| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | L1₹30.6 LAccepted-AOC 0000 UNNAMED ROAD GAJIYA KANTIT VINDHYACHAL MIRZAPUR UTTAR PRADESH 231307 | MIRZAPUR | UTTAR PRADESH | 231307 | L1 | Accepted-AOC Lowest Bidder | |
| 2 | L2₹37.2 L+₹5.8 L (18.3%)Rejected-Finance | L2 | Rejected-Finance Other than Lowest Bidder | |
| 3 | L3₹42.5 L+₹11.0 L (34.9%)Rejected-Finance | L3 | Rejected-Finance Other than Lowest Bidder | |
| 4 | L4₹48.3 L+₹16.8 L (53.3%)Rejected-Finance | L4 | Rejected-Finance Other than Lowest Bidder |
Tender Value
₹45 L
EMD Value
₹90,000
Closing Date
2 Feb 2023, 6:00 pmClosed
GE Kapurthala
GE Kapurthala
Repair replacement maintenance of street security perimeter lights repair maint and load testing of EOT crane and testing of earthing at Mil Stn Beas and Jandiala Guru under GE Kapurthala
2023_MES_572927_1
GE KPT- /2022-23
Open Tender
Civil Works
Item Rate
270 days
GE Kapurthala
Please refer Tender documents.
8 documents required · 8 mandatory
₹500
Yes
GE Kapurthala
₹90,000
Yes
11 Apr 2023
4 Jan 2023
4 Feb 2023
4 Jan 2023
2 Feb 2023
19 Jan 2023
Amount
Attending of day to day street/security/Gate light/Post top lantern/High mast light fixed at up to 16 mtr height (HPSV,MH,Flourescent tube light, T-5, LED , Flood light fittings etc. of any make), street light panels, rectifying defects in cable, over head conductor/jumper etc and complaints received through telephone or in person and reactification of defects installed on street light poles 9/11 mtr long, building walls, roof by bringing down the fittings on ground or in position including , cleaning of glass/acrylic cover for clear reflection of light, replacement of flexible wire to make the light fitting functional (Vehicle, ladder, tools and takes as required at site for repair/for making light fittings functional shall be provided by the contractor at his own cost and arrangement).Note : (i) Light fitting, and LED drive if required to be replaced in repair shall be measured and paid separetely under relevant item of this BOQ for supply and fixing in replacement. All consumable materials such as tape, flexible wire, nuts, bolts, washer (if found missing), in clamp for bracket, shall be deemed to be included in the quoted rate (ii) contractor will confirm availability of electrician and helper for attending and reactifying the complaints at 2 ASD Depot Area and Bde HQ Area & 415 Engr Sqn Jandiala within 6 hours on receipt of complaints. (iii) contractor manpower should be daily recieve a complaints at complaint cell at 9.00 AM by JE E/M and report after completion of complaints and handover a complaint slip as record of complaints with user signature. (II) Recovery @ 120/- per complaints is not being attended within six hours from intimation by rep of E/M subdivision through or telephonic/digital/ written complaints complete all as specified and directed by Engr-in-Charge.
Taking down old unserviceable any type fitting and Supply and fixing LED street light fitting 35 Watt 230 V AC Raptor NEO street lights are aerodynamically designed for weather conditions with excellent thermal management made with high pressure die cast housing with toughened glass and high power LEDs with secondery optical and IP 66 protection efficiency > 110LPW 10KV SPD included complete all as specified and directed by Engr-in-Charge. Make-Crompton /Havells/Bajaj/Philips.
Taking down old unserviceable any type fitting and Supply and fixing LED street light fitting 60 Watt 230 V AC Raptor NEO street lights are aerodynamically designed for weather conditions with excellent thermal management made with high pressure die cast housing with toughened glass and high power LEDs with secondery optical and IP 66 protection efficiency > 110LPW 10KV SPD included complete all as specified and directed by Engr-in-Charge. Make-Crompton /Havells/Bajaj/Philips.
Taking down old unserviceable any type fitting and Supply and fixing LED street light fitting 70 Watt 230 V AC Raptor NEO street lights are aerodynamically designed for weather conditions with excellent thermal management made with high pressure die cast housing with toughened glass and high power LEDs with secondery optical and IP 66 protection efficiency > 110LPW 10KV SPD included complete all as specified and directed by Engr-in-Charge. Make-Crompton /Havells/Bajaj/Philips.
Taking down old unserviceable any type fitting and Supply and fixing Energy saving LED flood light 70 watts made up of pressure die cast aluminium housing with toughened glass and high pressure LEDs and secondery lenses with IP66 protection system complete fitting including all accessories complete all as specified and directed by Engr-in-Charge. Make-Crompton /Havells/Bajaj/Philips.
Taking down old unserviceable any type fitting and Supply and fixing Energy saving LED flood light 100 watts made up of pressure die cast aluminium housing with toughened glass and high pressure LEDs and secondery lenses with IP66 protection system , efficiency > 110/125LPW 10KV SPD Ccomplete fitting including all accessories complete all as specified and directed by Engr-in-Charge. Make-Crompton /Havells/Bajaj/Philips.
Taking down old unserviceable any type fitting and Supply and fixing Energy saving LED flood light 120 watts made up of pressure die cast aluminium housing with toughened glass and high pressure LEDs and secondery lenses with IP66 protection system , efficiency > 110LPW 10KV SPD Ccomplete fitting including all accessories complete all as specified and directed by Engr-in-Charge. Make-Crompton /Havells/Bajaj/Philips.
Taking down old unserviceable any type fitting and Supply and fixing Energy saving LED flood light 170 watts made up of pressure die cast aluminium housing with toughened glass and high pressure LEDs and secondery lenses with IP66 protection system, efficiency > 110LPW 10KV SPD Ccomplete fitting including all accessories complete all as specified and directed by Engr-in-Charge. Make-Crompton /Havells/Bajaj/Philips.
Supply and fixing in replacement of LED Driver sutable for LED security light Fittings 35 Watt complete all as specified and directed by Engr-in-Charge.
Supply and fixing in replacement of LED Driver sutable for LED security light Fittings 45 Watt complete all as specified and directed by Engr-in-Charge.
Supply and fixing in replacement of LED Driver sutable for LED security light Fittings 60 Watt complete all as specified and directed by Engr-in-Charge.
Supply and fixing in replacement of LED Driver sutable for LED security light Fittings 120 Watt complete all as specified and directed by Engr-in-Charge.
Taking down old unserviceable any type of post top lantern fitting and supply and fixing decorative LED post top lantern 20 watt powder coated aluminium die cast and spun aluminium body with clear/opel diffuser suitable for Landscape lighting available in 5700K CCT IP65 input voltage from 120-270 V power factor above 0.95 complete fitting including all accessories complete all as specified and directed by Engr-in-Charge. Make-Crompton /Havells/Bajaj/Philips.
Taking down old unsv garden light and supply and fixing LED decorative Bollard garden lights suitable for 10 Watt IP65 10 watt in inverted pyramid tropod type LED Bollard with soft 360 light, resistant to corrosion with better optic for uniform distribution complete with all accessories prewired and including connecting up with twin core twisted flexible copper conductor cable complete all as specified and directed by Engr-in-Charge. Make : Havells/ Philips/Bajaj
Supply and install hot dip galvanized steel Octagonal pole 7.0 mtr long, top dia 70 mm & bottom dia 130 mm having thickness 3 mm having door operating of size 500 mm above ground level with CI Base plate of size 200x200x12mm having PCD 200 mm, foundation bolts of size 20 mm dia(04 Nos)600 mm long and having hot dip galvanized double plain arm bracket 1000 mm long overhang with 48.3 mm outer dia pipe of thickness 3.2 mm fixed on top with bolts complete all as specified and directed by Engr-in-Charge. Make : BAJAJ/CROMPTON/HAVELLS Note: PCC and earth work shall be measured and paid seperately
Supply & Fix junction box factory made weather proof size 250mmx200mmx100mm made of 16 gaugesteel sheet powder coated inculded 25mmx6mm aluminium TPN bus bars & 02 MCB 25 Amps for controlled two No's of LED Lights complete all as specified and directed by Engr-in-Charge.
Material & labour for PCC work (1:4:8) type D-2 using 40 mm graded stone aggregate in foundation of electric pole, etc including necessary form work and fare finish to exposed surfaces without using extra cement etc. complete all as specified and directed by Engr-in-Charge.
All as per description of seiral item No 33 here-in-before but PCC (1:2:4) type B-1 using 20 mm graded stone aggregates as in coping of poles complete all as specified and directed by Engr-in-Charge.
Supply and fixing in replacement 1100 volt grade heavy duty cable 3 core 1.50 Sqmm PVC insulated copper stranded conductor passing through in 20 mm PVC pipe of cable size size 1.50 Sqmm for connection pupose of street light fitting from DB to street light fitting, Rate of PVC pipe shall be included in quoted rate by contractor complete all as specified and directed by Engr-in-Charge.
Supplying, laying, jointing and testing under ground XLPE insulated armoured heavy duty electric cable with aluminium conductor 1100 vols grade cross sectional area 300 Sqmm 3.5 core laid in trences, in floor, in duct, through pipes or along the pole including taking down old one complete all as specified and directed by Engr-in-Charge. Make : Havells, Polycab, KEI,Finolex
All as per item ser No 20 above here in before but size 95 sq mm 3.5 core
All as per item ser No 20 above here in before but size 25 sq mm 4 core
All As per item No 20 but cross sectional area 16 Sqmm 4 core.
All As per item No 20 but cross sectional area 16 Sqmm 2 core.
All As per item No 20 but cross sectional area 10 Sqmm 2 core.
Excavation in trenches in soft/loose soil not exceeding 1.50 mtr wide and not exceeding 1.50 mtr in depth for foundation of poles/ stays/ laying of cables etc and getting out including trimming of sides of trenches complete all as specified and directed by Engr-in-Charge.
Returning, filling the soft / loose soil including spreading, leveling watering and well ramming in layers not exceeding 25 cms thick each layer complete all as specified and directed by Engr-in-Charge.
Removing of surplus excavated soil to a distance not exceeding 50 mtr away and depositing where directed at a level not exceeding 1.5 mtr above the starting point complete all as specified and directed by Engr-in-Charge.
Material and labour for sand cushioning to under ground cable with a layer of sand 8 cm thick before laying of cable and 15 cm thick after laying of cable complete all as specified and directed by Engr-in-Charge.
Material and labour for brick protection using old size sub class ‘B’ bricks, laid flat, dry adjacent to each other laid length wise perpendicular to the axis of cable complete all as specified and directed by Engr-in-Charge.
Supply & fixing GI pipe light grade 50 mm bore for cable protection fixed to pole/along wall/floor/under road etc complete all as specified and directed by Engr-in-Charge.
Supply & fixing GI pipe light grade 100 mm bore for cable protection fixed to pole/along wall/floor/under road etc complete all as specified and directed by Engr-in-Charge.
M&L for preparation of old painted surface of Steel tubler Street light poles and applying two coats of synthetic Aluminium paint from top to botom including Light breakets complete all as specified and directed by Engr-in-Charge.
Labour only for cutting/pruning of tree branches 1.5 mtr all around the LT overhead lines of span n.exc 70 mtr and around the pole obstruction the overhead line & removing the branches to distance n.exc 50 mtr to be the entire satisfaction of Engineer-in-charge complete all as specified and directed by Engr-in-Charge.
M&L for Earthing complete with galvanized steel earth plate electrode 60 cm x 60 cm x 6 mm thick surrounded with charcoal and salt, buried directly in ground (earth pit not less than 2.25 metre deep below ground level) with top edge of plate not less than 1.5 metre below normal ground level connected to galvanized earth lead wire 4 mm dia by means of bolts, nuts, check nuts and washers of galvanized iron or steel all as shown in electrical Plate No 3 of MES SSR Part-I connected to main switch board or main control board all as specified and testing on completion including provision of earth wire protected by galvanized iron 15 mm dia light grade pipe and watering pipe shall be 20 mm bore light grade including all excavation and earth work in any type of soil, PCC pit with pre-cast RCC cover, charcoal/salt, funnel etc complete all as specified and directed by Engr-in-Charge.
Supply and fix in replacement of Time light distribution board analog Time switch 230 volt three phase of 16 Amps rating with contactor fixed inside steel enclosure box and fixed to pole/LT Panel including clamps, nuts, bolts and washers etc complete all as specified and directed by Engr-in-Charge. Make Indo-Asian cat part No TL016ABO or equivalent in Legrand/Scheneider
S & F in replacment MCCB 250 Amp, 4 pole, 36 KA 415 Volt 50 Hz with adjustable thermal release and adjustable magnetic setting complete all as specified and directed by Engr-in-Charge. Make : Legrand/ Havell's/ Siemen's/ Schnieder)
S & F in replacment MCCB 200 Amp, 4 pole, 36 KA 415 Volt 50 Hz with adjustable thermal release and adjustable magnetic setting complete all as specified and directed by Engr-in-Charge. Make : Legrand/ Havell's/ Siemen's/ Schnieder)
S & F in replacment MCCB 160 Amp, 4 pole, 36 KA 415 Volt 50 Hz with adjustable thermal release and adjustable magnetic setting complete all as specified and directed by Engr-in-Charge. Make : Legrand/ Havell's/ Siemen's/ Schnieder)
M&L for Servicing , testing,repair and load testing certification of following capacity of cranes including any special T&P required at site complete all as specified and directed by Engr-in-Charge. Note:-(i)Servicing,Testing,repair and load testing certification of cranes to be carried out at MSD Site of 2 ASD by an expert service engineer and necessary load testing certificate to be submitted to Engr-In-Charge duly signed by user by contractor. (ii) Item required for replacement will be measured and paid seperately under this schedule (iii)Load of suitable capacity for testing in one shed shall be provided by the Department and be transported to other shed and again brought back to Intial site is contractors responsibility. Rate quoted by contractor shall deemed to include this provision.
(a) 5 Ton Flame Proof Crane
(b) 10 Ton Flame Proof Crane
Opening the required parts of EOT crane capacity 05/10 Ton for carrying out following repairs/ replacement and reassembling after completion of repair/replacement, testing complete all as specified and directed by Engr-in-Charge.:-
Opening the main gear box used for up-down movement(1 No), left-right movement(3 Nos), thrustor(5 Nos) and cleaning the gear box/thrustor, including testing and setting the gears/parts for proper functioning, complete change/toping up the gear box/thrustor with recommended lubricants and hydraulic brake fluid, replacement of worn out gaskets, Greasing the reduction gear, steel rope , motor bearings with grease gun including set-right and lubrication the all other moving parts of the crane checking and tightning of rope clamps. Note: Lubrication oil for gear box/thrustor will be measured & paid seperately.
Material and labour for replacement of brake shoe liner of the crane complete all as specified and directed by Engr-in-Charge.
M&L for replacement of limit switches with 3&4 contacts in oil tight die cast aluminium housing accurate type with 2 No + 2NC type 3SE 404-OE with normal span action. Make :- Siemens
M&L for replacement of power contactor with 2 NO (normally open) + 2NC (normally colsed) auxillary contacts, rated curent 25A, 110 volt AC
M&L for replacement of power contactor with 2 NO (normally open) + 2NC (normally colsed) auxillary contacts, rated curent 40A, 110 volt AC
M&L for replacement moveable and fix switcing element with fixing parts for 3 RT14 AC-1 duty power contacter Make : Sieimens .
M&L for repair/maintenance of Input /Output interface card (I/O Card) 18 input & 18 out put operating with in built power supply complete all as specified and directed by Engr-in-Charge.
Supply only Grease for lubrication
M&L for repair/maintenance of thruster brake shoe drum hydrolic type of EOT crane capacity 5/10 ton for the smooth functioning of brake system
Opening, taking down the defective flame proof electric motor capacity 10 HP from the platform, transportion to workshop cutting and taking out the burnt winding and rewinding the motor with super enamelled copper winding wire of existing gauge, providing clean insulation, taping,varnishing, replacement of bearings ,re-assembling, transportion and fixing at site including making connection testing and commissioning the complete all as specified and directed by Engr-in-Charge.
Opening, taking down the defective flame proof electric motor capacity 1 HP from the platform, transportion to workshop cutting and taking out the burnt winding and rewinding the motor with super enamelled copper winding wire of existing gauge, providing clean insulation, taping,varnishing, replacement of bearings ,re-assembling, transportion and fixing of site including making connection testing and commissioning the complete all as specified and directed by Engr-in-Charge.
Opening, dismantling and taking down defective FLP/WP electro Hydrolic thrustor with integral motor use on upto 1100 V, 3 PH, 50 Hz with max thrust upto 40 Kg, conducting required repair, including repair/replacement of shaft rode, and taking out the burnt 3 PH motor winding, re-winding the motor with super enamelled copper winding wire of existing guage and reassembling after cleaning and all required repair, filling recommended oil, fixing and making connection, testing and commissioning complete all as specified and directed by Engr-in-Charge.
Attending complaints and rectification of electrical and mechanical defects of EOT Crane of capacity 5/10 Ton and testing after complete all as specified and directed by Engr-in-Charge. Note :- (i) The complaint shall be notified to the contractor by Engr-in-Charge or JE E/M telephonically/personnely or by SMS and recorded in the register maintained for the purpose. Contractor shall make necessary arrangement to attend complaint within 24 hrs failing which penalty @ Rs 1000/ day will be recoverd from contractor for not attending complaint within stipulated time frame. (ii) Cost of any minor nature of repair, replacement of petty items such as nuts, bolts, washers, screws, piece of electric cable upto 0.50 metre length etc is deemed included in the unit rate quoted by the contractor. (iii) Any other major items/repair required for rectification shall be measured and paid seperately under respective item of this schedule.
S & F in replacement Steel wire rope for EOT crane 12mm dia 6x36 constn for heavy duty for lifting load confirming to IS 2266 complete all as specified and directed by Engr-in-Charge.
S & F in replacement Steel Guard wire 4mm dia for supporting suspended controll cable from EOT crane to Remote switch unit complete all as specified and directed by Engr-in-Charge.
Supply & Fixing in replacement of unserviceable Veriable Frequency Drive(VFD) 15 HP ,3 Ph ,415 V (+/- 10%) and speed regulation 1:100 , Speed control accuracy =/- 0.5 % fo raing sychronous speed and taking out the old unserviceable VFD from existing panelcomplete all as specified and directed by Engr-in-Charge. Make: Siemens or Equivalent
Supply & Fixing in replacement of Braking resistors sutiable for Veriable Frequency Drive(VFD)15 HP ,3 Ph ,415 V and taking out the old unserviceable braking resistors complete all as specified and directed by Engr-in-Charge. Make : Siemens or Equivalent
Supply & Fixing in replacement of unserviceable Veriable Frequency Drive(VFD) 5 HP ,3 Ph ,415 V (+/- 10%) and speed regulation 1:100 , Speed control accuracy =/- 0.5 % fo raing sychronous speed and taking out the old unserviceable VFD from existing panel complete all as specified and directed by Engr-in-Charge. Make: Siemens or Equivalent
Supply & Fixing in replacement of unserviceable Veriable Frequency Drive(VFD) 3 HP ,3 Ph ,415 V (+/- 10%) and speed regulation 1:100 , Speed control accuracy =/- 0.5 % fo raing sychronous speed and taking out the old unserviceable VFD from existing panel complete all as specified and directed by Engr-in-Charge. Make: Siemens or Equivalent
M & L for taking down unserviceable Veriable Frequency Drive(VFD) 3 Ph ,415 V of any capacity/Make, from control panel and transportation to workshop and back, re-fixing, testng and cummissioning complete after necessary repair /replacement of following items as required complete all as specified and directed by Engr-in-Charge.
(a) Power Supply card 440 V, 31/35A
(b)VFD IGBT Module
Supply & Fixing in replacement of Input /Output interface card (I/O Card) 18 input & 18 out put operating with in built power supply complete all as specified and directed by Engr-in-Charge.
Supply & install in replacement of transformer 440v/110v , 2 KVA and taking out the unserviceable transformer from existing panel complete all as specified and directed by Engr-in-Charge.
Supply & Fill Oil for the thustor is transformer oil to IS: 335-1983 (EHV Grade) or equivalent complete all as specified and directed by Engr-in-Charge.
Supply & Fill Oil Grade EP 140 for gear box model 3510HNG & 320CT complete all as specified and directed by Engr-in-Charge.
Supply & fill Oil Grade ISO VG220 for gear box Type: G33-10-SN complete all as specified and directed by Engr-in-Charge.
M&L pendent push button for controlling all motions ie, start/Stop/ Reset/hoist/micro speed/long travel/ cross travel motions of EOT crane of capacity 10/5 Ton from floor level complete all as specified and directed by Engr-in-Charge.
S&F in replacement PVC insulated PVC sheathed cable copper conductor 6 Sqmm 4 core, multistranded FRLS round type fixed for EOT crane complete all as specified and directed by Engr-in-Charge. Make : Plaza/ICC/Havells/Rallison
S&F in replacement PVC insulated PVC sheathed cable copper conductor 2.5 Sqmm 3 core, multistranded FRLS round type fixed for EOT crane complete all as specified and directed by Engr-in-Charge. Make : Plaza/ICC/Havells/Rallison
S&F in replacement PVC insulated PVC sheathed cable copper conductor 1.5 Sqmm 4 core, multistranded FRLS round type fixed for EOT crane complete all as specified and directed by Engr-in-Charge. Make : Plaza/ICC/Havells/Rallison
S&F in replacement PVC insulated PVC sheathed cable copper conductor 1.5 Sqmm 2 core, multistranded FRLS round type fixed for EOT crane complete all as specified and directed by Engr-in-Charge. Make : Plaza/ICC/Havells/Rallison
S&F in replacement PVC insulated PVC sheathedmulti core cable copper conductor 1.5 Sqmm 19 core, multistranded FRLS round type fixed for EOT crane complete all as specified and directed by Engr-in-Charge. Make : Plaza/ICC/Havells/Rallison
Supply and fix in replacement cable jointing kit for 1.1 KV grade cable for straight through joint complete with Jointing material (Epoxy Based) and accessories suitable for 3½/ 4 core XLPE armoured Al conductor cable of size 70 to 95 sq mm indoor/outdoor type complete all as specified and directed by Engr-in-Charge.
-do- but for cable of size 300 Sq mm
M & L for cleaning the earth pit by removing mud/soil etc from any type of earth pit as required at site and removing rust from the aluminium/copper strip and taking reading of earth resistance by using good quality earth resistance machine and preparing of test results in prescribed format all as directed by Engr in Charge. Each earth pit result to be submitted to Engr-in-Charge duly signed by user and MES rep. Note : EP No should be mentioned on indivudual earth pits and ER value of installation etc complete all as specified and directed by Engr-in-Charge.
M&L for repairing earth pit such as brick/PCC/Plastering work etc as required at site, complete all as specified and directed by Engr-in-Charge.
M & L for earth continuity conductor or main earthing lead fixed to wall on batten or chases or buried in ground or drawn in conduit /pipe or fixed to poles or any other indicated situation for loop earthing etc as required, 25x3mm copper strip complete all as specified and directed by Engr-in-Charge.
Supply and fixing GI strip 32 x 6mm thick as earthing lead fixed to wall/roofs etc complete all as specified and directed by Engr-in-Charge.
Supply and fixing Aluminium strip 25 x 3mm with saddles and fixing screws etc. for roof conductors and down conductors above ground complete all as specified and directed by Engr-in-Charge.
S&F epoxy base insulators of suitable size 40mm height for fixing GI earth strip on wall/ceiling/floor/poles etc complete all as specified and directed by Engr-in-Charge.
Taking out and refixing only copper strip 25 x3mm thick as earthing lead fixed to wall/roofs etc drawn in conduit/GI pipe etc complete all as specified and directed by Engr-in-Charge.
Taking out and refixing only Aluminium strip 25 x 3mm thick as earthing lead fixed to wall/roofs etc drawn in conduit/GI pipe etc complete all as specified and directed by Engr-in-Charge.
Taking out and refixing only Aluminium strip 25 x 3mm thick as earthing lead fixed to wall/roofs etc drawn in conduit/GI pipe etc complete all as specified and directed by Engr-in-Charge.
M&L earth test point terminal block made of gun metal or phosphorus bronze size 75x75x25mm drilled and screwed including 3 nos. 8mm dia 25mm long hex. head screw and GI bolts, nuts and washers complete all as specified and directed by Engr-in-Charge.
Supply and spread common salt commercial in trenches to improve the ER value of existing earth pits complete all as specified and directed by Engr-in-Charge. (Note : Excavation and earth work shall be measured and paid separetly)
Supply and spread charcoal dust/Breeze in trenches to improve the ER value of existing earth pits complete all as specified and directed by Engr-in-Charge. (Note : Excavation and earth work shall be measured and paid separetly)
Excavation in existing earth pit and spreading Common Salt, Charcoal dust and Magnesium sulfate complete all as specified and directed by Engr-in-Charge. (Common Salt, Charcoal dust and Magnesium sulfate shall be measured in relevant item of schedule)
Supply and fixing PCC earth chamber 1:3:6, RCC1:2:4 cover slab with 6mm dia TMT bar ,100mm c/c,MS bar lifting hook including replacement of rusted watering pipe 20mm bore light grade, UNSV GI funnel with wire mesh complete all as specified and directed by Engr-in-Charge.
Earthing with copper Earth Plate Electrode 600x600x3.15mm thick burried directly in Ground (Earth Pit not less than 2.25 Metre below Ground Level) with Top edge of the Plate not less than 1.50 Metre below Ground Level, connected with copper Earth Strip of size 20x3mm by means of Bolts, Nuts, Check Nuts and Washers of copper and connected Earthing Testing Point/Bus-bar including GI 40mm bore (dia) light grade Protection Pipe, Earth Plate surrounded by a packed thickness of Char Coal or Coke Dust mixed with Common Salt, Magneisum Sulphate (1 : 1 : 0.5) in alternate layers of not exc 150mm thick, PCC Pit in Cement Concrete 1:3:6 (20mm graded stone aggregate) and Pre-cast RCC Cover Slab of size 350x350x50 mm in Cement Concrete 1:2:4 (20mm graded stone aggregate), reinforced with 10mm dia TMT Bars @ 100mm Centre to Centre in both ways, GI Wire Mesh, Funnel with GI Watering Pipe 20mm bore (dia) medium grade including necessary Excavation in any type of soil, Returning, Filling in and Removal of surplus Spoil disposal to out side MD land and all as shown in Electrical Plate No. 3 of MES Schedule Part-I and Testing on Completion including taking down old unserviceable one complete all as specified and directed by Engr-in-Charge.
Earthing with Galvanised Earth Plate Electrode 600x600x 6mm thick burried directly in Ground (Earth Pit not less than 2.25 Metre below Ground Level) with Top edge of the Plate not less than 1.50 Metre below Ground Level, connected with GI Strip of size 32x 6 mm by means of Bolts, Nuts, Check Nuts and Washers of GI or steel and connected Earthing Testing Point/Bus-bar including GI 40mm bore (dia) light grade Protection Pipe, Earth Plate surrounded by a packed thickness of Char Coal or Coke Dust mixed with Common Salt, Magneisum Sulphate (1 : 1 : 0.5) in alternate layers of not exc 150mm thick, PCC Pit in Cement Concrete 1:3:6 (20mm graded stone aggregate) and Pre-cast RCC Cover Slab of size 350x350x50 mm in Cement Concrete 1:2:4 (20mm graded stone aggregate), reinforced with 10mm dia TMT Bars @ 100mm Centre to Centre in both ways, GI Wire Mesh, Funnel with GI Watering Pipe 20mm bore (dia) medium grade including necessary Excavation in any type of soil, Returning, Filling in and Removal of surplus Spoil disposal to out side MD land and all as shown in Electrical Plate No. 3 of MES Schedule Part-I and Testing on Completion including taking down old unserviceable one complete all as specified and directed by Engr-in-Charge.
DUGGAL CONSTRUCTION CO
PAWAN KUMAR GOVT. CONTRACTORS
AGGARWAL ENGINEERING CO
stage.html
html • 0.05 MB
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .