| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | L1₹2.4 CrAccepted-AOC | ₹2.4 Cr Quoted ₹2.5 Cr | L1 | Accepted-AOC LOWEST BIDDER |
| 2 | L2₹2.5 Cr+₹1.1 L (0.43%)Rejected-AOC PLOT NO 28 SANTOSHIMA COLONY WEST MARREDPALLY SECUNDERABAD 500026 | HYDERABAD | TELANGANA | 500026 | ₹2.5 Cr+₹1.1 L (0.43%) | L2 | Rejected-AOC NOT BEING LOWEST |
| 3 | L3₹2.5 Cr+₹3.9 L (1.58%)Rejected-AOC | ₹2.5 Cr+₹3.9 L (1.58%) | L3 | Rejected-AOC NOT BEING LOWEST |
| 4 | L4₹2.5 Cr+₹5.5 L (2.22%)Rejected-AOC 74 AJANTA COMMERCIAL CENTRE ASHRAM ROAD AHMEDABAD 380014 | AHMEDABAD | AHMEDABAD | GUJARAT | 380014 | ₹2.5 Cr+₹5.5 L (2.22%) | L4 | Rejected-AOC NOT BEING LOWEST |
| 5 | L5₹2.6 Cr+₹13.1 L (5.31%)Rejected-AOC HOUSE NO 2 4 136 LINGREDDY MANSION BLOCK NO IV OPP HANUMAN TEMPLE TADBUND SECUNDERABAD 500009 | SECUNDERABAD | HYDERABAD | TELANGANA | 500009 | ₹2.6 Cr+₹13.1 L (5.31%) | L5 | Rejected-AOC NOT BEING LOWEST |
Tender Value
₹3 Cr
EMD Value
₹3.8 L
Closing Date
25 Dec 2021, 6:00 pmClosed
Chief Engineer Chennai Zone chennai
HQ CECZ Island Grounds Chennai - 09
CONVERSION OF LT OH LINE TO UG CABLE AT MH SECUNDERABAD UNDER GE(U) SECUNDERABAD.
2021_MES_491159_1
89053/E8
Open Tender
Electrical and Maintenance Works
Item Rate
305 days
GE (U) Secunderabad
As per tender documents
8 documents required · 8 mandatory
₹2,000
Yes
GE (U) Secunderabad
₹3.8 L
Yes
10 Feb 2022
29 Nov 2021
27 Dec 2021
29 Nov 2021
25 Dec 2021
20 Dec 2021
29 Nov 2021 - 10 Dec 2021
Amount
Design , Supply, Installation, testing and Commissioning CPRI APPROVED factory fabricated, out door type,LT FEEDER PILLAR BOX IP 55 protection grade, made out of 3.15 mm thick CRCA Sheet with projected Globe roof for rain water protection Dust and Vermin Proof , Double door with both side opening including Neoprene Rubber Gasket,, suitable for 440 Volt 3 Phase 4 Wire System ,including Danger Plate, Earthing Strip Point and Ventilation Louvers at Rear Side, Bottom detachable Gland Plate comp-lete with suitable size Zinc Chromium Plated Nuts, Bolts and Washers , cable glands of appropriate size , etc. and supported with 65X65X6mm Mild Steel Angle Iron Frame and 500 mm above ground lavel , embeded in PCC 1:2:4, type C-2, 45 Cm below ground level and 50 Cm above ground level complete with internal connection with suitable size of strip ,cable lugs,and cable glands and Test-ing after Installation complete all as specified and comprising of the following :- (Size of the panel board should not be less than 1.25 M X2.0 MX0.45M)(Main LT Panel for Pump house)
Bus bar aluminium duly insulated with colour coded heat shrinkable sleeve and mounted on suitable size of 'F' class insulators made of non hygroscopic, non combustible, track resistant high strength FRP insulators 1000 Amps for phases and Neural, set of 4 for RYB &N - 01 set. MCCB 4 Pole 630 Amps 50KA -01 Nos. adjustable type (incommer) MCCB 4 Pole 400 Amps 36KA -02 Nos. (Outgoing) MCCB 4 Pole 250 Amps 36KA -01 Nos. (Outgoing) MCCB 4 Pole 160 Amps 36KA -02 Nos. (Outgoing) Three phase Panel mounted Digital type Voltmeter meter 0-500 Volts, Ammeter 630/5A LT-CT operated complete - 01 Set Indicating type lamp for Red, Yellow and Blue phases - 01 Set Quoted rates inclusive of the following ( For Item No. 01 to 40) :- (a) All incoming and outgoing cables are to be connected to the above panels with proper lugs, double compression copper stain less steel armoured cable gland, nuts, bolts etc the cost of the items deemed to be included in the quoted rates. (b) Make of MCCB's and MCB's to be used in the panels are : L&T / lEGRAND /siemens (c) The panel shall be Fabricated from a reputed firm(CPRI Approved) . (d) All Internal connection between ACB, MCCB ( ABOVE 63 AMPS ) and Changeover and Bus bar shall be done by aluminium strip of suitable size and capacity . (e) All MCCB to be connected with both side Spreader Link And All Incomer and outgoing MCCB of Panels should be thermal magnetic release with adjustable settings ( Min 70% to 100 %) and Ics = 100% Icu (f) Sufficient space to be provided for cable connection between MCCB and Bottom of the panel board.( Minimum space for MCCB up to 200 amps = 35 CM , Minimum space for MCCB 250 to 400 amps = 45 CM , Minimum space for MCCB above 400 amps = 55 CM ) (g) Base of the panel should not be less than 500 mm above the ground level. Necessary PCC for base /foundation required deemed to be included in the quoted rate. h) Cable alley / chamber to along with connector of suitable size to be provided for connection of Out going cable .
i) Necessary approval of drawing to be taken from GE before placing order to the manufacturer. j)All existing incoming and out going cables also to be connected to the above panel as per site requirement with proper lugs, glands nuts, bolts etc (k) Door hinge of industrial type heavy duty to be provided minimum 3 nos for each door (l) The rate shall deemed to be include in the item rate for al the points mentioned above.
Design , Supply, Installation, testing and Commissioning CPRI APPROVED factory fabricated, out door type,LT FEEDER PILLAR BOX IP 55 protection grade, made out of 3.15 mm thick CRCA Sheet with projected Globe roof for rain water protection Dust and Vermin Proof , Double door with both side opening including Neoprene Rubber Gasket,, suitable for 440 Volt 3 Phase 4 Wire System ,including Danger Plate, Earthing Strip Point and Ventilation Louvers at Rear Side, Bottom detachable Gland Plate comp-lete with suitable size Zinc Chromium Plated Nuts, Bolts and Washers , cable glands of appropriate size , etc. and supported with 65X65X6mm Mild Steel Angle Iron Frame and 500 mm above ground lavel , embeded in PCC 1:2:4, type C-2, 45 Cm below ground level and 50 Cm above ground level complete with internal connection with suitable size of strip ,cable lugs,and cable glands and Test-ing after Installation complete all as specified and comprising of the following :- (Size of the panel board should not be less than 1.2 M X1.60 MX0.40M) (LT Panel No-1 at Near T-4) (a) Bus bar aluminium duly insulated with colour coded heat shrinkable sleeve and mounted on suitable size of 'F' class insulators made of non hygroscopic, non combustible, track resistant high strength FRP insulators 650 Amps for phases and Neural, set of 4 for RYB &N - 01 set. (a) MCCB 4 Pole 400 Amps 36KA -01 No. Thermal Magnetic release (incommer) (b) MCCB 4 Pole 350 Amps 36KA -03 No. Thermal Magnetic release (Panel-5 & Panel-08 , O/G) (b) MCCB 4 Pole 250 Amps 36KA -02 Nos. (Outgoing) (c) MCCB 4 Pole 32 Amps 36KA -02 Nos. (Outgoing) (d) Three phase Panel mounted Digital type Voltmeter meter 0-500 Volts, Ammeter 500/5A LT-CT operated complete - 01 Set (e) Indicating type lamp for Red, Yellow and Blue phases - 01 Set
Design , Supply, Installation, testing and Commissioning CPRI APPROVED factory fabricated, out door type,LT FEEDER PILLAR BOX IP 55 protection grade, made out of 3.15 mm thick CRCA Sheet with projected Globe roof for rain water protection Dust and Vermin Proof , Double door with both side opening including Neoprene Rubber Gasket,, suitable for 440 Volt 3 Phase 4 Wire System ,including Danger Plate, Earthing Strip Point and Ventilation Louvers at Rear Side, Bottom detachable Gland Plate comp-lete with suitable size Zinc Chromium Plated Nuts, Bolts and Washers , cable glands of appropriate size , etc. and supported with 65X65X6mm Mild Steel Angle Iron Frame and 500 mm above ground lavel , embeded in PCC 1:2:4, type C-2, 45 Cm below ground level and 50 Cm above ground level complete with internal connection with suitable size of strip ,cable lugs,and cable glands and Test-ing after Installation complete all as specified and comprising of the following :- (Size of the panel board should not be less than 1.2 M X1.8 MX0.40M) (LT panel No at T-5):- (a) Bus bar aluminium duly insulated with colour coded heat shrinkable sleeve and mounted on suitable size of 'F' class insulators made of non hygroscopic, non combustible, track resistant high strength FRP insulators 400 Amps for phases and Neural, set of 4 for RYB &N - 01 set. MCCB 4 Pole 200 Amps 36KA -01 No. Thermal Magnetic release (incommer) MCCB 4 Pole 160 Amps 36KA -01 Nos. (Outgoing) MCCB 4 Pole 125 Amps 18KA -04 Nos. (Outgoing) MCCB 4 Pole 32 Amps 18KA -05 Nos. (Outgoing)` Three phase Panel mounted Digital type Voltmeter meter 0-500 Volts, Ammeter 400/5A LT-CT operated complete - 01 Set Indicating type lamp for Red, Yellow and Blue phases - 01 Set
Design , Supply, Installation, testing and Commissioning CPRI APPROVED factory fabricated, out door type,LT FEEDER PILLAR BOX IP 55 protection grade, made out of 3.15 mm thick CRCA Sheet with projected Globe roof for rain water protection Dust and Vermin Proof , Double door with both side opening including Neoprene Rubber Gasket,, suitable for 440 Volt 3 Phase 4 Wire System ,including Danger Plate, Earthing Strip Point and Ventilation Louvers at Rear Side, Bottom detachable Gland Plate comp-lete with suitable size Zinc Chromium Plated Nuts, Bolts and Washers , cable glands of appropriate size , etc. and supported with 65X65X6mm Mild Steel Angle Iron Frame and 500 mm above ground lavel , embeded in PCC 1:2:4, type C-2, 45 Cm below ground level and 50 Cm above ground level complete with internal connection with suitable size of strip ,cable lugs,and cable glands and Test-ing after Installation complete all as specified and comprising of the following :- (Size of the panel board should not be less than 1.15 M X1.5 MX0.40M) (LT Panel No-3 at MMG) :- (a) Bus bar aluminium duly insulated with colour coded heat shrinkable sleeve and mounted on suitable size of 'F' class insulators made of non hygroscopic, non combustible, track resistant high strength FRP insulators 300 Amps for phases and Neural, set of 4 for RYB &N - 01 set. MCCB 4 Pole 160 Amps 36KA -01 No. Thermal MCCB 4 Pole 125 Amps 18KA -01 Nos. (Outgoing) MCCB 4 Pole 63 Amp 18 KA-04 Nos (Outgoing) MCB 4 Pole 32 Amp 18KA-03 (Outgoing) Three phase Panel mounted Digital type Voltmeter meter 0-500 Volts, Ammeter 400/5A LT-CT operated complete - 01 Set Indicating type lamp for Red, Yellow and Blue phases - 01 Set
Design , Supply, Installation, testing and Commissioning CPRI APPROVED factory fabricated, out door type,LT FEEDER PILLAR BOX IP 55 protection grade, made out of 3.15 mm thick CRCA Sheet with projected Globe roof for rain water protection Dust and Vermin Proof , Double door with both side opening including Neoprene Rubber Gasket,, suitable for 440 Volt 3 Phase 4 Wire System ,including Danger Plate, Earthing Strip Point and Ventilation Louvers at Rear Side, Bottom detachable Gland Plate comp-lete with suitable size Zinc Chromium Plated Nuts, Bolts and Washers , cable glands of appropriate size , etc. and supported with 65X65X6mm Mild Steel Angle Iron Frame and 500 mm above ground lavel , embeded in PCC 1:2:4, type C-2, 45 Cm below ground level and 50 Cm above ground level complete with internal connection with suitable size of strip ,cable lugs,and cable glands and Test-ing after Installation complete all as specified and comprising of the following :- (Size of the panel board should not be less than 1.5M X1.0MX0.35M) (LT Panel No-3 at Football Ground)) :- (a) Bus bar aluminium duly insulated with colour coded heat shrinkable sleeve and mounted on suitable size of 'F' class insulators made of non hygroscopic, non combustible, track resistant high strength FRP insulators 200 Amps for phases and Neural, set of 4 for RYB &N - 01 set. MCCB 4 Pole 63 Amps 18KA -01 No. Thermal Magnetic release (incommer) MCCB 4 Pole 32 Amps 18KA -05 Nos. (Outgoing) Three phase Panel mounted Digital type Voltmeter meter 0-500 Volts, Ammeter 400/5A LT-CT operated complete - 01 Set Indicating type lamp for Red, Yellow and Blue phases - 01 Set
Design , Supply, Installation, testing and Commissioning CPRI APPROVED factory fabricated, out door type,LT FEEDER PILLAR BOX IP 55 protection grade, made out of 3.15 mm thick CRCA Sheet with projected Globe roof for rain water protection Dust and Vermin Proof , Double door with both side opening including Neoprene Rubber Gasket,, suitable for 440 Volt 3 Phase 4 Wire System ,including Danger Plate, Earthing Strip Point and Ventilation Louvers at Rear Side, Bottom detachable Gland Plate comp-lete with suitable size Zinc Chromium Plated Nuts, Bolts and Washers , cable glands of appropriate size , etc. and supported with 65X65X6mm Mild Steel Angle Iron Frame and 500 mm above ground lavel , embeded in PCC 1:2:4, type C-2, 45 cm below ground level and 50 Cm above ground level complete with internal connection with suitable size of strip ,cable lugs,and cable glands and Test-ing after Installation complete all as specified and comprising of the following :- (Size of the panel board should not be less than 1.25 M X2.25 MX0.40M) (LT Panel at E-15) :- (a) Bus bar aluminium duly insulated with colour coded heat shrinkable sleeve and mounted on suitable size of 'F' class insulators made of non hygroscopic, non combustible, track resistant high strength FRP insulators 650 Amps for phases and Neural, set of 4 for RYB &N - 01 set. MCCB 4 Pole 350 Amps 36KA -01 Nos. adjustable type (incomer) MCCB 4 Pole 160 Amps 25KA -03 Nos. (Outgoing) MCCB 4 Pole 100 Amps 25KA -02 Nos. (Outgoing) MCCB 4 Pole 63 Amps 15KA -05 Nos. (Outgoing) MCCB 4 Pole 32 Amps 15KA -02 Nos. (Outgoing) Three phase Panel mounted Digital type Voltmeter meter 0-500 Volts, Ammeter 630/5A LT-CT operated complete - 01 Set Indicating type lamp for Red, Yellow and Blue phases - 01 Set
Design , Supply, Installation, testing and Commissioning CPRI APPROVED factory fabricated, out door type,LT FEEDER PILLAR BOX IP 55 protection grade, made out of 3.15 mm thick CRCA Sheet with projected Globe roof for rain water protection Dust and Vermin Proof , Double door with both side opening including Neoprene Rubber Gasket,, suitable for 440 Volt 3 Phase 4 Wire System ,including Danger Plate, Earthing Strip Point and Ventilation Louvers at Rear Side, Bottom detachable Gland Plate comp-lete with suitable size Zinc Chromium Plated Nuts, Bolts and Washers , cable glands of appropriate size , etc. and supported with 65X65X6mm Mild Steel Angle Iron Frame and 500 mm above ground lavel , embeded in PCC 1:2:4, type C-2, 45 Cm below ground level and 50 Cm above ground level complete with internal connection with suitable size of strip ,cable lugs,and cable glands and Test-ing after Installation complete all as specified and comprising of the following :- (Size of the panel board should not be less than 1.1 M X1.8MX0.35M) (LT Panel No at E-10) :- (a) Bus bar aluminium duly insulated with colour coded heat shrinkable sleeve and mounted on suitable size of 'F' class insulators made of non hygroscopic, non combustible, track resistant high strength FRP insulators 300 Amps for phases and Neural, set of 4 for RYB &N - 01 set. MCCB 4 Pole 160 Amps 25KA -01 Nos. Thermal Magnetic release (Outgoing) MCCB 4 Pole 100 Amps 18KA -03 Nos. (Outgoing) MCCB 4 Pole 63 Amps 10 KA -07 Nos (Outgoing) Three phase Panel mounted Digital type Voltmeter meter 0-500 Volts, Ammeter 400/5A LT-CT operated complete - 01 Set Indicating type lamp for Red, Yellow and Blue phases - 01 Set
Design , Supply, Installation, testing and Commissioning CPRI APPROVED factory fabricated, out door type,LT FEEDER PILLAR BOX IP 55 protection grade, made out of 3.15 mm thick CRCA Sheet with projected Globe roof for rain water protection Dust and Vermin Proof , Double door with both side opening including Neoprene Rubber Gasket,, suitable for 440 Volt 3 Phase 4 Wire System ,including Danger Plate, Earthing Strip Point and Ventilation Louvers at Rear Side, Bottom detachable Gland Plate comp-lete with suitable size Zinc Chromium Plated Nuts, Bolts and Washers , cable glands of appropriate size , etc. and supported with 65X65X6mm Mild Steel Angle Iron Frame and 500 mm above ground lavel , embeded in PCC 1:2:4, type C-2, 45 Cm below ground level and 50 Cm above ground level complete with internal connection with suitable size of strip ,cable lugs,and cable glands and Test-ing after Installation complete all as specified and comprising of the following :- (Size of the panel board should not be less than 1.25 M X2.0 MX0.40M) (LT Panel at DS -27) :- (a) Bus bar aluminium duly insulated with colour coded heat shrinkable sleeve and mounted on suitable size of 'F' class insulators made of non hygroscopic, non combustible, track resistant high strength FRP insulators 650 Amps for phases and Neural, set of 4 for RYB &N - 01 set. MCCB 4 Pole 350 Amps 36KA -01 Nos. Thermal Magnetic release (Incomer) MCCB 4 Pole 200 Amps 36KA -02 Nos. (Panel-9, Panel-10) MCCB 4 Pole 125 Amps 36KA -03 Nos. (Outgoing) MCCB 4 Pole 100 Amps 36 KA-03 Nos (Outgoing) MCCB 4 Pole 63 Amps 18 KA-02 Nos (Outgoing) Three phase Panel mounted Digital type Voltmeter meter 0-500 Volts, Ammeter 400/5A LT-CT operated complete - 01 Set Indicating type lamp for Red, Yellow and Blue phases - 01 Set
Design , Supply, Installation, testing and Commissioning CPRI APPROVED factory fabricated, out door type,LT FEEDER PILLAR BOX IP 55 protection grade, made out of 3.15 mm thick CRCA Sheet with projected Globe roof for rain water protection Dust and Vermin Proof , Double door with both side opening including Neoprene Rubber Gasket,, suitable for 440 Volt 3 Phase 4 Wire System ,including Danger Plate, Earthing Strip Point and Ventilation Louvers at Rear Side, Bottom detachable Gland Plate comp-lete with suitable size Zinc Chromium Plated Nuts, Bolts and Washers , cable glands of appropriate size , etc. and supported with 65X65X6mm Mild Steel Angle Iron Frame and 500 mm above ground lavel , embeded in PCC 1:2:4, type C-2, 45 Cm below ground level and 50 Cm above ground level complete with internal connection with suitable size of strip ,cable lugs,and cable glands and Test-ing after Installation complete all as specified and comprising of the following :- (Size of the panel board should not be less than 1.1 M X1.6MX0.35M (LT Panel at DS-26) :- (a) Bus bar aluminium duly insulated with colour coded heat shrinkable sleeve and mounted on suitable size of 'F' class insulators made of non hygroscopic, non combustible, track resistant high strength FRP insulators 400 Amps for phases and Neural, set of 4 for RYB &N - 01 set. MCCB 4 Pole 200 Amps 36KA -01 Nos. Thermal Magnetic release (incoming) MCCB 4 Pole 125 Amps 18KA -03 Nos. (Outgoing) MCCB 4 Pole 63 Amps 18KA -05 Nos. (Outgoing) Three phase Panel mounted Digital type Voltmeter meter 0-500 Volts, Ammeter 400/5A LT-CT operated complete - 01 Set Indicating type lamp for Red, Yellow and Blue phases - 01 Set
Design , Supply, Installation, testing and Commissioning CPRI APPROVED factory fabricated, out door type,LT FEEDER PILLAR BOX IP 55 protection grade, made out of 3.15 mm thick CRCA Sheet with projected Globe roof for rain water protection Dust and Vermin Proof , Double door with both side opening including Neoprene Rubber Gasket,, suitable for 440 Volt 3 Phase 4 Wire System ,including Danger Plate, Earthing Strip Point and Ventilation Louvers at Rear Side, Bottom detachable Gland Plate comp-lete with suitable size Zinc Chromium Plated Nuts, Bolts and Washers , cable glands of appropriate size , etc. and supported with 65X65X6mm Mild Steel Angle Iron Frame and 500 mm above ground lavel , embeded in PCC 1:2:4, type C-2, 45 Cm below ground level and 50 Cm above ground level complete with internal connection with suitable size of strip ,cable lugs,and cable glands and Test-ing after Installation complete all as specified and comprising of the following :- (Size of the panel board should not be less than 1.1 M X1.3 MX0.35M) (LT Panel at DS-) :- MCCB 4 Pole 200 Amps 36KA -01 Nos. Thermal Magnetic release (incoming) MCCB 4 Pole 63 Amps 18KA -03 Nos. (Outgoing) MCCB 4 Pole 32 Amps 18KA -02 Nos. (Outgoing) Three phase Panel mounted Digital type Voltmeter meter 0-500 Volts, Ammeter 400/5A LT-CT operated complete - 01 Set Indicating type lamp for Red, Yellow and Blue phases - 01 Set
Supply, Installation, test and Commissioning CPRI APPROVED factory fabricated, out door type,LT FEEDER PILLAR BOX Double Door , Both side openable made out of 3.15 mm thick CRCA Sheet of size 07MX0.6mX.35M with projected Globe roof for rain water protection duly treated through 8 tank pre treatment process and painted with epoxy powder coated mat finish of SIEMENS GREY structural RAL 7032 shade colour Dust and Vermin Proof , Double door with both side opening including Neoprene Rubber Gasket,, suitable for 440 Volt 3 Phase 4 Wire System ,including Danger Plate, Earthing Strip Point and Ventilation Louvers at Rear Side, Bottom detachable Gland Plate complete with suitable size Zinc Chromium Plated Nuts, Bolts and Washers, etc. and embeded with 50X50X6mm Mild Steel Angle Iron Frame and 600 mm above the Normal Ground Level complete with internal connection with suitable size of cable ,cable lugs,and cable glands PCC Foundation in Cement Concrete 1:3:6 (20mm Graded Stone Aggregate) and Testing after Installation complete all as specified and directed.Comprising of the following :– (Size of the panel board should not be less than 0.80M X0.60 MX0.50M) Aluminium bas bar 600amps - 04 Nos, supported with suitable size of heavy duty porcelin stand lock with suitable size of brass nut, bolts and washer with heat shrinkable PVC sleeving. The bar shall be colour coded (red, yellow and blue) for three phases and black for neutral. MCCB 320 amps ,415 volt ,35 KA Breaking capacity 4 pole Electromagnetic release duly connected to Bus Bar As IN COMING - 01 Nos Make Schinder/L&T/Hagar
Design , Supply, Installation, testing and Commissioning CPRI APPROVED factory fabricated, out door type,LT FEEDER PILLAR BOX IP 55 protection grade, made out of 3.15 mm thick CRCA Sheet with projected Globe roof for rain water protection Dust and Vermin Proof , Double door with both side opening including Neoprene Rubber Gasket,, suitable for 440 Volt 3 Phase 4 Wire System ,including Danger Plate, Earthing Strip Point and Ventilation Louvers at Rear Side, Bottom detachable Gland Plate comp-lete with suitable size Zinc Chromium Plated Nuts, Bolts and Washers , cable glands of appropriate size , etc. and supported with 65X65X6mm Mild Steel Angle Iron Frame and 500 mm above ground lavel , embeded in PCC 1:2:4, type C-2, 45 Cm below ground level and 50 Cm above ground level complete with internal connection with suitable size of strip ,cable lugs,and cable glands and Test-ing after Installation complete all as specified and comprising of the following :- (Size of the panel board should not be less than 1.25 M X2.0 MX0.45M) (Panel Board No. 01, Location :- Near Transformer) (a) Bus bar aluminium duly insulated with colour coded heat shrinkable sleeve and mounted on suitable size of 'F' class insulators made of non hygroscopic, non combustible, track resistant high strength FRP insulators 1000 Amps for phases and Neural, set of 4 for RYB &N - 01 set. (a) MCCB 4 Pole 630 Amps 50KA -01 Nos. adjustable type (incomer) (b) MCCB 4 Pole 400 Amps 36KA -03 Nos. adjustable type (Outgoing) (c) MCCB 4 Pole 63 Amps 16KA -01 Nos. (Outgoing) (d) MCCB 4 Pole 16 Amps 16KA -02 Nos. (Outgoing) (e) Three phase Panel mounted Digital type Voltmeter meter 0-500 Volts, Ammeter 400/5A LT-CT operated complete - 01 Set (f) Indicating type lamp for Red, Yellow and Blue phases - 01 Set
Design , Supply, Installation, testing and Commissioning CPRI APPROVED factory fabricated, out door type,LT FEEDER PILLAR BOX IP 55 protection grade, made out of 3.15 mm thick CRCA Sheet with projected Globe roof for rain water protection Dust and Vermin Proof , Double door with both side opening including Neoprene Rubber Gasket,, suitable for 440 Volt 3 Phase 4 Wire System ,including Danger Plate, Earthing Strip Point and Ventilation Louvers at Rear Side, Bottom detachable Gland Plate comp-lete with suitable size Zinc Chromium Plated Nuts, Bolts and Washers , cable glands of appropriate size , etc. and supported with 65X65X6mm Mild Steel Angle Iron Frame and 500 mm above ground lavel , embeded in PCC1:2:4, type C-2, 45 Cm below ground level and 50 Cm above ground level complete with internal connection with suitable size of strip,cable lugs,and cable glands and Test-ing after Installation complete all as specified and comprising of the following :- (Size of the panel board should not be less than 1.20 M X1.90 MX0.40M) (Panel Board N0. 02, Location:- Near FAFA Office) (a) Bus bar aluminium duly insulated with colour coded heat shrinkable sleeve and mounted on suitable size of 'F' class insulators made of non hygroscopic, non combustible, track resistant high strength FRP insulators 200 Amps for phases and Neural, set of 4 for RYB &N - 01 set. MCCB 4 Pole 63 Amps 16KA -01 No. Thermal Magnetic release (incommer) MCCB 4 Pole 16 Amps 16KA -04 Nos. Thermal Magnetic release (Outgoing) MCB 2 Pole 10 Amps 10KA -02 Nos. (Outgoing) Three phase Panel mounted Digital type Voltmeter meter 0-500 Volts, Ammeter 400/5A LT-CT operated complete - 01 Set Indicating type lamp for Red, Yellow and Blue phases - 01 Set
Design , Supply, Installation, testing and Commissioning CPRI APPROVED factory fabricated, out door type,LT FEEDER PILLAR BOX IP 55 protection grade, made out of 3.15 mm thick CRCA Sheet with projected Globe roof for rain water protection Dust and Vermin Proof , Double door with both side opening including Neoprene Rubber Gasket,, suitable for 440 Volt 3 Phase 4 Wire System ,including Danger Plate, Earthing Strip Point and Ventilation Louvers at Rear Side, Bottom detachable Gland Plate comp-lete with suitable size Zinc Chromium Plated Nuts, Bolts and Washers , cable glands of appropriate size , etc. and supported with 65X65X6mm Mild Steel Angle Iron Frame and 500 mm above ground lavel , embeded in PCC 1:2:4, type C-2, 45 Cm below ground level and 50 Cm above ground level complete with internal connection with suitable size of strip ,cable lugs,and cable glands and Test-ing after Installation complete all as specified and comprising of the following :- (Size of the panel board should not be less than 1.2 MX1.6MX0.40M) (Panel Board No. 03, Location:- Near Block No - 205) Bus bar aluminium duly insulated with colour coded heat shrinkable sleeve and mounted on suitable size of 'F' class insulators made of non hygroscopic, non combustible, track resistant high strength FRP insulators 650 Amps for phases and Neural, set of 4 for RYB &N - 01 set. MCCB 4 Pole 400 Amps 36KA -01 No. Thermal Magnetic release (incommer) MCCB 4 Pole 160-200 Amps 25KA -02 Nos. Thermal Magnetic release (Outgoing) MCCB 4 Pole 63 Amps 16KA -03 Nos. (Outgoing) MCCB 4 Pole 16 Amps 16KA -01 Nos. (Outgoing) Three phase Panel mounted Digital type Voltmeter meter 0-500 Volts, Ammeter 400/5A LT-CT operated complete - 01 Set Indicating type lamp for Red, Yellow and Blue phases - 01 Set
Design , Supply, Installation, testing and Commissioning CPRI APPROVED factory fabricated, out door type,LT FEEDER PILLAR BOX IP 55 protection grade, made out of 3.15 mm thick CRCA Sheet with projected Globe roof for rain water protection Dust and Vermin Proof , Double door with both side opening including Neoprene Rubber Gasket,, suitable for 440 Volt 3 Phase 4 Wire System ,including Danger Plate, Earthing Strip Point and Ventilation Louvers at Rear Side, Bottom detachable Gland Plate comp-lete with suitable size Zinc Chromium Plated Nuts, Bolts and Washers , cable glands of appropriate size , etc. and supported with 65X65X6mm Mild Steel Angle Iron Frame and 500 mm above ground lavel , embeded in PCC 1:2:4, type C-2, 45 Cm below ground level and 50 Cm above ground level complete with internal connection with suitable size of strip ,cable lugs,and cable glands and Test-ing after Installation complete all as specified and comprising of the following :- (Size of the panel board should not be less than 1.2 MX1.7MX0.40M) Panel Board No. 04, Location :- Near Block No - 197 Bus bar aluminium duly insulated with colour coded heat shrinkable sleeve and mounted on suitable size of 'F' class insulators made of non hygroscopic, non combustible, track resistant high strength FRP insulators 650 Amps for phases and Neural, set of 4 for RYB &N - 01 set. MCCB 4 Pole 400 Amps 36KA -01 No. Thermal Magnetic release (incommer) MCCB 4 Pole 200 Amps 25KA -02 Nos. Thermal Magnetic release (Outgoing) MCCB 4 Pole 63 Amps 16KA -04 Nos. (Outgoing) MCCB 4 Pole 32 Amps 16KA -02 Nos. (Outgoing) Three phase Panel mounted Digital type Voltmeter meter 0-500 Volts, Ammeter 400/5A LT-CT operated complete - 01 Set Indicating type lamp for Red, Yellow and Blue phases - 01 Set
Design , Supply, Installation, testing and Commissioning CPRI APPROVED factory fabricated, out door type,LT FEEDER PILLAR BOX IP 55 protection grade, made out of 3.15 mm thick CRCA Sheet with projected Globe roof for rain water protection Dust and Vermin Proof , Double door with both side opening including Neoprene Rubber Gasket,, suitable for 440 Volt 3 Phase 4 Wire System ,including Danger Plate, Earthing Strip Point and Ventilation Louvers at Rear Side, Bottom detachable Gland Plate comp-lete with suitable size Zinc Chromium Plated Nuts, Bolts and Washers , cable glands of appropriate size , etc. and supported with 65X65X6mm Mild Steel Angle Iron Frame and 500 mm above ground lavel , embeded in PCC 1:2:4, type C-2, 45 Cm below ground level and 50 Cm above ground level complete with internal connection with suitable size of strip ,cable lugs,and cable glands and Test-ing after Installation complete all as specified and comprising of the following :- (Size of the panel board should not be less than 1.0 M X1.2 MX0.35M)(Location:- Near Block No - 206) Bus bar aluminium duly insulated with colour coded heat shrinkable sleeve and mounted on suitable size of 'F' class insulators made of non hygroscopic, non combustible, track resistant high strength FRP insulators 320 Amps for phases and Neural, set of 4 for RYB &N - 01 set. MCCB 4 Pole 200 Amps 25KA -01 Nos. Thermal Magnetic release (iNCOMING) MCCB 4 Pole 63 Amps 16KA -04 Nos. (Outgoing) Three phase Panel mounted Digital type Voltmeter meter 0-500 Volts, Ammeter 400/5A LT-CT operated complete - 01 Set Indicating type lamp for Red, Yellow and Blue phases - 01 Set
Design , Supply, Installation, testing and Commissioning CPRI APPROVED factory fabricated, out door type,LT FEEDER PILLAR BOX IP 55 protection grade, made out of 3.15 mm thick CRCA Sheet with projected Globe roof for rain water protection Dust and Vermin Proof , Double door with both side opening including Neoprene Rubber Gasket,, suitable for 440 Volt 3 Phase 4 Wire System ,including Danger Plate, Earthing Strip Point and Ventilation Louvers at Rear Side, Bottom detachable Gland Plate comp-lete with suitable size Zinc Chromium Plated Nuts, Bolts and Washers , cable glands of appropriate size , etc. and supported with 65X65X6mm Mild Steel Angle Iron Frame and 500 mm above ground lavel , embeded in PCC 1:2:4, type C-2, 45 Cm below ground level and 50 Cm above ground level complete with internal connection with suitable size of strip ,cable lugs,and cable glands and Test-ing after Installation complete all as specified and comprising of the following :- (Size of the panel board should not be less than 1.1 M X1.3 MX0.35M) ( Location:- Near Block No - 205) Bus bar aluminium duly insulated with colour coded heat shrinkable sleeve and mounted on suitable size of 'F' class insulators made of non hygroscopic, non combustible, track resistant high strength FRP insulators 350 Amps for phases and Neural, set of 4 for RYB &N - 01 set. MCCB 4 Pole 200 Amps 25KA -01 Nos. Thermal Magnetic release (iNCOMING) MCCB 4 Pole 63 Amps 16KA -04 Nos. (Outgoing) MCCB 4 Pole 32 Amps 16KA -01 Nos. (Outgoing) Three phase Panel mounted Digital type Voltmeter meter 0-500 Volts, Ammeter 400/5A LT-CT operated complete - 01 Set Indicating type lamp for Red, Yellow and Blue phases - 01 Set
Design , Supply, Installation, testing and Commissioning CPRI APPROVED factory fabricated, out door type,LT FEEDER PILLAR BOX IP 55 protection grade, made out of 3.15 mm thick CRCA Sheet with projected Globe roof for rain water protection Dust and Vermin Proof , Double door with both side opening including Neoprene Rubber Gasket,, suitable for 440 Volt 3 Phase 4 Wire System ,including Danger Plate, Earthing Strip Point and Ventilation Louvers at Rear Side, Bottom detachable Gland Plate comp-lete with suitable size Zinc Chromium Plated Nuts, Bolts and Washers , cable glands of appropriate size , etc. and supported with 65X65X6mm Mild Steel Angle Iron Frame and 500 mm above ground lavel , embeded in PCC 1:2:4, type C-2, 45 Cm below ground level and 50 Cm above ground level complete with internal connection with suitable size of strip ,cable lugs,and cable glands and Test-ing after Installation complete all as specified and comprising of the following :- (Size of the panel board should not be less than 0.7 M X0.60 MX0.45M) ( Location :- Near Block No - 205) (a) Aluminium bas bar 400amps - 04 Nos, supported with suitable size of heavy duty porcelin stand lock with suitable size of brass nut, bolts and washer with heat shrinkable PVC sleeving. The bar shall be colour coded (red, yellow and blue) for three phases and black for neutral. b) MCCB 200 amps ,415 volt ,16 KA Breaking capacity 4 pole Electromagnetic release duly connected to Bus Bar As IN COMING - 01 NosMake Legrand Schinder/L&T/Hagar
Design , Supply, Installation, testing and Commissioning CPRI APPROVED factory fabricated, out door type,LT FEEDER PILLAR BOX IP 55 protection grade, made out of 3.15 mm thick CRCA Sheet with projected Globe roof for rain water protection Dust and Vermin Proof , Double door with both side opening including Neoprene Rubber Gasket,, suitable for 440 Volt 3 Phase 4 Wire System ,including Danger Plate, Earthing Strip Point and Ventilation Louvers at Rear Side, Bottom detachable Gland Plate comp-lete with suitable size Zinc Chromium Plated Nuts, Bolts and Washers , cable glands of appropriate size , etc. and supported with 65X65X6mm Mild Steel Angle Iron Frame and 500 mm above ground lavel , embeded in PCC 1:2:4, type C-2, 45 Cm below ground level and 50 Cm above ground level complete with internal connection with suitable size of strip ,cable lugs,and cable glands and Test-ing after Installation complete all as specified and comprising of the following :- (Size of the panel board should not be less than 1.2 M X1.65 MX0.35M)(MH Panel N0. 01 Location:- Near Exchange) (a) Bus bar aluminium duly insulated with colour coded heat shrinkable sleeve and mounted on suitable size of 'F' class insulators made of non hygroscopic, non combustible, track resistant high strength FRP insulators 400 Amps for phases and Neural, set of 4 for RYB &N - 01 set. (a) MCCB 4 Pole 200 Amps 25KA -01 Nos. adjustable type (incommer) (d) MCCB 4 Pole 32 Amps 18KA -11 Nos. (Outgoing) (e) Three phase Panel mounted Digital type Voltmeter meter 0-500 Volts, Ammeter 400/5A LT-CT operated complete - 01 Set (f) Indicating type lamp for Red, Yellow and Blue phases - 01 Set
Design , Supply, Installation, testing and Commissioning CPRI APPROVED factory fabricated, out door type,LT FEEDER PILLAR BOX IP 55 protection grade, made out of 3.15 mm thick CRCA Sheet with projected Globe roof for rain water protection Dust and Vermin Proof , Double door with both side opening including Neoprene Rubber Gasket,, suitable for 440 Volt 3 Phase 4 Wire System ,including Danger Plate, Earthing Strip Point and Ventilation Louvers at Rear Side, Bottom detachable Gland Plate comp-lete with suitable size Zinc Chromium Plated Nuts, Bolts and Washers , cable glands of appropriate size , etc. and supported with 65X65X6mm Mild Steel Angle Iron Frame and 500 mm above ground lavel , embeded in PCC 1:2:4, type C-2, 45 Cm below ground level and 50 Cm above ground level complete with internal connection with suitable size of strip ,cable lugs,and cable glands and Test-ing after Installation complete all as specified and comprising of the following :- (Size of the panel board should not be less than 1.20 M X1.5 MX0.40M)(MH Panel N0. 02 Location:- Near Family Ward - II) (a) Bus bar aluminium duly insulated with colour coded heat shrinkable sleeve and mounted on suitable size of 'F' class insulators made of non hygroscopic, non combustible, track resistant high strength FRP insulators 800 Amps for phases and Neural, set of 4 for RYB &N - 01 set. (b) MCCB 4 Pole 400-500 Amps 36KA -01 No. Thermal Magnetic release (incommer) (c) MCCB 4 Pole 320-400 Amps 36KA -03 Nos. Thermal Magnetic release (Outgoing) (d) MCCB 4 Pole 160 Amps 25KA -03 Nos. (Outgoing) (e) Three phase Panel mounted Digital type Voltmeter meter 0-500 Volts, Ammeter 400/5A LT-CT operated complete - 01 Set (f) Indicating type lamp for Red, Yellow and Blue phases - 01 Set
Design , Supply, Installation, testing and Commissioning CPRI APPROVED factory fabricated, out door type,LT FEEDER PILLAR BOX IP 55 protection grade, made out of 3.15 mm thick CRCA Sheet with projected Globe roof for rain water protection Dust and Vermin Proof , Double door with both side opening including Neoprene Rubber Gasket,, suitable for 440 Volt 3 Phase 4 Wire System ,including Danger Plate, Earthing Strip Point and Ventilation Louvers at Rear Side, Bottom detachable Gland Plate comp-lete with suitable size Zinc Chromium Plated Nuts, Bolts and Washers , cable glands of appropriate size , etc. and supported with 65X65X6mm Mild Steel Angle Iron Frame and 500 mm above ground lavel , embeded in PCC 1:2:4, type C-2, 45 Cm below ground level and 50 Cm above ground level complete with internal connection with suitable size of strip ,cable lugs,and cable glands and Test-ing after Installation complete all as specified and comprising of the following :- (Size of the panel board should not be less than 1.2 M X1.5MX0.35M)(MH Panel N0. 03 Location:- Near QM House) (a) Bus bar aluminium duly insulated with colour coded heat shrinkable sleeve and mounted on suitable size of 'F' class insulators made of non hygroscopic, non combustible, track resistant high strength FRP insulators 250 Amps for phases and Neural, set of 4 for RYB &N - 01 set. (b) MCCB 4 Pole 125-160 Amps 36KA -01 No. Thermal Magnetic release (incommer) (c) MCCB 4 Pole 100 Amps 25KA -02 Nos. Thermal Magnetic release (Outgoing) (d) MCCB 4 Pole 63 Amps 18KA -01 Nos. (Outgoing) (e) MCCB 4 Pole 32 Amps 18KA -04 Nos. (Outgoing) (f) Three phase Panel mounted Digital type Voltmeter meter 0-500 Volts, Ammeter 400/5A LT-CT operated complete - 01 Set (g) Indicating type lamp for Red, Yellow and Blue phases - 01 Set
Design , Supply, Installation, testing and Commissioning CPRI APPROVED factory fabricated, out door type,LT FEEDER PILLAR BOX IP 55 protection grade, made out of 3.15 mm thick CRCA Sheet with projected Globe roof for rain water protection Dust and Vermin Proof , Double door with both side opening including Neoprene Rubber Gasket,, suitable for 440 Volt 3 Phase 4 Wire System ,including Danger Plate, Earthing Strip Point and Ventilation Louvers at Rear Side, Bottom detachable Gland Plate comp-lete with suitable size Zinc Chromium Plated Nuts, Bolts and Washers , cable glands of appropriate size , etc. and supported with 65X65X6mm Mild Steel Angle Iron Frame and 500 mm above ground lavel , embeded in PCC 1:2:4, type C-2, 45 Cm below ground level and 50 Cm above ground level complete with internal connection with suitable size of strip ,cable lugs,and cable glands and Test-ing after Installation complete all as specified and comprising of the following :- (Size of the panel board should not be less than 1.2 M X1.6MX0.40M)(MH Panel N0. 04 Location:- Near Department of Surgery) (a) Bus bar aluminium duly insulated with colour coded heat shrinkable sleeve and mounted on suitable size of 'F' class insulators made of non hygroscopic, non combustible, track resistant high strength FRP insulators 500 Amps for phases and Neural, set of 4 for RYB &N - 01 set. (b) MCCB 4 Pole 250-320 Amps 36KA -01 No. Thermal Magnetic release (incommer) (c) MCCB 4 Pole 200 Amps 25KA -02 Nos. Thermal Magnetic release (Outgoing) (d) MCCB 4 Pole 100 Amps 18KA -03 Nos. (Outgoing) (e) MCCB 4 Pole 32 Amps 18KA -02 Nos. (Outgoing) (f) Three phase Panel mounted Digital type Voltmeter meter 0-500 Volts, Ammeter 400/5A LT-CT operated complete - 01 Set (g) Indicating type lamp for Red, Yellow and Blue phases - 01 Set
Design , Supply, Installation, testing and Commissioning CPRI APPROVED factory fabricated, out door type,LT FEEDER PILLAR BOX IP 55 protection grade, made out of 3.15 mm thick CRCA Sheet with projected Globe roof for rain water protection Dust and Vermin Proof , Double door with both side opening including Neoprene Rubber Gasket,, suitable for 440 Volt 3 Phase 4 Wire System ,including Danger Plate, Earthing Strip Point and Ventilation Louvers at Rear Side, Bottom detachable Gland Plate comp-lete with suitable size Zinc Chromium Plated Nuts, Bolts and Washers , cable glands of appropriate size , etc. and supported with 65X65X6mm Mild Steel Angle Iron Frame and 500 mm above ground lavel , embeded in PCC 1:2:4, type C-2, 45 Cm below ground level and 50 Cm above ground level complete with internal connection with suitable size of strip ,cable lugs,and cable glands and Testing after Installation complete all as specified and comprising of the following :- (Size of the panel board should not be less than 1.1 M X1.1 MX0.35M) (MH Panel N0. 05 Location:- Near Cardiology Ward) (a) Bus bar aluminium duly insulated with colour coded heat shrinkable sleeve and mounted on suitable size of 'F' class insulators made of non hygroscopic, non combustible, track resistant high strength FRP insulators 300 Amps for phases and Neural, set of 4 for RYB &N - 01 set. (b) MCCB 4 Pole 200 Amps 25KA -01 Nos. Thermal Magnetic release (iNCOMING) (c) MCCB 4 Pole 100 Amps 18KA -04 Nos. (Outgoing) (d) Three phase Panel mounted Digital type Voltmeter meter 0-500 Volts, Ammeter 400/5A LT-CT operated complete - 01 Set (e) Indicating type lamp for Red, Yellow and Blue phases - 01 Set
Design , Supply, Installation, testing and Commissioning CPRI APPROVED factory fabricated, out door type,LT FEEDER PILLAR BOX IP 55 protection grade, made out of 3.15 mm thick CRCA Sheet with projected Globe roof for rain water protection Dust and Vermin Proof , Double door with both side opening including Neoprene Rubber Gasket,, suitable for 440 Volt 3 Phase 4 Wire System ,including Danger Plate, Earthing Strip Point and Ventilation Louvers at Rear Side, Bottom detachable Gland Plate comp-lete with suitable size Zinc Chromium Plated Nuts, Bolts and Washers , cable glands of appropriate size , etc. and supported with 65X65X6mm Mild Steel Angle Iron Frame and 500 mm above ground lavel , embeded in PCC 1:2:4, type C-2, 45 Cm below ground level and 50 Cm above ground level complete with internal connection with suitable size of strip ,cable lugs,and cable glands and Test-ing after Installation complete all as specified and comprising of the following :- (Size of the panel board should not be less than 1.1 M X1.0 MX0.35M)(MH Panel N0. 06 Location:- Near SHO Bldg) (a) Bus bar aluminium duly insulated with colour coded heat shrinkable sleeve and mounted on suitable size of 'F' class insulators made of non hygroscopic, non combustible, track resistant high strength FRP insulators 300 Amps for phases and Neural, set of 4 for RYB &N - 01 set. (b) MCCB 4 Pole 200 Amps 25KA -01 Nos. Thermal Magnetic release (iNCOMING) (c) MCCB 4 Pole 160 Amps 25KA -02 Nos. (Outgoing) (d) MCCB 4 Pole 63 Amps 18KA -01 Nos. (Outgoing) (e) MCCB 4 Pole 32 Amps 18KA -01 Nos. (Outgoing) (f) Three phase Panel mounted Digital type Voltmeter meter 0-500 Volts, Ammeter 400/5A LT-CT operated complete - 01 Set (g) Indicating type lamp for Red, Yellow and Blue phases - 01 Set
Design , Supply, Installation, testing and Commissioning CPRI APPROVED factory fabricated, out door type,LT FEEDER PILLAR BOX IP 55 protection grade, made out of 3.15 mm thick CRCA Sheet with projected Globe roof for rain water protection Dust and Vermin Proof , Double door with both side opening including Neoprene Rubber Gasket,, suitable for 440 Volt 3 Phase 4 Wire System ,including Danger Plate, Earthing Strip Point and Ventilation Louvers at Rear Side, Bottom detachable Gland Plate comp-lete with suitable size Zinc Chromium Plated Nuts, Bolts and Washers , cable glands of appropriate size , etc. and supported with 65X65X6mm Mild Steel Angle Iron Frame and 500 mm above ground lavel , embeded in PCC 1:2:4, type C-2, 45 Cm below ground level and 50 Cm above ground level complete with internal connection with suitable size of strip ,cable lugs,and cable glands and Test-ing after Installation complete all as specified and comprising of the following :- (Size of the panel board should not be less than 1.1 M X1.2 MX0.35M)(MH Panel N0. 07 Location:- Near School of Nursing) (a) Bus bar aluminium duly insulated with colour coded heat shrinkable sleeve and mounted on suitable size of 'F' class insulators made of non hygroscopic, non combustible, track resistant high strength FRP insulators 200 Amps for phases and Neural, set of 4 for RYB &N - 01 set. (b) MCCB 4 Pole 100 Amps 25KA -01 Nos. Thermal Magnetic release (Incoming) (c) MCCB 4 Pole 32 Amps 18KA -05 Nos. (Outgoing) (e) Three phase Panel mounted Digital type Voltmeter meter 0-500 Volts, Ammeter 400/5A LT-CT operated complete - 01 Set (e) Indicating type lamp for Red, Yellow and Blue phases - 01 Set
Design , Supply, Installation, testing and Commissioning CPRI APPROVED factory fabricated, out door type,LT FEEDER PILLAR BOX IP 55 protection grade, made out of 3.15 mm thick CRCA Sheet with projected Globe roof for rain water protection Dust and Vermin Proof , Double door with both side opening including Neoprene Rubber Gasket,, suitable for 440 Volt 3 Phase 4 Wire System ,including Danger Plate, Earthing Strip Point and Ventilation Louvers at Rear Side, Bottom detachable Gland Plate comp-lete with suitable size Zinc Chromium Plated Nuts, Bolts and Washers , cable glands of appropriate size , etc. and supported with 65X65X6mm Mild Steel Angle Iron Frame and 500 mm above ground lavel , embeded in PCC 1:2:4, type C-2, 45 Cm below ground level and 50 Cm above ground level complete with internal connection with suitable size of strip ,cable lugs,and cable glands and Test-ing after Installation complete all as specified and comprising of the following :- (Size of the panel board should not be less than 1.1 M X1.2MX0.35M) (MH Panel N0. 08 & 09 Location:- Near Ranga Shala Open Air Theatre and Beside Medical Store) (a) Bus bar aluminium duly insulated with colour coded heat shrinkable sleeve and mounted on suitable size of 'F' class insulators made of non hygroscopic, non combustible, track resistant high strength FRP insulators 300 Amps for phases and Neural, set of 4 for RYB &N - 01 set. (b) MCCB 4 Pole 160 Amps 25KA -01 Nos. Thermal Magnetic release ( iNCOMING) (c) MCCB 4 Pole 63 Amps 18KA - 05 Nos. (Outgoing) (d) Three phase Panel mounted Digital type Voltmeter meter 0-500 Volts, Ammeter 400/5A LT-CT operated complete - 01 Set (e) Indicating type lamp for Red, Yellow and Blue phases - 01 Set Note : (a)All existing incoming and out going cables are to be connected to the above panel with proper lugs, glands nuts, bolts etc the cost of work is deemed to be included in the above item. (b) The cost shall also be include the breaking of floors/walls etc including digging of trenches for removing of cables of loops and connecting to the new panel boards and making good the disturbed surfaces to match with the existing surfaces (c) The panel shall be Fabricated from a reputed firm(CPRI Approved) . Make of MCCB's:Havells/L&T/HPL
Design , Supply, Installation, testing and Commissioning CPRI APPROVED factory fabricated, out door type,LT FEEDER PILLAR BOX IP 55 protection grade, made out of 3.15 mm thick CRCA Sheet with projected Globe roof for rain water protection Dust and Vermin Proof , Double door with both side opening including Neoprene Rubber Gasket,, suitable for 440 Volt 3 Phase 4 Wire System ,including Danger Plate, Earthing Strip Point and Ventilation Louvers at Rear Side, Bottom detachable Gland Plate comp-lete with suitable size Zinc Chromium Plated Nuts, Bolts and Washers , cable glands of appropriate size , etc. and supported with 65X65X6mm Mild Steel Angle Iron Frame and 500 mm above ground lavel , embeded in PCC 1:2:4, type C-2, 45 Cm below ground level and 50 Cm above ground level complete with internal connection with suitable size of strip ,cable lugs,and cable glands and Test-ing after Installation complete all as specified and comprising of the following :- (Size of the panel board should not be less than 1.25 M X2.0 MX0.45M) (MH Panel N0. 10 Location:- Near OHT) (a) Bus bar aluminium duly insulated with colour coded heat shrinkable sleeve and mounted on suitable size of 'F' class insulators made of non hygroscopic, non combustible, track resistant high strength FRP insulators 1000 Amps for phases and Neural, set of 4 for RYB &N - 01 set. (b) MCCB 4 Pole 200 Amps 25KA -01 Nos. Thermal Magnetic release (Incoming) (c) MCCB 4 Pole 160 Amps 18KA - 02 Nos. (Outgoing) (d) MCCB 4 Pole 63 Amps 18KA - 05 Nos. (Outgoing) (e) Three phase Panel mounted Digital type Voltmeter meter 0-500 Volts, Ammeter 400/5A LT-CT operated complete - 01 Set (f) Indicating type lamp for Red, Yellow and Blue phases - 01 Set
Design , Supply, Installation, testing and Commissioning CPRI APPROVED factory fabricated, out door type,LT FEEDER PILLAR BOX IP 55 protection grade, made out of 3.15 mm thick CRCA Sheet with projected Globe roof for rain water protection Dust and Vermin Proof , Double door with both side opening including Neoprene Rubber Gasket,, suitable for 440 Volt 3 Phase 4 Wire System ,including Danger Plate, Earthing Strip Point and Ventilation Louvers at Rear Side, Bottom detachable Gland Plate comp-lete with suitable size Zinc Chromium Plated Nuts, Bolts and Washers , cable glands of appropriate size , etc. and supported with 65X65X6mm Mild Steel Angle Iron Frame and 500 mm above ground lavel , embeded in PCC 1:2:4, type C-2, 45 Cm below ground level and 50 Cm above ground level complete with internal connection with suitable size of strip ,cable lugs,and cable glands and Test-ing after Installation complete all as specified and comprising of the following :- (Size of the panel board should not be less than 1.2 M X1.5MX0.35M) (MH Panel N0. 11 Location:- Opp Nursing Officers Mess) (a) Bus bar aluminium duly insulated with colour coded heat shrinkable sleeve and mounted on suitable size of 'F' class insulators made of non hygroscopic, non combustible, track resistant high strength FRP insulators 300 Amps for phases and Neural, set of 4 for RYB &N - 01 set. (b) MCCB 4 Pole 200 Amps 25KA -01 Nos. Thermal Magnetic release (iNCOMING) (c) MCCB 4 Pole 100 Amps 18KA - 02 Nos. (Outgoing) (d) MCCB 4 Pole 63 Amps 18KA - 05 Nos. (Outgoing) (e) Three phase Panel mounted Digital type Voltmeter meter 0-500 Volts, Ammeter 400/5A LT-CT operated complete - 01 Set (f) Indicating type lamp for Red, Yellow and Blue phases - 01 Set
Design , Supply, Installation, testing and Commissioning CPRI APPROVED factory fabricated, out door type,LT FEEDER PILLAR BOX IP 55 protection grade, made out of 3.15 mm thick CRCA Sheet with projected Globe roof for rain water protection Dust and Vermin Proof , Double door with both side opening including Neoprene Rubber Gasket,, suitable for 440 Volt 3 Phase 4 Wire System ,including Danger Plate, Earthing Strip Point and Ventilation Louvers at Rear Side, Bottom detachable Gland Plate comp-lete with suitable size Zinc Chromium Plated Nuts, Bolts and Washers , cable glands of appropriate size , etc. and supported with 65X65X6mm Mild Steel Angle Iron Frame and 500 mm above ground lavel , embeded in PCC 1:2:4, type C-2, 45 Cm below ground level and 50 Cm above ground level complete with internal connection with suitable size of strip ,cable lugs,and cable glands and Test-ing after Installation complete all as specified and comprising of the following :- (Size of the panel board should not be less than 0.70 M X0.6 MX0.45M) (Location :- Near peersonnel Line and Near Medical Store) (a) Aluminium bas bar 400amps - 04 Nos, supported with suitable size of heavy duty porcelin stand lock with suitable size of brass nut, bolts and washer with heat shrinkable PVC sleeving. The bar shall be colour coded (red, yellow and blue) for three phases and black for neutral. b) MCCB 200 amps ,415 volt ,16 KA Breaking capacity 4 pole Electromagnetic release duly connected to Bus Bar As IN COMING - 01 NosMake Legrand Schinder/L&T/Hagar
Design , Supply, Installation, testing and Commissioning CPRI APPROVED factory fabricated, out door type,LT FEEDER PILLAR BOX IP 55 protection grade, made out of 3.15 mm thick CRCA Sheet with projected Globe roof for rain water protection Dust and Vermin Proof , Double door with both side opening including Neoprene Rubber Gasket,, suitable for 440 Volt 3 Phase 4 Wire System ,including Danger Plate, Earthing Strip Point and Ventilation Louvers at Rear Side, Bottom detachable Gland Plate comp-lete with suitable size Zinc Chromium Plated Nuts, Bolts and Washers , cable glands of appropriate size , etc. and supported with 65X65X6mm Mild Steel Angle Iron Frame and 500 mm above ground lavel , embeded in PCC 1:2:4, type C-2, 45 Cm below ground level and 50 Cm above ground level complete with internal connection with suitable size of strip ,cable lugs,and cable glands and Test-ing after Installation complete all as specified and comprising of the following :- (Size of the panel board should not be less than 1.20 M X1.7 MX0.40M) (Main LT Panel for Robert Line) (a) Bus bar aluminium duly insulated with colour coded heat shrinkable sleeve and mounted on suitable size of 'F' class insulators made of non hygroscopic, non combustible, track resistant high strength FRP insulators 650 Amps for phases and Neural, set of 4 for RYB &N - 01 set. (b) MCCB 4 Pole 400 Amps 36KA -01 Nos. adjustable type (incommer) (c) MCCB 4 Pole 250 Amps 36KA -03 Nos. adjustable type (Outgoing) (d) MCCB 4 Pole 160 Amps 36KA -02 Nos. (Outgoing) (e) MCCB 4 Pole 32 Amps 18KA -02 Nos. (Outgoing) (f) Three phase Panel mounted Digital type Voltmeter meter 0-500 Volts, Ammeter 630/5A LT-CT operated complete - 01 Set (g) Indicating type lamp for Red, Yellow and Blue phases - 01 Set
Design , Supply, Installation, testing and Commissioning CPRI APPROVED factory fabricated, out door type,LT FEEDER PILLAR BOX IP 55 protection grade, made out of 3.15 mm thick CRCA Sheet with projected Globe roof for rain water protection Dust and Vermin Proof , Double door with both side opening including Neoprene Rubber Gasket,, suitable for 440 Volt 3 Phase 4 Wire System ,including Danger Plate, Earthing Strip Point and Ventilation Louvers at Rear Side, Bottom detachable Gland Plate comp-lete with suitable size Zinc Chromium Plated Nuts, Bolts and Washers , cable glands of appropriate size , etc. and supported with 65X65X6mm Mild Steel Angle Iron Frame and 500 mm above ground lavel , embeded in PCC 1:2:4, type C-2, 45 Cm below ground level and 50 Cm above ground level complete with internal connection with suitable size of strip ,cable lugs,and cable glands and Test-ing after Installation complete all as specified and comprising of the following :- (Size of the panel board should not be less than 1.15 M X1.35 MX0.40M) (LT Panel No-1 at Near B-231 & B-233) (a) Bus bar aluminium duly insulated with colour coded heat shrinkable sleeve and mounted on suitable size of 'F' class insulators made of non hygroscopic, non combustible, track resistant high strength FRP insulators 500 Amps for phases and Neural, set of 4 for RYB &N - 01 set. (b) MCCB 4 Pole 250 Amps 36KA -01 No. Thermal Magnetic release (incommer) (c) MCCB 4 Pole 160 Amps 36KA -04 No. Thermal Magnetic release (Outgoing) (d) MCCB 4 Pole 63 Amps 18KA -02 Nos. (Outgoing) (e) Three phase Panel mounted Digital type Voltmeter meter 0-500 Volts, Ammeter 500/5A LT-CT operated complete - 01 Set (f) Indicating type lamp for Red, Yellow and Blue phases - 01 Set
Design , Supply, Installation, testing and Commissioning CPRI APPROVED factory fabricated, out door type,LT FEEDER PILLAR BOX IP 55 protection grade, made out of 3.15 mm thick CRCA Sheet with projected Globe roof for rain water protection Dust and Vermin Proof , Double door with both side opening including Neoprene Rubber Gasket,, suitable for 440 Volt 3 Phase 4 Wire System ,including Danger Plate, Earthing Strip Point and Ventilation Louvers at Rear Side, Bottom detachable Gland Plate comp-lete with suitable size Zinc Chromium Plated Nuts, Bolts and Washers , cable glands of appropriate size , etc. and supported with 65X65X6mm Mild Steel Angle Iron Frame and 500 mm above ground lavel , embeded in PCC 1:2:4, type C-2, 45 Cm below ground level and 50 Cm above ground level complete with internal connection with suitable size of strip ,cable lugs,and cable glands and Test-ing after Installation complete all as specified and comprising of the following :- (Size of the panel board should not be less than 1.15 M X1.65 MX0.35M) (LT Panel No-3 at B-212) :- (a) Bus bar aluminium duly insulated with colour coded heat shrinkable sleeve and mounted on suitable size of 'F' class insulators made of non hygroscopic, non combustible, track resistant high strength FRP insulators 500 Amps for phases and Neural, set of 4 for RYB &N - 01 set. (b) MCCB 4 Pole 250 Amps 36KA -01 No. Thermal Magnetic release (incommer) (c) MCCB 4 Pole 160 Amps 18KA -05 Nos. (Outgoing) (d) MCCB 4 Pole 63 Amps 18KA -02 Nos. (Outgoing) (e) Three phase Panel mounted Digital type Voltmeter meter 0-500 Volts, Ammeter 400/5A LT-CT operated complete - 01 Set (f) Indicating type lamp for Red, Yellow and Blue phases - 01 Set
Design , Supply, Installation, testing and Commissioning CPRI APPROVED factory fabricated, out door type,LT FEEDER PILLAR BOX IP 55 protection grade, made out of 3.15 mm thick CRCA Sheet with projected Globe roof for rain water protection Dust and Vermin Proof , Double door with both side opening including Neoprene Rubber Gasket,, suitable for 440 Volt 3 Phase 4 Wire System ,including Danger Plate, Earthing Strip Point and Ventilation Louvers at Rear Side, Bottom detachable Gland Plate comp-lete with suitable size Zinc Chromium Plated Nuts, Bolts and Washers , cable glands of appropriate size , etc. and supported with 65X65X6mm Mild Steel Angle Iron Frame and 500 mm above ground lavel , embeded in PCC 1:2:4, type C-2, 45 Cm below ground level and 50 Cm above ground level complete with internal connection with suitable size of strip ,cable lugs,and cable glands and Test-ing after Installation complete all as specified and comprising of the following :- (Size of the panel board should not be less than 1.15 M X1.65 MX0.35M) (Main LT Panel at Thimmaya area) :- (a) Bus bar aluminium duly insulated with colour coded heat shrinkable sleeve and mounted on suitable size of 'F' class insulators made of non hygroscopic, non combustible, track resistant high strength FRP insulators 650 Amps for phases and Neural, set of 4 for RYB &N - 01 set. (b) MCCB 4 Pole 400 Amps 36KA -01 Nos. adjustable type (incommer) (c) MCCB 4 Pole 250 Amps 36KA -05 Nos. adjustable type (Outgoing) (d) MCCB 4 Pole 160 Amps 36KA -02 Nos. (Outgoing) (e) Three phase Panel mounted Digital type Voltmeter meter 0-500 Volts, Ammeter 630/5A LT-CT operated complete - 01 Set (f) Indicating type lamp for Red, Yellow and Blue phases - 01 Set
Design , Supply, Installation, testing and Commissioning CPRI APPROVED factory fabricated, out door type,LT FEEDER PILLAR BOX IP 55 protection grade, made out of 3.15 mm thick CRCA Sheet with projected Globe roof for rain water protection Dust and Vermin Proof , Double door with both side opening including Neoprene Rubber Gasket,, suitable for 440 Volt 3 Phase 4 Wire System ,including Danger Plate, Earthing Strip Point and Ventilation Louvers at Rear Side, Bottom detachable Gland Plate comp-lete with suitable size Zinc Chromium Plated Nuts, Bolts and Washers , cable glands of appropriate size , etc. and supported with 65X65X6mm Mild Steel Angle Iron Frame and 500 mm above ground lavel , embeded in PCC 1:2:4, type C-2, 45 Cm below ground level and 50 Cm above ground level complete with internal connection with suitable size of strip ,cable lugs,and cable glands and Test-ing after Installation complete all as specified and comprising of the following :- (Size of the panel board should not be less than 1.15 M X1.3 MX0.35M) (LT Panel No 1 at B- J91) :- (a) Bus bar aluminium duly insulated with colour coded heat shrinkable sleeve and mounted on suitable size of 'F' class insulators made of non hygroscopic, non combustible, track resistant high strength FRP insulators 400 Amps for phases and Neural, set of 4 for RYB &N - 01 set. (b) MCCB 4 Pole 250 Amps 25KA -01 Nos. Thermal Magnetic release (incomming) (c) MCCB 4 Pole 160 Amps 18KA -03 Nos. (Outgoing) (d) MCCB 4 Pole 63. Amps 10 KA -02 Nos (Outgoing) (e) Three phase Panel mounted Digital type Voltmeter meter 0-500 Volts, Ammeter 400/5A LT-CT operated complete - 01 Set (f) Indicating type lamp for Red, Yellow and Blue phases - 01 Set
Design , Supply, Installation, testing and Commissioning CPRI APPROVED factory fabricated, out door type,LT FEEDER PILLAR BOX IP 55 protection grade, made out of 3.15 mm thick CRCA Sheet with projected Globe roof for rain water protection Dust and Vermin Proof , Double door with both side opening including Neoprene Rubber Gasket,, suitable for 440 Volt 3 Phase 4 Wire System ,including Danger Plate, Earthing Strip Point and Ventilation Louvers at Rear Side, Bottom detachable Gland Plate comp-lete with suitable size Zinc Chromium Plated Nuts, Bolts and Washers , cable glands of appropriate size , etc. and supported with 65X65X6mm Mild Steel Angle Iron Frame and 500 mm above ground lavel , embeded in PCC 1:2:4, type C-2, 45 Cm below ground level and 50 Cm above ground level complete with internal connection with suitable size of strip ,cable lugs,and cable glands and Test-ing after Installation complete all as specified and comprising of the following :- (Size of the panel board should not be less than 1.2 M X2.0 MX0.40M) (LT Panel No-2 at B-252 ) :- (a) Bus bar aluminium duly insulated with colour coded heat shrinkable sleeve and mounted on suitable size of 'F' class insulators made of non hygroscopic, non combustible, track resistant high strength FRP insulators 400 Amps for phases and Neural, set of 4 for RYB &N - 01 set. (b) MCCB 4 Pole 250 Amps 36KA -01 Nos. Thermal Magnetic release (incoming) (c) MCCB 4 Pole 160 Amps 18KA -06 Nos. (Outgoing) (d) MCCB 4 Pole 63 Amps 18KA -03 Nos. (Outgoing) (e) Three phase Panel mounted Digital type Voltmeter meter 0-500 Volts, Ammeter 400/5A LT-CT operated complete - 01 Set (f) Indicating type lamp for Red, Yellow and Blue phases - 01 Set
Design , Supply, Installation, testing and Commissioning CPRI APPROVED factory fabricated, out door type,LT FEEDER PILLAR BOX IP 55 protection grade, made out of 3.15 mm thick CRCA Sheet with projected Globe roof for rain water protection Dust and Vermin Proof , Double door with both side opening including Neoprene Rubber Gasket,, suitable for 440 Volt 3 Phase 4 Wire System ,including Danger Plate, Earthing Strip Point and Ventilation Louvers at Rear Side, Bottom detachable Gland Plate comp-lete with suitable size Zinc Chromium Plated Nuts, Bolts and Washers , cable glands of appropriate size , etc. and supported with 65X65X6mm Mild Steel Angle Iron Frame and 500 mm above ground lavel , embeded in PCC 1:2:4, type C-2, 45 Cm below ground level and 50 Cm above ground level complete with internal connection with suitable size of strip ,cable lugs,and cable glands and Test-ing after Installation complete all as specified and comprising of the following :- (Size of the panel board should not be less than 1.2 M X1.4 MX0.40M) (LT Panel-03 at B-249) :- (a) Bus bar aluminium duly insulated with colour coded heat shrinkable sleeve and mounted on suitable size of 'F' class insulators made of non hygroscopic, non combustible, track resistant high strength FRP insulators 500 Amps for phases and Neural, set of 4 for RYB &N - 01 set. (b) MCCB 4 Pole 250 Amps 36KA -01 Nos. Thermal Magnetic release (incoming) (c) MCCB 4 Pole 160 Amps 36KA -04 Nos. Thermal Magnetic release (Outgoing) (d) MCCB 4 Pole 63 Amps 18KA -02 Nos. (Outgoing) (e) Three phase Panel mounted Digital type Voltmeter meter 0-500 Volts, Ammeter 400/5A LT-CT operated complete - 01 Set (f) Indicating type lamp for Red, Yellow and Blue phases - 01 Set
Design , Supply, Installation, testing and Commissioning CPRI APPROVED factory fabricated, out door type,LT FEEDER PILLAR BOX IP 55 protection grade, made out of 3.15 mm thick CRCA Sheet with projected Globe roof for rain water protection Dust and Vermin Proof , Double door with both side opening including Neoprene Rubber Gasket,, suitable for 440 Volt 3 Phase 4 Wire System ,including Danger Plate, Earthing Strip Point and Ventilation Louvers at Rear Side, Bottom detachable Gland Plate comp-lete with suitable size Zinc Chromium Plated Nuts, Bolts and Washers , cable glands of appropriate size , etc. and supported with 65X65X6mm Mild Steel Angle Iron Frame and 500 mm above ground lavel , embeded in PCC 1:2:4, type C-2, 45 Cm below ground level and 50 Cm above ground level complete with internal connection with suitable size of strip ,cable lugs,and cable glands and Test-ing after Installation complete all as specified and comprising of the following :- (Size of the panel board should not be less than 1.2 M X1.5 MX0.35M) (LT Panel-4 at B-226 offrs Mess) :- (a) Bus bar aluminium duly insulated with colour coded heat shrinkable sleeve and mounted on suitable size of 'F' class insulators made of non hygroscopic, non combustible, track resistant high strength FRP insulators 500 Amps for phases and Neural, set of 4 for RYB &N - 01 set. (b) MCCB 4 Pole 250 Amps 36KA -01 Nos. Thermal Magnetic release (incoming) (c) MCCB 4 Pole 160 Amps 36KA -03 Nos. Thermal Magnetic release (outcoming) (d) MCCB 4 Pole 63 Amps 18KA -03 Nos. (Outgoing) (e) Three phase Panel mounted Digital type Voltmeter meter 0-500 Volts, Ammeter 400/5A LT-CT operated complete - 01 Set (f) Indicating type lamp for Red, Yellow and Blue phases - 01 Set
Design , Supply, Installation, testing and Commissioning CPRI APPROVED factory fabricated, out door type,LT FEEDER PILLAR BOX IP 55 protection grade, made out of 3.15 mm thick CRCA Sheet with projected Globe roof for rain water protection Dust and Vermin Proof , Double door with both side opening including Neoprene Rubber Gasket,, suitable for 440 Volt 3 Phase 4 Wire System ,including Danger Plate, Earthing Strip Point and Ventilation Louvers at Rear Side, Bottom detachable Gland Plate comp-lete with suitable size Zinc Chromium Plated Nuts, Bolts and Washers , cable glands of appropriate size , etc. and supported with 65X65X6mm Mild Steel Angle Iron Frame and 500 mm above ground lavel , embeded in PCC 1:2:4, type C-2, 45 Cm below ground level and 50 Cm above ground level complete with internal connection with suitable size of strip ,cable lugs,and cable glands and Test-ing after Installation complete all as specified and comprising of the following :- (Size of the panel board should not be less than 0.70 M X0.60 MX0.50M) (a) Aluminium bas bar 400amps - 04 Nos, supported with suitable size of heavy duty porcelin stand lock with suitable size of brass nut, bolts and washer with heat shrinkable PVC sleeving. The bar shall be colour coded (red, yellow and blue) for three phases and black for neutral. b) MCCB 250 amps ,415 volt ,16 KA Breaking capacity 4 pole Electromagnetic release duly connected to Bus Bar As IN COMING - 01 NosMake Legrand /Schinder/L&T/Hagar
Supply and lay in trenches/fixed to walls/poles etc connecting buy using lugs, testing and commissioning XLPE insulated and PVC sheathed heavy duty LT 1100 Volts grade armoured under ground cable with solid/ stranded aluminium conductor 4 Core 10 Sqmm complete all as specified and directed
Supply and lay in trenches/fixed to walls/poles etc connecting buy using lugs, testing and commissioning XLPE insulated and PVC sheathed heavy duty LT 1100 Volts grade armoured under ground cable with solid/ stranded aluminium conductor 2 Core 10 Sqmm complete all as specified and directed
Supply and lay in trenches/fixed to walls/poles etc connecting buy using lugs, testing and commissioning XLPE insulated and PVC sheathed heavy duty LT 1100 Volts grade armoured under ground cable with stranded aluminium conductor 4 Core 16 Sqmm complete all as specified and directed
Supply and lay in trenches/fixed to walls/poles etc connecting buy using lugs, testing and commissioning XLPE insulated and PVC sheathed heavy duty LT 1100 Volts grade armoured under ground cable with stranded aluminium conductor 4 Core 25 Sqmm complete all as specified and directed
Supply and lay in trenches/fixed to walls/poles etc connecting buy using lugs, testing and commissioning XLPE insulated and PVC sheathed heavy duty LT 1100 Volts grade armoured under ground cable with stranded aluminium conductor 3.5 Core 35 Sqmm complete all as specified and directed
Supply and lay in trenches/fixed to walls/poles etc connecting buy using lugs, testing and commissioning XLPE insulated and PVC sheathed heavy duty LT 1100 Volts grade armoured under ground cable with stranded aluminium conductor 3.5 Core 50 Sqmm complete all as specified and directed
Supply and lay in trenches/fixed to walls/poles etc connecting buy using lugs, testing and commissioning XLPE insulated and PVC sheathed heavy duty LT 1100 Volts grade armoured under ground cable with stranded aluminium conductor 3.5 Core 70 Sqmm complete all as specified and directed
Supply and lay in trenches/fixed to walls/poles etc connecting buy using lugs, testing and commissioning XLPE insulated and PVC sheathed heavy duty LT 1100 Volts grade armoured under ground cable with stranded aluminium conductor 3.5 Core 95 Sqmm complete all as specified and directed
Supply and lay in trenches/fixed to walls/poles etc connecting buy using lugs, testing and commissioning XLPE insulated and PVC sheathed heavy duty LT 1100 Volts grade armoured under ground cable with stranded aluminium conductor 3.5 Core 120 Sqmm complete all as specified and directed
Supply and lay in trenches/fixed to walls/poles etc connecting buy using lugs, testing and commissioning XLPE insulated and PVC sheathed heavy duty LT 1100 Volts grade armoured under ground cable with stranded aluminium conductor 3.5 Core 150 Sqmm complete all as specified and directed
Supply and lay in trenches/fixed to walls/poles etc connecting buy using lugs, testing and commissioning XLPE insulated and PVC sheathed heavy duty LT 1100 Volts grade armoured under ground cable with stranded aluminium conductor 3.5 Core 185 Sqmm complete all as specified and directed
Supply and lay in trenches/fixed to walls/poles etc connecting buy using lugs, testing and commissioning XLPE insulated and PVC sheathed heavy duty LT 1100 Volts grade armoured under ground cable with stranded aluminium conductor 3.5 Core 240 Sqmm complete all as specified and directed
Supply and lay in trenches/fixed to walls/poles etc connecting buy using lugs, testing and commissioning XLPE insulated and PVC sheathed heavy duty LT 1100 Volts grade armoured under ground cable with stranded aluminium conductor 3.5 Core 300 Sqmm complete all as specified and directed
Taking out and Relaying of LT cable of size 10sq mm to 50 Sqmm 2/3.5 core after carrying out necessary Repair such as joining with Epoxy joint and laid with sand Cushioning and brick protection and making connection By using Lugs all as specified and directed . Note: ( Earth work , sand Cushioning, brick protection, Lt Joints shall be measured and paid separately under Relevent Item)
Taking out and Relaying of LT cable of size 70 sq mm to 150 Sqmm 3.5 core after carrying out necessary Repair such as joining with Epoxy joint and laid with sand Cushioning and brick protection and making connection By using Lugs all as specified and directed . Note: ( Earth work , sand Cushioning, brick protection, Lt Joints shall be measured and paid separately under Relevent Item)
Taking out and Relaying of LT cable of size 185 sq mm to 300 Sqmm 3.5 core after carrying out necessary Repair such as joining with Epoxy joint and laid with sand Cushioning and brick protection and making connection By using Lugs all as specified and directed . Note: ( Earth work , sand Cushioning, brick protection, Lt Joints shall be measured and paid separately under Relevent Item)
Supply and lay pipe galvanized, “ Light grade”, including fittings, 40mm (1.5”) dia.for protection of cable complete all as specified and directed
Supply and lay pipe galvanized, “Light grade”, including fittings, 50mm (2”) dia.for protection of cable complete all as specified and directed
Supply and lay pipe galvanized, “Light grade”, including fittings, 80mm (3”) dia.for protection of cable complete all as specified and directed
Supply and lay pipe galvanized, “Light grade”, including fittings, 100mm (4”) dia for protection of cable complete all as specified and directed
Supplying and laying of following size HDPE pipe pn 10 ISI marked along with all accessories like socket, bend, couplers etc. conforming to IS 14930, Part II complete with fitting and cutting, jointing etc.direct in ground , wall , floor complete all as directed
Cutting the existing road / hardstanding straight by manual, depth and width not less than 0.6 mtr below ground level for passing of underground cable and filling back with excavated soil upto 75% road portion and 25% shall be made with cement concrete 1:2:4 (using 20 mm graded aggregate stone complete all as specified and directed. Note : Quoted rates inclusive of PCC
Cutting the existing building plinth protection/ Floor by using suitable cutter , depth and width as required for laying of LTUG Cable of any size /any kind of pipes pipes up to 50 mm dia and making good of disturbed surface shall be made with cement concrete 1:2:4 type B1 (using 20 mm graded stone aggregate) and cement morter on any other things as required to match with the adjoining surface complete all as specified and directed.
Supply and fix on wall with necessary arrangements busbar chamber 100 amps 4 way 4 pole wall mounted IP -31 , made out of 1.6 mm thick CRCA sheet epoxy powdwer coated single layer operational voltage 440 Volt , Short circuit current capacity 25 KA for 1 Second including necessary cable connections complete all as specified and directed. Note: Quoted rates inclusive of necessary fixing arrangement and cable connections , cable glands as required for proper fixing / functioning of Bus Bar Chamber. Make : Havells/ HPL/Standerd,
Supply and fix on wall with necessary arrangements busbar chamber 200 amps 4 way 4 pole wall mounted IP -31 , made out of 1.6 mm thick CRCA sheet epoxy powdwer coated single layer operational voltage 440 Volt , Short circuit current capacity 25 KA for 1 Second including necessary cable connections complete all as specified and directed. Note: Quoted rates inclusive of necessary fixing arrangement and cable connections , cable glands as required for proper fixing / functioning of Bus Bar Chamber. Make : Havells/ HPL/Standerd,
S&FMCCB box made of CRCA sheet of 2mm thick size 40X30X20 CM Powder coated Suitable for fixing at Pole including two set of clamps / wall byusing anchor bolt comprising MCCB 63 Amps 16 KA FP WITH BOTH SIDE SPREADER LINK complete all as specified and directed.
S&FMCCB box made of sheet of 2mm thick size 40X30X20 CM Powder coated Suitable for fixing at Pole including two set of clamps / wall byusing anchor bolt comprising MCCB 100 Amps 16 KA FP WITH BOTH SIDE SPREADER LINK complete all as specified and directed.
Material and Labour for drawing two runs of PVC insulated unsheathed single core multi stranded copper conductor FRLS cable of size 1.50 sq mm with one run of PVC insulated unsheathed single core multi stranded copper conductor FRLS cable of size 1.50 sq mm including 20mm dia PVC conduit exclusive of boxes but inclusive of all tees, bends, elbow, reducers etc and fixing accessories such as couples, lock nuts, saddles, pipe hooks, 3 sets of clamps of suitable size for supporting on pole etc complete all as specified. Note: The above mentioned wire to be used for connection of lights from Junction box. Quoted rates inclusive of clamps of suitable size required for the same .
Material and Labour PVC insulated sheathed three core HV Round cable 1100 volt grade with multi stranded copper conductor FRLS cable of size 1.50 sq mm including 20mm dia flexible conduit conduit to be used for connection street light from Junction box through inside the steel tubuler pole complete all as specified.
M&L for road crossing/drain crossing by adopting trench less tunneling work through specified pipe jacking method by erecting the equipment to true to the allignment and gradient by haidrolic pipe jacking technique complete including tunneling, excavation in any type of soils including hard rock, HDPE pipe upto 110 mm dia of max length 15 m including jointing materials to carry LT UG cables of size upto 240 Sqmm and necessary conveyance charges of machinery and other required materials in co-ordination with the concerned authorites complete all as specified and as directed including refilling and making good of disturbed surface . Note : Quoted rate exclusive of HDPE pipe but including of necessary machinaries required for the above work
M&L for stright Through Joint heat shriankable type suitable for 1100 volt grade and of LTUG cable size 25 sq mm to 50 Sqmm 4 core complete including all jointing material complete all as specified and directed
M&L for stright Through Joint heat shriankable type suitable for 1100 volt grade and of LTUG cable size 70 sq mm to 150 Sqmm 4 core complete including all jointing material complete all as specified and directed
M&L for stright Through Joint heat shriankable type suitable for 1100 volt grade and of LTUG cable size 185 sq mm to 300 Sqmm 4 core complete including all jointing material complete all as specified and directed
Supply and Fixing of cable jointing kit for 1.1 KV grade cable for outdoor end termination heat shrinkable type joint complete with jointing material and accessories suitable for 3.5 core XLPE armoured aluminium conductor cable of size 25 sqmm to 50 sqmm complete including taking out old unserviceable one all as specifide and directed.
Supply and Fixing of cable jointing kit for 1.1 KV grade cable for outdoor end termination heat shrinkable type joint complete with jointing material and accessories suitable for 3.5 core XLPE armoured aluminium conductor cable of size 70 sqmm to 150 sqmm complete including taking out old unserviceable one all as specifide and directed.
Supply and Fixing of cable jointing kit for 1.1 KV grade cable for outdoor end termination heat shrinkable type joint complete with jointing material and accessories suitable for 3.5 core XLPE armoured aluminium conductor cable of size 185 sqmm to 300 sqmm complete including taking out old unserviceable one all as specifide and directed.
Excavation in trenches, n exc 1.5 m wide and n exc 1.5 m in depth, for foundation of PCC/Steel pole, laying of cable in trenches etc and getting out in Hard / Dense soil complete all as specified and directed.
Earth work in excavation by mechanical means in trenches in all kind of soil not exceeding 1.5 m in width including dressing of side , lift upto 1.5 m including getting out the excavated soil for laying of LTUG cable and disposal of surplus excavated soil as directed
Returning, filling in, including spreading, leveling, watering and well ramming in layers not exc 25 cm in soils complete all as specified and directed.
Removing excavated material (soils) n exc. 50m and depositing where directed at a level n exc. 1.5 m above the starting point complete all as specified and directed.
M&L filling river sand in trenches for cushioning of laying of cables to the full width of excavated trench 8 cm thick before laying the cable and 15 cm above the cable, gently punned down, stretching and testing of cable on transformer yard etc complete all as specified and directed. Note :- Thickness of river sand cushion after punning down (i.e 18 cm) shall be measured for payment.
Supply and Laying bricks, common burnt clay building bricks, sub class 'B' of size 230 x 115 x 75 mm laid across in trenches for cable protection complete all as specified and directed.
Supplying and laying unreinforced precast concrete cable cover class LV , Type 1 flat with size 250mm x150 mm x 40mm all asspecified and directed by Engr-in-Charge.
Advance Maintenance Free G.I. SAFE EARTHING Electrode with PIPE of not less than 50 mm outer dia( THICKNESS NOT LESS THAN -2.5MM) and two meter length, The electrode should be of galvinised (80 -100 micron) along with earth lead as Galvanised steel strip of size 32 X6 mm 7.5 m . The GI Electrode shall be pre-filled with Cristaline Conductive Material (CCM) . The GI electrode shall be surrounded with 25 kg BackFill compound to provide maximum contact between the electrode and Back Fill Compound. Backfill compound should be eco-frendly and having RoHs certification. GI Electrode Shall be tested from CPRI. The earting pit should be cover with PCC 1:2:4, B1 cover of 300 x 300 mm complete all as specified and directed make ASHLOK / INDELEC/JMV /TERCEL.
S & F hot press moulded SMC junction / terminal box of size with internal diamensions of 200 x 140 x 95 mm with hinged door, incl provision of 4 way connector 415 Volts, 32 Amps made out of polycarbonate or bakelite and 1 No MCB of 6 Amps with DIN bar, drilling holes for cable connections, connecting incoming and or out going cables by providing suitable of size of cable lugs and glands, fixied on pole by means of 2 sets of clamps made out of MS flat iron of size 25 mm x 3 mm icomplete all as specified and as directed.Make: Hensel/Syntex/C&S
M&L for Making hole 2 nos ( one hole near JB another hole near bottom portion of bracket ) on existing steel tubuler pole ( SP -31 ) of suitable size for passing of Street light connection HV Round cable 3 core 1.5 / 2.5 Sqmm from Junction Box to street light complete all as directed
Pertially Demolotion of coping of pole as required for placing of cable protection pipe and making good the same by using PCC and rendering complete al as speccified and directed. Note: Quoted rates inclusive of PCC and rendering
Disconnection existing LT UG cable of any size from pole/OH line and connect the same to federpiller box by using cable lugs etc as required complete all as directed
Dismantling cross-arms of M.S. channel or angle sections etc. complete and setting aside for re-use with in 50m
Dismantling insulators any type, any size
Dismantling stay assembly complete.
Dismantling of ACSR or AAC conductors
Dismantling of Service wire of any size and type
Universal refrigeration and Engineering Company
SANJEEV CONSTRUCTIONS
Electricals India
omsai thermax engineers
Shri Sai Electricals
M/S UnitedConstruction
M/s R.L.PAREEK
Shekhar Enterprises
stage.html
html • 0.07 MB
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .