Loading…
Loading…
| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | L1₹39.0 LAccepted-AOC BALTIKURI INDUSTRIAL ESTATE PLOT NO A 01 DASNAGAR HOWRAH 711113 | HOWRAH | HOWRAH | WEST BENGAL | 711113 | L1 | Accepted-AOC L1 bidder | |
| 2 | L2₹39.8 L+₹81,860 (2.10%)Rejected-Finance 8 TOWNSHEND ROAD KOLKATA 700025 | KOLKATA | KOLKATA | WEST BENGAL | 700025 | L2 | Rejected-Finance 2nd lowest bidder | |
| 3 | L3₹43.3 L+₹4.4 L (11.2%)Rejected-Finance 19 LAKE TEMPLE ROAD KOLKATA 700029 | KOLKATA | WEST BENGAL | 700029 | L3 | Rejected-Finance 3rd lowest bidder |
Tender Value
Refer Docs
EMD Value
₹80,000
Closing Date
7 Feb 2022, 12:00 pmClosed
EE_II Kol. South Health El. Divn., P.W.Dte
75 D H Road Kidderpore Kol_23
Electrical Installation work for 24 Beded hybrid CCU at Vidyasagar S.G. Hospital,Behala,Kolkata_SITC of HVAC systems with negative pressure.
2022_WBPWD_361277_1
WBPWD/KSHED/Q53/21-22
Open Tender
A/C ORG
Item Rate
15 days
Kolkata
Please refer Tender documents.
2 documents required · 2 mandatory
₹80,000
4 May 2023
19 Jan 2022
9 Feb 2022
19 Jan 2022
7 Feb 2022
29 Jan 2022
Amount
Supply of Ceiling Mounted Ductable DX type Air Conditioning Unit with 198000 BTU/hr Cooling capacity,6600 CFM Air Flow, with 3/2 nos, Scroll compressor, 400V/3 Ph/50 Hz Microprocessor based Controller of 16.5 TR nominal capacity with R-410A/R407C/R32 Refrigerant. (Make - Hitachi / O-General / Carrier / Voltas / Daikin / Blue Star). (HDU_2R & 1S)(Male Medicine_1R & 1S).
Supply of Ceiling Mounted Ductable DX type Air Conditioning Unit with 132000 BTU/hr Cooling capacity, 4400 CFM Air Flow, with 2 nos, Scroll compressor, 400V/3 Ph/50 Hz Microprocessor based Controller of 11.0 TR nominal capacity with R-410A/R407C/R32 Refrigerant. (Make - Hitachi / O-General / Carrier /Voltas / Daikin / Blue Star)(HDU_1R & 1S).
SITC of Single Skin Centrifugal Cabinet Type Fan complete with DIDW- forward/Back curved belt/direct driven centrifugal blower Rotation of fan 1435 RPM, Epoxy/ galvanized steel sheet cabinet with service access doors, Inlet & outlet drilled flanges 2.7 KW, 4 pole, IE - 2, IP -55 Standard 1Ph/220V/50 hz Motor, (Make: ABB/ Ostberge) with Fixed base, common base frame with spring isolators, Flange at inlet and outlet are provided to facilitate duct connection necessary hanging/supporting members, water proof Dimer Panel for Fan's Speed control etc. Sound level-65 dba. Capacity 70mm/wc Static pressure, 2500 CFM,(Make- Ostberge/ Marathon/Kruger)(HDU_2R & 1S)(Male Medicine_1R & 1S).
SITC of 10 Micron Pre Filter (Make - FMI / SPECTRUM / AIRTECH / AFI / AHU manufacture standard) with Frame, it will be fitted on Centrifugal Exhaust fan, TFA Units & on the Fresh air Damper.
SITC of MERV-17 0.3 Micron Hefa Filter (Make - FMI / SPECTRUM / AIRTECH / AFI / AHU manufacture standard) and it would be fitted on Centrifugal Exhust fan.
Supply and fixing of UVC EMIITTER (Make - ALFA / RUKS) for the above fan's for prevention of fungus. The minimum UV intensity in the coils should be 700-800 UW-SEC/CM2. The unit shall be UL.Listed (UL-1995).
Installation, Testing & Commissioning of the above Air Conditioning systems with all necessary accessories for hanging Indoor & Outdoor Units.
For 16.5 TR Ductable Units.
For 11.0 TR Ductable Units.
Supplying & laying of Copper refrigeration pipe line (Make: Rajco / Royko / Mandev) for liquid and suction line with hard drawn copper piping with supports & brackets.
Cu. Pipes Suction line dia 12.7 mm with minimum thickness 0.9 mm
Cu. H D Pipe Suction line dia 22.2 mm (minimum thickness 0.9 mm) with 13mm thick nitrile insulation (Make: Armacell / K Flex / Vedio Flex).
Supply and fixing of necessary electrical arrangements of Air Conditioning Units, PVC insulated FRLS grade Copper cable for connection between indoor and outdoor units, 1.1 KV grade.
3 core x 1.5 mm² (Make- Polycab / Havells / Finolex / RR Kabel).
3 core x 2.5 mm² (Make- Polycab / Havells / Finolex / RR Kabel).
Supply & fixing of following dia UPVC drain pipes with all necessary hanging arrangements & 9 mm Heat Retardant Thermal insulation.
Dia 32 mm
Dia 25 mm
SITC of Site Fabricated G.I Sheet Metal (TATA/SAIL) Square Air Duct complete with Angle, Fastener, supports, dampers etc. as per specifications & site requirement.
For 24 SWG
For 22 SWG
Supply and fixing Heat Retardant closed cell Class 'O' 9 mm thick Nitrile Rubber insulation (Make: Armacell / K Flex / Vedio Flex) inside Supply Air duct.
Supply and fixing Heat Retardant closed cell Class 'O' 9mm thick Nitrile Rubber insulation (Make: Armacell / K Flex / Vedio Flex) with AI Foil Faced Outside Supply Air duct.
Supply & Fixing of Liner type AI Powder Coated Continuous Grill (Make: Ravi Star / Dynacraft / Caryaire) with VCD for Supply Air.
Supply & Fixing of Liner type AI Powder Coated Continuous Grill (Make: Ravi Star / Dynacraft / Caryaire) without VCD for Return Air.
Supply and Fixing of Fresh Air Volume Control Damper (Make: Ravi Star / Dynacraft / Premier).
Supply and Fixing of Motorized Non-Return Type Flow Control Damper (Make: Ravi Star / Dynacraft / Premier).
Supply & Fixing of Fusible Link Fire Damper (Make: Ravi Star / Dynacraft / Caryair), Galvanized Steel Sheet with 125 GSM Zink Coated, Certified by CBRI (U-555, 1995),with minimum fire rating not less than 120 min, must be Fusible Link Spring with 74°C Temperature rating Ul Listed.
Providing and fixing fire retardant nonporous double layer flexible connection between IDU, Exhaust, TFA units and duct.
SITC of heavy duty anti vibration pad to protect the system from any kind of unwanted vibration.
Supply & Fixing of Fresh Air Damper with Bird Screen as per direction of E.I.C (Make: Premier / AR Enterprise / Air Premier).
Supplying, fabrication & fixing 03 Nos. M.S. Angle / MSC channel of size (75 mm x 75 mmx6mm) for placing the outdoor unit of ductable split AC incl. drilling 05 nos. holes in each Angle including cutting holes into the wall & grouting the same (1:1 ½ :3) etc for Air Conditioning Units.
Supplying, fabrication & fixing 4 Nos. M.S u-channel of 6 mm thick of size (75 mm x 40 mm x 40 mm) for making Base Frame table type for installation of Exhaust Cabinet incl. drilling 2 nos holes in each channel fabricated with 4 Nos. Barricaded the same for maintenance horizontal angle of 50 mm x 50 mm x 6 mm Inscl Platform as per direction of E.I.C.. Area of Platform 9mtr x 1.8mtr for Placing the Exhaust Units including scaffolding charges.
Supply & Fixing of IDU & Duct Covered with 3mm thick ACP Board (Make: Aludecor/Protap Bond) Complete with linkages, levers, fittings, supports, all accessories any other item required to make the system complete as per direction of E.I.C.
Charges for Trap door with ACP Board (Make: Aludecor/Protap Bond) Complete with linkages, levers, fittings, supports, all accessories for IDU Maintenance make with ACP Board as per direction of E.I.C.
Civil Work like-Wall Cutting, Finishing & Painting etc. as per direction of EIC.
The Agency must procure the materials from the Manufacturer/OEM or from their authorized sales channel so that the standard warranty/supprot of the Manufacturer/OEM becomes applicable to the products to be delivered and installed by them.
Documents that authenticates such procurement from the Manufacturer/OEM or from their authorized sales channel and standard warranty/support should be sent from the e-mail of the Manufacturer/OEM/authorized sales channel to the e-mail of Engineer-in-Charge and hard copy of it to be submitted during execution of work/submission of bill.
If any refurbished material is supplied and installed, penal action will be taken as per existing rules.
Defect Liability Period - 1 (One) year.
SKY DECORATIONS PRIVATE LIMITED
Shinryo Suvidha Engineers India Pvt Ltd
tech_bid_open.pdf
tech_eval.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.pdf
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .