Loading…
Loading…
| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | L1₹13.7 LAccepted-AOC | L1 | Accepted-AOC L1 | |
| 2 | L2₹14.1 L+₹46,202 (3.38%)Rejected-AOC | L2 | Rejected-AOC L2 | |
| 3 | L3₹15.1 L+₹1.4 L (10.3%)Rejected-AOC | L3 | Rejected-AOC L3 |
Tender Value
₹20 L
EMD Value
₹40,000
Closing Date
1 Feb 2022, 6:00 pmClosed
Shri Kislay Kishore, IDSE
GE (AFA) Hyderabad
REPAIRS TO INTERNAL ELECTRICAL WIRING, FITTING/ FIXTURES AND RELATED WORKS IN BLDGS AT ADM AREA, FCM, SNCO MESS, AIRMEN MESS, DSC MESS, OI ETC. AT AFA HYDERABAD
2022_MES_499152_1
8210/E8
Open Tender
Civil Works
Item Rate
GE (AFA) Hyderabad
As per tender docuements
4 documents required · 4 mandatory
₹500
Yes
₹40,000
Yes
15 Mar 2022
3 Jan 2022
3 Feb 2022
3 Jan 2022
1 Feb 2022
17 Jan 2022
3 Jan 2022 - 16 Jan 2022
Amount
Taking down carefully un serviceable point wiring of light points, fan, socket out let on TW battens/PVC pipes/casing & caping including removing the materials from site and making good the disturbed portion of walls/floors ceiling etc including making good disturbed portion to match with existing finish ie. painting/colour washing/distempering complete all as specified and as directed.
M&L for cutting chases not exc 10 cm girth , pinning in. making good to facings on brick wall / stone, concrete block where required and pointing in cement mortar 1:3 to ends or edges of landings, steps, cills, sunshades, shelves, lintels, etc.; and cutting chases for concealed conduit wiring, etc., and making good, including painting/colour washing/distempering complete all as per existing specification of the surroundings complete all as specified and as directed.
M & L for Point wiring with 1.5 Sqmm multistranded copper conductor wire with unsheathed, FRLS grade PVC insulated, single core with earth continuity conductor of 1.5 sqmm FRLS grade PVC insulated multistranded copper conductor and including rigid PVC conduit of suitable size but not less than 20mm dia. and all accessories fixed to the surface of the roof/ walls or in chases etc. including terminal boxes made out of MS sheet of thickness should be not lessthan 1.2mm thick for fixing of switches, fan regulators socket outlet etc along-with 3mm thick top laminated bakelite sheet for housing switches, etc complete all as specified and as directed for the following :-
(a) One light point controlled by one switch
(b) One light point controlled by two nos 2 way switches
(c) One ceiling / Exhaust fan point controlled by one switch
(d) One three pin socket 5 Amps independent board
(e) One Bell point controlled by one way bell switch
(f) One three pin socket 5 Amps plug point on same board
(g) One 3 pin 5amps socket outlet independent but below the switch board of light points in the same vertical plane.
M & L for Point wiring with 1.5 Sqmm multistranded copper conductor wire with unsheathed, FRLS grade PVC insulated, single core with earth continuity conductor of 1.5 sqmm FRLS grade PVC insulated multistranded copper conductor and including rigid PVC Casing & capping of suitable size and all accessories fixed to the surface of the roof/ walls or in chases etc. including PVC terminal boxes for fixing of switches, fan regulators socket outlet etc. complete all as specified and as directed for the following :-
(a) One light point controlled by one switch
(b) One light point controlled by two Nos, 2 way switches
(c) One ceiling / Exhaust fan point controlled by one switch
(d) One three pin socket 5 Amps plug point on independent board
(e) One Bell point controlled by one way bell switch
(f) One three pin socket 5 Amps plug point on same board
(g) One 3 pin 5amps socket outlet independent but below the switch board of light points in the same vertical plane.
All as per Ser item No 3 above but with 2.5 sq mm multistranded copper wire with 2.5 Sq mm multistranded copper wire as earth continuity conductor in and including PVC conduit (not less than 20 mm) complete all as specified and as directed for 15A socket.
All as per Ser item No 4 above but with 2.5 sqmm copper cable in the casing & capping complete all as specified and as directed 15A socket.
All as per Ser item No 3 above but with 1.5 sqmm copper cable in the existing Concealed/surface conduit complete all as specified and as directed
All as per Ser item No 4 above but with 2.5 sq mm copper cable in the existing Concealed/surface CASING & CAPING complete all as specified and as directed
S&F in repairs of ceiling rose, three terminal, PVC/polycarbonate, insulated body, ISI marked complete all as specified and as directed.
S&F in repairs of point wiring for one light point controled by 2 way switchs with cables 1.5 sqmm size in PVC conduits/ Casing & Caping complete all as specified and as directed.
S&F in repair of Switch Piano type polycarbonate white 1 way, 6A, 240Volts complete all as specified and as directed.
S&F in repair of Bell Switch flush type polycarbonate white 6A 240Volts complete all as specified and as directed.
S&F in repair of Socket outlet polycarbonate white 6A - 2/3 pin complete all as specified and as directed.
S&F in repair of Switch socket combination polycarbonate white 2 in 1, 3 pin, 5 flush type universal complete all as specified and as directed.
S&F in repair of Switch socket combination polycarbonate white 2 in 1, 3 pin, 5 and 15 Amp flush type universal complete all as specified and as directed.
S&F in repair of Switch 15 Amp flush type universal complete all as specified and as directed.
S&F in repair of Socket out let polycarbonate white 2 in 1, 3 pin, 15 Amp flush type universal complete all as specified and as directed.
S&F in repair of Bell Multi Music type / Ding Dong AC 230 V complete all as specified and as directed.
S&F in repair of stepped type polycarbonate white electronic fan regulator flush type complete all as specified and as directed.
S&F in repair of polycarbonate white angle holder/batten holder insulated complete all as specified and as directed.
S&F in repair of PVC Gang Box suitable for 5 Amps Switch Socket Combination complete all as specified and as directed.
S&F in repair of PVC Gang Box suitable for 15Amps Switch Socket Combination complete all as specified and as directed.
S & F in repair modular switch 6 Amp one way 230 V AC complete all as specified and as directed.
S & F in repair modular switch 16 Amp one way 230 V AC complete all as specified and as directed.
S & F in repair modular switch 6 Amp bell push, 230 V AC complete all as specified and as directed.
S & F in repair modular socket outlet 6Amp intel multi socket for all pins 230 V AC complete all as specified and as directed.
S & F in repair modular socket outlet 16Amp and 6/16 Amp heavy duty 230 V AC complete all as specified and as directed.
S & F in repair modular step type fan regulator heavy duty 230 V AC complete all as specified and as directed.
S&F of 1x10W LED Tube light fitting having housing with high pressure die cast alluminium, poly carbonate front diffuser cover including LED driver, Lamp and all accessories internally pre-wired, connecting up with three core twisted flexible copper conductor cable with cross sectional area 1.5 Sqmm including taking out old unserviceable one complete all as specified and as directed. (Make : Luker Cat Part No LT510 or equivalent)
S&F surface mounting / wall mounted LED tube light fitting 1x20 Watt (Lumen output not less than 1980 lumen) high efficiency, anti glare, maintenance free operation including LED driver, Tube 20W/18W and mounting arrangements, all accessories internally pre-wired, connecting up with three core twisted flexible copper conductor cable with cross sectional area 1.5 Sqmm including taking out old unserviceable one complete all as specified and as directed. (Make : Luker Cat Part No LT520 or equivalent)
S&F LED street light luminaries 35W 230 V AC including suitable inbuilt driver and complete accessories with MS housing finished & having clear acrylic cover, and provision of 1.20 mtr bracket made with light grade GI pipe of 25 mm dia for fixing on walls with MS flat (25mm X 3mm) clamps and anchor fastner after removing the unserviceable fitting complete all as specified and as directed. (Make : Luker Cat Part No LST36 or equivalent)
S&F flush / surafce type light fittings of size 600x600mm suitable for 36W LED complete with inbuilt driver surface mounted/recessed type slim box type luminaries with CRCA housing white powder coated finish suitable to operate with 230 V AC, complete with all accessories internally pre-wired and including connecting up with three core twisted flexible copper conductor cable with cross sectional area 1.5 Sqmm after removing old U/S rusted fittings complete all as specified and as directed. (Make : Luker Cat Part No LPS40 or equivalent)
S&F flush surface/rcessed type light fittings square / round as per site requirement suitable for 12 W LED complete with inbuilt driver surface mounted slim box type luminaries with CRCA housing white powder coated and finish suitable to operate with 220 V AC complete with all accessories internally pre-wired and including connecting up with twin core twisted flexible copper conductor cable with suitable size after removing old U/S rusted fittings complete all as specified and as directed. (Make : Luker Cat Part No LNPR12 or equivalent)
S&F laminated hylam sheet 3 mm thick with suitable chromium plated machine screws with cup washers for fixing switches/ sockets etc including cutting for accommodating the switches / sockets and removing the damaged switch plates by carefully removing the switches /wiring/ sockets for refixing and re connecting the removed wires testing the circuits complete all as specified and as directed.
M&L for Sub Main wiring with four runs of 10sq mm 1100 V grade (nominal area) single core FRLS grade PVC insulated unsheathed wire with multi-stranded copper conductor, drawn through and including medium grade, rigid non-metallic PVC conduit / casing & caping (as per site requirement) of suitable size with all necessary fittings, surface in walls/roof/floor duly earthed with two runs of single core cable of same size but green in colour as continuous earthing wire and connecting to common earth dolly complete incl taking out the existing sub-main wiring etc. complete all as specified and as directed.
Note :- (i) Necessary PVC dummy plates & rigid PVC junction boxes for maint./inspection purpose as required on site/directed by Engr-in-charge shall deemed to be included in the quoted rate.
(ii) Same size wire shall be used for phase, neutral & earth conductor
(iii) The wiring shall be done strictly by following proper colour coding using red, yellow and blue for phase, black for neutral and green for earth leads.
(iv) Six runs of cable and one run of PVC conduit / casing caping will be measured as one uint.
M&L for Sub Main wiring with four runs of 6sq mm 1100 V grade (nominal area) single core PVC insulated unsheathed cable multi-stranded copper conductor drawn through medium grade, rigid non-metallic PVC conduit / casing & caping (as per site requirement) of suitable size with all necessary fittings, surface in walls/roof/floor duly earthed with two runs of single core cable of same size but green in colour as continuous earthing wire and connecting to common earth dolly complete incl taking out the existing sub-main wiring etc. complete all as specified and as directed.
Note :- (i) Necessary PVC dummy plates & PVC rigid junction boxes for identifying junction as required on site/directed by Engr-in-charge shall deemed to be included in the quoted rate.
(ii) Same size wire shall be used for phase, neutral & earth conductor
(iii) The wiring shall be done strictly by following proper colour coding using red, yellow and blue only for phase, black for neutral and green for earth leads.
(iv) Six runs of cable and one run of PVC conduit / casing caping will be measured as one length.
M&L for Sub Main wiring with two runs of 6sq mm 1100 V grade (nominal area) single core PVC insulated unsheathed cable multi-stranded copper conductor drawn through and including medium grade, rigid non-metallic PVC conduit / casing & caping (as per site requirement) of suitable size with all necessary fittings, surface in walls/roof/floor duly earthed with one run of single core cable of same size but green in colour as continuous earthing wire and connecting to common earth dolly complete incl taking out the existing sub-main wiring etc. complete all as specified and as directed.
Note:-(i) Necessary PVC dummy plates & rigid PVC junction boxes for maint./inspection purpose as required on site/directed by Engr-in-charge shall deemed to be included in the quoted rate.
(ii) Same size wire shall be used for phase, neutral & earth conductor
(iii) The wiring shall be done strictly by following proper colour coding using red, yellow and blue only for phase, black for neutral and green for earth leads.
(iv) Three runs of cable and one run of PVC conduit / casing caping will be measured as one uint.
M&L for Sub Main wiring with two runs of 6sq mm 1100 V grade (nominal area) single core PVC insulated unsheathed cable multi-stranded copper conductor drawn through existing conduit with all necessary fittings, surface in walls/roof/floor duly earthed with one run of single core cable of same size but green in colour as continuous earthing wire and connecting to common earth dolly complete incl taking out the existing sub-main wiring etc. complete all as specified and as directed.
Note:-(i) Necessary PVC dummy plates & rigid PVC junction boxes for maint./inspection purpose as required on site/directed by Engr-in-charge shall deemed to be included in the quoted rate.
(ii) Same size wire shall be used for phase, neutral & earth conductor
(iii) The wiring shall be done strictly by following proper colour coding using red, yellow and blue only for phase, black for neutral and green for earth leads.
M&L for Sub Main wiring with two runs of 4sq mm 1100 V grade (nominal area) single core PVC insulated unsheathed cable multi-stranded copper conductor drawn through and including medium grade, rigid non-metallic PVC conduit / casing & caping (as per site requirement) of suitable sizewith all necessary fittings, surface in walls/roof/floor duly earthed with one run of single core cable of same size but green in colour as continuous earthing wire and connecting to common earth dolly complete incl taking out the existing sub-main wiring etc. complete all as specified and as directed.
Note:-(i) Necessary PVC dummy plates & rigid PVC junction boxes for maint./inspection purpose as required on site/directed by Engr-in-charge shall deemed to be included in the quoted rate.
(ii) Same size wire shall be used for phase, neutral & earth conductor
(iii) The wiring shall be done strictly by following proper colour coding using red, yellow and blue only for phase, black for neutral and green for earth leads.
(iv) Three runs of cable and one run of PVC conduit / casing caping will be measured as one uint.
M&L for Sub Main wiring with two runs of 2.5sq mm 1100 V grade (nominal area) single core PVC insulated unsheathed cable multi-stranded copper conductor drawn through and including medium grade, rigid non-metallic PVC conduit / casing & caping (as per site requirement) of suitable size with all necessary fittings, surface in walls/roof/floor duly earthed with one run of single core cable of same size but green in colour as continuous earthing wire and connecting to common earth dolly complete incl taking out the existing sub-main wiring etc. complete all as specified and as directed.
Note:-(i) Necessary PVC dummy plates & rigid PVC junction boxes for maint./inspection purpose as required on site/directed by Engr-in-charge shall deemed to be included in the quoted rate.
(ii) Same size wire shall be used for phase, neutral & earth conductor
(iii) The wiring shall be done strictly by following proper colour coding using red, yellow and blue only for phase, black for neutral and green for earth leads.
(iv) Three runs of cable and one run of PVC conduit / casing caping will be measured as one uint.
M&L for Sub Main wiring with two runs of 2.5sq mm 1100 V grade (nominal area) single core PVC insulated unsheathed cable multi-stranded copper conductor drawn through existing conduit with all necessary fittings, surface in walls/roof/floor duly earthed with one run of single core cable of same size but green in colour as continuous earthing wire and connecting to common earth dolly complete incl taking out the existing sub-main wiring etc. complete all as specified and as directed.
Note :- (i) Necessary PVC dummy plates & rigid PVC junction boxes for maint./inspection purpose as required on site/directed by Engr-in-charge shall deemed to be included in the quoted rate.
(ii) Same size wire shall be used for phase, neutral & earth conductor
(iii) The wiring shall be done strictly by following proper colour coding using red, yellow and blue only for phase, black for neutral and green for earth leads.
Taking out old unserviceable distribution board of any type and S&F of MCB DB SPN 4 way with copper bus bar & neutral link double door type to be fixed in the wall including connections and making good the disturbed surface of wall to perfectly match with the exsting wall complete all as specified and as directed.
Taking out old unserviceable distribution board of any type and S&F of MCB DB SPN 8 way with copper bus bar & neutral link double door type to be fixed in the wall including connections and making good the disturbed surface of wall to perfectly match with the exsting wall complete all as specified and as directed.
Taking out old unserviceable distribution board of any type and S&F of MCB DB SPN 12 way with copper bus bar & neutral link double door type to be fixed in the wall including connections and making good the disturbed surface of wall to perfectly match with the exsting wall complete all as specified and as directed.
Taking out old unserviceable distribution board of any type and S&Fof MCB DB double door 4 way triple pole vertical type 415 volts 50 Hz AC supply suitable for 4 pole MCCB incomer, fixed to the existing wall (concealed/surface) after removing the existing un serviceable MCB DB and reconnecting the electrical connections and making good the disturbed surface of wall to perfectly match with the exsting wall complete all as specified and as directed.
Taking out old unserviceable distribution board of any type and S&F of MCB DB,,double door 8 way triple pole vertical type 415 volts 50 Hz AC supply suitable for 4 pole MCCB incomer, fixed to the existing wall (concealed/surface) after removing the existing un serviceable MCB DB and reconnecting the electrical connections and making good the disturbed surface of wall to perfectly match with the exsting wall complete all as specified and as directed. Note for items 45&46 : MCCB will be measured and paid separately under relavant items.
Taking out old unserviceable MCCB from distribution board of any type and S&F of MCCB 4 pole 63Amps, 16KA breaking capacity, 415Volts 3-phase supply complete all as specified and as directed.
Taking out old unserviceable MCCB from distribution board of any type and S&F of MCCB 4 pole 100Amps, 16KA breaking capacity, 415Volts 3-phase supply complete all as specified and as directed.
Taking out old unserviceable MCB any type and S&F of MCB SPN 6 to 32A, 10KA rupturing capacity complete all as specified and as directed.
Taking out old unserviceable MCB any type and S&F of Fix MCB SP 6 to 32 A 10 KA rupturing capacity complete all as specified and as directed.
Taking out old unserviceable MCB and S&F of single pole and neutral enclosure with a two pin and earth plug and socket complete with one number single pole MCB 20 Amps , 240 Volts complete all as specified and as directed.
S&F in replacement of post top lantern LED type 20 watt 230V AC outdoor type with Decorative post top for 360 dgree indirect light IP 65 protection with impect and corrosion resistant complete with driver and lamp complete.
S&F in repairs Ceiling fan capacitor AC 230 volts, 2.5/3.15 MFD complete all as specified directed.
S&F including taking out unserviceable electronic driver for LED street light 35 watts complete all as directed.
SRI SAI CONSTRUCTIONS
M.chandraiahsons
stage.html
html • 0.05 MB
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .