Loading…
Loading…
| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | 1st₹27.4 LAccepted-AOC | 1st | Accepted-AOC The lowest bidder M/s Kailash Chand Babulal has been accepted pl. | |
| 2 | 2nd₹32.2 L+₹4.3 L (15.4%)Rejected-Finance | 2nd | Rejected-Finance L2 | |
| 3 | 3rd₹32.3 L+₹4.4 L (15.7%)Rejected-Finance | 3rd | Rejected-Finance L3 |
Tender Value
₹30 L
EMD Value
₹60,000
Closing Date
29 Apr 2022, 6:00 pmClosed
GE AWC MHOW
GE AWC MHOW
REPAIR / MAINT AND REPLACEMENT OF UNSERVICEABLE JUNCTION BOXES, POLE PAINTING REPLACEMENT OF UG CABLE AT ARMY WAR COLLEGE UNDER GE (AWC) MHOW.
2022_MES_516162_1
8575 GE(AWC) /MHOW / OF 2022-23
Open Tender
Electrical and Maintenance Works
Item Rate
180 days
GE AWC MHOW
All as per NIT and Tender Documents.
7 documents required · 7 mandatory
₹500
Yes
GE AWC MHOW
₹60,000
Yes
19 May 2022
1 Apr 2022
30 Apr 2022
2 Apr 2022
29 Apr 2022
16 Apr 2022
Amount
Excavation in trenches, not exc 1.5 m wide and not exc 1.5 m in depth; for laying of cables, pipes etc. and getting out all excavated material in any type of soil complete all as specified and directed.
Returning, filling in and including spreading, levelling, watering and well ramming in layers not exceeding 25 cm thick complete all as specified and as directed.
Removing of excavated surplus soil to a distance not exc 50 m and depositing where directed at a level not exc. 1.5 m above the starting point complete all as specified and directed.
M&L of Locally available river sand filling in trenches below and above / around UG cable for cable protection, in duct under & above the cables including punning around cable complete all as specified and directed. Note - Punned thickness shall only be measured and paid.
Supply and laying GI pipe 'light grade' 40 mm bore in trenches, under floors, roads, along poles for protection of cables with all necessary fittings and sealing ends complete all as specified and directed. Make:- Jindal, Prakash Surya, Tata
Description same as per Item No. 5.00 above but GI pipe 'light grade' 50 mm bore
Taking down old unserviceable PCC street light pole complete including dismantling of street light complete all as specified and directed. Note - Excavation, concrete and copping shall be measured and paid separately.
Excavating in trenches exc 1.5m wide but exc 1.5m and n exc 3.0m deep for foundation of poles strut/stays etc n exc 10 sqm on plan and getting out in any type of soil.
M&L PCC 1:4:8 type D-2 (using 40 mm graded crushed stone aggregate) as in foundation filling and mass concrete complete all as specified and directed.
M&L PCC 1:3:6 type C-2 (using 40 mm graded crushed stone aggregate) as in foundation filling and mass concrete complete all as specified and directed.
M&L PCC 1:2:4 type B-1 (using 20 mm graded crushed stone aggregate) as in coping including existing pole including weathering slightly rounded / chamfered angle with and including necessary use and waste of foam work for fair finished surfaces complete all as specified and directed.
M&L steel tubular swaged poles complete with cast iron base plate, finial tapper plug, bolts, nuts & screws as specified type 410 SP-31(9 mtr long) complete all as specified including painting of pole with one coat of black bituminous paint (up to planting depth) and above plinth block / concrete coller with two coats of aluminium paint over a coat of red oxide primer including making five alternate strips 30 cm wide with black and yellow paint in two coats, marking MES number with black pain including three core wire minimum 1.5 sqmm from junction box to street light complete all as specified and directed. Make NTC Kanpur, BCW Kanpur,Bharat Conduit
S&F in replacement of security light bracket with 40 mm dia GI Pipe light grade 1.2 mtr long bend to an angle of 120 degrees with two nos. MS flat iron clamp 50 x 6 mm, nuts, bolts and washers, duly painted with two coats of synthetic enamel paint over a coat of red oxide primer complete all as specified and directed.
S&F in replacement of PVC junction box IP - 66 DK 1000 G thermoplastic poly carbonate including connector block and 20Amp,SP MCB including two holes for incoming and outgoing cables, providing cable glands double compression as per requirement, providing DIN rail for mounting MCB SP and clamps made out of MS flat iron 25 x 4 mm, MS hexagonal bolts, nuts and washers for arrangements to pole/ surfaces complete all as specified and directed. Make - Hensel / Schineder / GE
Supplying, laying, fixing, jointing and testing LT under ground XLPE insulated, galvanised teel strip or wire armoured heavy duty electric cable with alumimium conductor,with multi stranded 1100 volts grade, cross sectional area 10 Sqmm x 2 Core, ISI-7098 marked, with electric connection lugs, laid in trenches/under floor or fixed naked with walls / on poles/ in ducts / in GI pipes etc. and including taking down complete all as specified and directed. Note - Excavation, earth work, sand cushioning, protection bricks/tiles/ block, clamps, nuts , bolts, washers and pipe shall be measured and paid separately. Make - Gloster / RR kable/ Polycab / RPG (asian)
Description same as per Item No. 15.00 above but 10 sqmm x 4 Core
Description same as per Item No. 15.00 above but 25 sqmm x 4 Core
Supplying, laying, fixing, jointing and testing LT services cable heavy duty electric cable with copper conductor, 1100 volts grade, cross sectional area 6 sqmm 4 core, ISI marked, with electric connection lugs, fixed naked with walls / on poles/ on high mast / in GI pipes etc. and including taking down complete all as specified and directed. Make - Gloster / RR kable/ Havells / Finolex
Supply and laying unreinforced PCC Cable protection cover, class LV, type-1 flat with size 250 x 150 x 40 mm laid flat width wise complete all as specified and directed. Make - Mehtab/ Nitco
M&L for painting of security light steel tubular pole upto 09 mtrs length including clamp, bracket and junction box with two coats of aluminium paint after preparation of old painted surface and providing 03 no. alternate strip of 30 cm wide with black and Yellow super quality enamel paint above embeded level and writing pole no. with 02 inch wide letter complete all as specified and directed by Engr-in-Charge. Make of paint - Asian / Nerolac / Berger
M&L for painting of security light steel tubular pole upto 09 mtrs length double arms including clamp, bracket and junction box with two coats of aluminium paint after preparation of old painted surface and providing 03 no. alternate strip of 30 cm wide with black and white super quality enamel paint above embeded level and writing pole no. with 02 inch wide letter complete all as specified and directed. Make of paint - Asian / Nerolac / Berger
Supply, Installation, Testing and Commissioning of LED Streetlight Fitting with a nominal system 5300 lumen output of lumens, minimum system efficacy of 115 lm/W and total power consumption not exceeding 45 W (including driver). The luminaire shall have a rated system lifetime of 50,000 burning hours at L70B50. The luminaire should have a color temperature of 5700 - 6500K and CRI>80. The luminaire shall meet IP66/IK07 or IK08 rating with THD<10% and PF > 0.95. The luminaire housing should made of pressure die cast aluminium and the integrated luminaire optics shall have a high efficiency diffuser with more than 85% transmittance. The fitting should have an internal SPD of minimum 4 kV. The driver should have phase to phase protection for 8 hours. The luminaire should have a NABL approved LM79 report. LM80 report from the LED manufacture is a must along with photo biological report. Luminaire and the driver shall be BIS certified separately and shall posses separate "R" numbers. Fitting should include nut bolt and SS screws for suitably fixing on the exiting steel tubular pole complete all as specified and directed. Make - Philips / Bajaj / Havells / Wipro
Description same as per Item no. 22.00 above but with nominal system output of 8400 lumens, minimum system efficacy of 110 lm/W and total power consumption not exceeding 70 W (including driver).
Description same as per Item no. 22.00 above but with nominal system output of 11000 lumens, minimum system efficacy of 120 lm/W and total power consumption not exceeding 90 W (including driver).
Description same as per Item no. 22.00 above but with nominal system output of 15000 lumens, minimum system efficacy of 120 lm/W and total power consumption not exceeding 120 W (including driver).
Disconnecting and lowering carefully light fittings from high mast, 12-20 mtr high for maintenace / repairs of light fittings and refixing the light fittings after repairs complete all as specified and directed. Note:- Supply only driver SPD shall be measured and paid separately.
Supply, Installation, Testing and Commissioning of LED Floodlight Fitting with a nominal system 16200 lumen output of lumens, minimum system efficacy of 110 lm/W and the total power consumption should not exceed 150 W (including driver). The luminaire shall have a rated system lifetime of 25,000 burning hours at L70B50. The luminaire should have a color temperature of 5700 - 6500K and CRI>80. The luminaire shall meet IP65/IK07 rating with THD<10% and PF > 0.95. The luminaire housing should made of pressure die cast aluminium and the integrated luminaire optics shall have a high efficiency diffuser with more than 85% transmittance. The fitting should have an internal SPD of minimum 4 kV. The luminaire should have a NABL approved LM79 report. LM80 report from the LED manufacture is a must along with photo biological report. Luminaire and the driver shall be BIS certified separately and shall posses separate "R" numbers. Fitting should include nut bolt and SS screws for suitably fixing on the exiting steel tubular pole complete all as specified and directed. Make - Philips / Havells /Wipro / Bajaj
Description same as per Item no. 27.00 above but with nominal system output of 21600 lumens, minimum system efficacy of 110 lm/W and total power consumption not exceeding 240 W (including driver).
Disconnecting and taking down street / security light fitting of any size / capacity / make from the pole / bldg for repair / replacment of unservisable spare parts etc., testing, cleaning the fitting internally and externally and replacement of unserviceable wiring not more than 0.3 Mtrs with 1.5 sqmm PVC insulate copper wire, checking and repairing of loose connections, replacement of wire connectors, nuts, bolts, screws and fixing the light fitting in original position on wall / pole / santry post / top of building including necessary electrical connection complete all as specified and directed by Engr-in-Charge. Note:- Supply only driver SPD shall be measured and paid separately.
Supply, only SPD for LED Street light / flood light fitting with suitable surge capacity complete all as specified and directed. Make - Bajaj, Havells, Philips, Wipro
Supply, only Driver for LED Street light / flood light fitting with suitable surge capacity complete all as specified and directed. Make - Bajaj, Havells, Philips, Wipro
M&L in replacement of cross arms bracings, supports, clamps and back plates fabricated from structural steel sections including nuts, bolts, washers, welding, bending cold or hot, drilling holes for bolts, in any shape or size and inclusive of one primer coat, one under coat and one finishing coat of paint complete all as specified and directed.
S&F in replacement busbar 200 Amp capacity, colour code with neutral including arrangement of 100 Amp MCCB three phase and netural and including street light timer with encloser including fixing arrangement complete all as specified and directed. Make of MCCB - Indo Asian, Schneider, L&T, Havells, C&S
S&F in repairs 8 kW, single phase nature switch for automatic switching on / off street light based on lux level of nature light, consisting of sensor, overload protection fuse gear, power contactor and MCB of suitable capacity, terminal blocks for cable entry & control unit enclosed in pole / wall mountable enclosure made out of rust proof, shock proof, termite proof FR grade SMC, conforming to IP 54, with universal lock and key arrangement complete all as specified and as directed. Make - Swadeep, L&T, Hager, Havells
Description same as per Item no. 34.00 above but 12 kW, Three phase.
ms shrilaxminarayan and sons
Vinayak Trading House
stage.html
html • 0.05 MB
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .