Loading…
Loading…
| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | L1₹1.3 LAccepted-Finance | L1 | Accepted-Finance TECHNICALLY AND FINANCIALLY QUALIFIED | |
| 2 | L2₹1.9 L+₹52,700 (39.7%)Accepted-Finance | L2 | Accepted-Finance TECHNICALLY AND FINANCIALLY QUALIFIED |
Tender Value
₹1.9 L
EMD Value
₹3,880
Closing Date
28 Oct 2022, 3:00 pmClosed
EX. ENGINEER KPDCL DIV.SPN
OFFICE OF THE EX. ENGINEER KPDCL DIV.SPN NEAR DEGREE COLLEGE SHOPIAN
Installation of 01 No. 11 KV HT Tri-Vector Meter CT and PT operated for Oxygen plant and Sub-District Hospital Zainapora
2022_PDD_192623_1
EDS/eTENDER/56 OF 2022-23 DATED 17-10-2022
Open Tender
Electrical and Maintenance Works
Turn-key
30 days
UNDER THE JURISDICTION OF KPDCL DIVISION SHOPIAN
PLEASE REFER TO SBD
7 documents required · 7 mandatory
₹510
Yes
EX. ENGINEER KPDCL DIV.SPN
₹3,880
Yes
31 Oct 2022
17 Oct 2022
29 Oct 2022
17 Oct 2022
28 Oct 2022
18 Oct 2022
18 Oct 2022 - 18 Oct 2022
Amount
11 KV Pilfer resistant metering cubicle for 3 Phase 4 wire metering system made of MS sheet steel thickness not less than 2mm duly power coat painted suitable for indoor as well as outdoor as per the site requiremnet. The cubicle shall be painted through 7-tank process. The external dimensions hsould be adequate. Pannel having two compartments-upper meter compartment and lower CT/PT compartment, provided with synthetic or semisynthetic gasket firmly glued to the surface, dust, weather & vermin proof and shall comply degree of protection as per IP65. Both the chambers having one sided hinged door arrangements. The metering panel shall be provided with two no. MS channels of size 100*50 mm on the front and rear sides duly welded and 4 No. of lifting hooks. It should be possible to take meter reading manually, through CMRI and computer without opening the LV Chamber
Single Phase, Single Core, epoxy resin cast Current Transformers suitable for 11 KV copper wound primary type with rated burden 5VA and accuracy class 0.5 or better and confirming to IS2705 (Part I&II) aamended upto date. ISF shall be upto 5. The CT ratio shall be as under: i. 2.5/5 for 25 KVA DT ii. 5/5 for 63 KVA DT iii. 7.5/5 for 100 KVA DT iv. 15/5 for 200 KVA DT v. 20/5 for 250 KVA DT vi. 25/5 for 400 KVA DT vii. 50/5 for 630 KVA DT viii. 75/5 for 1 MVA DT
11 KV/110V three phase epoxy resin cast PT with rated burden 15 VA per phase and accuracy class 0.5 or better and confirming to IS3156 (Part I&II) amended upto date with proper colour coded identification. PTs shall be of uniform insulating and withstand separate source 23 KV pf for one minute.
Bus bar details: CTs bus bar: 40*6 mm copper strip or adequate site PTs bus bar: copper wire 8 SWG or 30*0.6 mm copper flat strip to connect PT terminal or adequate size duly insulated by the monoplast tape.
PVC Copper wire flexible multi-strand of required size for secondary connections for CT wiring the minimum wire size shall be 4 sq.mm (RYB) and for PT wiring minimum wire size shall be 2.5 sq.mm (RYB)
Copper Lugs preferably ring type duly crimpled for termination of wires and tapes
Grounding bus of minimum 40 mm copper, 25 cm long fixed to the unit in HV chamber. The CTs, PT meter and 11 KV Cable sheath shall be grounded to the bus through grounding wire (green) of min size 10 sq.mm
3 Ph 3 Wire HT CT/PT operated fully static smart Tri-vector energy meter DLMS compliant category C with RS232 port for modem compatibility. 11 KV /110 V ph-ph (3Ph 3 Wire) meters for measurement of different electrical parameters including active energy (KWh/MWh) Reactive Energy (KVArh/MVArh), apparent energy (KVAh/MVAh) etc (make L&T, Secure, AA)
Independent flexible PVC pipes for CT wiring and PT wiring of appropriate size from HT compartment to meter compartment
Pedestal made out of MS channel of size 75*40 mm or angle iron of size 65*65*5 mm duly painted as per site requirements for mounting of metering panel including concrete forundation whereever required including cost of nuts and bolts
3 Core 11 KV Aluminium cable XLPE armoured 35 sq.mm including cost of clamp for its fixing whereever required
Cable termination kits suitable for 3 x 35 mm2 XLPE Cable (indoor/outdoor)
Earthing by wayof 40 mm GI Pipe earthing . Job includes , excavation, enhancement materail and Main Hole Chamber (500x450x600) with frame and cover.
Identification of assets by marking of Transformer with white paint & marking of poles with Black paint at a height of 2.40 mtr from ground level. (Note : Mention Name of Scheme , Implementing Agency (JKPDD), Year of Implementing (2021-22)
Geo Tagged Photographs of high resolution (Pre and Post Photographs) Both hard and soft copy (for e-compendium) 4 Photographs Per site
Global Engineering Services
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .