₹ 14,999.15 ₹ 1,739,901.40
capacity 3 litre/6 litre( adjustable to 4 litre/8 litres),including seat cover
and cistern fittings,nuts,bolts and gasket etc. complete.
Providing and fixing wash basin with C.I. brackets, 15 mm dia CP Brass
single hole basin mixer of approved quality and make, including painting
of fittings and brackets, cutting and making good the walls wherever
a) White Vitreous China Wash basin size 630x450 mm with a 15 mm CP
Brass single hole basin mixer
Providing and fixing 8 mm dia C.P. / S.S. Jet with flexible tube upto 1
metre long with S.S. triangular plate to Eureopean type W.C. of quality and
make as approved by Engineer - in - charge.
Providing and fixing CP Brass 32mm size bottle trap of approved quality
& make and as per the direction of engineer in charge.
17.34 Providing and fixing toilet paper holder
Supply, Receiving, Storing & Fixing of C.P. brass twin coat hook with
PVC rawl plug & C.P. brass screw complete as required. Make :
Providing and fixing C.P. brass angle valve for basin mixer and geyser
18.53 points of approved quality conforming to IS:8931.
Providing and fixing unplasticised P.V.C. connection pipe with PTMT
18.74 Nuts, collar and bush of approved quality and colour.
Digitally signed by VARUN
ADMIN CUM ACADEMIC BLOCK COLLEGE OF HORTICULTURE, MORENA
TOTAL DSR Amount (in MR Rate MR Amount
DSR 2023 Description Unit DSR Rate (in Rs.)
QUANTITY Rs.) (in Rs.) (in Rs.)
18.74.2 15 mm nominal bore with 45 cm length Each 366 ₹ 121.90 ₹ 44,615.40
Providing and fixing Chromium Plated towel ring Rectangular shape with
concealed fittings arrangement of approved quality and colour, of
approved brand & manufacture complete as per direction of Engineer in
Providing and fixing Cp bras liquid soap container 109 mm wide, 125
mm high and 112 mm distance from wall of standard shape with bracket
of the same materials with snap fittings of approved quality and colour,
weighing not less than 105 gms.
Providing and fixing white vitreous china battery based infrared sensor
operated urinal of approx. size 610 x 390 x 370 mm having pre & post
flushing with water (250 ml & 500 ml consumption), having water inlet
from back side, including fixing to wall with suitable brackets all as per
manufacturers specification and direction of Engineer-in-charge.
Providing and fixing 75 mm high, 50 mm deep and 18 mm thick stone slab
table rubbed, edges rounded and polished, fixed in urinal partitions by
cutting a chase of appropriate width with chase cutter and embedding the
stone in the chase with epoxy grout or with cement concrete 1:2:4 (1
cement : 2 coarse sand : 4 graded stone aggregate 6 mm nominal size) as
per direction of Engineer-in-charge and finished smooth.
8.10.2 Granite Stone of approved shade Sqm 44 ₹ 4,051.85 ₹ 178,281.40
Supply and fixing of water cooler fully stainless steel of 60 litres cooling
capacity and 120 litres storage capacity to be operated on single phase
supply with ISI mark. Each Cooler shall be provide with 4 Nos pessmatic
tap for Drinking purpose.
Providing and fixing 600x450 mm beveled edge mirror of superior glass
17.31 (of approved quality) complete with 6 mm thick hard board ground fixed Each 98 ₹ 1,607.95 ₹ 157,579.10
to wooden cleats with C.P. brass screws and washers complete.
Providing and fixing C.P. brass long body bib cock of approved quality
conforming to IS standards and weighing not less than 690 gms.
Providing and fixing low flow type two way bib tap as per approved
make complete in all respect as per engineer in the charge.
TOTAL CARRIED OVER TO SUMMARY ₹ 3,362,455.20 ₹ 3,597,170.00
Digitally signed by VARUN
ADMIN CUM ACADEMIC BLOCK COLLEGE OF HORTICULTURE, MORENA
TOTAL DSR Amount (in MR Rate MR Amount
DSR 2023 Description Unit DSR Rate (in Rs.)
QUANTITY Rs.) (in Rs.) (in Rs.)
INTERNAL & EXTERNAL WATER SUPPLY
Providing and fixing Chlorinated Polyvinyl Chloride (CPVC) pipes,
having thermal stability for hot & cold water supply, including all CPVC
plain & brass threaded fittings, i/c fixing the pipe with clamps at 1.00 m
spacing. This includes jointing of pipes & fittings with one step CPVC
solvent cement and the cost of cutting chases and making good the same
including testing of joints complete as per direction of Engineer in Charge.
Concealed work, including cutting chases and making good the walls etc.
Providing and fixing Chlorinated Polyvinyl Chloride (CPVC) pipes,
having thermal stability for hot & cold water supply, including all CPVC
plain & brass threaded fittings, including fixing the pipe with clamps at
1.00 m spacing. This includes jointing of pipes & fittings with one step
CPVC solvent cement and testing of joints complete as per direction of
Engineer in Charge.
Internal work - Exposed on wall
Derived 65mm nominal bore Mtr. 103.5 ₹ 1,125.00 ₹ 116,437.50
Derived 80mm nominal bore Mtr. 23 ₹ 1,467.00 ₹ 33,741.00
Derived 100mm nominal bore Mtr. 23 ₹ 1,990.00 ₹ 45,770.00
Providing and fixing gun metal gate valve with C.I. wheel of approved
quality (screwed end) :
Providing and fixing ball valve (brass) of approved quality, High or low
pressure, with plastic floats complete :
Derrived 32 mm nominal bore Each 12 ₹ 2,297.00 ₹ 27,564.00
Derrived 40 mm nominal bore Each 6 ₹ 2,297.00 ₹ 13,782.00
Digitally signed by VARUN
ADMIN CUM ACADEMIC BLOCK COLLEGE OF HORTICULTURE, MORENA
TOTAL DSR Amount (in MR Rate MR Amount
DSR 2023 Description Unit DSR Rate (in Rs.)
QUANTITY Rs.) (in Rs.) (in Rs.)
Supplying, fixing, testing and commissioning of butterfly valve of PN 1.6
rating with bronze/gunmetal seat duly ISI marked complete with nuts,
bolts, washers, gaskets conforming to IS 13095 of following sizes as
Providing and fixing motorized valve with sensor of approved quality, to
complete the work.
a) 40 mm dia ( Flushing Riser) Each 1 ₹ 34,879.00 ₹ 34,879.00
b) 50 mm dia ( Domestic Riser) Each 1 ₹ 35,424.00 ₹ 35,424.00
Providing and placing on terrace (at all floor levels) polyethylene water
storage tank, IS : 12701 marked, with cover and suitable locking
arrangement and making necessary holes for inlet, outlet and overflow
pipes but without fittings and the base support for tank.
TOTAL CARRIED OVER TO SUMMARY ₹ 2,110,335.00 ₹ 307,597.50
Digitally signed by VARUN
ADMIN CUM ACADEMIC BLOCK COLLEGE OF HORTICULTURE, MORENA
TOTAL DSR Amount (in MR Rate MR Amount
DSR 2023 Description Unit DSR Rate (in Rs.)
QUANTITY Rs.) (in Rs.) (in Rs.)
SOIL, WASTE, VENT PIPES, RAIN WATER PIPES & FITTINGS.
Providing and fixing soil, waste and vent pipes
Supplying, Installation, Testing and Commissioning of uPVC pipes type -
B conforming to IS 13592 (1992) for soil, waste and vent pipes including
all fittings rubber ring type (plain or with access door) e.g. bends,
junctions, cowls, offsets, access pieces, jointing with rubber ring joints
with lubricant etc. fixed with clamps to walls with cement concrete 1:2:4
blocks complete in all respects. (For Soil & Waste Pipe)
Providing, laying, Jointing, Testing and commissioning of uPVC pressure
pipes of 6Kg/Sqcm pressure rating class 5 (IS : 4985-2000) including
fittings, tees, bends, clamps, coupling and adaptors supports, and jointing
with solvent joint, testing and necessary earth work in excavation,
backfilling, disposal of surplus earth with a lead upto 50m complete,
compaction and consolidation Including laying cement concrete 1:2:4
alround UPVC pipe including bed concrete and thrust blocks at bends as
per standard design (For Soil & Waste Pipe)
Supplying, Installation, Testing and Commissioning of uPVC, P or S trap
of self cleansing design with / without vent. arm Setting in cement
concrete 1:2:4 mix complete including cost of cutting & making good the
Wall / Floors wherever required.
Providing and fixing floor drain with jali size 110X50 size inlet and
MR-10 outlet including cutting and making good the walls and floors wherever
required complete in all respects.
Providing and fixing 125 mm dia, 3 mm thick Stainless steel grating
MR-11 with frame for floor traps or drains of required pattern including cutting
and making good the floors complete.
Digitally signed by VARUN
ADMIN CUM ACADEMIC BLOCK COLLEGE OF HORTICULTURE, MORENA
TOTAL DSR Amount (in MR Rate MR Amount
DSR 2023 Description Unit DSR Rate (in Rs.)
QUANTITY Rs.) (in Rs.) (in Rs.)
Providing and fixing cast brass Cleanout plug with suitable insert keys
for opening in brass cap, male threaded joint/reducer with G.I. socket
caulked to Pipe/fittings of CI pipe including cost of lead joints etc.
complete in all respect.
Making khurras 45x45 cm with average minimum thickness of 5 cm
cement concrete 1:2:4 (1 cement : 2 coarse sand : 4 graded stone aggregate
of 20 mm nominal size) over P.V.C. sheet 1 m x1 m x 400 micron, finished
with 12 mm cement plaster 1:3 (1 cement : 3 coarse sand) and a coat of
neat cement, rounding the edges and making and finishing the outlet
complete.450 X 450mm -
Providing and fixing on wall face unplasticised Rigid PVC rain water
pipes conforming to IS : 13592 Type A, including jointing with seal ring
conforming to IS : 5382, leaving 10 mm gap for thermal expansion, (i)
Single socketed pipes.
Derived 160 mm diameter (with all fittings) Metre 324.3 ₹ 1,350.00 ₹ 437,805.00
Providing and fixing to the inlet mouth of rain water pipe cast iron grating
15 cm diameter and weighing not less than 440 grams.
TOTAL CARRIED OVER TO SUMMARY ₹ 5,647.20 ₹ 1,440,782.70
EXTERNAL SEWERAGE AND STORM WATER DRAINAGE
Making connection of drain or sewer line with existing manhole
including breaking into and making good the walls, floors with cement
concrete 1:2:4 mix (1 cement : 2 coarse sand : 4 graded stone aggregate 20
mm nominal size) cement plastered on both sides with cement mortar 1:3
(1 cement : 3 coarse sand), finished with a floating coat of neat cement and
making necessary channels for the drain etc. complete :
19.21.2 For pipes 250 to 300 mm diameter Each 10 ₹ 922.40 ₹ 9,224.00
19.21.3 For pipes 350 to 450 mm diameter Each 10 ₹ 1,328.45 ₹ 13,284.50
TOTAL CARRIED TO SUMMARY ₹ 22,508.50
Digitally signed by VARUN
NATIONAL LAW UNIVERSITY AT DWARKA
Project Name:-NEW CAMPUS OF COLLEGE OF HORTICULTURE AT MORENA
SUB HEAD DESCRIPTION AMOUNT DSR AMOUNT NDSR
SUB HEAD -1.0 PIPING, HYDRANT , SPRINKLER AND ACCESSORIES SYSTEM FOR
B SUB HEAD-2.0 FIRE FIGHTING PUMPS ₹ 1,075,869.00 ₹ 0.00
GRAND TOTAL FOR DSR AND NON DSR ₹ 7,582,877.13
GRAND TOTAL FOR DSR AND NON DSR ₹ 7,582,877.13
Digitally signed byFighting
NATIONAL LAW UNIVERSITY AT DWARKA
Project Name:-NEW CAMPUS OF COLLEGE OF HORTICULTURE AT MORENA
FIRE FIGHTING ESTIMATE
ITEM CODE NO. DSR 2025 FF
S.NO. DESCRIPTION OF ITEMS TOTAL QUANTITY UNIT
WORKS DSR 2025 NDSR DSR NDSR
A. SUB HEAD -1.0 PIPING, HYDRANT , SPRINKLER AND ACCESSORIES
SYSTEM FOR BUILDINGS
1 27.6 Providing Laying Testing and Commissioning of C class Heavy duty MS
Pipe Conforming to IS : 1239 / 3589 including Fittings like elbows , tees ,
flanges , tapers , nuts , bolts , gaskets etc in ground including welding
excavation and Providing cement concrete blocks as supports
anticorrosive treatment with coaltar / asphalts tape as per IS :10221
refilling the trench etc of following sizes complete as required .
2 27.7 Providing Laying Testing and Commissioning of C class Heavy duty MS
Pipe Conforming to IS : 1239 / 3589 including Fittings like elbows , tees ,
flanges , tapers , nuts , bolts , gaskets etc and fixing the pipe on the wall /
ceiling with suitable clamp / support frame and painting with two or more
coats of synthetic enamel paint of required shade complete as required .
3 27.9 Supplying and Fixing Single Headed Internal Hydrant Valve with
instantaneous gunmetal coupling of 63 mm dia with cast iron wheel ISI
marked conforming to IS : 5290 ( Type A ) with blank gunmetal material
cap and chain as required .
3.1 27.9.1 Single Headed Gunmetal Material 10 Set ₹ 8,208.00 ₹ 82,080.00
4 27.10 Supplying and Fixing Single Headed External Yard Hydrant Valve with 1
Nos 63 mm dia instantaneous female Gunmetal material Coupling and
cast iron wheel ISI marked Conforming to IS : 5290 ( Type A ) with blank
stainless steel cap and chain as required .
4.1 27.10.1 Single Headed Gunmetal Material 6 Set ₹ 8,208.00 ₹ 49,248.00
5 27.11 Supplying Fixing Testing and Commissioning of butterfly valve of PN 1.6
Rating with Bronze Gunmetal Sheet duly ISI marked complete with nuts ,
bolts , washers , gaskets conforming to IS : 13095 of following sizes as
SQ - 2 Digitally signed by VARUN
Fire Fighting - Internal
NATIONAL LAW UNIVERSITY AT DWARKA
ITEM CODE NO. DSR 2025 FF
S.NO. DESCRIPTION OF ITEMS TOTAL QUANTITY UNIT
WORKS DSR 2025 NDSR DSR NDSR
6 27.13 Supplying and Fixing orifice plate made out of 6 mm thick stainless steel (
Grade 304 ) with orifice of required size to be fitted between flange and
landing valve of external and internal hydrants to reduce pressure at the ₹ 14,360.00
outlet to the level of 3.5 kg / sqcm complete as required .
7 27.14 Providing Installation Testing and Commissioning of Non Return Valve of
following sizes conforming to IS : 5312 complete with rubber gasket , GI
Bolts , Nuts , washers etc as required .
8 27.15 Providing Installation Testing and Commissioning of stainless steel y-
strainer fabricated out of 1.6 mm thick stainless steel, grade 304, sheet
with 3mm dia holes with stainless steel flange.
9 27.16 Supplying and Fixing 63 mm dia 15 m Long RRL Hose pipe with 63 mm dia
male and female coupling duly bound with GI wire , rivet etc . Conforming
to IS : 636 ( Type A ) as Required .
10 27.17 Supplying and Fixing First aid hose reel with MS Construction Spray
painted in Post office red conforming to IS : 884 complete with the
following as required
20 mm nominal internal dia water hose thermoplastic ( Textile Reinforced
) Type - 2 as per IS : 12585
20 mm nominal internal dia gunmetal globe valve and nozzle
Drum and Brackets for fixing the equipments on wall
Connections from Riser with 25 mm dia stop gunmetal valve and MS Pipe
11 27.18 Supplying and Fixing 63 mm dia Gunmetal Material Short Branch Pipe
with 20 mm nominal internal diameter size nozzle conforming to IS : 903
suitable for instantaneous connection to interconnect hose pipe coupling
12 27.19 Supplying and Fixing of Fire brigade connection of Cast iron body with
gunmetal male intantaneous inlet coupling complete with cap and chain
as required for suitable dia ms pipe connection conforming to IS : 904 as
SQ - 3 Digitally signed by VARUN
Fire Fighting - Internal
NATIONAL LAW UNIVERSITY AT DWARKA
ITEM CODE NO. DSR 2025 FF
S.NO. DESCRIPTION OF ITEMS TOTAL QUANTITY UNIT
WORKS DSR 2025 NDSR DSR NDSR
13 27.20 Supplying and Fixing Air Vessel made of 250 mm dia 8 mm thick ms sheet
1200 mm in height with air release valve on top and flanged connection to
riser drain arrangement with 25 mm dia gunmetal wheel valve with
required accessories pressure gauge and painting with synthetic enamel ₹ 19,402.00
paint of approved shade as required
14 27.21 Providing, fixing, testing & commissioning of 15mm dia quartzoid bulb
type sprinklers of rating 68 degree centigrade with required accessories :
14.1 27.21.1 Pendent Sprinkler 667 Each ₹ 599.00 ₹ 399,533.00
15 27.22 Providing and fixing of pressure switches in MS pipe line including connection extra as required.
Supplying, fixing, testing & commissioning of double flanged sluice valve of rating PN 1.6 with non
rising spindle, bronze/gun metal seat, ISI] marked complete with nuts, bolts, washers, gaskets and
conforming to IS 780 of following sizes as required :
27.25 Supplying, installation, testing & commissioning of sprinkler flexible pipe
stainless steel complete with 15 NPT on reducer thread with maximum
working pressure of
175 PSI test pressure of 875 PSI (Burst) with branch line (Inlet) 25mm NPT
sprinkler head (Outlet) 15mm NPT female thread with reducer, nipple, 2
side brackets, center
bracket, stockbar of following sizes complete as required
27.29 Providing,installation,testing&commissioning of adjustable rosette plate 667 Each
for15mm dia in white finish UL Listed or FM approved complete as ₹ 264.00 ₹ 176,088.00
17 NS-1 Providing and fixing of Fire Hose Cabinet size not less than 2.1 x 1.2 x 0.90
mtr made out of M.S. sheet not less than 1.5 mm thick having central
opening and 4 mm thick glazed glass doors (Two nos.) suitably marked
on the outside 'with the letters "FIRE HOSE" including necessary locking
arrangement and painting in PO red colour suitable to accommodate,
internal hydrant valve, 2 nos 15 mtr long Hose pipe, branch pipe, nozzle
and fire man's axe. It shall be fixed inside the FHC Cabinet Complete as
18 NS-2 Providing and fixing standard firemans axe with heavy rubber handle.
SQ - 4 Digitally signed by VARUN
Fire Fighting - Internal
NATIONAL LAW UNIVERSITY AT DWARKA
ITEM CODE NO. DSR 2025 FF
S.NO. DESCRIPTION OF ITEMS TOTAL QUANTITY UNIT
WORKS DSR 2025 NDSR DSR NDSR
19 NS-3 Providing and fixing dial type pressure gauge with isolation cock and
copper pipe on main header Dial diameter 100 mm celebration 0-16 / sq.
20 NS-4 Providing and fixing Fire Extinguishers (CO2 type powder ) 4.5 Kg
Capacity complete with all accessories as per manufacturers
specifications. 20 Each ₹ 5,625.85 ₹ 112,516.94
21 NS-5 Providing and fixing Fire Extinguishers (A, B, C type powder ) 6 Kg
Capacity complete with all accessories as per manufacturers
specifications. 20 Each ₹ 2,649.65 ₹ 52,993.09
22 NS-6 Providing and fixing Fire Extinguishers (A, B, C type powder ) 9 Kg
Capacity complete with all accessories as per manufacturers
specifications. 20 Each ₹ 3,203.36 ₹ 64,067.29
24 NS-8 Providing and fixing Fe 36 modular Fire Extinguishers 10 Kg Capacity
complete with all accessories as per manufacturers specifications.
TOTAL CARRIED TO SUMMARY SHEET FOR SUB HEAD A ₹ 6,007,337.14 ₹ 499,670.99
SUB HEAD-2.0 FIRE FIGHTING PUMPS
1 27.1 Supplying, installation, testing and commissioning of Electric driven Main
Fire Pump suitable for automatic operation and consisting of following,
complete in all respects, as required :
(a) Horizontal type, multistage, centrifugal, split casing pump of cast iron
body & bronze impeller with stainless steel shaft, mechanical seal
conforming to IS 1520.
(b) Suitable HP Squirrel cage induction motor, TEFC, synchronous speed 1500
RPM, suitable for operation on 415 volts, 3 phase 50 Hz, AC supply with IP
55 protection for enclosure, horizontal foot mounted type with Class-'F'
insulation, conforming to IS-325.
(c) M.S. fabricated Common base plate, coupling, coupling guard, foundation
bolts etc. as required.
(d) Suitable cement concrete foundation duly plastered with anti vibration
Note: *The head of the pump is selected in a manner so as to give a
minimum 3.5kgf/cm2 pressure at the highest/farthest point.
2 27.2 Supplying, installation, testing and commissioning of diesel engine driven
main fire pump suitable for automatic operation and consisting of
following, complete in all respects, as required : (Diesel Driven Pump)
(a) Horizontal type, multistage, centrifugal pump of cast of iron body and
bronze impeller with stainless steel shaft, mechanical seal conforming to
(b) Suitable HP, 1500 RPM water cooled with radiator, diesel engine
conforming to relevant IS standard complete with auto starting
mechanism, 12 /24 volts electric starting equipment, diesel tank, exhaust
pipe extended upto 10 m outside pump house duly insulated with 50 mm
thick glass wool with 1.0 mm thick aluminium sheet cladding, residential
silencer, instruments and protection as per standard specification, stop
solenoid for auto stop in the event of fault with audio indications, painted
with post office red colour etc. as required.
(c) M.S fabricated, common base plate, coupling, coupling guard, foundation
bolts etc. as required.
SQ - 5 Digitally signed by VARUN
Fire Fighting - Internal
NATIONAL LAW UNIVERSITY AT DWARKA
ITEM CODE NO. DSR 2025 FF
S.NO. DESCRIPTION OF ITEMS TOTAL QUANTITY UNIT
WORKS DSR 2025 NDSR DSR NDSR
Suitable cement concrete foundation duly plastered with anti vibration
Note: *The head of the pump is selected in a manner so as to give a
minimum 3.5kgf/cm2 pressure at the highest/farthest point.
3 27.3 Supplying, installation, testing and commissioning of electric driven
pressurisation pump suitable for automatic operation and consisting of
following, complete in all respects, as required : (Jockey Pump).
(a) Horizontal type, multistage, centrifugal split casing pump of cast iron
body and bronze impeller with stainless steel shaft, mechanical seal
conforming to IS : 1520.
(b) Suitable HP squirell cage induction motor TEFC type suitable for operation
on 415 volts, 3 phase 50 Hz AC supply with IP 55 class of protection for
enclosure, horizontal foot mounted type with Class-'F' insulation,
conforming to IS : 325.
(c) M.S.fabricated Common base plate, coupling, coupling guard, foundation
bolts etc. as required.
(d) Suitable cement concrete foundation duly plastered and with anti
vibration pads.
TOTAL CARRIED TO SUMMARY SHEET FOR SUB HEAD A ₹ 1,075,869.00 ₹ 0.00
SQ - 6 Digitally signed by VARUN
Fire Fighting - Internal
ADMIN CUM ACADEMIC BLOCK COLLEGE OF HORTICULTURE, MORENA
PROJECT :- PROPOSED COLLEGE OF HORTICULTURE AT MORENA (M.P.)
BUILDING NAME : ADMIN CUM ACDEMIC BLOCK
SUMMARY OF COST_HVAC WORKS
S. No. Description
1) Sub Head-'A'- HVAC EQUIPMENTS ₹ 2,590,462.00 ₹ 1,417,943.75
2) Total of Sub Head 'B'- Piping ₹ 394,825.00 ₹ 480,411.37
3) Total of Sub Head-'C'- Air Distribution ₹ 4,809,705.00 ₹ 1,305,722.85
4) Total of Sub-Head-'D'-"Electrical (In HVAC Scope)" ₹ 407,286.00 ₹ 1,238,814.84
5) Sub Head-'E'- Split AC ₹ 344,214.00 ₹ 0.00
TOTAL (HVAC ) ₹ 12,989,384.82
Digitally signed by VARUN
ADMIN CUM ACADEMIC BLOCK COLLEGE OF HORTICULTURE, MORENA
PROJECT :- PROPOSED COLLEGE OF HORTICULTURE AT MORENA (M.P.)
BUILDING NAME : ADMIN CUM ACDEMIC BLOCK
BILL OF QUATITIES_HVAC WORKS
DSR 2025 DSR AMOUNT NSR AMOUNT
S.NO. DESCRIPTION OF ITEM UNIT QUANTITY NS RATE
RATE (IN RS.) (IN RS.)
DSR-31.3 Variable Refrigerant Volume / Flow Air-conditioning System (Heating & Cooling both)
Supply, Installation, Testing & Commissioning of Modular type Variable Refrigerant
Flow/Variable Refrigerant Volume air cooled Outdoor units suitable for cooling/heating having
100% hermetically sealed inverter type Compressor(s),microprocessor based Controller, top
discharge type condensing unit(s), with R-410-A Refrigerant or equivalent, vibration Isolators with
suitable foundation etc. complete as required. To have better efficiency condenser fan shall be
capable to operate at different speed with respect to load. The unit shall deliver the rated
capacity and in confirmation as per IS 18728:2024 and CPWD Specifications and work even at
50°C ambient temperature without tripping. The system shall be able to deliver 100% of the rated
capacity upto 39 Degree Celcius.The unit shall be suitable to work on 400V +/- 10%, 3 Phase, 50Hz
AC power supply and BMS compatible. The unit shall be filled with first charge of the refrigerant
and ready for use as required. The condenser should be coated with a hydrophilic film to prevent
water accumulation on the surface of the heat exchanger, enhance water dispersion, and reduce the
risk of degradation, thereby improving overall performance and durability and complete as per
CPWD specification, connections, inter connections etc. as required.
For Cooling or Heating Both
Supply, Installation, Testing and Commissioning of following minimum capacity 4 way Cassette Type
Indoor ceiling mounted unit equipped with synthetic washable media pre-filter, fan section with low
noise fan / dynamically balanced blower, multispeed motor, coil section with DX Copper coil,
electronic expansion valve, outer cabinet, drain pump, grill, necessary supports, vibration Isolation,
DSR-31.4 Corded remote control etc., suitable for operation on single phase 230 V ± 10%, 50Hz AC supply,
complete, as required. The Indoor units must shut down upon receiving a singal from the BMS
System/Fire Signals. The system shall be capable to adjust air flow as per room requirement in auto
mode. The cooling capacity of indoor unit will be at air inlet conditions of 27 Degree C DB and 19
Degree C WB temperature. (Make will be same as of Outdoor)
High Static Ductable Units (Minimum 49 to 77 Pascal External Static Pressure)
Supply, Installation, Testing and Commissioning of following minimum capacity and external static
pressure VRF/VRV ceiling mounted high ductable type Indoor unit equipped with washable
synthetic media pre-filter,
fan section with low noise fan/dynamically balanced blower, multispeed motor, coil section with DX
DSR-31.12 copper coil, electronic expansion valve, corded remote control, outer cabinet, vibration Isolators,
drain pan, drain pump, other necessary supports etc., suitable for operation on single phase AC
supply 230 V ± 10%, 50 Hz complete as required. The Indoor units must shut down upon receiving a
singal from the BMS System/Fire Signals.The cooling capacity of indoor unit will be at air inlet
conditions of 27 Degree C DB and 19 Degree C WB temperature. (Make will be same as of Outdoor)
DSR-31.12.1 High Static Ductable units (minimum 78 pascal external static pressure)
NS-1 VRV/VRF Central Controller for Indoor & Outdoor Units
Supply, installation, testing & commissioning of Central Controller capable of controlling of all IDUs,
ODUs complete with necessary hardware, accessories etc. to perform the following functions:
Control of IDUs, ODUs Units as above with monitoring of vital parameters such as temperature
sensing & setting, ON/OFF, status etc.
c Permit / prohibit function of each remote controlled unit
Digitally signed by VARUN
ADMIN CUM ACADEMIC BLOCK COLLEGE OF HORTICULTURE, MORENA
DSR 2025 DSR AMOUNT NSR AMOUNT
S.NO. DESCRIPTION OF ITEM UNIT QUANTITY NS RATE
RATE (IN RS.) (IN RS.)
d Operation of units in individually or in group
e Fault indication with Alarm
f Provide interface to connect complete VRF system with third party BMS system
The central controller will be complete including all hardware & software suitable to perform above
function.Complete in all respect as required at site.
NS-2.0 Air handeling Units (Suitable For VRV/VRF System) Suitable for Installation at Terrace
Supply, Installation, Testing and commissioning of factory built floor mounted/ceiling
suspended DX Type double skin type horizontal/vertical air handling units made of 25mm thick
panels consisting of pre plasticized G.I. casing of thickness 0.8mm outside layer and 0.8 mm
inside layer with polyurethane foam (PUF) insulation factory injected between them by injection
moulding Equipments, complete with Plug fans with blower suitable for static pressure as
required, minimum 2 bend GSS/PVC eliminators, cooling coil section with aluminium finned
copper tubes (tubes thickness not less than 0.5mm) cooling coil of 4/6 row deep, filter section
with 50mm thick metal viscous/ washable synthetic type air prefilters, belt drive package with
TEFC drive motor of efficiency class IE3 suitable for 415 ± 10% volts, 50Hz, 3 Phase AC supply
with suitable variable frequency drive control panel, drain connections.
1) Plug Fans (with min. 70% efficiency) with motor (VFD compatible) ,volume control damper and
duct flexible connection. The supply fan shall be provided with variable frequency drive and input /
output signal compatible to BMS system. Squirrel cage induction motors suitable for 415 ± 10%
volts, 50 Hz, AC supply & high efficiency (IE-3 Efficiency), H.P of motor shall be as per actual
selection meeting other technical requirements.
2) 6 Row Deep Cooling Coil with Alu. fins-Coated
3) SITC UVGI Emitter system along with power / control wiring. Access doors should be fitted with
interlocks which will turn off the UV in the event the door is opened. Precaution labels should be
posted near access doors to any equipment with UV systems.
5) COIL- 6 row Copper tubes and Aluminum fins 12 fin./inch, Coil size shall be selected for air
velocity of 350 ft./minute & velocity across filters at 350 ft./minute.
6) Equipments shall be BMS compatible for control and monitoring,cost shall be inclusive of all BMS
component (like controller,cabeling etc.) to make system complete as required by engineer in-charge.
In Built VFD & Screen Controller :- VFD designed for HVAC applications with built-in PID controller,
control panel (keypad & display) , IP-65 enclosure for use on standard centrifugal plug fans. The
display should be in alpha-numeric characters and programming facility should be in user-friendly
HVAC terminology. VFD’s shall have built-in harmonic filters. EACH VFD panel to be provided with
digital display showing electrical parameters like voltage, current and power consumption.EACH
VFD shall be installed in a dedicated external IP-65 enclosure and the inter connecting wires
between driver and MCC shall be included. Item tabulated separately.
NS-2.1 7000 CFM/18.5 TR/60 mm Static pressure Each 2 261916 523831.854
NS-2.2 3000 CFM/6.0 TR/60 mm Static pressure Each 1 125202 125201.5695
Supply ,installation, testing and commissioning of Refrigerant Line accessories kit for AHU suitable
NS-3.0 to operate with VRV/VRF system.Sytem includes Expansion Valve Kit, Controller with Wired EACH 3 55549.2021 166647.6063
Remote.Complete as per OEM Standard.
Supply, installation, testing & commissioning Refrigerant 'Y'Joint (Pair) required for distribution of
refrigerant in copper piping etc. complete as per specifications.Make:Same as per selected VRV OEM.
NS-5.0 AXIAL FLOW FAN (AMCA Certified for Sound & Preformance):
Digitally signed by VARUN
ADMIN CUM ACADEMIC BLOCK COLLEGE OF HORTICULTURE, MORENA
DSR 2025 DSR AMOUNT NSR AMOUNT
S.NO. DESCRIPTION OF ITEM UNIT QUANTITY NS RATE
RATE (IN RS.) (IN RS.)
Supplying, installation, testing and commissioning of AMCA Certified (For Air and Sound
Performance) ceiling hung / floor mounted vane/tube axial flow fans of following capacity with GSS
casing/ standard M.S. construction and aluminium alloy impellers with high efficiency aero-foil
sections, blades, the impeller directly driven by TEFC induction motor should be of high efficiency
IE3 insulation for Fresh Air and Pressurization Fans and class 'H' insulation for Exhaust Fans. Fire
rated flexible connection etc. including all accessories complete as required and as per specifications.
Motor of exhaust fans shall be of high temperature resistance "Class H Smoke Spill" 250° C for 2 hrs.
Fan shall be EN 12101-3 Certified & CE/UL Listed for high temprature. Motor make shall be same as
mentioned on the fire certificate. Fan total efficiency should not be less than 70%. All the fans shall
be hot dip galvanized with minimum 220 GSM Zinc Coating and complete with bird screen at inlet.
Suitable TP isolator within MS enclosure should be provided. Gravity louvers will be provided at the
discharge of the fan so as to avoid reverse flow. Static pressure shall be checked/verified by
contractor prior to order. Entire fan model & AMCA Seal shall appear in technical submittal of fan.
Complete as required as per site conditions.
NS-5.1 Air Quantity : 10000 CFM
Static Pressure : 40 mm wg
Insulation : Class H Nos. 2 109371 218742.972
Sub Head-'A'- HVAC EQUIPMENTS 2590462 1417944
Sub Head-'B'- Communication cable,Refrigerant & drain Piping,
Supply, Installation, testing and commissioning including vaccumiazation and Nitrogen
testing of following nominal sizes of soft/hard drawn copper refrigerant piping for VRV/VRF
system,complete with fittings, with suitable adjustable ring type hanger supports,
DSR-31.14 jointing/brazing including accessories, insulated with Class-O closed cell elastometric
nitrile rubber tubular sleeves sections of 19 mm thick insulation with factory laminated aluminum
sheet as given below for Suction and Liquid lines, all accessories as per specifications etc. as
DSR-31.14.1 6.4 mm dia (OD) (Soft drawn) with tube thickness 1.2 mm with 19 mm thick insulation Rmt 45 256 11520
DSR-31.14.2 9.5 mm dia (OD) (Soft drawn) with tube thickness 1.2 mm with 19 mm thick insulation Rmt 40 346 13840
DSR-31.14.3 12.7 mm dia (OD) (Soft drawn) with tube thickness 1.2 mm with 19 mm thick insulation Rmt 50 487 24350
DSR-31.14.4 15.86 mm dia (OD) (Soft drawn) with tube thickness 1.2 mm with 19 mm thick insulation Rmt 45 615 27675
DSR-31.14.5 19 mm dia (OD) (Hard drawn) with tube thickness 1.2 mm with 19 mm thick insulation Rmt 50 739 36950
DSR-31.14.6 22.2 mm dia (OD) (Hard drawn) with tube thickness 1.2 mm with 19 mm thick insulation Rmt 55 904 49720
DSR-31.14.8 28.58 mm dia (OD) (Hard drawn) with tube thickness 1.2 mm with 19 mm thick insulation Rmt 50 1157 57850
DSR-31.14.10 34.9 mm dia (OD) (Hard drawn) with tube thickness 1.62 mm with 19 mm thick insulation Rmt 60 1286 77160
41.27 mm dia (OD) (Hard drawn) with tube thickness 1.62 mm with 19 mm thick insulation.
Supply & fixing Of MS stand with weather proof paint and primer for outdoor units.
Digitally signed by VARUN
ADMIN CUM ACADEMIC BLOCK COLLEGE OF HORTICULTURE, MORENA
DSR 2025 DSR AMOUNT NSR AMOUNT
S.NO. DESCRIPTION OF ITEM UNIT QUANTITY NS RATE
RATE (IN RS.) (IN RS.)
NS-10 Supply & fixing Of Branch Kit Joints. EACH 20 13815 276307
Supply,Installation,testing and commissioning Control/communication wiring between indoor and
outdoor units with FRLS PVC conduit and necessary clamps/saddling etc. complete as Required.
Supplying, laying, fixing and installation of rigid heavy duty PVC drain piping of 6 kg/sqcm, duly
insulated with 6mm thick nitrile rubber pipe section with factory laminated aluminum foil, complte
with all necessary fitting such as elbow, tees, reducers, serviceable "P" traps etc. and supports such
as clamps etc. complete as per specifications.
Total of Sub Head 'B'- Piping 394825 480411
DUCTING, GRILLS, DIFFUSER AND INSULATION
Supplying, installation, balancing and commissioning of fabricated at site GSS sheet metal rectangular/
round ducting complete with neoprene rubber gaskets, elbows, splitter dampers, vanes, hangers,
DSR-2025-30.12.2 supports, bends, transitions, reducers, end caps, collars etc as required complete in all respect in
confirmation with IS : 655 and approved drawings and specifications of following sheet thickness
complete as required.
30.12.2.1 Thickness 0.63 mm sheet Sqm 550 1213 667150
30.12.2.2 Thickness 0.80 mm sheet Sqm 460 1415 650900
30.12.2.3 Thickness 1.00 mm sheet Sqm 350 1851 647850
30.12.2.4 Thickness 1.25 mm sheet Sqm 150 2063 309450
Supplying, installation, testing and commissioning of GI volume control duct damper complete with
30.13 neoprene rubber gaskets, nuts, bolts, screws linkages, flanges etc in confirmation to SMACNA/IS and as Sqmt 10 7580 75800
per specifications complete etc. as required.
Supplying, Fixing, installation, testing and commissioning of powder coated extruded aluminium Supply
30.15 Air Grills with aluminium volume control dampers in confirmation to SMACNA/IS and as per specifications Sqmt 25 9623 240575
complete etc. as required.
Supplying & fixing of powder coated extruded aluminium Return Air Grills with louvers but without
30.16 volume control dampers complete in confirmation to SMACNA/IS and as per specifications complete etc. Sqmt 25 6285 157125
Supply, installation, testing & balancing of removable core type ,linear, fixed bar extruded
aluminium powder coated Exhaust Air grills, normal flow, 15° angle one way / two way deflection
NS-17 with all sides flanges.Blade thickness shall be minimum 5mm in front and 1.0 mm in rear side.Grills
shall be supplied in accordance with specifications and approved shop drawings. Make:
Airflow(mapro), Ruskin titus, Systemair.
Supply, installation, testing & balancing of key operated extruded Aluminium volume control
NS-18 dampers in black mat finish for supply/return/exhaust air duct collars as per approved shop Sqmt 15 5036.84475 75553
drawings and specifications. Make: Airflow(mapro), Ruskin titus, Systemair.
Digitally signed by VARUN
ADMIN CUM ACADEMIC BLOCK COLLEGE OF HORTICULTURE, MORENA
DSR 2025 DSR AMOUNT NSR AMOUNT
S.NO. DESCRIPTION OF ITEM UNIT QUANTITY NS RATE
RATE (IN RS.) (IN RS.)
Supplying, Fixing, installation, testing and commissioning of supply air diffusers of powder coated
30.17 aluminium with aluminium volume control dampers with anti smudge ring & removable core in Sqmt 25 12841 321025
confirmation to SMACNA/IS and as per specifications complete etc. as required.
Supplying, Fixing, installation, testing and commissioning of Return air diffusers of powder coated
30.18 aluminium without volume control dampers with anti smudge ring & removable core in confirmation to Sqmt 25 8595 214875
SMACNA/IS and as per specifications complete etc. as required.
Supplying, Fixing, testing and commissioning of fire dampers of minimum 90 minutes fire rated in supply
air duct/main branch and return air path as and where required of required sizes i/c control wiring, the
30.20 damper shall be motorized and spring return so as to close the damper in the event of power failure
automatically and open the same in case of power being restored. The spring return action shall be inbuilt
mechanism and not externally mounted. The damper shall also be closed in the event of fire signal and, in
confirmation to IS and as per specifications complete etc. as required..
30.20.1 Fire Dampers. Sqmt 5 11355 56775
30.20.2 actuator Each 4 10645 42580
Note: Raw power shall be tapped off from the respective starter panels by the HVAC vendor for Fire
Supply & Installation of acoustic lining within supply and return air ducting using open cell
elastomeric insulation with antimicrobial protection having 140-160 Kg/cum. density.All ducts
shown cross hatched on the approved shop drawings shall be provided with acoustic lining as per
the specifications.Make:Armacell,ALP,
NS-22.1.0 15 mm thick for Ducting Sqmt 160 1381.53456 221046
NS-22.1.1 20 mm thick for AHU Plenum Sqmt 80 1669.35426 133548
Underdeck insulation for TIRI S1 Pro Double Bubble is made up of 8mm thick fibre free PE Air
Bubbles sandwiched between 2 layers of High Resistant Pure Aluminium Foils.It has a R Value of
3.10M2K/W.It has a High Reflectivity of 95-97% & Low Emissivity of 3-5%..complete as per
Supply,installation and testing of double layer flexible duct connector consisting of a flame
retardant fabric secured to extruded aluminium frame on both sides to provide a wear resistant
airtight flexible connection. Fabric shall be mildew resistant, water proof and silicon
impregnated.Flexible connector shall be supplied in accordance with the specifications and drawings.
Supplying, installing, testing and commissioning of Fresh Air powder coated Anodized extruded
NS-27 aluminium construction fresh air louvers (50 mm deep) (Fresh air louver with VCD , bird screen & Sqmt 5 16118 80590
rattle-free) complete as per specification.
Supplying, installing, testing and commissioning of Exhaust Air powder coated Anodized extruded
NS-28 aluminium construction fresh air louvers (50 mm deep) air louver without VCD , bird screen & Sqmt 5 13815 69077
rattle-free)complete as per specification.
30.23 Supplying and fixing of following thickness duly
laminated aluminium foil of mat finish closed cell
Nitrile rubber (Class "O") insulation on existing duct
after applying suitable adhesive for Nitrile rubber. The
joints shall be sealed with 50 mm wide and 3 mm thick
self adhesive nitrile rubber tape insulation complete
as per specifications and as required.
Total of Sub Head-'C'- Air Distribution 4809705 1305723
Digitally signed by VARUN
ADMIN CUM ACADEMIC BLOCK COLLEGE OF HORTICULTURE, MORENA
DSR 2025 DSR AMOUNT NSR AMOUNT
S.NO. DESCRIPTION OF ITEM UNIT QUANTITY NS RATE
RATE (IN RS.) (IN RS.)
Sub Head 'D' - HVAC ELECTRICAL PANELS/CABLES & ACCESSORIES
VI. Preamble to BOQ for MCC , Distribution Boards & wall mounted Starter Panels
General Notes & Specifications as given below shall be applicable to all panels.The vendors shall
consider the following details in their item rates, wherever required:
1 Supporting rigid steel framework.
2 Cubicle type, 14 gauge CRCA sheet steel enclosure.
3 Panel Complete with interconnections and distribution bus bars.
4 Proper bonding to earth.
5 Painting/lettering on Breakers and distribution boards, the location they serve, Providing on each panel its
circuit diagram.
6 Providing cable clamps / supports within distribution boards cable alley.
7 TPN MCCBs shall mean 3 pole MCCBs with adequate size of neutral link.
8 All MCBs shall be of minimum 10 KA breaking capacity.
9 All motor feeders MCCBs shall be of motor duty and shall be able to carry the inrush current of motor.
10 Distribution panels shall be Powder Coated with Siemens gray paint shade no. RAL-7032 of IS-5.
11 Degree of protection for following type of distribution panel enclosure shall be as per IS:13947-1993.
12 IP 42 for indoor panels.
13 IP 55 for outdoor panels with double door enclosure.
14 All MCCB’s shall be provided with operating mechanism for door interlock.
15 Current density of aluminium shall be 1 sq mm for 1.0 amps for rated current of bus bars and current
density of copper shall be 1 sq.mm for 1.25 amps for rated current of bus bars.
16 Tinned copper earth bus shall be provided through out the length of each board.
17 All measuring instruments (Meters) shall be of digital electronic with LED of approved make and compatible
18 All indicating lamps shall be LED type.
19 All current/voltage transformers shall be cast resin type.
20 All hinged door shall be earthed through 2.5 sq mm tinned braided copper wire.
21 All panels shall have provision of the following:
22 Pad locking of Switch board doors.
23 Pad locking of MCCB’s handles in “OFF” Position.
i Additional set of C.T.s, potential free contacts, connectors, contactors with wiring etc are to be provided for
BAS including space required for various transducers in Main Switch Board sections. Only transducers shall
be supplied by BAS contractor.
ii All MCB’s used for protection of resistive and lightly inductive load shall be type “B” characteristic and
inductive (motor) load shall be of type “C” characteristic and discharge lamps and UPS etc. shall be of type
D characteristic.
iii All incoming and outgoing air circuit breakers shall be placed on middle portion of the vertical in single tier
24 All PTs / control transformers shall be provided with centre tap earth secondary.
25 All DOL & Star-Delta Starters shall be provided with voltage based SPPR (single phase preventor relay)
and 2 nos. of Aux.Contacts for Remote operation/monitor.
26 The Panel fabricator shall provide Aluminium Bus-bars link from Breakers wherever more than two nos. of
cables are terminated in the breakers.
27 Readymade 16SWG Sheet steel Enclosure with cutout For MCBs
28 The breaking capacity of MCCB’s shall be mentioned panel wise. All MCCB’s shall be with thermal
magnetic releases upto 250 amps and miroprocessor based above 250 amps capacity, unless specified
29 All internal control wiring shall be heat resistant type.
30 Bus bar chamber shall be provided at top only. Incoming and outgoing cable entry shall be from top/bottom
31 Live parts shall not be accessible after opening the door, Transparent acrylic sheet to be provided to cover
32 Spare contacts of ACBs / MCCBs / Relay / Contactor shall be wired upto terminal block.
33 All Switchgear used in Starter Circuit shall be type-2 coordinated. Contactor rating shall be selected as per
the kVAR rating of the capacitor bank from capacitor duty contactor range. Vendor to furnish the type-2
coordination chart and capacitor duty contactor selection chart.
Digitally signed by VARUN
ADMIN CUM ACADEMIC BLOCK COLLEGE OF HORTICULTURE, MORENA
DSR 2025 DSR AMOUNT NSR AMOUNT
S.NO. DESCRIPTION OF ITEM UNIT QUANTITY NS RATE
RATE (IN RS.) (IN RS.)
34 Protection Releases Microprocessor based (PRMB) & Thermal magnetic (PRTM) shall be as describe
A Protection Release Microprocessor Based (PRMB-1)
Over-current/long time protection range 105% - 120 % with Time setting
short circuit /short time protection range 100% - 1000 % with Time setting
Instantaneous short circuit Protection range 200% - 1500 % with Time setting
Earth Fault Protection range 20% - 100 % with Time setting
Under voltage & over voltage protection
Current unbalance
Power (Active,Reactive & Apparent)
Energy ((Active,Reactive & Apparent)
B Protection Release Microprocessor Based (PRMB-2)
Over-current/long time protection range 105% - 120 % with Time setting
short circuit /short time protection range 100% - 1000 % with Time setting
Instantaneous short circuit Protection range 200% - 1500 % with Time setting
Earth Fault Protection range 20% - 100 % with Time setting
C Protection Release Microprocessor Based (PRMB-3)
Over-current/long time protection range 105% - 120 % with Time setting
Instantaneous short circuit Protection range 200% - 1500 % with Time setting
D Protection Release Thermal-Magnetic Based (PRTM)
Preambles to BOQ for Cables and Cable Trays
The contractor shall consider the following details in their item rates, wherever required:
The rate shall also include the following :
i Providing and fixing junction boxes with covers including painting where ever required.
ii Providing all fixing accessories such as clamping devices nuts, bolts and screws.
iii Wherever the cables are of aluminium and bus bars of copper bimetallic lugs shall be used.
iv All the DB incomer cables shall be unarmoured cable.
v All cable shall be laid with one diameter gap.
vi All cables shall (conform IS norms) be IS approved.
vii Double compression glands
Fire retardent paint one meter on both side of wall penetration and at termination as per specifications.
NS-30 HVAC Panel 1 Weather Proof
Design, fabrication, assembly, wiring and supply of front operated dead front cubicle type
compartmentalised as per Form 3B, rear access free standing, dust and vermin proof (IP 65 ingress
protection) main switchboards suitable for use at 415 volts, 3 phase 4 wire 50 Hertz system suitable
for a symmetrical fault level of 35 kA at 415 volts, fabricated from 2 mm thick CRCA MS sheets with
hinged, gasketted (metal based neoprene) and lockable doors having structural reinforcement with
suitable angle/channel/T/flat sections including 3 mm thick gland plates on top and bottom and
including lifting hooks and including GI earth strip of required size with 2 nos earthing terminals and
including powder coated paint finish of approved shade over metal surface cleaned and treated with
seven tank process complete with interconnections etc as per specifications, as required and as
below.Complete as required as per site conditions.
EACH Motor control Centre(MCC)/Panel shall include cost of cabling, wiring, control wiring & inter
locking in order to execute the required sequence of operation.
Digitally signed by VARUN
ADMIN CUM ACADEMIC BLOCK COLLEGE OF HORTICULTURE, MORENA
DSR 2025 DSR AMOUNT NSR AMOUNT
S.NO. DESCRIPTION OF ITEM UNIT QUANTITY NS RATE
RATE (IN RS.) (IN RS.)
A separate Each of CTs to be provided for wiring from CT’s and voltage transducers to be brought on
to separate Each of terminals.
Note : ACB shall be motor duty and suitable for 35 KA (ICS) fault current
Motor Control Centre (415 V) consisting of
1 No. 200 amps 4 Pole ACB ICU=ICS=35KA having front operating handle with door interlock and as
per preamble above complete with the following :
i. 0 - 630 volts 96 x 96 sq mm digital voltMETER with selector switch - 1 Each
0 - 1600 amps 96 x 96 sq mm digital amMETER with 200/5 amps CT’s and selector switch - 1 Each
Over voltage tripping mechanism for persistent voltage exceeding 110% of the rated voltage for
more than 5 minutes - 1 Each
iv. Phase indicating lamps, with toggle switches.
v. Terminals to receive XLPE insulated Aluminium cables
TPN bus bars shall be of aluminium and shall be sleeved. Phase bus bars shall be rated at 250 amps
and neutral bus bar shall be of 50% capacity suitable to withstand symmetrical fault level of 25KA of
Maximum density of aluminium bus bars for current carrying capacity shall be one amp per square
3 No. EACH 25 amps MCCB outgoing feeders to 12HP VRV outdoor unit .EACH of these compartment
i. shall contain CT operated digital amMETER of 0-25 amps range with selector switch, and an
indicating lamp with MCB and toggle switch for ‘ON’ status.(1 spare but without metering )
3 No. EACH 32 amps MCCB outgoing feeders to 10 HP/8 HP VRV outdoor unit .EACH of these
iii. compartment shall contain CT operated digital amMETER of 0-60 amps range with selector switch,
and an indicating lamp with MCB and toggle switch for ‘ON’ status.(1 spare but without metering )
3 No. EACH 40 amps MCCB outgoing feeders to 16 HP & 18 HP VRV outdoor unit .EACH of these
iv. compartment shall contain CT operated digital amMETER of 0-60 amps range with selector switch,
and an indicating lamp with MCB and toggle switch for ‘ON’ status.(1 spare but without metering )
Supplying,Receiving, fixing, testing & commissioning of HVAC Panel for VRV-1 as described
above.Complete as required as per site conditions.
NS-32 CONTROL PANELS FOR AXIAL FLOW FANS
Design, manufacture, supply, installation, testing and commissioning of the following cubicle type,
dead front, sheet steel, wall mounted control panels,suitable for outdoor applications, including
anchoring into the wall, wiring terminating into MCCB and copper earthing, in each panel shall be
provided by the electrical contractor.
All outgoing shall be provided with Stop /Manual /Auto selector switch to facilitate operation
through BAS. All starters shall be provided with potential free Contact for Connections to Building
Automation System.
All wiring and copper earthing of motors from the panel shall be included.
The panel shall include the following components & accessories.
MCCB/MCB as per the ratings given below, suitable for motor duty and able to withstand fault level
b. DOL / SD starter as per HP gratings given.
c. Terminal block for power distribution as required.
d. Contractor, over load relay with built in single phasing protection.
e. Phase indicating lights and indicating light for `ON’ status.
f. Digital voltmeter and digital ammeter with selector switches.
g. Time delay relay for delayed automatic restart of air handling unit motor.
Wiring/Control wiring from fire damper panel to AHU panel to fire damper motor & micro switch for
stopping the AHU fan when fire damper closes(as required by application)
Digitally signed by VARUN
ADMIN CUM ACADEMIC BLOCK COLLEGE OF HORTICULTURE, MORENA
DSR 2025 DSR AMOUNT NSR AMOUNT
S.NO. DESCRIPTION OF ITEM UNIT QUANTITY NS RATE
RATE (IN RS.) (IN RS.)
For on/off/remote and local operation, 3 pole single throw switch shall be provided in each
AHU/Fan Section panel to facilitate override of the automatic operation.
All starters shall be provided with suitable potential free contact for connections to the Building
Automation System.
3 Nos of Single Pole MCB's Shall be provided at the incoming section of the starter panel for fire
damper actuator & as a spare.
The number of control panels shall be as follows.
NS-32.1.5 16A 4P MCB with 5.0 HP DOL Starter Nos. 2 9354 18708.2805
NS-33 AHU Panel
1 No.63A TP MCCB, 25 kA breaking capacity with thermal release and adjustable setting and with
B METERING & INDICATION
1 Set - digital multifunction meter (showing harmonics along with all other electrical parameters
such as voltage current, Hz, KW, KWHr, PF.) with RS 485 port with matching cast resin CT's
1 Set - 0-500V 96 sqmm Voltmeter with selector switch, 3 No. phase indicating LED lamp to show the
incoming power with control SP MCB.
1Set of indicating LED lamps for MCCB On/Off with protective SP MCB's.
1 Set of CTs of the ratio 40/5A with class 0.5 Accuracy for Metering, burden 15 VA
120A TPN Aluminium Bar with colour coded PVC Sleeves
2 Nos. 63A TP MCCB with---HP SD starter with VFD bypass with contactor
2 Nos. 32A TP MCB (including 1 no spare) with ---HP DOL starter with VFD bypass with contactor
2 Nos. 10A DP MCB
3 Nos. 16A SPN MCB c curve 10 KA
Note- Necessary wiring and interlocking for the above equipments shall be done with the Fire Alarm
system such that required fan gets actuated and shut off the AHU in case of fire as per fire zones.
No/NC contacts & supply arrangements shall also be spared for the fire damper actuation & control.
Supplying,Receiving, fixing, testing & commissioning of AHU Panel as described above Set 2 93541 187082.805
Supplying & erecting approved make RCBO (Electro magnetic type only) working on residual current
device having 10 KA short circuit breaking capacity and 300 mAmp.tripping time conforming to IS
12640 test knob facility trip free mechanism operating for rated leakage at nominal ten volt,
complete erected including all materials lugs screws etc. completed.
NS-34.1.0 6A to 25 A, 4 Pole Three Phase Cat. II Ea. 1 13815 13815.3456
NS-34.1.1 32A to 40 A, 4 Pole Three Phase Cat. II Ea. 4 17989 71954.925
NS-34.1.2 63A, 4 pole Three Phase Cat. II Ea. 2 23457 46914.6111
Supplying & fixing box for housing RCBO combination made of 18 SWG sheet steel duly powder
NS-35 coated with gasket, dust & vermin proof,water proof, bakelite shield two earthing terminals for
following type of RCCB, RCBO
Digitally signed by VARUN
ADMIN CUM ACADEMIC BLOCK COLLEGE OF HORTICULTURE, MORENA
DSR 2025 DSR AMOUNT NSR AMOUNT
S.NO. DESCRIPTION OF ITEM UNIT QUANTITY NS RATE
RATE (IN RS.) (IN RS.)
Providing and erecting XLPE(IS:7098)(I)-88 ISI armoured cable multistrand Aluminium conductor
NS-36 for 1.1 KV. to be laid on wall with necessary clamps or in existing trench / pipe of following size of
Providing and erecting XLPE(IS:7098)(I)-88 ISI armoured cable multistrand / Solid Copper
NS-37 conductor for 1.1 KV. to be laid on wall with necessary clamps or in existing trench / pipe at road
crossing or floor of following size of cables.
Providing and erecting XLPE(IS:7098)(I)-88 ISI armoured cable multistrand Copper conductor for
NS-38 1.1 KV. to be laid on wall with necessary clamps or in existing trench / pipe at road crossing or
floor of following size of cables.
Supplying and installaton following size of perforated painted with powder coating M.S. cable trays with
perforation not more than 17.5%, in convenient sections, joined with connectors, suspended from the
ceiling with two numbers MS/GI Suspenders i/c base of suitable size MS/GI angle, bolts & nuts, painting
suspenders, fastener etc as required.
4.1.2 150 mm width X 50 mm depth X 1.6 mm thickness Rmt. 150 686 102900
4.1.4 300 mm width X 50 mm depth X 1.6 mm thickness Rmt. 55 866 47630
4.1.6 450 mm width X 50 mm depth X 2.0 mm thickness Rmt. 86 1243 106898
4.1.11 600 mm width X 62.5 mm depth X 2.0 mm thickness Rmt. 10 1597 15970
4.1.12 750 mm width X 62.5 mm depth X 2.0 mm thickness Rmt. 10 1830 18300
Total of Sub-Head-'D'-"Electrical (In HVAC Scope)"
Supplying and installation following size of perforated painted with powder coating M.S. cable trays bends
with perforation not more than 17.5%, joined with connectors, suspended from the ceiling with two
numbers MS/GI Suspenders i/c base of suitable size MS/GI angle, bolts & nuts, painting suspenders,
fastener etc as required.
4.2.2 150 mm width X 50 mm depth X 1.6 mm thickness Each 8 1105 8840
4.2.4 300 mm width X 50 mm depth X 1.6 mm thickness Each 3 1544 4632
4.2.6 450 mm width X 50 mm depth X 2.0 mm thickness Each 2 2437 4874
4.2.11 600 mm width X 62.5 mm depth X 2.0 mm thickness Each 2 3244 6488
4.2.12 750 mm width X 62.5 mm depth X 2.0 mm thickness Each 2 3805 7610
Supplying and installation following size of perforated painted with powder coating M.S. cable trays Tee
with perforation not more than 17.5%, joined with connectors, suspended from the ceiling with two
numbers MS/GI Suspenders i/c base of suitable size MS/GI angle, bolts & nuts, painting suspenders,
fastner etc as required.
4.3.2 150 mm width X 50 mm depth X 1.6 mm thickness Each 6 1281 7686
4.3.4 300 mm width X 50 mm depth X 1.6 mm thickness Each 2 1826 3652
4.3.6 450 mm width X 50 mm depth X 2.0 mm thickness Each 3 2923 8769
4.3.11 600 mm width X 62.5 mm depth X 2.0 mm thickness Each 3 3885 11655
4.3.12 750 mm width X 62.5 mm depth X 2.0 mm thickness Each 1 4578 4578
Digitally signed by VARUN
ADMIN CUM ACADEMIC BLOCK COLLEGE OF HORTICULTURE, MORENA
DSR 2025 DSR AMOUNT NSR AMOUNT
S.NO. DESCRIPTION OF ITEM UNIT QUANTITY NS RATE
RATE (IN RS.) (IN RS.)
Supplying and installing following size of perforated painted with powder coating M.S. cable trays Cross
Member with perforation not more than 17.5%, joined with connectors, suspended from the ceiling with
two numbers MS/GI Suspenders i/c base of suitable size MS/GI angle, bolts & nuts, painting suspenders,
fastner etc as required.
4.4.2 150 mm width X 50 mm depth X 1.6 mm thickness Each 5 1498 7490
4.4.4 300 mm width X 50 mm depth X 1.6 mm thickness Each 2 2110 4220
4.4.6 450 mm width X 50 mm depth X 2.0 mm thickness Each 2 3410 6820
4.4.11 600 mm width X 62.5 mm depth X 2.0 mm thickness Each 1 4526 4526
4.4.12 750 mm width X 62.5 mm depth X 2.0 mm thickness Each 1 5352 5352
Supplying and installing following size of perforated painted with powder coating M.S. cable trays Reducer
with perforation not more than 17.5%, joined with connectors, suspended from the ceiling with two
numbers MS/GI Suspenders i/c base of suitable size MS/GI angle, bolts & nuts, painting suspenders,
fastner etc as required.
4.5.2 150 mm width X 50 mm depth X 1.6 mm thickness Each 4 1281 5124
4.5.4 300 mm width X 50 mm depth X 1.6 mm thickness Each 1 1876 1876
4.5.6 450 mm width X 50 mm depth X 2.0 mm thickness Each 1 2933 2933
4.5.11 600 mm width X 62.5 mm depth X 2.0 mm thickness Each 1 3885 3885
4.5.12 750 mm width X 62.5 mm depth X 2.0 mm thickness Each 1 4578 4578
Total of sub head 407286 1238814.844
5 Sub Head-'E'- Split AC
Supplying , Installation, Testing and Commissioning of Air Cooled Hi Wall split type Air conditioners
complete with Indoor unit(IDU), Out door unit (ODU), surface / concealed copper Refrigerant piping with
insulation (closed cell elastomeric nitrile rubber tubular pipe section) upto 3 Mtr (IDU to ODU), copper
power cable upto 3.5 Mtr (IDU to ODU) i/c drain pipe R-32/R-410/ R-407 Green Refrigerant, wireless
Remote control, suitable for working between 180 260V with low & high voltage cutoff and 50 hz ,1 phase
AC supply capable of performing cooling, dehumidification, air circulation of following capacity with Scroll
/ rotary compressor. The system shall be able to deliver 100% of the rated capacity upto 42 0C. Min 5 year
Original Equipment Manufacturer (OEM) warranty both compressor
DSR-2025-32.2 and Printed Circuit Board (PCB). Must comply : Electrical
cable IS 694 or IS 9968 temperature sensing control IS
/International Electrotechnical Commission (IEC) 60730,
hermetic compressor IS 10617, heat exchanger IS 11329,
capacitor IS 2993 and motor IS 12615. Complete as per
CPWD specification and IS : 1391 Part II 2023. The system
shall be able to operate up to 50 0C (out door ambient
32.2.4 2.0 TR with 5 Star BEE Rating Each 6 57369 344214
Total of Sub Head 344214
Digitally signed by VARUN
ADMIN CUM ACADEMIC BLOCK COLLEGE OF HORTICULTURE, MORENA
PROJECT :- PROPOSED COLLEGE OF HORTICULTURE AT MORENA (M.P.)
BUILDING NAME : ADMIN CUM ACADEMIC BLOCK
S.No Works Amount ( DSR) Amount ( MR)
1 SITC of Fire Alarm system & Public Address System ₹ 4,353,960.00 ₹ 1,836,767.00
2 SITC of LAN & WiFi Network System ₹ 6,647,960.00 ₹ 276,652.00
4 SITC of Video Surveillance System(CCTV) ₹ 2,219,227.00 ₹ 340,491.00
5 SITC of Conference Room ₹ 0.00 ₹ 4,745,296.00
6 SITC of Auditorium System ₹ 0.00 ₹ 14,578,980.00
Net Total ₹ 38,463,670.00
Digitally signed by VARUN
ADMIN CUM ACADEMIC BLOCK COLLEGE OF HORTICULTURE, MORENA
SECTION A - FIRE ALARM & PA SYSTEM
S.No./ Amount Amount
Unit Rate DSR Unit Rate MR
DSR Description Unit Qtys DSR ITEMS MR ITEMS
2022 (INR) (INR)
28.2 INTELLIGENT FIRE ALARM SYSTEM
28.2.1 Supplying, installation, testing and commissioning of micro
processor based intelligent addressable main fire alarm
panel, central processing unit with the following loop
modules and capable of supporting not less than 240
devices (including detectors) and minimum 120 detectors per
loop and loop length up to 2 km, network communication
card, minimum 320 character graphics/ LCD display with
touch screen or other keypad and minimum 4000 events
history log in the non volatile memory (EPROM), power
supply unit (230 ± 5 % V, 50 hz), 48 hrs back-up with 24 volt
sealed maintenance free batteries with automatic charger.
The panel shall have facility to connect printer to printout log
and facility to have seamless integration with analog/digital
voice evacuation system (which is part of the schedule of
work under SH: PA System) and shall be complete with all
accessories . The panel shall be compatible for IBMS system
with open protocol BACnet/ Modbus over IP complete as per
specifications.
Supply Of Graphics software for fire detection & alarm system to be connected to the main for
fire alarm panel The software shall be capable of the following including licence as per
specification, Upload/download configuration files without taking the whole system off-line.
Shall provide "Take Action" messages to first responders with specific, real-time information
about alarms at the site including note about hazadous materials, vulnerable building
occupants and management contact. Upload/download configuration files without taking the
whole system off-line. shall have auto-watch option to alows the operator to automatically scan
individual buildings.
Supplying, installation, testing & commissioning of repeater
panel with 320 character/ Touch screen LCD display with
inbuilt reset, acknowledge and silence switches complete as
Supplying, installation, testing & commissioning of intelligent
3.0 28.2.4 analog addressable photothermal detector complete with Nos 400 3,004.00 1,201,600.00
mounting base complete as required.
Supplying, installation, testing & commissioning of intelligent
4.0 28.2.9 addressable thermal detector with rate of rise cum fixed Nos 1 2,866.00 2,866.00
temperature thermistor complete with base as required.
Supplying, installation, testing & commissioning of
addressable beam detector with short circuit isolator (inbuilt
5.0 28.2.12 or separate) complete with emitter and receiver including Nos 6 78,525.00 471,150.00
connections with remote test features etc complete as
Supplying, installation, testing & commissioning of
addressable manual call point complete as required.
Supplying, installation, testing & commissioning of
addressable fire control module complete as required.
Supplying, installation, testing & commissioning of
addressable horn cum strobe complete as required
9.0 28.2.19 Supplying, installation, testing & commissioning of fire fighter Nos 22 1,689.00 37,158.00
phone jack complete as required.
Digitally signed by VARUN
ADMIN CUM ACADEMIC BLOCK COLLEGE OF HORTICULTURE, MORENA
S.No./ Amount Amount
Unit Rate DSR Unit Rate MR
DSR Description Unit Qtys DSR ITEMS MR ITEMS
2022 (INR) (INR)
Supplying, installation, testing & commissioning of fire fighter
telephone handset complete as required.
Supplying, installation, testing & commissioning of response
11.0 28.2.5 indicator on surface/recessed MS Box having two LED, Nos 305 306.00 93,330.00
metallic cover complete with all connections etc as required.
Supplying and installation of photo luminescent safety signage made up of LED based exit
signage with 90 min. battery backup as per NBC including arrangement for fixing on wall /
ceiling etc. complete as required (size 150 mm x 300 mm)
28.3 PUBLIC ADDRESS SYSTEM
28.3.1 Supplying, installation, testing & commissioning of 6 zone,
voice alarm controller with USB, MP4 player (including 6
zone button paging station) with seamless integration facility
with main fire alarm panel for voice evacuation complete as
Supplying, installation, testing & commissioning of Voice
13.0 28.3.9 command keypad 6 zone, with microphone assembly Nos 1 85,450.00 85,450.00
complete as required.
Supplying, installation, testing & commissioning of 1.5/3/6W
ceiling speaker complete as required.
Supplying, installation, testing & commissioning of
15.0 28.3.4 ceiling/wall mounted loud speaker, 3/1.5 Watt in ABS Nos 2 2,555.00 5,110.00
enclosure complete as required.
Supplying, installation, testing & commissioning of digital audio amplifier having 250 Watt
Power Amplifier having audio signal amplification for public address and voice alarm system
MR-4 and 100v & 4-16 OHMS Transformer, Super Class-D Topology Full Band with PWM Modulator, Nos 7 169,524.00 1,186,668.00
complete as required.
Supplying & laying of 2x1.5 sqmm fire survival armoured
cable, 600/1000V rated with annealed copper conductor
having glass mica fire barrier tape covered by an extruded
layer of Cross Linkable Ethylene Propylene Rubber (EPR)
insulation and LSZH inner bedding, steel wire armouring &
LSZH outer sheath complete as required.
Supplying and drawing of cable Fire Retardant PVC
insulated copper conductor cable in the existing surface /
recessed steel conduit of following pairs, cores and size
including connections and interconnections etc. as required.
28.5.3.1 speaker cable Single pair, 2-core, 1.5 sqmm Mtr 1200 61.00 73,200.00
Digitally signed by VARUN
ADMIN CUM ACADEMIC BLOCK COLLEGE OF HORTICULTURE, MORENA
SECTION B - LAN BACKBONE NETWORK + Wi-Fi System
S.No. Unit Rate DSR Unit Rate MR AMOUNT DSR AMOUNT MR
Description Unit Qtys
(INR) (INR) ITEMS ITEMS
Supplying, Installation, Testing and commissioning of
CAT6 Copper Information Outlet (IO) with face plate
of color as per site requirement, should have ETL/UL
1.0 39.14 verification program certificate for compliance with Nos 300 212 - 63,600.00
ANSI/TIA-568.2-D. All copper Cable and Components
should be from same OEM to maintain compatibility
and interoperability etc. complete as required.
Supply& Fixing of Face Plate : Single/Double Port Flush & surface mount. Polycarbonate Hi-
Grade Plastic FR Grade with ABS underplate & CRCA metal fram & UV Resistant 850 degree
C/ Glow Wire Test. The face plate should be compatible for Cat5e, Cat6 range of RJ45 and
different types of AV connectors.The face plate Size should be of minimum 86x86mm as
Supplying, Installation, Testing and commissioning of
following CAT6A Patch Cord should have ETL/UL
verification program certificate for compliance with
ANSI/TIA-568.2-D etc. complete as required.
39.13.1 Copper Patch Cords of length 1m (3ft) Each 294 173.00 50,862.00
39.13.2 Copper Patch Cords of length 3m (10ft) Each 258 405.00 104,490.00
Supply, Installation, testing and commissioning of 24 port Cat 6A 19" Modular Patch Panel
(loaded) enable all possible combinations of the various types of cable (UTP, FTP, SFTP)
mounted on the same panel by using various toolless connector blocks/modules. Have a metal
structure enabling them to be durably fixed to the uprights of the 19” chassis and assuring
automatic grounding between toolless RJ-45 connectors, the panel, and the 19” uprights of the
enclosure. Include rear cable support with plastic cable guides to hold cable without need for
cable ties. Include quick mounting system to mount the panel into the 19” rails without use of
cage-nuts. These may be used to secure the connections of wifi access points, IP cameras,
servers, or other critical devices. MAF Required by System Intigrator, Front Removal IO's
option for maintenance and trouble shooting with 6 Different Colours Labels for Labelling &
Identification of Individual Ports. Tested and guaranteed under dual circuit IEEE PoE++ more
than 90W for up to 2500 on-load connections / disconnections
39.18 Supplying, drawing, Testing and commissioning of
Cat6A UTP 4 pair, 23 AWG solid copper cable in
existing conduit/ on surface, U/FTP, LSZH, Non-
Plenum, Horizontal (solid) Cable suitable for high
speed data networking application supporting upto
10Gbps over a 100 meter channel. The 4 Unshielded
Twisted Pairs (UTP) cable with color coded insulation
for easy indentification should have FLAME
PROPERTIES i.e. Flammability Test - IEC 60332-1,
Smoke Density - IEC 61034, LSZH standards
compliance: ANSI/TIA-568 C.2, ISO/IEC 11801, IEEE
802.3an, RoHS. Delay Skew should be < 45NS. The
outer Cable Diameter should be 7.5 + 2 mm. Cable
should have been tested and verified by UL/ ETL etc.
Digitally signed by VARUN
ADMIN CUM ACADEMIC BLOCK COLLEGE OF HORTICULTURE, MORENA
S.No. Unit Rate DSR Unit Rate MR AMOUNT DSR AMOUNT MR
Description Unit Qtys
(INR) (INR) ITEMS ITEMS
complete as required.
39.20 Supplying and drawing following core Multi mode
Fiber Optic Cable having corrugated steel armoring,
leser optimize 50/125 μm with HDPE jacket, LSZH
(Low smoke Zero Halogen), Tight-buffered or loose
tube, maximum attenuation: < 3.5 dB/km at 850 nm, <
1.5 dB/km at 1300 nm, bandwidth > 2000 MHz-km at
850 nm, > 500 MHz-km at 1300 nm compliance and
certifications: ISO/IEC 11801 Ed. 2.2, ANSI/TIA-568-
C.3, ITU-T G.651.1 RoHS compliant. Multi Mode Fiber
shall be Central-loose tube filled with Thixotropic jelly,
duly following Standards: ISO 11801, IEC 60793-
1/60794-1-2, ITU-T-REC G.652D and Telecordia GR-
20-core, High quality Electro Chromium Coated
Corrugated Steel tape (ECCS ) and HDPE- Sheath,
Operating ambient Temperature should be – 5 0C to
+50 0C and Storage Temperature should be – 5 0C to
+50 0C, Maximum Attenuation ± 3.5 dB/km at
Operational Wavelength 850 nm and ± 1.5 dB / km at
Operational Wavelength 1300 nm . type of fiber
should be 50/125 / G.652D & Refractive Index should
be 1.483/1.478, The value for Mode-filed,Cladding
Diameter 50 ± 2.5 μm and 125 ± 1μm correspondingly
i/c splicing & marking etc complete as required.
39.20.1 6 Core Multi Mode Optical Fiber Cable Mtr 325 87.00 28,275.00
7.0 39.2 Supply and fixing following port Rack Mount loaded
LIU with pigtail, Front-mounted cable saddles for
jumper management, suitable to manage both splices
and terminations, Pre-assembled shelves in multiple
configurations, Rubber fiber slotted bracket built-in,
metal splice shelf to protect the fibers, 2 fiber spools
built-in for 900μm tight buffered fiber storing, Capable
of storing up to 3 meters of 900μm tight buffered fiber
per adapter, Removable front and rear covers for
better access to interior of LIU, Should be Single /
Multi mode LC Type fully loaded. Accessory kit
consists of cable ties, mounting ear screws, and spiral
wrap tube etc complete as required.
Digitally signed by VARUN
ADMIN CUM ACADEMIC BLOCK COLLEGE OF HORTICULTURE, MORENA
S.No. Unit Rate DSR Unit Rate MR AMOUNT DSR AMOUNT MR
Description Unit Qtys
(INR) (INR) ITEMS ITEMS
Supplying and fixing Patch Cord of Optical Fiber Multi
Mode or Single Mode LC to LC Fiber Duplex having
high precision ceramic ferrule with good concentricity,
Fiber corning single mode G652D, Cable Type 2mm
DSR2025 with Mechanical specification Apex Offset < 50 μm,
39.22 Fiber Height + 100 nm, End-face radius of Curvature
7mm < R <25mm, Repeatability < 0.2 db, Working
ambient Temperature – 5 0C to +50 0C, Storage
Temperature – 10 0C to +50 0C, Length -- 2meter,
Type -- LC-LC Duplex etc complete as required.
9.0 39.3 Supplying, installation, Testing and commissioning of
following capacity 24 port Layer 2 indoor Network
Switch having features and specifications etc. as
mentioned here under: At least 24 X RJ-45 Gigabit
Ethernet Ports and additional 2 X 10G Base -T with 4
X SFP Ports with non-blocking architecture by having
Switching capacity of min. 168Gbps and packet
forwarding rate of 125Mpps or higher, 16K MAC table.
Console Port, USB port, Stacking support of min. 8
units per stack. Internal dual AC Power supply, STP,
RSTP, MSTP, BPDU Filter, BPDU Restriction, Min. 9K
Jumbo Frame, LBD, IGMP Snooping V1/V2/V3, MLD
Snopping V1/V2. IGMP /MLD Groups 1K or more,
IPv4/IPv6 Loopback Interface, 16 L3 IP Interface, Ipv6
ND, VRRPv3, UDP Helper, ECMP. VLAN: 802.1Ǫ,
Port based, Ǫ-in-Ǫ, Multicast VLAN, Protocol VLAN,
VLAN Trunking, DHCP Snopping, Server, server
Screening. RADIUS , TACACS+ Authentication, ǪoS:
802.1P, 8 queues per port, ǪoS : WRR, Strict+WRR,
WRED, 802.1p. ACL: MAC based, IPv4C IPv6,
TCP/UDP Port number, time based ACL, TFTP Client,
SNMP V1, v2c, v3, SNMP traps, RMON, DHCP
server, relay, client, LLDP, LLDP-MED, OAM, Dying
Gasp, 802.3ah, sflow, RIP, OSPF v2/v3, policy based
route, SSL, SSH. 6 kV surge protection on all Gigabit
Ethernet ports and on all GE RJ-45 access ports.
Certifications: UL, CE, FCC, RoHS, MTCTE,
OEM/Product must be on Trusted Telecom Portal of
Department of Telecommunication, Government of
India etc. complete as required.
39.3.1 24 port PoE Layer 2 Network Switch with PoE
Support of 370W or higher with each copper port
supporting 802.3at PoE+ min. Nos 27 125,393.00 3,385,611.00
10.0 39.4 Supplying, installation, Testing and commissioning of
following capacity 24 port Layer 3 Network Switch
having features and specifications etc. as mentioned
here under: At least 20 X RJ-45 Gigabit Ethernet Ports
and additional 4 combo 10/100/1000 base-t/SFP Ports
with additional 4 SFP+ ports non-blocking architecture
Digitally signed by VARUN
ADMIN CUM ACADEMIC BLOCK COLLEGE OF HORTICULTURE, MORENA
S.No. Unit Rate DSR Unit Rate MR AMOUNT DSR AMOUNT MR
Description Unit Qtys
(INR) (INR) ITEMS ITEMS
by having Switching capacity of min. 128Gbps and
packet forwarding rate of 95Mpps or higher, 16K MAC
table. Console Port, USB port, Internal AC Power
supply with operating temperature of 0 to +50 0C.
Stacking port with stacking support of minimum 8 units
per stack. 48K Mac address, 9K or more Jumbo
frame, ERPS with enabling ring to converge in less
than 50 ms from node or link failure, Static routing,
Static, 6to4, ISATAP and GRE, IPv6 Neighbor
Discovery (ND), BGP, ISIS, MPLS, VRRP v2,
OSPFv2/v3, PBR, Route Redistribution, RIPv1/v2/ng,
IP Helper all L3 Protocols should support from day 1
for both IPv6 and IPv4, 802.1x, Port security , Radius
C TACACS+ authentication C accounting, DAD, DAI,
DoS attack prevention, SSH, Guest VLAN, IP Access
List, MAC Access List. Multicast: VLAN, PIM-SM, PIMDM,
PIM- SDM, PIM-SMv6, DVMRP v3 and MSDP,
IGMP C MLD Snooping, Flow mirroring, IGMP C MLD
Snooping Ǫuerier, Per-VLAN IGMP C MLD Snooping.
SNMP, Dual configurations, Multiple images, RMON,
LLDP/LLDP-MED, sFlow, DHCP/BOOTP Client,
IPv4/IPv6, Syslog server, Debug command, 802.3ah
Ethernet Link OAM, 802.1ag Connectivity Fault,
Y.1731 OAM, 802.1Ǫbb Priority- based Flow Control
(PFC), Dying Gasp, Cable Diagnostics , 6 kV surge
protection on all Gigabit Ethernet ports and on all GE
RJ-45 access ports. Certifications: UL, CE, FCC,
RoHS, MTCTE, OEM/Product must be on Trusted
Telecom Portal of Department of Telecommunication,
Government of India etc. complete as required. Nos 1.00 193,791.00 193,791.00
11.0 39.8 Supplying, Installation, Testing and commissioning of
indoor Wireless Access Point for High density use
having features and specifications etc. as mentioned
here under- WiFi6 802.11ax 574Mbps (2.4GHz) +
2402Mbps (5GHz), WIFI 6 Certified, 1 x RJ45 console
port, MG 2.5G LAN POE Port, factory reset,
WPA/WPA2/WPA3™ Personal/Enterprise, WEP
64/128-bit, SSID broadcast disable, MAC address
access control, Internal RADIUS server, SNMP,
Customizable Captive Portal, Auto Channel, Works as
Access Point, WDS, WDS with AP, Wireless Client .,
Web (HTTP), Secure Socket Layer (SSL), Traffic
control, Support ATF/Fast Roaming/Band Steering,
Supports enhanced security – WPA-PSK/WPA2-
PSK/WPA3-PSK and RADIUS client, and Cipher
negotiation, and MAC/ IP ACL for networks,
Certifications: MTCTE, CE, FCC.
Works as Standalone, Compatible with S/W & H/W
Controller with addtional features like - Real-Time
Monitoring and Alerts, Rich Advanced Features,
Digitally signed by VARUN
ADMIN CUM ACADEMIC BLOCK COLLEGE OF HORTICULTURE, MORENA
S.No. Unit Rate DSR Unit Rate MR AMOUNT DSR AMOUNT MR
Description Unit Qtys
(INR) (INR) ITEMS ITEMS
Centralized Device Management, Role-Based
Administration, Real-Time Monitoring, VLAN and
Access Control, Auto RF Management and Bandwidth
Optimization, Multi-SSID and Captive Portal
Authentication.OEM/Product must be on Trusted
Telecom Portal of Department of Telecommunication,
Government of India etc. complete as required. Nos 25 35,559.00 888,975.00
12.0 39.6 Supplying, Installation, Testing and commissioning of
small form-Pluggable (SFP) for Network Switches.
Must be hot Pluggable, RoHS Complaint, etc.
complete as required.
39.6.3 10 G SFP + Single Mode/Multi Mode Nos 30 14,972.00 449,160.00
39.23 Supplying and fixing of following size Wall Mount
Rack having Fixed Structure with 0.8mm CRCA
Sheet, completely knocked-down condition (CKD)
Shape, Vertical Mounting Rail 1.6 mm with 'U'Marking,
Minimum 2 cable entry/exit provision at Top and
bottom with rubber protection, Front 5mm Toughened
Glass with lock, wall mounting kit, Powder coated
Color- RAL- 7035, complied with UL & RoHS, 2 x 6
sockets 16A power distribution units, 3 numbers
closed cable organizer, Hardware mounting screws
packet of 20 x 1 number, etc. complete as required.
39.25 Supplying and fixing 42U Rack with 6 inch Castor
wheels and front brake Floor Standing Rack with
Main Frame Pillar of 1.6mm CRCA Sheet with
removable side panels, L- Shape adjustable Vertical
Mounting Rail of 2mm with 'U'Marking completely
knocked-down condition (CKD) Shape, fitted with 4
number cooling fans, minimum 8nos two line cable
entry/exit provision at top and bottom with rubber
protection, Front door 5mm Toughened Glass with
MS frame or MS perforated with lock, Rear MS vented
or perforated door, Powder coated Color- RAL- 7035
or black, complied with UL & RoHS, 2 x 6 sockets 16A
power distribution units, 3 numbers closed cable
organizer, Hardware mounting screws packet of 20 x 1
number, etc. complete as required. Each 2 32,954.00 65,908.00
Total Amount 6647960.0 276652.0
Total Amount 6647960.0 276652.0
Digitally signed by VARUN
ADMIN CUM ACADEMIC BLOCK COLLEGE OF HORTICULTURE, MORENA
SECTION C - IPPBX SYSTEM
S.No. Unit Rate
Unit Rate MR AMOUNT DSR AMOUNT MR
DSR Description Unit Qtys DSR
(INR) ITEMS ITEMS
38.2 Supplyiing, installation, testing and Commissioning of
IP at its core with IP switching technology and 100%
non blocking communication system with 04 Port
Voicemail, 04 Port FXS, 04 Port FXO, 1 PRI Trunk
lines (30 Channels) Circuit with CLIP Facility, min 100
IP users License with provision for further additions,
100 analog users, 01 Number IP based Operator
Console, 45 Party Conference, Speed Dial, Music on
Hold, Internal/ External ring difference, Call Barring,
Call Pickup. The system should be redundant which
offer 100% duplication of power supply and CPU card
and to match the hybrid IP-PBX as per technical
specification including supporting accessories etc
complete as required. The system should have valid
TEC GR approval from DoT. Each 1 1,246,949.00 1,246,949.00
Supply Installation, Testing and Commissioning of Integrated Viocemail System 4 Level IVR
software with 6 different languages and 4 time schedule(As per OEM), and License for web
integration for aspire net license integrated with hub exchange.
Supplying, Installation, Testing and commissioning of
CAT6 Copper Information Outlet (IO) with face plate
of color as per site requirement, should have ETL/UL
3.0 39.14 verification program certificate for compliance with Nos 115 212.00 24,380.00
ANSI/TIA-568.2-D. All copper Cable and Components
should be from same OEM to maintain compatibility
and interoperability etc. complete as required.
Supplying, Installation, Testing and commissioning of
following CAT6 Patch Cord should have ETL/UL
verification program certificate for compliance with
ANSI/TIA-568.2-D etc. complete as required.
39.12.1 Copper Patch Cords of length 1m (3ft) Nos 190 151.00 28,690.00
Supply, Installation, testing and commissioning of 50 Port Telephone Jack Panel complete as
39.2 Supplying, drawing, Installation, Testing and
commissioning of CAT6 UTP LSZH 23AWG Twisted
Pair Cable in existing conduit/ on surface, Category 6
Unshielded Twisted Pair, 4 pair should be complied as
per UL/ETL verification program for compliance with
ANSI/TIA-568.2-D standard. Outer diameter should be
in the range of 6.1mm nominal with Operating
Temperature Range : -5° to +60°C, Bending Radius :
< 4 X Cable Diameter at –5°C ± 1°C and Pulling Force
: 11.5Kg etc. complete as required.
Digitally signed by VARUN
ADMIN CUM ACADEMIC BLOCK COLLEGE OF HORTICULTURE, MORENA
S.No. Unit Rate
Unit Rate MR AMOUNT DSR AMOUNT MR
DSR Description Unit Qtys DSR
(INR) ITEMS ITEMS
Supplying, Installation, Testing & Commissioning of
Type 1 IP Phone having 2 VoIP account, 120 x40 DOT
8.0 matrix screen with backlight, Full HD duplex speaker Nos 8 11,698.00 93,584.00
phone, IPV6, Gigabit Etherent, PoE etc. complete as
Supply Installation Testing and Commissioning of Type 2 Level IP Phone complete as requried
Supply Installation Testing and Commissioning of Type 3 Level IP Phone complete as requried
Supply Installation Testing and Commissioning of Type 2 Level IP with DSS Console Operator
Phone complete as requried
Digitally signed by VARUN
ADMIN CUM ACADEMIC BLOCK COLLEGE OF HORTICULTURE, MORENA
SECTION D - CCTV SYSTEM
Unit Rate DSR Unit Rate MR AMOUNT DSR AMOUNT MR
Description Unit Qtys
(INR) (INR) ITEMS ITEMS
1.0 DSR2025 5/6MP IP IR Dome Camera
40.5 Supplying Installation Testing and Commissioning of
5/6MP IP IR Dome Camera having following
specifications and features etc :-
1)Type of Camera: Dome Camera
2) Image Sensor: 1/2.8" or better progressive Scan
CMOS get color image even at night condition
3) Signal System: PAL/NTSC
4) Minimum Illumination: 0.008Lux@ F1.4, AGC ON, 0
lux with IR or better
5) Imaging: 1/3s to 1/30000s Shutter Support, Auto
Gain Control , White Balance- Auto, Back Light
Compensation, Multi zone Privacy Masking, HLC,
Digital Watermarking.
6) On Screen Display: Camera should display Camera
title, Date & Time in live & recorded video both.
7) Signal to Noise Ratio: > 50 dB
8) Day & Night: True Day & Night High Performance
Mechanical IR cut filter with auto switch, IR Source-
Inbuilt IR LED's with effective distance upto 50 Mtrs
integrated IR 30 Mtrs for colour view in night.
9) Video Compression (Minimum): H.265 or better,
Audio:- G.711U/A, G.711Mu, G.726, AAC, G.723
10) Wide Dynamic Range: WDR (120dB or more)
11) Digital Noise Reduction: DNR (2D/3D) On/Off
12) Streaming: Triple streaming, configurable
13) Video Streaming & Frame Rates: Triple streaming
Main stream: 5/6MP @25/30 fps, Sub streams:
D1@25/30 fps or better
14) Image Setting: Rotate Mode, saturation,
brightness, contrast, sharpness adjustable through
client software or web browser
15) Profile Management: User configuration import,
16) Security: User Authentication, Water Marking
17) Onboard Storage: Camera should support built-in
Micro SD/SDHC/SDXC Card slot upto 512 GB. It
should be supplied with minimum 128GB memory
18) Recording Management: Format SD, overwrite,
storage management, video to NAS device,
19) Edge Analytics : Tripwire, Intrusion, Motion
20) Alarm Trigger : Motion/tampering detection;
network disconnection detection; IP conflict detection;
memory card state detection; memory space detection
21) Alarm Support: It should have 1/1 Alarm In/ Out
Digitally signed by VARUN
ADMIN CUM ACADEMIC BLOCK COLLEGE OF HORTICULTURE, MORENA
Unit Rate DSR Unit Rate MR AMOUNT DSR AMOUNT MR
Description Unit Qtys
(INR) (INR) ITEMS ITEMS
22) Audio Support: It should have 1x Built-In Mic and
1/1 Audio In/ Out Port for external Mic. and Speaker
(As per site requirement) with G.711U/A/ G.711Mu/
AAC/ G.726 audio compression
23) Network Protocol: SFTP, IPv6, IPv4, DNS,RTCP,
NTP, RTP, HTTP, HTTPS, SNMP TCP/IP, PPPoE,
NFS, UDP, ICMP, SSL, DHCP, SMTP, RTSPS,
24) System Capability: ONVIF
25) VMS: Camera shall support open source VMS
26) Cyber Security: trusted boot, AES 256-bit
Encryption, Configuration encryption, trusted
execution, Digest, security logs, , account lockout,
video encryption, IP/MAC filtering, HTTPS, trusted
27) Ethernet: 1 RJ 45 10/100 Ethernet port
28) Power Input: The camera should support
simultaneous dual power input—12 VDC (via power
adapter) and PoE—to ensure continuous operation in
the event of a failure in one power source.
29) Power Requirement: 12VDC/24VDC/PoE
30) Enclosure: IP67 weather proof, IK10
31) Operating Condition: Ambient Temperature:- (-)
05°C to 50°C, humidity 95% (max) (non-condensing)
32) IR life: 40000 hours or higher
33) Video Bit rate: 32 KBPS - 8 MBPS or better
34) Standards: BIS with ER, STQC Certified, CE, FCC
40.5.1 5MP/6MP IP IR 2.8/ 3.6/6/8/12 mm fixed lens (as per site requirement) Dome Camera. Each 50 12,800.00 640,000.00
2.0 DSR2025 5MP /6MP IP IR Bullet Camera
40.6 Supplying Installation Testing and Commissioning of
5MP/6 MP IP IR Bullet Camera having following
specifications, type of lens and features etc :-
1) Type of Camera: Bullet Camera
2) Image Sensor: 1/2.8" or better progressive Scan
CMOS get color image even at night condition
3) Signal System: PAL/NTSC
4) Minimum Illumination: 0.006Lux@ F1.4, AGC ON,
0 lux with IR or better
5) Imaging: 1/3s to 1/30000s, Auto Gain Control ,
White Balance- Auto, Back Light Compensation, Multi
zone Privacy Masking, HLC, Digital Watermarking.
6) On Screen Display: Camera should display
Camera title, Date & Time in live & recorded video
7) Signal to Noise Ratio: > 50 dB
8) Lens Type & Focus: as given below.
9) Day & Night: True Day & Night High Performance
Digitally signed by VARUN
ADMIN CUM ACADEMIC BLOCK COLLEGE OF HORTICULTURE, MORENA
Unit Rate DSR Unit Rate MR AMOUNT DSR AMOUNT MR
Description Unit Qtys
(INR) (INR) ITEMS ITEMS
Mechanical IR cut filter with auto switch, IR Source-
Inbuilt IR LED's with effective distance upto 50 Mtrs
integrated IR and 30 Mtrs for colour view in night.
10) Video Compression (Minimum): H.265 or better,
Audio:- G.711U/A, G.711Mu, G.726, AAC, G.723
11) Wide Dynamic Range: WDR (120dB or more)
12) Digital Noise Reduction: DNR (2D/3D) On/Off
13) Streaming: Triple streaming, configurable
14) Video Streaming & Frame Rates: Triple streaming
, configurable Main stream: 5MP/6MP @25/30 fps,
Sub streams: D1@25/30 fps or better
15) Image Setting: Rotate Mode, saturation,
brightness, contrast, sharpness adjustable through
client software or web browser
16) Profile Management: User configuration import,
17) Security: User Authentication, Digital Water
18) Onboard Storage: Camera should support built-in
Micro SD/SDHC/SDXC Card slot upto 512 GB. It
should be supplied with minimum 128GB memory
19) Recording Management: Format SD, overwrite,
storage management, video to NAS device,
20) Edge Analytics: Tripwire, Intrusion, Motion
21) Alarm Trigger : Motion/tampering detection;
network disconnection detection; IP conflict detection;
memory card state detection; memory space detection
22) Alarm Support: It should have 1/1 Alarm In/ Out
23) Audio Support: It should have 1x Built-In Mic and
1/1 Audio In/ Out Port for external Mic. and Speaker
(As per site requirement) with G.711U/A / G.711Mu/
AAC/ G.726 audio compreesion
24) Network Protocol: SFTP, IPv6, IPv4, DNS,RTCP,
NTP, RTP, HTTP, HTTPS, SNMP TCP/IP, PPPoE,
NFS, UDP, ICMP, SSL, DHCP, SMTP, RTSPS,
25) System Capability: ONVIF
26) VMS: Camera shall support open source VMS
27) Cyber Security: trusted boot, AES 256-bit
Encryption, Configuration encryption, trusted
execution, Digest, security logs, account lockout, ,
video encryption, IP/MAC filtering, HTTPS, trusted
28) Ethernet: 1 RJ 45 10/100 Ethernet port
29) Power Input: The camera should support
simultaneous dual power input—12 VDC (via power
adapter) and PoE—to ensure continuous operation in
Digitally signed by VARUN
ADMIN CUM ACADEMIC BLOCK COLLEGE OF HORTICULTURE, MORENA
Unit Rate DSR Unit Rate MR AMOUNT DSR AMOUNT MR
Description Unit Qtys
(INR) (INR) ITEMS ITEMS
the event of a failure in one power source.
30) Power Requirement: 12VDC/24V DC/PoE
31) Enclosure: IP67 weather proof, IK10
32) Operating Condition: Ambient Temperature:- (-
)05°C to 50°C, humidity 95% (max) (non-condensing)
33) IR life: 40000 hours or higher
34) Video Bit rate: 32 KBPS - 8 MBPS or better
35) Standards: BIS with ER, STQC Certified, CE, FCC
40.6.2 5MP/6MP IP IR 2.7 to 4 mm ~12 to 13.5mm or better Varifocal Motorized lens outdoor
40.11 Supplying Installation Testing and Commissioning of
following Channel Network Video Recorder (NVR)
with camera licenses to record for all channels having
specifications and features etc as mentioned below :
1) Network Video Recorder Embedded/ Installed OS
(Linux) along with Camera Licenses to record per NVR
and to provide a live view, storage and simultaneously
Multi-channel playback of all IP camera or more and
must be ONVIF with minimum support of 384 Mbps
incoming Bandwidth.
2) NVR should support video compressions : H.265 or
better, H.264, MJPEG.
3) Must support 1 channel RCA Input, 2 channel RCA
Output for Two-way Talk with G.711U/A, G.711u,
PCM, G726 audio compressions.
4) Intelligent auto power on when power resumes after
5) Storage: It should support minimum 8 SATA Slots
with 20TB capacity/ Slot and RAID support of RAID
6) Connectivity Interface : 2 Nos. x 10/100/1000 Mbps
Ethernet Ports, 1x RS485, 1x RS232, 1x eSATA Port
7) Backup Interface : Its should have 4 Nosx USB port
(2x USB3.0, 2xUSB2.0)
8) Video Output Ports: 2x HDMI and 2 VGA
9) Alarm Ports: It should have 16/8 Ch In/ Out ports to
connect various type of external sensors and output
devices like hooter/ Siren etc.
10) Email & SMS Altert options: Option for SMS/
Email Alerts to minimum 5 designated mobile number
for power failure, HDD failure, vandalism, tempring,
network disconnection and panic
11) Web & Mobile Application: Web, Mobile app ( For
iPhone, iPad, Android Phone) for alerts and viewing.
12) Protocols: HTTP, HTTPS, TCP/IP, IPv4/IPv6,
UDP, DHCP, DNS, SMTP, UPnP, IP Filter, PPPoE,
FTP, DDNS, Alarm Server, IP Search, Multicast, Auto
Digitally signed by VARUN
ADMIN CUM ACADEMIC BLOCK COLLEGE OF HORTICULTURE, MORENA
Unit Rate DSR Unit Rate MR AMOUNT DSR AMOUNT MR
Description Unit Qtys
(INR) (INR) ITEMS ITEMS
Registration, ONVIF (Profile T, Profile S, Profile G),
CGI, SDK and OEM Cloud for remote monitoring
without any public IP need.
13) Standards: CE, FCC, RoHS, BIS Certified
14) Power Supply : Should support AC100-240V,
50/60Hz Power supply.
15) Operating Condition : -5°C to 50°C, humidity 90%
(max) (non-condensing)
16) The VMS application shall support all the features
& functionalities of the offered cameras.
17) VMS should consist Licenses for all channels to
record Cameras with General, motion detection,
intelligent, alarm and POS recording modes. VMS
should be provided with Camera Licenses , with no
dependency of VMS licenses by binding with the MAC
address of the cameras to achieve the functionality.
18) The NVR OEM shall be responsible for providing a
mobile application compatible with both Android and
iOS devices, enabling remote monitoring and playback
of cameras/NVR footage.
19) The OEM must provide its own DDNS server
hosted in India, eliminating the need for a public IP
address for remote monitoring over the Internet.
20) Must support Continuous, Alarm, Motion, Instant,
Panic Recording Mode
21) It should support Resolution: 32MP; 24MP; 16MP;
12MP; 8MP; 5MP; 4MP; 1080p; 720p; D1; CIF; QCIF
22) When alarm recording is enabled and an event
occurs, you can click the alarm icon on monitoring
page to view the alert details. The snapshot function is
supported on monitoring and playback page
23) The Network Video Recorder (NVR) shall be
configured to send email whenever a system message
is created or an alarm event occurs. The email server
shall be a valid SMTP server. Each recipient email
address shall be configured to receive any
combination of critical, warning, or informational
messages or alarm notifications. When an alarm
occurs, the email message includes the NVR name,
time of alarm and a list of camera that is configured to
record upon alarm
24) It should have Web and GUI interface.
25) Built-In Artificial Intelligence: NVR should have
- 2 Channel face detection and recognition, - Minimum
4 Channel perimeter protection, - Minimum 8 Channel
Smart Motion Detection
26) Face Recognition Database Capacity: It should
support total Blacklist and Whitelist capacity of
Minimum 20,000 Faces or more with Face Detection
Digitally signed by VARUN
ADMIN CUM ACADEMIC BLOCK COLLEGE OF HORTICULTURE, MORENA
Unit Rate DSR Unit Rate MR AMOUNT DSR AMOUNT MR
Description Unit Qtys
(INR) (INR) ITEMS ITEMS
speed of 12 face images/sec and facility to add Name,
gender, birthday, address, credential type, credential
No., countries & regions and state to each face image.
27) Face & Human Attributes Search: Search
Pictures/ Video by Gender, age group, glasses,
expressions, face mask, beard, Top color, top type,
hat, bag, age, gender and umbrella.
28) ANPR Capability: It should support ANPR
Camera with License plate, plate color, vehicle body,
vehicle model, vehicle logo, calling, seatbelt, vehicle
registration location etc vehicle attributes.
29) Alarm Notifications based on: Motion detection,
video tampering, video loss, scene changing, PIR
alarm, Camera external alarm, Face detection, face
recognition, perimeter protection (intrusion and
tripwire), ANPR, people counting, stereo analysis,
crowd distribution, heat map, Disk Full, Storage Error,
IP Conflict and abnormal behavior of fan,
cybersecurity exception
30) Alarm Notification should be linked with Recording,
snapshots, Camera external alarm output, buzzer,
logs, presets and email.
31) General AI Based Search: Search Pictures by
channel, time, event type, target classification (Fall
Detection, People Approach Detection, People No.
Exception Detection, People Staying Detection,
Violence Detection.
32) Smart playback function: Should support smart
search for the selected area in the video and smart
playback to improve the playback efficiency
33) VCA (Video Content Analytic): Should support
multiple video contented analytics based on camera
34) Analytics by NVR: Perimeter protection and face
40.11.2 64 Channel Network Video Recorder (NVR) having
display split :- Main screen: 1/4/8/9/16/25/36/64, 2nd
40.12 Supplying, Installation, Testing and Commissioning
following capacity Serveillance grade Hard Disk with
upto 256MB/s Transfer Rate, 256 MB Cache, 7200
RPM Disk Speed, 3.5 inch form factor, SATA
Interface, BSMI, ICES-003/NNB-003, CE, FCC, KC,
Maghreb, RCM, UKCA, VCCI, CB-Scheme, TUV, UL
Certifications. Each 10 20,119.00 201,190.00
40.12.3 8TB (Terabytes)
Digitally signed by VARUN
ADMIN CUM ACADEMIC BLOCK COLLEGE OF HORTICULTURE, MORENA
Unit Rate DSR Unit Rate MR AMOUNT DSR AMOUNT MR
Description Unit Qtys
(INR) (INR) ITEMS ITEMS
Supply, Installation , Testing & Commissioning of 55'' 4K HDR Professional DIsplay Panel,
24x7 Application, 75" diagonal LED Panel, UHD (3840 x 2160) Resolution, Response Time:
8ms, LED backlight, landscape/portrait, wide array of inputs, 400 nit brightness, Portrait/tilt,
Aspect Ratio: 16:9, Built in Speaker(10W x 2), fan-less LCD design, Control: LAN/HDMIx2,
RS232 Control with accessories.
Supplying, Installation, Testing and commissioning of
CAT6 Copper Information Outlet (IO) with face plate
of color as per site requirement, should have ETL/UL
7.0 39.14 verification program certificate for compliance with Nos 75 212.00 15,900.00
ANSI/TIA-568.2-D. All copper Cable and Components
should be from same OEM to maintain compatibility
and interoperability etc. complete as required.
Supply, Installation, testing and commissioning of Face Plate : Flush & surface mount.
Polycarbonate Hi-Grade Plastic FR Grade with ABS underplate & CRCA metal fram & UV
Resistant 850 degree C/ Glow Wire Test. The face plate should be compatible for Cat5e, Cat6
range of RJ45 and different types of AV connectors.The face plate Size should be of minimum
39.2 Supplying, drawing, Installation, Testing and
commissioning of CAT6 UTP LSZH 23AWG Twisted
Pair Cable in existing conduit/ on surface, Category 6
Unshielded Twisted Pair, 4 pair should be complied as
per UL/ETL verification program for compliance with
ANSI/TIA-568.2-D standard. Outer diameter should be
in the range of 6.1mm nominal with Operating
Temperature Range : -5° to +60°C, Bending Radius :
< 4 X Cable Diameter at –5°C ± 1°C and Pulling Force
: 11.5Kg etc. complete as required.
Supplying Installation Testing and Commissioning of
24 port Cat6 Patch Panel loaded. Must be of 1U height
with clear label holders and white label with the panel. 24 Ports Cat-6 Patch Panel should
verification program certificate for compliance with
ANSI/TIA-568.2-D etc. complete as required.
Total Amount 2219227.0 340,491.00
Total Amount 2219227.0 340,491.00
Digitally signed by VARUN
ADMIN CUM ACADEMIC BLOCK COLLEGE OF HORTICULTURE, MORENA
SECTION 1 - AUDIO VIDEO SOLUTION
Unit Rate DSR Unit Rate MR AMOUNT AMOUNT MR
Description Unit Qtys
(INR) (INR) DSR ITEMS ITEMS
CONFERENCE ROOM
Supply, installation, testing and commissioning of 85" LED Display having 4K Resolution
(3,840 x 2,160 (16:9)), 500 nit Brightness, Landscape/Portrait Orientation, 4,000:1 Contrast
Ratio (typ.), 24/7 Operational Hours, 2 x HDMI Port, 1x DP Port, 2x USB Port, Stereo mini
Jack, External Control : RS232C (In/Out), RJ45, UHD Signage Compatiable, 1.6GHz Quad-
Core Processor, Temperature Sensor, Ambient Sensor, Auto Level, Wi-Fi complete as
Supply, installation, testing and commissioning of 4K (30 fps) Video conference system having
AI based smart camera technology, Dual 4K lenses, NoiseBlockAI and Acoustic Fence
technologies, Privacy Shutter, 120-degree and 70 degree HFOV, Group framing, speaker
framing and people framing, Two way stereo with bass ports Speaker, Certified for Microsoft
Teams, Zoom, Google Meet, Diagonal field of view (dFoV): 140° (wide); 78° (narrow), Camera
Megapixels: 2 x 20 MP, External I/O ports: 1 USB Type-C® 5Gbps signaling rate 2 USB Type-
A 5Gbps signaling rate, Network capabilities: IPv4; IPv6; 1x 10/100/1G Ethernet; AutoMDIX;
H.323.Lost Packet Recovery (LPR) technology; Dynamic bandwidth allocation, Beamforming
microphone complete as required.
SITC of Cable Manager, table mount modular multi-Connection Solution with inputs for 1 HDMI
3.0 MR-33 active input plate, 2 LAN, 2 Universal AC Power Outlet , etc. Nos 3 46,567.00 139,701.00
Supply, Installation, Testing & Commissioning of 4x4 HDMI matrix switchers for computer and
video signals at resolutions up to 4K/60 with 4:4:4 color sampling. It should support HDMI 2.0
specifications, including data rates up to 16 Gbps, HDR, HD lossless audio formats. The
4.0 MR-34 HDCP 2.3-compliant matrix switchers incorporate HDMI input equalization and output Nos 1 377,096.00 377,096.00
regeneration, to ensure reliable system operation. The switcher should have inbuilt option of
Digital audio de-embedding from any input and assigned to digital or analog stereo outputs for
ease of integration.
Supply, Installation, Testing & Commissioning of Control System, Supports USB mass
storage class devices via the rear panel USB 2.0 host port, supports computer console via the
front panel USB 2.0 device port, Ethernet, 100/1000 Mbps, auto-switching, auto-negotiating,
auto-discovery, full/half duplex, RS-232/422/485, For 2-way device control and monitoring,
COM port supports RS-232 up to 115.2k baud with software handshaking, SDRAM 2 GB,
Memory Card Supports SD and SDHC cards up to 32 GB, Flash 8 GB, External Storage,
Supports USB mass storage devices up to 1 TB, RELAY OUTPUT 1–8, (2) 8-pin 3.5 mm
detachable terminal blocks, 2.1 x 5.5 mm DC power connector; 24 VDC power input; PW-
2420RU power pack included; Passes through to the NET port to power,
Supply, installation, testing and commissioning of Multi-Touch display with User Control
Interface (UCI) Deployment etc all complete with Sleeves & induction based, wall mounted
8.0 MR-36 docking station, 32.78 cm or 27.59 cm (13” or 11”) Liquid Retina display1 P3 wide colour True Nos 1 200,471.00 200,471.00
Tone Antireflective coating programmable network appliance specifically designed to control
Supply, installation, testing and commissioning of digital signal processors leverages the
highest quality components and the expertise of veteran audio industry engineers to deliver a
revolutionary audio processing platform, Analog-To-Digital Conversion 24-bit 48 kHz,
Frequency Response 20 Hz to 20 kHz ±0.5 dB, Connectors MIC/LINE INPUTS 1 – 8, (8) 3-pin
3.5 mm detachable terminal blocks; Balanced microphone/line-level audio inputs; Input Level:
+24 dBu maximum; Gain Range: 66 dB; Input Impedance: 10k Ohms balanced; Phantom
Power: +48 Volts DC, 12 mA, software enabled/disabled per channel.
Digitally signed by VARUN
ADMIN CUM ACADEMIC BLOCK COLLEGE OF HORTICULTURE, MORENA
Unit Rate DSR Unit Rate MR AMOUNT AMOUNT MR
Description Unit Qtys
(INR) (INR) DSR ITEMS ITEMS
Supply, installation, testing and commissioning of Ceiling Array Microphone, Patented
automatic dynamic beamforming, TruVoicelift 28 Electret condenser capsules, Perfect speech
intelligibility, Dante or Analog Output PoE, Certified for: MS Teams, Zoom, DingTalk and
Tencent, Exclusion Zones, Priority Zone, Network/Control One RJ-45 Ethernet socket for PoE
10.0 MR-38 supply and data/ control, Transducer principle Pre-polarized condenser microphone, AF Nos 2 519,208.00 1,038,416.00
frequency response 160 Hz to 18,000 Hz, Sensitivity 0 dBV/Pa (988 mV/Pa), Signal-to-noise
ratio 83 dB(A), Latency 4 ms, Equivalent noise level 11 dB(A), Number of KE 10-237
microphone capsules 28, Pick-up pattern Beam pattern, Max . sound pressure level 104 dB
SPL, Dynamic range 93 dB(A)
SITC of 2.5 inch x 12 drivers with 2 x passive radiators, frequency response 65Hz - 14KHz,
200 watts continuous, 800 Watts peak, Transformer taps : 120W, 60 W; 30 W; 15 W; 8 W,
Dispersion angle : 130° x 20° (narrow) / 40° (wide); Axial sensitivity: 93dB, Maximum SPL @ 1
11.0 MR-39 m: 126dB (narrow) / 123dB(wide), IP56c rating , and EN54-24 Type B certified for all weather Nos 2 153,230.00 306,460.00
applications also includes Accessories to to mount. Bidder to submit MAF for Audio system.
Supply, installation, testing & Commissioning of Ceiling 4-inch coaxial two-way loudspeaker
Frequency range (-10 dB) (Hz) 1 70 Hz – 20,000 Hz, Maximum SPL (continuous) (dB) 2 106
dB, Maximum SPL (peak) (dB) 2 . 112 dB, Coverage angle conical (°) 130°, Power handling
(continuous) (W) 4 70 W, Transformer taps 70 V line (W) 30 W; 15 W; 7.5 W; 3.75 W; 1.88 W
complete as required.Bidder to submit MAF for Audio system.
SITC of 4-channel power amplifier shall have a total power of 600 W, capable of power
sharing either 4-ohm, 8-ohm, 70 V or 100 V conditions on any channel simultaneously, shall
have thermal design to operate in extreme thermal conditions < 45 °C without reduction or
shutdown. The amplifier shall be equipped with a PFC power supply and protections to ensure
reliable and safe operation including High Frequency Limiter , Output Current Limiter , High
Frequency Protection, DC Protection, Over Current Protection, Mains Fail Protection, Output
Balance Protection, Over Temperature Protection, Over Voltage Protection etc.
SITC of 2 Conductor 16 AWG Speaker Cable, stranded Bare copper conductors, PVC/Nylon
insulation, PVC jacket (as per actual) etc all complete
SITC of 2 Conductor 24 AWG Microphone Cable, stranded tinned copper conductors,
15.0 MR-43 Ethylene Propylene Diene Monomer insulation, PVC jacket (as per actual) etc all complete Mtr 30 258.00 7,740.00
16.0 MR-44 SITC of Category 6A Cable, 4 Pair, S/FTP, PVC jacket (as per actual) etc all complete Mtr 100 87.00 8,700.00
Supply and Laying of 15 Meters HDMI Cable in existing conduit.
Make-Crestron/Kramer/Bestnet/Logic
Supply & Fixing of 22U Floor Stand (600W x 600D) rack with Multi hollow extrusion Aluminium
profile frame, Top and bottom cover with provision of either brush cable entry or cable entry
18.0 MR-46 holes with rubber grommets, Front single door with Glass/ Mesh and rear double door with Nos 1 36,784.00 36,784.00
mesh, Static load bearing capacity of Upto 1200KG.,Colour - Combination of RAL 7037 (For
frame) & RAL 7035 (For other parts) with fine texture
Total Amount 0.0 4,745,296.00
Total Amount 0.0 4,745,296.00
Digitally signed by VARUN
aoc.pdf
Download all tender documents and submit your bid