Loading…
Loading…
| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | L1₹4.4 CrAccepted-AOC | ₹4.4 Cr Quoted ₹4.6 Cr | L1 | Accepted-AOC approved lowest bid |
| 2 | L2₹4.8 Cr+₹18.8 L (4.09%)Rejected-AOC | ₹4.8 Cr+₹18.8 L (4.09%) | L2 | Rejected-AOC higher bid |
| 3 | L3₹4.9 Cr+₹28.6 L (6.20%)Rejected-AOC | ₹4.9 Cr+₹28.6 L (6.20%) | L3 | Rejected-AOC higher bid |
Tender Value
₹2.0 Cr
EMD Value
₹2.3 L
Closing Date
1 Jun 2021, 11:00 amClosed
Executive Engineer
Jal Shakti Shimla Rural Division at Suni
C-o Protection wall barbed wire fencing pump house delivery tank at Mashadhar RCC Sector storage tank 10000 lts. cap. at node no. 11, Sector storage tanks P-L Rising main and S-E pumping machinery etc under JJM
2021_HPIPH_47590_1
SNN-SML-03-740-Tndr /2021-926-31 dt 19/5/21
Open Tender
Civil Works - Water Works
Item Rate
365 days
Suni
Please refer Tender documents.
11 documents required · 11 mandatory
₹2,500
EE Suni
₹2.3 L
11 Aug 2021
19 May 2021
1 Jun 2021
19 May 2021
1 Jun 2021
19 May 2021
19 May 2021 - 1 Jun 2021
Amount
Description of items
Cutting in earth work and disposal of excavated earth upto a lead of 20 meters spade Work,Pick work & Jumper work.
Excavation in foundation trenches etc.in earth work upto all depths in all kinds of soil such as pick work,jumper work,blasting and chiselling soft/hard rocks where blasting is prohibited in all leads and lifts including trimming and dressing of side levelling of bed to correct grade and returning the stacked soil in trenches in 15cm.layers by ramming and watrering and then disposing of all surplus excavated soil as directed in all leads and lifts and soring strutting/timbering and dewatering where ever required including restoration of un metalled/metalled paved surfaces to its original conditions including caution boards in all respect and to the entire satisfaction of the Engineer-in-Charge.
Providing and laying cement concrete 1:6:12 (1cement:6 sand:12 graded stone aggregate 40mm nominal size) and curring complete excluding cost of centering & shuttering in foundation and plinth.
R/R stone masonery/Polygonal rubber masnory (uncoursed/Brought to courses) with haded stone of approved quality in foundation and plinth including levelling up with cement concrete !;6:12 (1:cement:6 sand:12 graded stone aggregate 20mm nominal size) at plinth level in cement motor 1:6(1 cement:6 sand).
Providing and laying cement concrete 1:2:4 (1cement:2 sand:4 graded stone aggregate 20mm nominal size) and curring complete excluding cost of form work and reinforcement for reinforced concrete work in.
Suspended floors roofs,landing and shelves and their supports, balconies,beams,girders bressumers and cantilever up to floor two levels.
Plinth & Foundation
Providing and laying cement concrete 1:3:6(1cement:3 sand:6 graded stone agg.40mm nominal size)and curing complete excluding cost of form work in foundation and plinth in all leads and lifts.
Providing and laying cement concrete 1:1/2 :3 ( 1cement: 1/2 sand: 3graded stone aggregate 20 mm nominal size ) and curing complete excluding the cost of form work and reinforcement for reinforced concrete work in :-
Foundation and footings etc. in all leads & lifts.
Walls(any thickness but not less than 0.1 mtr thickness) attached pilasters, buttresses, plinth and string courses etc. from top of foundation level up to floor two level in all leads & lifts.
Providing form work with steel plates 3.15mm thick welded with angle iron in frame 30x30x5mm so as to give a fair finish including centring, shuttering ,strutting and propping etc. with wooden battens and ballies height of propping and centring below supporting floor to ceiling in all heights and removal of the same for insitu reinforced concrete and plain concrete workin:-
Flat surfaces such as soffits of suspended floors, roofs landings and the like: floors etc. up to 200 mm in thickness in all leads & lifts.
Vertical surfaces such as walls(any thickness)partitons and the like including attached pillasters,buttresses plinth and string courses and the like in all leads and lifts
Providing form work of ordinary timber planking's so as to give a fair finish including centering,shuttering,propping etc. height of propping & centring below supporting floor to ceiling & removal of the same for-in-situ reinforced concrete & concrete work in arches exceeding 6 mtrs. span(Dome) as per direction & to the entire satisfaction of Er.-in-charge.
Brick work using common burnt clay building bricks in foundation and plinth in cement motar 1:4 (1 cenent :4 sand( First class bricks).
Half Brick masonry in common burnt clay building bricks in cement motar 1:4 (1 cenent :4 sand( First class bricks)in super-structure.
providing wood work in frames of door, window ,clearstory.window and other frames wrought ,framed and fixed in position:2nd class deodar wood.
Providing fixing panelled glazed or panelled and glazedshutters for doors windows and clerestory window including black enamelled iron butt hinges with necessary screws 40mm thick 2nd class deodar wood .including entire carriage of material upto all leads and lifts.
Providing fixing Wire gauge shtters using galvanized M.S Wire gauge designation 85 G with wire of dia 0.56mm for door windows and clearstory windows i/c black enamelled iron butt hinges with necessary screws:40mm thick 2nd class deodar wood.
Providingand fixing M.S.Grills of required pattern in wooden frames of windows etc. with M.S. wire flats, Square or round bars with round headed bolts and nuts or by the screws(Plain Grill).
20mm cement plaster in single coat on the rough side of stone masonry for interior plastering up to floor to level i/c arises,internal rounded angles, chamfers and/or rounded angles not exceeding 80mm in grith and finished even and smooth in c.m 1:6(1 cement:6 sand).
15 mm cement plaster in single coat on the rough side of stone masonry for interior plastering up to floor to level i/c arises,internal rounded angles, chamfers and/or rounded angles not exceeding 80mm in grith and finished even and smooth in c.m 1:6(1 cement:6 sand).
6mm cement plaster to celling(a)in cement mortar 1:3(1 Cement;3 Sand).
Applying priming coat over new wood and wood based surfaces after and including preparing the surface by throughly cleaning oil,grease,dirt and other foreign matter .with ready mixed paint brushing wood primer pink.including entire carriage of material upto all leads and lifts.
Painting two coat excluding priming coat on new wood and wood surfaces with enamel paint to give an even shade including cleaning the surface of dirt,dust and other foreign matter sand papering & stoping:- Ready mixed paint other than white including entire carriage of material upto all leads & lifts
White washing with lime on undecorated wall surfaces two coat to give an even shade i/c thoroughly brooming the surface to remove the dirt, dust, mortar and other foreign matter .
White washing with lime on ceiling or slopping roof
Providing 40x3mm flat iron hold fast 40cms long including fixing to frame with 10mm diameter bolts nuts and wooden plugs and embedding in cement concrete block 30x10x15cms 1:3:6 (1cement:3sandf:6graded stone aggregate 20mm nominal size) including entire carriage of material upto all leads and lifts.
Providing and fixing anodized aluminium sliding door bolts and nuts screws etc.complete
Providing and fixing anodized aluminium tower bolt anodized transparent or dyed to required shade colour with screws etc.complete
Providing and fixing anodized aluminium Handles anodized transparent or dyed to required shade colour with screws etc.complete
Providing and fixing Oxidized M.S. hooks and ayes
Boulder filling dry hand packed tightly under floors
40mm thick cement conc.Flooring 1:2:4(1 cement:2 sand:4 graded stone agg.20mm nominal size) laid in one layer finished with a floating coat of of neat cement
Pointing on Brick work with cement mortar 1:3(1 cement :3 sand) raised and cut
Providing and plinth Protection 50mm thick in cement concrete 1:3:6(1 cement:3 sand:6 graded stone aggregate 20mm nominal size) including finishing the top surface of concrate smooth
Providing mild steel/tor steel reinforcement for RCC work including bending,binding and placing in position complete up to floor two level
Applying Birla white wall care Putty over plaster surface after throughly brushing the surface free from motar drops,dust,loose,materails and other to give matters sand parpered smooth to give final matter finish to the surface complete
White glazed tiles 6mm thick in flooring,treads of steps and landing laid on a bed of 12mm thick cement motar 1:3)
Laying and Jointing intrenches GMS Tube Tube fitting(earth work in trenches to be measured and paid for separately.
150 dia(M.G)(Scour pipe)
50mm dia
32mm dia
Providing and fixing Sand cast Iron/Cast iron spun spigot and sacketed soil waste and ventilating pipe( lead lanlked joint to be measured & paid for seprately 100 mm dia.
Manufacturing MS Manhole Cover 600x450mm with frame of MS Angle 50x50x6mm and cover of black sheet 2.00mm thick complete with angle frames,flates etc. including welding with locking arrangements(Locks)(excluding Cement Concrete).
Providing and fixing C.I. Sluice Valve wheel valve with wheel 150mm nominal bore(ISI mark Leader make)
Providing in RCC work smooth finishing of the exposed surfaces with cement mortar 1:3 (1 cement : 3 sand)complete in all leads and lifts.
Making connection of galvanised steel distribution branch with galvanised mild steel main 20mm to 40mm nominal bore by providing and fixing tee including cutting and threading the pipes complete
Providing and fixing Brass Full way wheel valve with wheel
50mm dia
32mm dia
Steel work welded in built up sections, trusses and framed work including cutting, hoisting, fixing in position complete in grating, framed guards & ladders etc. ( V.M 50x50x6mm & H. M 25X25X4MM.)
Providing and laying cement concrete 1:2:4(1 cement:2 sand:4 graded crushed stone aggregate and 20mm nominal size) and curing complete excluding the cost of from work in foundation and plinth in all leads and lifts for fencing post.
1.80 mtr.High fencing with 2.50 mtr.M.S Angle iron post of size 50x50x5mm(min) including cutting & hosting and welding including painting complete in all respect.
1.80 mtr.High fencing with 2.50 mtr.M.S Angle iron post of size 50x50x5mm(min)center to center with 9 horizonal lines & two daiginals Galvanised steel barbed wire(IS-278-1962 Type-1) weighing 9.38Kg/per 100 mtr.(minium) strained and fixed to posts with 6.1 stples including with painting of M.S.Angle iron complete(Angle50x50x5mm).
R/R masonry Polygonal rubble masonry (uncorsed/brought to courses) with hard stone of approved quality in foundation an Plinth laid dry bonded,faced with through stones and built with bond or through stones evenly placed at the rate two per square metre
Providing & laying cement concrete 1:4:8(1cement : 4 sand : 8 graded stone aggregate40 mm nominal size) & curing Complete excluding the cost of centring & shuttering in Foundation & plinth in all leads and lists.
Providing,Laying, jointing and testing in trenches to be leveled to grades, IS marked (API Pipes conforming to ISO 3183-2007 )MSERW Pipe ,including flanged pipes of following diameters confirming to (latest with up to date amendments ) having minimum wall thickness as for class of pipe specified below jointed with flanges conforming to tables as specified below of BIS 6392-1971 ( latest with up to date amendments) welded at both ends according to relevant BIS standards and detailed specifications as appended in NIT & provided with nuts & bolts of required sizes, 3mm thick compressed asbestos fiber gasket of synthetic rubber gasket confirming to relevant BIS codes as given in technical specifications i/c all kinds of leads and lifts, flanged short pieces, tees & other specials etc. made from parent tubes & welded with flanges of tables as applicable for the particular reach & of technical specifications appended in the NIT as per site conditions including flushing cleaning & hydraulic testing as per directions of engineer in charge.
1st Stage Nagar to Mashadhar
RD:- 0/0 To 300 , Length :- 300 , Dia :- 150 mm , Class :- API - X - 70 , Thick :- 4.80
RD:- 300 To 1200 , Length :- 900 , Dia :- 150 mm , Class :- API - X - 70 , Thick :- 4.80
RD:- 900 To 1740 , Length :- 840 , Dia :- 150 mm , Class :- API - X - 70 , Thick :- 4.80
LWSS Juni
RD:- 0/0 To 1200 , Length :- 1200 , Dia :- 65 mm , Class :- API - X - 42 , Thick :- 4.80
RD:- 1200 To 1500 , Length :- 300 , Dia :- 65 mm , Class :- GI (H)
RD:- 1500 To 1850 , Length :- 300 , Dia :- 65 mm , Class :- GI (M)
LWSS Mandhorghat 1st Stage
RD:- 0/0 To 600 , Length :- 600 , Dia :- 80 mm , Class :- API - X - 42 , Thick :- 4.80
RD:- 600 To 870 , Length :- 270 , Dia :- 80 mm , Class :- GI (H)
LWSS Mandhorghat 2nd Stage
RD:- 0/0 To 600 , Length :- 600 , Dia :- 80 mm , Class :- API - X - 42 , Thick :- 4.80
RD:- 600 To 900 , Length :- 300 , Dia :- 80 mm , Class :- GI (H)
RD:- 900 To 990 , Length :- 900 , Dia :- 80 mm , Class :- GI (M)
Providing,Laying, jointing and testing in trenches to be leveled to grades, IS marked GI flanged pipes of following diameters confirming to IS1239-1990 ( part-II) (latest with up to date amendments ) having minimum wall thickness as for class of pipe specified below jointed with flanges conforming to tables as specified below of BIS 6392-1971 ( latest with up to date amendments) welded at both ends according to relevant BIS standards and detailed specifications as appended in NIT & provided with nuts & bolts of required sizes, 3mm thick compressed asbestos fiber gasket of synthetic rubber gasket confirming to relevant BIS codes as given in technical specifications i/c all kinds of leads and lifts, flanged short pieces, bends , tees & other specials etc. made from parent tubes & welded with flanges of tables as applicable for the particular reach & of technical specifications appended in the NIT as per site conditions including flushing cleaning & hydraulic testing as per directions of engineer in charge.
LWSS Juni
RD:- 1200 To 1500 , Length :- 300 , Dia :- 65 mm , Class :- GI (H) Flange Table :- 17
RD:- 1500 To 1800 , Length :- 300 , Dia :- 65 mm , Class :- GI (M) Flange Table :- 17
RD:- 1500 To 1800 , Length :- 300 , Dia :- 65 mm , Class :- GI (M) Flange Table :- 5
LWSS Mandhorghat 1st Stage
RD:- 600 To 870 , Length :- 270 , Dia :- 80 mm , Class :- GI (H) Flange Table :- 17
LWSS Mandhorghat 2nd Stage
RD:- 600 To 900 , Length :- 300 , Dia :- 80 mm , Class :- GI (H) Flange Table :- 17
RD:- 900 To 990 , Length :- 900 , Dia :- 80 mm , Class :- GI (M) Flange Table :- 5
PUMPING MACHINERY
LWSS Basantpur Kalvi.(Nagar to Masha Dhar)
Providing horizontal spindle horizontal/radial split casing/end section(back pull out arregement) single/double/multistages centifugal pump or combination of pumps,in series/parallel of recommended make such as Mather and platt/KSB/Becon weir/Kirloskar/BE/Jyoti/WASP/ASPEE as per BIS 1520-1980 with upto date ammendments,read with IS-1937-1978 or latest edition suitable for lifting clear water for under mentioned characterstics with bronze impellers/pumping funnels casing ring and shaft sleaves of bronze,shaft of steel grade-with cast iron casing coupled directly through a flexible coupling on a common C.I./Cast steel base plate(base plate to be from the manufacturers of the Pumping unit only) to Slip/Ring/Squarrel cage screen protected drip proof induction motor of standred make such as Kirloksar/Cromption/Bhel/NGEF/GEC/SIEMEN/JAYOTI/ABB suitable for operation on 415(+)/- 5% volts,50 cycles/second,3 phase AC electric supply.The power of electric motor should be atleast 10% in excess of the maximum power required by the pump in the operation range of(+)10% and(-) 25% of the duty point head.The motor should be as per IS:325-1978 with upto date ammendments read with IS 900-1972.It should include cost of bearing nuts,bolts and pointing etc.and should meet the following requirements:-
Scheme :- LWSS Basantpur Kalvi
(I) Discharge (Q) LPS :- 5.50
(a) LWL in sump well(h) : 760 Meters.
(d) Suction lift :- 3 Meters.
(e) Residual head:- 3 Meters.
(f) Static head:- 665.70 mtr
(iii) Rising main
(a) Length. :- 1740.00 mtr
(b) Dia :- 150 mm.
(iv) Pumping hours. 16 Hour's
(v) Altitude of Installation above MSL - Meters.
(vi) Characteristics of water
(a) Temperature oC
(b) Abient Temperature oC
© Turbidity Clear water JTU
(d) Alkalanity Mg/CA CO3
(e) Size of the solids. Mm.
(f) Other.
Providing ICTP Main switch of Kilburn/ L&T/ Siemens/ Crompton/Standard/Havells make and having Capacity 30% extra of the Operational rating as per IS:4064-1978 with upto date ammendment immediately after the power meter of HPSEB
Providing MS .sheet,steel fabricated floor mounted closed(Almirah type) switch board including angle iron post of suitable hright and size ISA 40x4-x6mm,duly painted,with steel sheet of 16 gauge comprising,capable of mounting the following accessories with all internal connections:
A.C.B./Oil circuit breaker of Kilburn/L&T/MEI/GEC make & of sutible capacity on incoming feeder with or without initial oil filling as the case may be with nrutral linked under voltage releases as per IS:2516-1985 with upto date ammendments with
Earth leakage circuit breaker of recommended make (Kilburn/L&T/MEI/GEC) as per 2516-1977 with upto date ammendment and of suitable range which should have control box operating handle and trip/reset bush button on/off indicators,re-indicating off spring condition of the circuit breaker for over current protection.The circuit should be equipped with magnet thermal release with metallic tape etc.It should also be fitted with earth fault for tripping of breaker on occurrence of earth fault on off breaker load side end.
The voltage monitor relay three phase with all protection and usual indicator and electric siren against single phasing low Voltage,high voltage reverse phasing over loading and voltage difference as per IS:3842(latest edition).
Power factor meter of standard make as per relevant IS code with upto date ammendments of suitable rating
Frequency meter of standard make as per relevant IS code with upto date ammendments of suitable rating.
Bus bar chamber having three bars of suitable rating for full length equal to the width og the board for three live phases and suitable for induced current,one copper bar of half the rating of full length for neutral phase as per IS:8084-1976 and IS: 11353-1985 read with BIS 5578-1985 with upto date ammendments
ICTP switches with HRC fuses of L&T/ Crompton /Kilburn/ Siemens/standard/Havells make and of suitable capacity as per IS 4064-1978 with upto date ammendments.
Three phase Indicator lamps complete with toggle switches for individual motors as per IS 3452(P-1&II)1983 with uoto date ammendments
Capacitor of Mechneil/Bhel/GEC/ L&T/ make as per IS:2834-1986 with uoto date ammendments to raise the power factor at site to 0.95 for direct connections to induction motor indiviually of required KVA rating according to offered including cables chamber to capactor and also including ICTP switches of appropriate range as per IS:4064-1978 with upto date ammendments.
Providing suitable Oil immersed star delta/direct on line /auto -tranformer/stater rotor starter of MEI/Kilburn/Jyoti/L&T/Siemens make as per IS:8544-1979 with upto date ammendments for squirrel cage/slip ring motor mounted on pannel board with magnetic type overload release and dashpot,time lag,under voltage release with or without initial oil filling as the case may be with single phase preventor as per IS 1248(P-V)-1983 with upto date ammenments.
Providing Hour run meter of recommended make of suitable capacity as per IS:722(Latest edition).
Prov. Antivibration pads under the pumps and motors of suitable size for the above pumping machinery as per IS:6337-1971
Prov. Cast iron flanged/screw type foot valves with strainer as per IS:4098-1986 with upto date ammendments of Kirloskar /Mechneil/ Kilburn/Leader make 150mm dia
Providing double flanged Cast Iron sluice valve of leader / Bhel/ Kirloskar/Kilburn/Gled/Fouress make and of 150mm for the delivery line of pump and capable of with standing normal seat pressure as per IS-780-1984 with upto date ammendments.
Providing double flanged Cast Iron sluice valve of leader / Bhel/Kirloskar/Kilburn/GLED/Fouress make and of 150mm dia for the delivery line of pump and capable of with standing normal seat pressure as per BS-1414 with upto date ammendments.
Providing double flanged(Swing type) Cast steel Reflux Valve of Leader/Bhel/Kirloskar/Kilburn/GLED/Fouress make and of 150mm dia having bye pass arrangement on the delivery line of pump and capable of with standing normal seat pressure as per BS:1868(P-1) with upto date ammendments.
Providing double flanged(Swing type) Cast steel Reflux Valve of Leader/Bhel/Kirloskar/Kilburn/GLED/Fouress make and of 150mm dia having bye pass arrangement for Rising Main and capable of with standing normal seat pressure as per BS:1868(P-1) with upto date ammendments.
Providing 150mm dia circular dia pressure gauge of Fiebing/Bourden/ prega/precision make complete with all accessories such as stop cock,copper tubing etc. as per IS 3624-1987 with upto date ammendments.
Prov.discharge meter standard make to be tiked on the rising main near the storage tank as per the directions of the Engineer-in-charge as per IS-2373-1981 with upto date ammendments.
Installation of all the items appearing at Serial No. 1 to 12… as per the systematic drawing attached with tender documents(Drg.No.1)
Providing and fixing double flanged MS/GI piping work layout to be approved by the Engineer-in-charge for suction and delivery pipes suitable to pumps offered and common header as per the rising main respectively complete with all specials such as bends,tees reducers/increasers with companion flanges matching with the relevant specifications of the accessores as indicated in the drawing No 2 including rubber/asbestos gasket of minimum 3mm thickness as per IS 2712-1979 and required number of nuts and volts as per IS 1364-1983.The pipes shall be as per relevant IS code and to withstand 1.5 times total head stipulated under item No-1.The size of the various components to be as under:-
(I) Suction pipe… 150 mm
(ii)Delivery pipe…150 mm
(iii)Common Header 150 mm
and will extended upto 5 mtrs from the outer wall of the pump
house in the direction to be jointed.
Providing and laying copper PVC insulated armoured power cable(One cable carring all the three Phases) of suitable size and capacity to and all other electrical equipments as per IS:1554(P-1) 1988 or latest with upto date ammendments of Siemens/Gloster/JEC/EICO National/Grandlay make including all other accessores such as thimbles,flexible,pipes solder,nuts and bolys cable glands etc.laid in pipes or trenches under floor.
Providing and fixing double loop earthing and copper plate 600mmx600mmx3mm thick electrode complete eith material such as thimbles,nuts and bolts,charcoal and common salt,25mmx3mm copper strips as per IS:3043-1987 with upto date ammendments for motors and other electrical equipments and digging of pits etc, complete in all respect.
LWSS MANDHORGHAT (1st STAGE)
Providing horizontal spindle horizontal/radial split casing/end section(back pull out arregement) single/double/multistages centifugal pump or combination of pumps,in series/parallel of recommended make such as Mather and platt/KSB/Becon weir/Kirloskar/BE/Jyoti/WASP/ASPEE as per BIS 1520-1980 with upto date ammendments,read with IS-1937-1978 or latest edition suitable for lifting clear water for under mentioned characterstics with bronze impellers/pumping funnels casing ring and shaft sleaves of bronze,shaft of steel grade-with cast iron casing coupled directly through a flexible coupling on a common C.I./Cast steel base plate(base plate to be from the manufacturers of the Pumping unit only) to Slip/Ring/Squarrel cage screen protected drip proof induction motor of standred make such as Kirloksar/Cromption/Bhel/ NGEF/GEC/SIEMEN/ JAYOTI/ABB suitable for operation on 415(+)/- 5% volts,50 cycles/second,3 phase AC electric supply.The power of electric motor should be atleast 10% in excess of the maximum power required by the pump in the operation range of(+)10% and(-) 25% of the duty point head.The motor should be as per IS:325-1978 with upto date ammendments read with IS 900-1972.It should include cost of bearing nuts,bolts and pointing etc.and should meet the following requirements:-
Scheme :- LWSS Mandhorghat
(I) Discharge (Q) LPS :- 4.44
(a) LWL in sump well(h) : 730 Meters
(d) Suction lift :- 3 Meters.
(e) Residual head:- 03 Meters.
(f) Static head:- 380 Meters
(iii) Rising main
(a) Length. :- 870 Meters
(b) Dia :- 80 mm
(iv) Pumping hours. 12 Hour's
(v) Altitude of Installation above MSL - Meters.
(vi) Characteristics of water
(a) Temperature oC
(b) Abient Temperature oC
© Turbidity Clear water JTU
(d) Alkalanity Mg/CA CO3
(e) Size of the solids. Mm.
(f) Other.
Providing ICTP Main switch of Kilburn/ L&T/ Siemens/ Crompton/Standard/Havells make and having Capacity 30% extra of the Operational rating as per IS:4064-1978 with upto date ammendment immediately after the power meter of HPSEB
Providing MS .sheet,steel fabricated floor mounted closed(Almirah type) switch board including angle iron post of suitable hright and size ISA 40x4-x6mm,duly painted,with steel sheet of 16 gauge comprising,capable of mounting the following accessories with all internal connections:
A.C.B./Oil circuit breaker of Kilburn/L&T/MEI/GEC make & of sutible capacity on incoming feeder with or without initial oil filling as the case may be with nrutral linked under voltage releases as per IS:2516-1985 with upto date ammendments with
Earth leakage circuit breaker of recommended make (Kilburn/L&T/MEI/GEC) as per 2516-1977 with upto date ammendment and of suitable range which should have control box operating handle and trip/reset bush button on/off indicators,re-indicating off spring condition of the circuit breaker for over current protection.The circuit should be equipped with magnet thermal release with metallic tape etc.It should also be fitted with earth fault for tripping of breaker on occurrence of earth fault on off breaker load side end.
The voltage monitor relay three phase with all protection and usual indicator and electric siren against single phasing low Voltage,high voltage reverse phasing over loading and voltage difference as per IS:3842(latest edition).
Power factor meter of standard make as per relevant IS code with upto date ammendments of suitable rating
Frequency meter of standard make as per relevant IS code with upto date ammendments of suitable rating.
Bus bar chamber having three bars of suitable rating for full length equal to the width og the board for three live phases and suitable for induced current,one copper bar of half the rating of full length for neutral phase as per IS:8084-1976 and IS: 11353-1985 read with BIS 5578-1985 with upto date ammendments
ICTP switches with HRC fuses of L&T/ Crompton /Kilburn/ Siemens/standard/Havells make and of suitable capacity as per IS 4064-1978 with upto date ammendments.
Three phase Indicator lamps complete with toggle switches for individual motors as per IS 3452(P-1&II)1983 with uoto date ammendments
Capacitor of Mechneil/Bhel/GEC/ L&T/ make as per IS:2834-1986 with uoto date ammendments to raise the power factor at site to 0.95 for direct connections to induction motor indiviually of required KVA rating according to offered including cables chamber to capactor and also including ICTP switches of appropriate range as per IS:4064-1978 with upto date ammendments.
Providing suitable Oil immersed star delta/direct on line /auto -tranformer/stater rotor starter of MEI/Kilburn/Jyoti/L&T/Siemens make as per IS:8544-1979 with upto date ammendments for squirrel cage/slip ring motor mounted on pannel board with magnetic type overload release and dashpot,time lag,under voltage release with or without initial oil filling as the case may be with single phase preventor as per IS 1248(P-V)-1983 with upto date ammenments.
Providing Hour run meter of recommended make of suitable capacity as per IS:722(Latest edition).
Prov. Antivibration pads under the pumps and motors of suitable size for the above pumping machinery as per IS:6337-1971
Prov. Cast iron flanged/screw type foot valves with strainer as per IS:4098-1986 with upto date ammendments of Kirloskar /Mechneil/ Kilburn/Leader make 80mm dia
Providing double flanged Cast Iron sluice valve of leader / Bhel/ Kirloskar/Kilburn/Gled/Fouress make and of 80mm for the delivery line of pump and capable of with standing normal seat pressure as per IS-780-1984 with upto date ammendments.
Providing double flanged Cast Iron sluice valve of leader / Bhel/Kirloskar/Kilburn/GLED/Fouress make and of 80mm dia for the delivery line of pump and capable of with standing normal seat pressure as per BS-1414 with upto date ammendments.
Providing double flanged(Swing type) Cast steel Reflux Valve of Leader/Bhel/Kirloskar/Kilburn/GLED/Fouress make and of 60mm dia having bye pass arrangement on the delivery line of pump and capable of with standing normal seat pressure as per BS:1868(P-1) with upto date ammendments.
Providing double flanged(Swing type) Cast steel Reflux Valve of Leader/Bhel/Kirloskar/Kilburn/GLED/Fouress make and of 60mm dia having bye pass arrangement for Rising Main and capable of with standing normal seat pressure as per BS:1868(P-1) with upto date ammendments.
Providing 60mm dia circular dia pressure gauge of Fiebing/Bourden/ prega/precision make complete with all accessories such as stop cock,copper tubing etc. as per IS 3624-1987 with upto date ammendments.
Prov.discharge meter standard make to be tiked on the rising main near the storage tank as per the directions of the Engineer-in-charge as per IS-2373-1981 with upto date ammendments.
Installation of all the items appearing at Serial No. 1 to 12… as per the systematic drawing attached with tender documents(Drg.No.1)
Providing and fixing double flanged MS/GI piping work layout to be approved by the Engineer-in-charge for suction and delivery pipes suitable to pumps offered and common header as per the rising main respectively complete with all specials such as bends,tees reducers/increasers with companion flanges matching with the relevant specifications of the accessores as indicated in the drawing No 2 including rubber/asbestos gasket of minimum 3mm thickness as per IS 2712-1979 and required number of nuts and volts as per IS 1364-1983.The pipes shall be as per relevant IS code and to withstand 1.5 times total head stipulated under item No-1.The size of the various components to be as under:-
(I) Suction pipe… 80 mm
(ii)Delivery pipe…80 mm
(iii)Common Header 80 mm
and will extended upto 5 mtrs from the outer wall of the pump
house in the direction to be jointed.
Providing and laying copper PVC insulated armoured power cable(One cable carring all the three Phases) of suitable size and capacity to and all other electrical equipments as per IS:1554(P-1) 1988 or latest with upto date ammendments of Siemens/Gloster/JEC/EICO National/Grandlay make including all other accessores such as thimbles,flexible,pipes solder,nuts and bolys cable glands etc.laid in pipes or trenches under floor.
Providing and fixing double loop earthing and copper plate 600mmx600mmx3mm thick electrode complete eith material such as thimbles,nuts and bolts,charcoal and common salt,25mmx3mm copper strips as per IS:3043-1987 with upto date ammendments for motors and other electrical equipments and digging of pits etc, complete in all respect.
LWSS MANDHORGHAT (2nd STAGE)
Providing horizontal spindle horizontal/radial split casing/end section(back pull out arregement) single/double/multistages centifugal pump or combination of pumps,in series/parallel of recommended make such as Mather and platt/KSB/Becon weir/Kirloskar/BE/Jyoti/WASP/ASPEE as per BIS 1520-1980 with upto date ammendments,read with IS-1937-1978 or latest edition suitable for lifting clear water for under mentioned characterstics with bronze impellers/pumping funnels casing ring and shaft sleaves of bronze,shaft of steel grade-with cast iron casing coupled directly through a flexible coupling on a common C.I./Cast steel base plate(base plate to be from the manufacturers of the Pumping unit only) to Slip/Ring/Squarrel cage screen protected drip proof induction motor of standred make such as Kirloksar/Cromption/Bhel/NGEF/GEC/SIEMEN/JAYOTI/ABB suitable for operation on 415(+)/- 5% volts,50 cycles/second,3 phase AC electric supply.The power of electric motor should be atleast 10% in excess of the maximum power required by the pump in the operation range of(+)10% and(-) 25% of the duty point head.The motor should be as per IS:325-1978 with upto date ammendments read with IS 900-1972.It should include cost of bearing nuts,bolts and pointing etc.and should meet the following requirements:-
Scheme :- LWSS Mandhorghat
(I) Discharge (Q) LPS :- 4.44
(a) LWL in sump well(h) : 1105 Meters
(d) Suction lift :- 3 Meters.
(e) Residual head:- 03 Meters.
(f) Static head:- 370 Meters
(iii) Rising main
(a) Length. :- 990 Meters
(b) Dia :- 80 mm
(iv) Pumping hours. 12 Hour's
(v) Altitude of Installation above MSL - Meters.
(vi) Characteristics of water
(a) Temperature oC
(b) Abient Temperature oC
© Turbidity Clear water JTU
(d) Alkalanity Mg/CA CO3
(e) Size of the solids. Mm.
(f) Other.
Providing ICTP Main switch of Kilburn/ L&T/ Siemens/ Crompton/Standard/Havells make and having Capacity 30% extra of the Operational rating as per IS:4064-1978 with upto date ammendment immediately after the power meter of HPSEB
Providing MS .sheet,steel fabricated floor mounted closed(Almirah type) switch board including angle iron post of suitable hright and size ISA 40x4-x6mm,duly painted,with steel sheet of 16 gauge comprising,capable of mounting the following accessories with all internal connections:
A.C.B./Oil circuit breaker of Kilburn/L&T/MEI/GEC make & of sutible capacity on incoming feeder with or without initial oil filling as the case may be with nrutral linked under voltage releases as per IS:2516-1985 with upto date ammendments with
Earth leakage circuit breaker of recommended make (Kilburn/L&T/MEI/GEC) as per 2516-1977 with upto date ammendment and of suitable range which should have control box operating handle and trip/reset bush button on/off indicators,re-indicating off spring condition of the circuit breaker for over current protection.The circuit should be equipped with magnet thermal release with metallic tape etc.It should also be fitted with earth fault for tripping of breaker on occurrence of earth fault on off breaker load side end.
The voltage monitor relay three phase with all protection and usual indicator and electric siren against single phasing low Voltage,high voltage reverse phasing over loading and voltage difference as per IS:3842(latest edition).
Power factor meter of standard make as per relevant IS code with upto date ammendments of suitable rating
Frequency meter of standard make as per relevant IS code with upto date ammendments of suitable rating.
Bus bar chamber having three bars of suitable rating for full length equal to the width og the board for three live phases and suitable for induced current,one copper bar of half the rating of full length for neutral phase as per IS:8084-1976 and IS: 11353-1985 read with BIS 5578-1985 with upto date ammendments
ICTP switches with HRC fuses of L&T/ Crompton /Kilburn/ Siemens/standard/Havells make and of suitable capacity as per IS 4064-1978 with upto date ammendments.
Three phase Indicator lamps complete with toggle switches for individual motors as per IS 3452(P-1&II)1983 with uoto date ammendments
Capacitor of Mechneil/Bhel/GEC/ L&T/ make as per IS:2834-1986 with uoto date ammendments to raise the power factor at site to 0.95 for direct connections to induction motor indiviually of required KVA rating according to offered including cables chamber to capactor and also including ICTP switches of appropriate range as per IS:4064-1978 with upto date ammendments.
Providing suitable Oil immersed star delta/direct on line /auto -tranformer/stater rotor starter of MEI/Kilburn/Jyoti/L&T/Siemens make as per IS:8544-1979 with upto date ammendments for squirrel cage/slip ring motor mounted on pannel board with magnetic type overload release and dashpot,time lag,under voltage release with or without initial oil filling as the case may be with single phase preventor as per IS 1248(P-V)-1983 with upto date ammenments.
Providing Hour run meter of recommended make of suitable capacity as per IS:722(Latest edition).
Prov. Antivibration pads under the pumps and motors of suitable size for the above pumping machinery as per IS:6337-1971
Prov. Cast iron flanged/screw type foot valves with strainer as per IS:4098-1986 with upto date ammendments of Kirloskar /Mechneil/ Kilburn/Leader make 80mm dia
Providing double flanged Cast Iron sluice valve of leader / Bhel/ Kirloskar/Kilburn/Gled/Fouress make and of 80mm for the delivery line of pump and capable of with standing normal seat pressure as per IS-780-1984 with upto date ammendments.
Providing double flanged Cast Iron sluice valve of leader / Bhel/Kirloskar/Kilburn/GLED/Fouress make and of 80mm dia for the delivery line of pump and capable of with standing normal seat pressure as per BS-1414 with upto date ammendments.
Providing double flanged(Swing type) Cast steel Reflux Valve of Leader/Bhel/Kirloskar/Kilburn/GLED/Fouress make and of 80mm dia having bye pass arrangement on the delivery line of pump and capable of with standing normal seat pressure as per BS:1868(P-1) with upto date ammendments.
Providing double flanged(Swing type) Cast steel Reflux Valve of Leader/Bhel/Kirloskar/Kilburn/GLED/Fouress make and of 80mm dia having bye pass arrangement for Rising Main and capable of with standing normal seat pressure as per BS:1868(P-1) with upto date ammendments.
Providing 80mm dia circular dia pressure gauge of Fiebing/Bourden/ prega/precision make complete with all accessories such as stop cock,copper tubing etc. as per IS 3624-1987 with upto date ammendments.
Prov.discharge meter standard make to be tiked on the rising main near the storage tank as per the directions of the Engineer-in-charge as per IS-2373-1981 with upto date ammendments.
Installation of all the items appearing at Serial No. 1 to 12… as per the systematic drawing attached with tender documents(Drg.No.1)
Providing and fixing double flanged MS/GI piping work layout to be approved by the Engineer-in-charge for suction and delivery pipes suitable to pumps offered and common header as per the rising main respectively complete with all specials such as bends,tees reducers/increasers with companion flanges matching with the relevant specifications of the accessores as indicated in the drawing No 2 including rubber/asbestos gasket of minimum 3mm thickness as per IS 2712-1979 and required number of nuts and volts as per IS 1364-1983.The pipes shall be as per relevant IS code and to withstand 1.5 times total head stipulated under item No-1.The size of the various components to be as under:-
(I) Suction pipe… 80 mm
(ii)Delivery pipe…80 mm
(iii)Common Header 80 mm
and will extended upto 5 mtrs from the outer wall of the pump
house in the direction to be jointed.
Providing and laying copper PVC insulated armoured power cable(One cable carring all the three Phases) of suitable size and capacity to and all other electrical equipments as per IS:1554(P-1) 1988 or latest with upto date ammendments of Siemens/Gloster/JEC/EICO National/Grandlay make including all other accessores such as thimbles,flexible,pipes solder,nuts and bolys cable glands etc.laid in pipes or trenches under floor.
Providing and fixing double loop earthing and copper plate 600mmx600mmx3mm thick electrode complete eith material such as thimbles,nuts and bolts,charcoal and common salt,25mmx3mm copper strips as per IS:3043-1987 with upto date ammendments for motors and other electrical equipments and digging of pits etc, complete in all respect.
LWSS JUNI
Providing horizontal spindle horizontal/radial split casing/end section(back pull out arregement) single/double/multistages centifugal pump or combination of pumps,in series/parallel of recommended make such as Mather and platt/KSB/Becon weir/Kirloskar/BE/Jyoti/WASP/ASPEE as per BIS 1520-1980 with upto date ammendments,read with IS-1937-1978 or latest edition suitable for lifting clear water for under mentioned characterstics with bronze impellers/pumping funnels casing ring and shaft sleaves of bronze,shaft of steel grade-with cast iron casing coupled directly through a flexible coupling on a common C.I./Cast steel base plate(base plate to be from the manufacturers of the Pumping unit only) to Slip/Ring/Squarrel cage screen protected drip proof induction motor of standred make such as Kirloksar/Cromption/Bhel/NGEF/GEC/SIEMEN/JAYOTI/ABB suitable for operation on 415(+)/- 5% volts,50 cycles/second,3 phase AC electric supply.The power of electric motor should be atleast 10% in excess of the maximum power required by the pump in the operation range of(+)10% and(-) 25% of the duty point head.The motor should be as per IS:325-1978 with upto date ammendments read with IS 900-1972.It should include cost of bearing nuts,bolts and pointing etc.and should meet the following requirements:-
Scheme :- LWSS Juni
(I) Discharge (Q) LPS :- 2.59
(a) LWL in sump well(h) : 960 Meters.
(d) Suction lift :- 3 Meters.
(e) Residual head:- 03 Meters.
(f) Static head:- 450.00 mtr
(iii) Rising main
(a) Length. :- 1850.00 mtr
(b) Dia :- 65 mm.
(iv) Pumping hours. 10 Hour's
(v) Altitude of Installation above MSL - Meters.
(vi) Characteristics of water
(a) Temperature oC
(b) Abient Temperature oC
© Turbidity Clear water JTU
(d) Alkalanity Mg/CA CO3
(e) Size of the solids. Mm.
(f) Other.
Providing ICTP Main switch of Kilburn/ L&T/ Siemens/ Crompton/Standard/Havells make and having Capacity 30% extra of the Operational rating as per IS:4064-1978 with upto date ammendment immediately after the power meter of HPSEB
Providing MS .sheet,steel fabricated floor mounted closed(Almirah type) switch board including angle iron post of suitable hright and size ISA 40x4-x6mm,duly painted,with steel sheet of 16 gauge comprising,capable of mounting the following accessories with all internal connections:
A.C.B./Oil circuit breaker of Kilburn/L&T/MEI/GEC make & of sutible capacity on incoming feeder with or without initial oil filling as the case may be with nrutral linked under voltage releases as per IS:2516-1985 with upto date ammendments with
Earth leakage circuit breaker of recommended make (Kilburn/L&T/MEI/GEC) as per 2516-1977 with upto date ammendment and of suitable range which should have control box operating handle and trip/reset bush button on/off indicators,re-indicating off spring condition of the circuit breaker for over current protection.The circuit should be equipped with magnet thermal release with metallic tape etc.It should also be fitted with earth fault for tripping of breaker on occurrence of earth fault on off breaker load side end.
The voltage monitor relay three phase with all protection and usual indicator and electric siren against single phasing low Voltage,high voltage reverse phasing over loading and voltage difference as per IS:3842(latest edition).
Power factor meter of standard make as per relevant IS code with upto date ammendments of suitable rating
Frequency meter of standard make as per relevant IS code with upto date ammendments of suitable rating.
Bus bar chamber having three bars of suitable rating for full length equal to the width og the board for three live phases and suitable for induced current,one copper bar of half the rating of full length for neutral phase as per IS:8084-1976 and IS: 11353-1985 read with BIS 5578-1985 with upto date ammendments
ICTP switches with HRC fuses of L&T/ Crompton /Kilburn/ Siemens/standard/Havells make and of suitable capacity as per IS 4064-1978 with upto date ammendments.
Three phase Indicator lamps complete with toggle switches for individual motors as per IS 3452(P-1&II)1983 with uoto date ammendments
Capacitor of Mechneil/Bhel/GEC/ L&T/ make as per IS:2834-1986 with uoto date ammendments to raise the power factor at site to 0.95 for direct connections to induction motor indiviually of required KVA rating according to offered including cables chamber to capactor and also including ICTP switches of appropriate range as per IS:4064-1978 with upto date ammendments.
Providing suitable Oil immersed star delta/direct on line /auto -tranformer/stater rotor starter of MEI/Kilburn/Jyoti/L&T/Siemens make as per IS:8544-1979 with upto date ammendments for squirrel cage/slip ring motor mounted on pannel board with magnetic type overload release and dashpot,time lag,under voltage release with or without initial oil filling as the case may be with single phase preventor as per IS 1248(P-V)-1983 with upto date ammenments.
Providing Hour run meter of recommended make of suitable capacity as per IS:722(Latest edition).
Prov. Antivibration pads under the pumps and motors of suitable size for the above pumping machinery as per IS:6337-1971
Prov. Cast iron flanged/screw type foot valves with strainer as per IS:4098-1986 with upto date ammendments of Kirloskar /Mechneil/ Kilburn/Leader make 65mm dia
Providing double flanged Cast Iron sluice valve of leader / Bhel/ Kirloskar/Kilburn/Gled/Fouress make and of 65mm for the delivery line of pump and capable of with standing normal seat pressure as per IS-780-1984 with upto date ammendments.
Providing double flanged Cast Iron sluice valve of leader / Bhel/Kirloskar/Kilburn/GLED/Fouress make and of 65mm dia for the delivery line of pump and capable of with standing normal seat pressure as per BS-1414 with upto date ammendments.
Providing double flanged(Swing type) Cast steel Reflux Valve of Leader/Bhel/Kirloskar/Kilburn/GLED/Fouress make and of 65mm dia having bye pass arrangement on the delivery line of pump and capable of with standing normal seat pressure as per BS:1868(P-1) with upto date ammendments.
Providing double flanged(Swing type) Cast steel Reflux Valve of Leader/Bhel/Kirloskar/Kilburn/GLED/Fouress make and of 65mm dia having bye pass arrangement for Rising Main and capable of with standing normal seat pressure as per BS:1868(P-1) with upto date ammendments.
Providing 65mm dia circular dia pressure gauge of Fiebing/Bourden/ prega/precision make complete with all accessories such as stop cock,copper tubing etc. as per IS 3624-1987 with upto date ammendments.
Prov.discharge meter standard make to be tiked on the rising main near the storage tank as per the directions of the Engineer-in-charge as per IS-2373-1981 with upto date ammendments.
Installation of all the items appearing at Serial No. 1 to 12… as per the systematic drawing attached with tender documents(Drg.No.1)
Providing and fixing double flanged MS/GI piping work layout to be approved by the Engineer-in-charge for suction and delivery pipes suitable to pumps offered and common header as per the rising main respectively complete with all specials such as bends,tees reducers/increasers with companion flanges matching with the relevant specifications of the accessores as indicated in the drawing No 2 including rubber/asbestos gasket of minimum 3mm thickness as per IS 2712-1979 and required number of nuts and volts as per IS 1364-1983.The pipes shall be as per relevant IS code and to withstand 1.5 times total head stipulated under item No-1.The size of the various components to be as under:-
(I) Suction pipe… 65 mm
(ii)Delivery pipe…65 mm
(iii)Common Header 65 mm
and will extended upto 5 mtrs from the outer wall of the pump
house in the direction to be jointed.
Providing and laying copper PVC insulated armoured power cable(One cable carring all the three Phases) of suitable size and capacity to and all other electrical equipments as per IS:1554(P-1) 1988 or latest with upto date ammendments of Siemens/Gloster/JEC/EICO National/Grandlay make including all other accessores such as thimbles,flexible,pipes solder,nuts and bolys cable glands etc.laid in pipes or trenches under floor.
Providing and fixing double loop earthing and copper plate 600mmx600mmx3mm thick electrode complete eith material such as thimbles,nuts and bolts,charcoal and common salt,25mmx3mm copper strips as per IS:3043-1987 with upto date ammendments for motors and other electrical equipments and digging of pits etc, complete in all respect.
LWSS Chanough( 1st Stage)
Providing horizontal spindle horizontal/radial split casing/end section(back pull out arregement) single/double/multistages centifugal pump or combination of pumps,in series/parallel of recommended make such as Mather and platt/KSB/Becon weir/Kirloskar/BE/Jyoti/WASP/ASPEE as per BIS 1520-1980 with upto date ammendments,read with IS-1937-1978 or latest edition suitable for lifting clear water for under mentioned characterstics with bronze impellers/pumping funnels casing ring and shaft sleaves of bronze,shaft of steel grade-with cast iron casing coupled directly through a flexible coupling on a common C.I./Cast steel base plate(base plate to be from the manufacturers of the Pumping unit only) to Slip/Ring/Squarrel cage screen protected drip proof induction motor of standred make such as Kirloksar/Cromption/Bhel/NGEF/GEC/SIEMEN/JAYOTI/ABB suitable for operation on 415(+)/- 5% volts,50 cycles/second,3 phase AC electric supply.The power of electric motor should be atleast 10% in excess of the maximum power required by the pump in the operation range of(+)10% and(-) 25% of the duty point head.The motor should be as per IS:325-1978 with upto date ammendments read with IS 900-1972.It should include cost of bearing nuts,bolts and pointing etc.and should meet the following requirements:-
Scheme :- LWSS Chanough
(I) Discharge (Q) LPS :- 4.61
(a) LWL in sump well(h) : 802 Meters.
(d) Suction lift :- 3 Meters.
(e) Residual head:- 03 Meters.
(f) Static head:- 450.00 mtr
(iii) Rising main
(a) Length. :- 1050.00 mtr
(b) Dia :- 80 mm.
(iv) Pumping hours. 8 Hour's
(v) Altitude of Installation above MSL - Meters.
(vi) Characteristics of water
(a) Temperature oC
(b) Abient Temperature oC
© Turbidity Clear water JTU
(d) Alkalanity Mg/CA CO3
(e) Size of the solids. Mm.
(f) Other.
Providing ICTP Main switch of Kilburn/ L&T/ Siemens/ Crompton/Standard/Havells make and having Capacity 30% extra of the Operational rating as per IS:4064-1978 with upto date ammendment immediately after the power meter of HPSEB
Providing MS .sheet,steel fabricated floor mounted closed(Almirah type) switch board including angle iron post of suitable hright and size ISA 40x4-x6mm,duly painted,with steel sheet of 16 gauge comprising,capable of mounting the following accessories with all internal connections:
A.C.B./Oil circuit breaker of Kilburn/L&T/MEI/GEC make & of sutible capacity on incoming feeder with or without initial oil filling as the case may be with nrutral linked under voltage releases as per IS:2516-1985 with upto date ammendments with
Earth leakage circuit breaker of recommended make (Kilburn/L&T/MEI/GEC) as per 2516-1977 with upto date ammendment and of suitable range which should have control box operating handle and trip/reset bush button on/off indicators,re-indicating off spring condition of the circuit breaker for over current protection.The circuit should be equipped with magnet thermal release with metallic tape etc.It should also be fitted with earth fault for tripping of breaker on occurrence of earth fault on off breaker load side end.
The voltage monitor relay three phase with all protection and usual indicator and electric siren against single phasing low Voltage,high voltage reverse phasing over loading and voltage difference as per IS:3842(latest edition).
Power factor meter of standard make as per relevant IS code with upto date ammendments of suitable rating
Frequency meter of standard make as per relevant IS code with upto date ammendments of suitable rating.
Bus bar chamber having three bars of suitable rating for full length equal to the width og the board for three live phases and suitable for induced current,one copper bar of half the rating of full length for neutral phase as per IS:8084-1976 and IS: 11353-1985 read with BIS 5578-1985 with upto date ammendments
ICTP switches with HRC fuses of L&T/ Crompton /Kilburn/ Siemens/standard/Havells make and of suitable capacity as per IS 4064-1978 with upto date ammendments.
Three phase Indicator lamps complete with toggle switches for individual motors as per IS 3452(P-1&II)1983 with uoto date ammendments
Capacitor of Mechneil/Bhel/GEC/ L&T/ make as per IS:2834-1986 with uoto date ammendments to raise the power factor at site to 0.95 for direct connections to induction motor indiviually of required KVA rating according to offered including cables chamber to capactor and also including ICTP switches of appropriate range as per IS:4064-1978 with upto date ammendments.
Providing suitable Oil immersed star delta/direct on line /auto -tranformer/stater rotor starter of MEI/Kilburn/Jyoti/L&T/Siemens make as per IS:8544-1979 with upto date ammendments for squirrel cage/slip ring motor mounted on pannel board with magnetic type overload release and dashpot,time lag,under voltage release with or without initial oil filling as the case may be with single phase preventor as per IS 1248(P-V)-1983 with upto date ammenments.
Providing Hour run meter of recommended make of suitable capacity as per IS:722(Latest edition).
Prov. Antivibration pads under the pumps and motors of suitable size for the above pumping machinery as per IS:6337-1971
Prov. Cast iron flanged/screw type foot valves with strainer as per IS:4098-1986 with upto date ammendments of Kirloskar /Mechneil/ Kilburn/Leader make 65mm dia
Providing double flanged Cast Iron sluice valve of leader / Bhel/ Kirloskar/Kilburn/Gled/Fouress make and of 80mm for the delivery line of pump and capable of with standing normal seat pressure as per IS-780-1984 with upto date ammendments.
Providing double flanged Cast Iron sluice valve of leader / Bhel/Kirloskar/Kilburn/GLED/Fouress make and of 80mm dia for the delivery line of pump and capable of with standing normal seat pressure as per BS-1414 with upto date ammendments.
Providing double flanged(Swing type) Cast steel Reflux Valve of Leader/Bhel/Kirloskar/Kilburn/GLED/Fouress make and of 80mm dia having bye pass arrangement on the delivery line of pump and capable of with standing normal seat pressure as per BS:1868(P-1) with upto date ammendments.
Providing double flanged(Swing type) Cast steel Reflux Valve of Leader/Bhel/Kirloskar/Kilburn/GLED/Fouress make and of 80mm dia having bye pass arrangement for Rising Main and capable of with standing normal seat pressure as per BS:1868(P-1) with upto date ammendments.
Providing 80mm dia circular dia pressure gauge of Fiebing/Bourden/ prega/precision make complete with all accessories such as stop cock,copper tubing etc. as per IS 3624-1987 with upto date ammendments.
Prov.discharge meter standard make to be tiked on the rising main near the storage tank as per the directions of the Engineer-in-charge as per IS-2373-1981 with upto date ammendments.
Installation of all the items appearing at Serial No. 1 to 12… as per the systematic drawing attached with tender documents(Drg.No.1)
Providing and fixing double flanged MS/GI piping work layout to be approved by the Engineer-in-charge for suction and delivery pipes suitable to pumps offered and common header as per the rising main respectively complete with all specials such as bends,tees reducers/increasers with companion flanges matching with the relevant specifications of the accessores as indicated in the drawing No 2 including rubber/asbestos gasket of minimum 3mm thickness as per IS 2712-1979 and required number of nuts and volts as per IS 1364-1983.The pipes shall be as per relevant IS code and to withstand 1.5 times total head stipulated under item No-1.The size of the various components to be as under:-
(I) Suction pipe… 80 mm
(ii)Delivery pipe…80 mm
(iii)Common Header 80 mm
and will extended upto 5 mtrs from the outer wall of the pump
house in the direction to be jointed.
Providing and laying copper PVC insulated armoured power cable(One cable carring all the three Phases) of suitable size and capacity to and all other electrical equipments as per IS:1554(P-1) 1988 or latest with upto date ammendments of Siemens/Gloster/JEC/EICO National/Grandlay make including all other accessores such as thimbles,flexible,pipes solder,nuts and bolys cable glands etc.laid in pipes or trenches under floor.
Providing and fixing double loop earthing and copper plate 600mmx600mmx3mm thick electrode complete eith material such as thimbles,nuts and bolts,charcoal and common salt,25mmx3mm copper strips as per IS:3043-1987 with upto date ammendments for motors and other electrical equipments and digging of pits etc, complete in all respect.
LWSS Chanough( 2nd Stage)
Providing horizontal spindle horizontal/radial split casing/end section(back pull out arregement) single/double/multistages centifugal pump or combination of pumps,in series/parallel of recommended make such as Mather and platt/KSB/Becon weir/Kirloskar/BE/Jyoti/WASP/ASPEE as per BIS 1520-1980 with upto date ammendments,read with IS-1937-1978 or latest edition suitable for lifting clear water for under mentioned characterstics with bronze impellers/pumping funnels casing ring and shaft sleaves of bronze,shaft of steel grade-with cast iron casing coupled directly through a flexible coupling on a common C.I./Cast steel base plate(base plate to be from the manufacturers of the Pumping unit only) to Slip/Ring/Squarrel cage screen protected drip proof induction motor of standred make such as Kirloksar/Cromption/Bhel/NGEF/GEC/SIEMEN/JAYOTI/ABB suitable for operation on 415(+)/- 5% volts,50 cycles/second,3 phase AC electric supply.The power of electric motor should be atleast 10% in excess of the maximum power required by the pump in the operation range of(+)10% and(-) 25% of the duty point head.The motor should be as per IS:325-1978 with upto date ammendments read with IS 900-1972.It should include cost of bearing nuts,bolts and pointing etc.and should meet the following requirements:-
Scheme :- LWSS Chanough
(I) Discharge (Q) LPS :- 4.61
(a) LWL in sump well(h) : 1242 Meters.
(d) Suction lift :- 3 Meters.
(e) Residual head:- 03 Meters.
(f) Static head:- 493.00 mtr
(iii) Rising main
(a) Length. :- 2700.00 mtr
(b) Dia :- 80 mm.
(iv) Pumping hours. 8 Hour's
(v) Altitude of Installation above MSL - Meters.
(vi) Characteristics of water
(a) Temperature oC
(b) Abient Temperature oC
© Turbidity Clear water JTU
(d) Alkalanity Mg/CA CO3
(e) Size of the solids. Mm.
(f) Other.
Providing ICTP Main switch of Kilburn/ L&T/ Siemens/ Crompton/Standard/Havells make and having Capacity 30% extra of the Operational rating as per IS:4064-1978 with upto date ammendment immediately after the power meter of HPSEB
Providing MS .sheet,steel fabricated floor mounted closed(Almirah type) switch board including angle iron post of suitable hright and size ISA 40x4-x6mm,duly painted,with steel sheet of 16 gauge comprising,capable of mounting the following accessories with all internal connections:
A.C.B./Oil circuit breaker of Kilburn/L&T/MEI/GEC make & of sutible capacity on incoming feeder with or without initial oil filling as the case may be with nrutral linked under voltage releases as per IS:2516-1985 with upto date ammendments with
Earth leakage circuit breaker of recommended make (Kilburn/L&T/MEI/GEC) as per 2516-1977 with upto date ammendment and of suitable range which should have control box operating handle and trip/reset bush button on/off indicators,re-indicating off spring condition of the circuit breaker for over current protection.The circuit should be equipped with magnet thermal release with metallic tape etc.It should also be fitted with earth fault for tripping of breaker on occurrence of earth fault on off breaker load side end.
The voltage monitor relay three phase with all protection and usual indicator and electric siren against single phasing low Voltage,high voltage reverse phasing over loading and voltage difference as per IS:3842(latest edition).
Power factor meter of standard make as per relevant IS code with upto date ammendments of suitable rating
Frequency meter of standard make as per relevant IS code with upto date ammendments of suitable rating.
Bus bar chamber having three bars of suitable rating for full length equal to the width og the board for three live phases and suitable for induced current,one copper bar of half the rating of full length for neutral phase as per IS:8084-1976 and IS: 11353-1985 read with BIS 5578-1985 with upto date ammendments
ICTP switches with HRC fuses of L&T/ Crompton /Kilburn/ Siemens/standard/Havells make and of suitable capacity as per IS 4064-1978 with upto date ammendments.
Three phase Indicator lamps complete with toggle switches for individual motors as per IS 3452(P-1&II)1983 with uoto date ammendments
Capacitor of Mechneil/Bhel/GEC/ L&T/ make as per IS:2834-1986 with uoto date ammendments to raise the power factor at site to 0.95 for direct connections to induction motor indiviually of required KVA rating according to offered including cables chamber to capactor and also including ICTP switches of appropriate range as per IS:4064-1978 with upto date ammendments.
Providing suitable Oil immersed star delta/direct on line /auto -tranformer/stater rotor starter of MEI/Kilburn/Jyoti/L&T/Siemens make as per IS:8544-1979 with upto date ammendments for squirrel cage/slip ring motor mounted on pannel board with magnetic type overload release and dashpot,time lag,under voltage release with or without initial oil filling as the case may be with single phase preventor as per IS 1248(P-V)-1983 with upto date ammenments.
Providing Hour run meter of recommended make of suitable capacity as per IS:722(Latest edition).
Prov. Antivibration pads under the pumps and motors of suitable size for the above pumping machinery as per IS:6337-1971
Prov. Cast iron flanged/screw type foot valves with strainer as per IS:4098-1986 with upto date ammendments of Kirloskar /Mechneil/ Kilburn/Leader make 65mm dia
Providing double flanged Cast Iron sluice valve of leader / Bhel/ Kirloskar/Kilburn/Gled/Fouress make and of 80mm for the delivery line of pump and capable of with standing normal seat pressure as per IS-780-1984 with upto date ammendments.
Providing double flanged Cast Iron sluice valve of leader / Bhel/Kirloskar/Kilburn/GLED/Fouress make and of 80mm dia for the delivery line of pump and capable of with standing normal seat pressure as per BS-1414 with upto date ammendments.
Providing double flanged(Swing type) Cast steel Reflux Valve of Leader/Bhel/Kirloskar/Kilburn/GLED/Fouress make and of 80mm dia having bye pass arrangement on the delivery line of pump and capable of with standing normal seat pressure as per BS:1868(P-1) with upto date ammendments.
Providing double flanged(Swing type) Cast steel Reflux Valve of Leader/Bhel/Kirloskar/Kilburn/GLED/Fouress make and of 80mm dia having bye pass arrangement for Rising Main and capable of with standing normal seat pressure as per BS:1868(P-1) with upto date ammendments.
Providing 80mm dia circular dia pressure gauge of Fiebing/Bourden/ prega/precision make complete with all accessories such as stop cock,copper tubing etc. as per IS 3624-1987 with upto date ammendments.
Prov.discharge meter standard make to be tiked on the rising main near the storage tank as per the directions of the Engineer-in-charge as per IS-2373-1981 with upto date ammendments.
Installation of all the items appearing at Serial No. 1 to 12… as per the systematic drawing attached with tender documents(Drg.No.1)
Providing and fixing double flanged MS/GI piping work layout to be approved by the Engineer-in-charge for suction and delivery pipes suitable to pumps offered and common header as per the rising main respectively complete with all specials such as bends,tees reducers/increasers with companion flanges matching with the relevant specifications of the accessores as indicated in the drawing No 2 including rubber/asbestos gasket of minimum 3mm thickness as per IS 2712-1979 and required number of nuts and volts as per IS 1364-1983.The pipes shall be as per relevant IS code and to withstand 1.5 times total head stipulated under item No-1.The size of the various components to be as under:-
(I) Suction pipe… 80 mm
(ii)Delivery pipe…80 mm
(iii)Common Header 80 mm
and will extended upto 5 mtrs from the outer wall of the pump
house in the direction to be jointed.
Providing and laying copper PVC insulated armoured power cable(One cable carring all the three Phases) of suitable size and capacity to and all other electrical equipments as per IS:1554(P-1) 1988 or latest with upto date ammendments of Siemens/Gloster/JEC/EICO National/Grandlay make including all other accessores such as thimbles,flexible,pipes solder,nuts and bolys cable glands etc.laid in pipes or trenches under floor.
Providing and fixing double loop earthing and copper plate 600mmx600mmx3mm thick electrode complete eith material such as thimbles,nuts and bolts,charcoal and common salt,25mmx3mm copper strips as per IS:3043-1987 with upto date ammendments for motors and other electrical equipments and digging of pits etc, complete in all respect.
LWSS Taror Panehra( 1st Stage)
Providing horizontal spindle horizontal/radial split casing/end section(back pull out arregement) single/double/multistages centifugal pump or combination of pumps,in series/parallel of recommended make such as Mather and platt/KSB/Becon weir/Kirloskar/BE/Jyoti/WASP/ASPEE as per BIS 1520-1980 with upto date ammendments,read with IS-1937-1978 or latest edition suitable for lifting clear water for under mentioned characterstics with bronze impellers/pumping funnels casing ring and shaft sleaves of bronze,shaft of steel grade-with cast iron casing coupled directly through a flexible coupling on a common C.I./Cast steel base plate(base plate to be from the manufacturers of the Pumping unit only) to Slip/Ring/Squarrel cage screen protected drip proof induction motor of standred make such as Kirloksar/Cromption/Bhel/NGEF/GEC/SIEMEN/JAYOTI/ABB suitable for operation on 415(+)/- 5% volts,50 cycles/second,3 phase AC electric supply.The power of electric motor should be atleast 10% in excess of the maximum power required by the pump in the operation range of(+)10% and(-) 25% of the duty point head.The motor should be as per IS:325-1978 with upto date ammendments read with IS 900-1972.It should include cost of bearing nuts,bolts and pointing etc.and should meet the following requirements:-
Scheme :- LWSS Taror Panehra
(I) Discharge (Q) LPS :- 5.18
(a) LWL in sump well(h) : 800 Meters.
(d) Suction lift :- 3 Meters.
(e) Residual head:- 03 Meters.
(f) Static head:- 275.00 mtr
(iii) Rising main
(a) Length. :- 610.00 mtr
(b) Dia :- 80 mm.
(iv) Pumping hours. 8 Hour's
(v) Altitude of Installation above MSL - Meters.
(vi) Characteristics of water
(a) Temperature oC
(b) Abient Temperature oC
© Turbidity Clear water JTU
(d) Alkalanity Mg/CA CO3
(e) Size of the solids. Mm.
(f) Other.
Providing ICTP Main switch of Kilburn/ L&T/ Siemens/ Crompton/Standard/Havells make and having Capacity 30% extra of the Operational rating as per IS:4064-1978 with upto date ammendment immediately after the power meter of HPSEB
Providing MS .sheet,steel fabricated floor mounted closed(Almirah type) switch board including angle iron post of suitable hright and size ISA 40x4-x6mm,duly painted,with steel sheet of 16 gauge comprising,capable of mounting the following accessories with all internal connections:
A.C.B./Oil circuit breaker of Kilburn/L&T/MEI/GEC make & of sutible capacity on incoming feeder with or without initial oil filling as the case may be with nrutral linked under voltage releases as per IS:2516-1985 with upto date ammendments with
Earth leakage circuit breaker of recommended make (Kilburn/L&T/MEI/GEC) as per 2516-1977 with upto date ammendment and of suitable range which should have control box operating handle and trip/reset bush button on/off indicators,re-indicating off spring condition of the circuit breaker for over current protection.The circuit should be equipped with magnet thermal release with metallic tape etc.It should also be fitted with earth fault for tripping of breaker on occurrence of earth fault on off breaker load side end.
The voltage monitor relay three phase with all protection and usual indicator and electric siren against single phasing low Voltage,high voltage reverse phasing over loading and voltage difference as per IS:3842(latest edition).
Power factor meter of standard make as per relevant IS code with upto date ammendments of suitable rating
Frequency meter of standard make as per relevant IS code with upto date ammendments of suitable rating.
Bus bar chamber having three bars of suitable rating for full length equal to the width og the board for three live phases and suitable for induced current,one copper bar of half the rating of full length for neutral phase as per IS:8084-1976 and IS: 11353-1985 read with BIS 5578-1985 with upto date ammendments
ICTP switches with HRC fuses of L&T/ Crompton /Kilburn/ Siemens/standard/Havells make and of suitable capacity as per IS 4064-1978 with upto date ammendments.
Three phase Indicator lamps complete with toggle switches for individual motors as per IS 3452(P-1&II)1983 with uoto date ammendments
Capacitor of Mechneil/Bhel/GEC/ L&T/ make as per IS:2834-1986 with uoto date ammendments to raise the power factor at site to 0.95 for direct connections to induction motor indiviually of required KVA rating according to offered including cables chamber to capactor and also including ICTP switches of appropriate range as per IS:4064-1978 with upto date ammendments.
Providing suitable Oil immersed star delta/direct on line /auto -tranformer/stater rotor starter of MEI/Kilburn/Jyoti/L&T/Siemens make as per IS:8544-1979 with upto date ammendments for squirrel cage/slip ring motor mounted on pannel board with magnetic type overload release and dashpot,time lag,under voltage release with or without initial oil filling as the case may be with single phase preventor as per IS 1248(P-V)-1983 with upto date ammenments.
Providing Hour run meter of recommended make of suitable capacity as per IS:722(Latest edition).
Prov. Antivibration pads under the pumps and motors of suitable size for the above pumping machinery as per IS:6337-1971
Prov. Cast iron flanged/screw type foot valves with strainer as per IS:4098-1986 with upto date ammendments of Kirloskar /Mechneil/ Kilburn/Leader make 65mm dia
Providing double flanged Cast Iron sluice valve of leader / Bhel/ Kirloskar/Kilburn/Gled/Fouress make and of 80mm for the delivery line of pump and capable of with standing normal seat pressure as per IS-780-1984 with upto date ammendments.
Providing double flanged Cast Iron sluice valve of leader / Bhel/Kirloskar/Kilburn/GLED/Fouress make and of 80mm dia for the delivery line of pump and capable of with standing normal seat pressure as per BS-1414 with upto date ammendments.
Providing double flanged(Swing type) Cast steel Reflux Valve of Leader/Bhel/Kirloskar/Kilburn/GLED/Fouress make and of 80mm dia having bye pass arrangement on the delivery line of pump and capable of with standing normal seat pressure as per BS:1868(P-1) with upto date ammendments.
Providing double flanged(Swing type) Cast steel Reflux Valve of Leader/Bhel/Kirloskar/Kilburn/GLED/Fouress make and of 80mm dia having bye pass arrangement for Rising Main and capable of with standing normal seat pressure as per BS:1868(P-1) with upto date ammendments.
Providing 80mm dia circular dia pressure gauge of Fiebing/Bourden/ prega/precision make complete with all accessories such as stop cock,copper tubing etc. as per IS 3624-1987 with upto date ammendments.
Prov.discharge meter standard make to be tiked on the rising main near the storage tank as per the directions of the Engineer-in-charge as per IS-2373-1981 with upto date ammendments.
Installation of all the items appearing at Serial No. 1 to 12… as per the systematic drawing attached with tender documents(Drg.No.1)
Providing and fixing double flanged MS/GI piping work layout to be approved by the Engineer-in-charge for suction and delivery pipes suitable to pumps offered and common header as per the rising main respectively complete with all specials such as bends,tees reducers/increasers with companion flanges matching with the relevant specifications of the accessores as indicated in the drawing No 2 including rubber/asbestos gasket of minimum 3mm thickness as per IS 2712-1979 and required number of nuts and volts as per IS 1364-1983.The pipes shall be as per relevant IS code and to withstand 1.5 times total head stipulated under item No-1.The size of the various components to be as under:-
(I) Suction pipe… 80 mm
(ii)Delivery pipe…80 mm
(iii)Common Header 80 mm
and will extended upto 5 mtrs from the outer wall of the pump
house in the direction to be jointed.
Providing and laying copper PVC insulated armoured power cable(One cable carring all the three Phases) of suitable size and capacity to and all other electrical equipments as per IS:1554(P-1) 1988 or latest with upto date ammendments of Siemens/Gloster/JEC/EICO National/Grandlay make including all other accessores such as thimbles,flexible,pipes solder,nuts and bolys cable glands etc.laid in pipes or trenches under floor.
Providing and fixing double loop earthing and copper plate 600mmx600mmx3mm thick electrode complete eith material such as thimbles,nuts and bolts,charcoal and common salt,25mmx3mm copper strips as per IS:3043-1987 with upto date ammendments for motors and other electrical equipments and digging of pits etc, complete in all respect.
LWSS Taror Panehra( 2nd Stage)
Providing horizontal spindle horizontal/radial split casing/end section(back pull out arregement) single/double/multistages centifugal pump or combination of pumps,in series/parallel of recommended make such as Mather and platt/KSB/Becon weir/Kirloskar/BE/Jyoti/WASP/ASPEE as per BIS 1520-1980 with upto date ammendments,read with IS-1937-1978 or latest edition suitable for lifting clear water for under mentioned characterstics with bronze impellers/pumping funnels casing ring and shaft sleaves of bronze,shaft of steel grade-with cast iron casing coupled directly through a flexible coupling on a common C.I./Cast steel base plate(base plate to be from the manufacturers of the Pumping unit only) to Slip/Ring/Squarrel cage screen protected drip proof induction motor of standred make such as Kirloksar/Cromption/Bhel/NGEF/GEC/SIEMEN/JAYOTI/ABB suitable for operation on 415(+)/- 5% volts,50 cycles/second,3 phase AC electric supply.The power of electric motor should be atleast 10% in excess of the maximum power required by the pump in the operation range of(+)10% and(-) 25% of the duty point head.The motor should be as per IS:325-1978 with upto date ammendments read with IS 900-1972.It should include cost of bearing nuts,bolts and pointing etc.and should meet the following requirements:-
Scheme :- LWSS Taror Panehra
(I) Discharge (Q) LPS :- 5.49
Others:
(a) LWL in sump well(h) : 1070 Meters.
(d) Suction lift :- 3 Meters.
(e) Residual head:- 03 Meters.
(f) Static head:- 250.00 mtr
(iii) Rising main
(a) Length. :- 695.00 mtr
(b) Dia :- 80 mm.
(iv) Pumping hours. 8 Hour's
(v) Altitude of Installation above MSL - Meters.
(vi) Characteristics of water
(a) Temperature oC
(b) Abient Temperature oC
© Turbidity Clear water JTU
(d) Alkalanity Mg/CA CO3
(e) Size of the solids. Mm.
(f) Other.
Providing ICTP Main switch of Kilburn/ L&T/ Siemens/ Crompton/Standard/Havells make and having Capacity 30% extra of the Operational rating as per IS:4064-1978 with upto date ammendment immediately after the power meter of HPSEB
Providing MS .sheet,steel fabricated floor mounted closed(Almirah type) switch board including angle iron post of suitable hright and size ISA 40x4-x6mm,duly painted,with steel sheet of 16 gauge comprising,capable of mounting the following accessories with all internal connections:
A.C.B./Oil circuit breaker of Kilburn/L&T/MEI/GEC make & of sutible capacity on incoming feeder with or without initial oil filling as the case may be with nrutral linked under voltage releases as per IS:2516-1985 with upto date ammendments with
Earth leakage circuit breaker of recommended make (Kilburn/L&T/MEI/GEC) as per 2516-1977 with upto date ammendment and of suitable range which should have control box operating handle and trip/reset bush button on/off indicators,re-indicating off spring condition of the circuit breaker for over current protection.The circuit should be equipped with magnet thermal release with metallic tape etc.It should also be fitted with earth fault for tripping of breaker on occurrence of earth fault on off breaker load side end.
The voltage monitor relay three phase with all protection and usual indicator and electric siren against single phasing low Voltage,high voltage reverse phasing over loading and voltage difference as per IS:3842(latest edition).
Power factor meter of standard make as per relevant IS code with upto date ammendments of suitable rating
Frequency meter of standard make as per relevant IS code with upto date ammendments of suitable rating.
Bus bar chamber having three bars of suitable rating for full length equal to the width og the board for three live phases and suitable for induced current,one copper bar of half the rating of full length for neutral phase as per IS:8084-1976 and IS: 11353-1985 read with BIS 5578-1985 with upto date ammendments
ICTP switches with HRC fuses of L&T/ Crompton /Kilburn/ Siemens/standard/Havells make and of suitable capacity as per IS 4064-1978 with upto date ammendments.
Three phase Indicator lamps complete with toggle switches for individual motors as per IS 3452(P-1&II)1983 with uoto date ammendments
Capacitor of Mechneil/Bhel/GEC/ L&T/ make as per IS:2834-1986 with uoto date ammendments to raise the power factor at site to 0.95 for direct connections to induction motor indiviually of required KVA rating according to offered including cables chamber to capactor and also including ICTP switches of appropriate range as per IS:4064-1978 with upto date ammendments.
Providing suitable Oil immersed star delta/direct on line /auto -tranformer/stater rotor starter of MEI/Kilburn/Jyoti/L&T/Siemens make as per IS:8544-1979 with upto date ammendments for squirrel cage/slip ring motor mounted on pannel board with magnetic type overload release and dashpot,time lag,under voltage release with or without initial oil filling as the case may be with single phase preventor as per IS 1248(P-V)-1983 with upto date ammenments.
Providing Hour run meter of recommended make of suitable capacity as per IS:722(Latest edition).
Prov. Antivibration pads under the pumps and motors of suitable size for the above pumping machinery as per IS:6337-1971
Prov. Cast iron flanged/screw type foot valves with strainer as per IS:4098-1986 with upto date ammendments of Kirloskar /Mechneil/ Kilburn/Leader make 65mm dia
Providing double flanged Cast Iron sluice valve of leader / Bhel/ Kirloskar/Kilburn/Gled/Fouress make and of 80mm for the delivery line of pump and capable of with standing normal seat pressure as per IS-780-1984 with upto date ammendments.
Providing double flanged Cast Iron sluice valve of leader / Bhel/Kirloskar/Kilburn/GLED/Fouress make and of 80mm dia for the delivery line of pump and capable of with standing normal seat pressure as per BS-1414 with upto date ammendments.
Providing double flanged(Swing type) Cast steel Reflux Valve of Leader/Bhel/Kirloskar/Kilburn/GLED/Fouress make and of 80mm dia having bye pass arrangement on the delivery line of pump and capable of with standing normal seat pressure as per BS:1868(P-1) with upto date ammendments.
Providing double flanged(Swing type) Cast steel Reflux Valve of Leader/Bhel/Kirloskar/Kilburn/GLED/Fouress make and of 80mm dia having bye pass arrangement for Rising Main and capable of with standing normal seat pressure as per BS:1868(P-1) with upto date ammendments.
Providing 80mm dia circular dia pressure gauge of Fiebing/Bourden/ prega/precision make complete with all accessories such as stop cock,copper tubing etc. as per IS 3624-1987 with upto date ammendments.
Prov.discharge meter standard make to be tiked on the rising main near the storage tank as per the directions of the Engineer-in-charge as per IS-2373-1981 with upto date ammendments.
Installation of all the items appearing at Serial No. 1 to 12… as per the systematic drawing attached with tender documents(Drg.No.1)
Providing and fixing double flanged MS/GI piping work layout to be approved by the Engineer-in-charge for suction and delivery pipes suitable to pumps offered and common header as per the rising main respectively complete with all specials such as bends,tees reducers/increasers with companion flanges matching with the relevant specifications of the accessores as indicated in the drawing No 2 including rubber/asbestos gasket of minimum 3mm thickness as per IS 2712-1979 and required number of nuts and volts as per IS 1364-1983.The pipes shall be as per relevant IS code and to withstand 1.5 times total head stipulated under item No-1.The size of the various components to be as under:-
(I) Suction pipe… 80 mm
(ii)Delivery pipe…80 mm
(iii)Common Header 80 mm
and will extended upto 5 mtrs from the outer wall of the pump
house in the direction to be jointed.
Providing and laying copper PVC insulated armoured power cable(One cable carring all the three Phases) of suitable size and capacity to and all other electrical equipments as per IS:1554(P-1) 1988 or latest with upto date ammendments of Siemens/Gloster/JEC/EICO National/Grandlay make including all other accessores such as thimbles,flexible,pipes solder,nuts and bolys cable glands etc.laid in pipes or trenches under floor.
Providing and fixing double loop earthing and copper plate 600mmx600mmx3mm thick electrode complete eith material such as thimbles,nuts and bolts,charcoal and common salt,25mmx3mm copper strips as per IS:3043-1987 with upto date ammendments for motors and other electrical equipments and digging of pits etc, complete in all respect.
MONO SUBMERSIBLE PUMP
Prov. 3 Phase Mono submersible pump set of reputed and approved make i.e. KSB model MR-3 confirming to letest BISspecifications i.e. 8304 . The pump set shall be fixed with free flow impellers of suitable allow as per BIS -8631-1976 with upto date amendmentsfor lifting raw water lubricated bush bearings of suitable alloy and shaft protection sleeves the pump shall be fitted coupled to submercible required cage motor com-pump to BIS 9283-1995 with upto date amendments corresponding to pump, fitted with water lubricated bush bearing alloys and shaft protection sleeve arrangement to counter balance the thrust caused due to water column in rising main and having cooling arrangement. The pump set should include the water level guard, errection clamps , cable clips and capable of following performances.
Total head = 28.82 mtrs
Discharge = 13.39 LPS
Dia of Rising main = 150 mm
Suction in line booster
Pumping hours = 16 Hour
P/F 3 core copper cable wire 25 mm Sqm (Flat Submersible Cable)
P/F control panel for 10 HP Three phase with Amp. Mete,r volt meter, stater MCB water level gurd.
Installation of Pump Set i/c Cutting , welding , Jointing ,complete in all respect at site.
Carriage of Pump Set & Other accessories.
CRANE GANTRY
Providing & errection of Power oprated Over Head Crane .
Electrical and sanitary fitting in pump house i.e. light, heating, ceiling,fan points, wash basin, flush cistern, tap etc. as per satissfection of Engineer-in-Charge
Note:The rates quoted shall be after Rebate for old pumping machinery and Rising main, which shall be replaced with new pumping machinery and Rising main, such dismentalled material shall be property of the contractor/ firm.
HARJEET SINGH
HILL CONSTRUCTION AND ENGINEERING CO. SOLAN
stage.html
html • 0.05 MB
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.04 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .