| Sl No | Description | Qty | Unit | M/s Prakash Enterprises L5 | Commercial Traders L6 | M/S S.K.Electricals L2 | M/S Delhi Engineering Co. L1 | A B K Enterprises L4 | SANWARIYA ENTERPRISES L3 | PARAS ENTERPRISES L9 | Ruchi enterprises L8 | YANSHIKA SECURITY SERVICES L7 |
|---|---|---|---|---|---|---|---|---|---|---|---|---|
| 1.00 | Finding out, locating and pin point the cable fault of any size and any capacity of cable from LT 1100 volt grade to 33000V with the help of cable fault loacator and with nessary disconnection of cable from two ends and connection after repairs and having the following items with electrician at site up to lenth of 1 KM cable complete all as specified and directed by Engr-in-Charge :-
(a) Surge Generator with accessories-01 Nos, (b) Head Phone-01 Nos , (c) Pin Point Set T-505 with accessories-01 Nos, (d) Earthing cable with clamp-01 set, (e) Cable fault Locator T-905 with accessories-01 Nos, (f) TC-808 with accessories-01 Nos, (, g) Soldering Iron-01 Nos, (h) Soldering wire-01 Nos, (j) Plier-01 Nos, (k) Soldering paste-01 Nos, (l) Capacitor Unit-01 Nos,
(m) Capacitor connecting cables-01 Nos, (n) Power cable-01 Nos, (o) Nose Plier-01 Nos, (p) Card for SSG-1100-01 Nos
Note :- Transportation charges for shifting of cable fault locator will deem to be include in above said job and nothing extra on this account will be admissible.
(ii ) The area of this contract is very critical for safety reason so as to contractor has to arrange 24X7 hours fault locating machine and jointing kit when fault occurs and when denied by the contractor, double of quoted rate as panelty will be imposed by Engineer-in-Charge .
(iii) Fault to be located within 3 hours of report failing which penality @ Rs. 1000/- per hour to be charged for delay. | 18 | Each Job | 5,000 ₹90,000 | 2,500 ₹45,000 Lowest | 5,000 ₹90,000 | 5,500 ₹99,000 | 5,000 ₹90,000 | 5,600 ₹1,00,800 | 5,500 ₹99,000 | 7,000 ₹1,26,000 | 9,000 ₹1,62,000 |
| 2.00 | M&L for rewinding of burnt out HT/LT coils of transformer of capacity 100 KVA to 1500 KVA with super enamelled copper winding wire of existing gauge and proper number of turns alongwith insulating material i.e leatheroid, paper insulation, cotton tapes, empire tapes, wooden block packings, PVC sleeves, soldering and varnishing with insulating varnish , colding/drying etc complete all as specified and directed. | 300 | Kg | 1,200 ₹3,60,000 | 720 ₹2,16,000 | 900 ₹2,70,000 | 625 ₹1,87,500 | 600 ₹1,80,000 Lowest | 622 ₹1,86,600 | 1,200 ₹3,60,000 | 1,500 ₹4,50,000 | 900 ₹2,70,000 |
| 3.00 | Taking down/dismantling and refixing of any capacity of transformer by using Hydra mechine/suitable crane complete and including tranportation shifting to approved manufacturer/Workshop including testing and commissioning all as directed.
Note- Dismantling and disconnecting HT cable and LT cables and refixing after rewinding and Transportation from 13 BRD to Workshop and workshop to 13 BRD will be paid as one job | 1 | Each Job | 5,000 ₹5,000 | 5,000 ₹5,000 | 7,000 ₹7,000 | 7,000 ₹7,000 | 5,000 ₹5,000 | 7,088 ₹7,088 | 25,000 ₹25,000 | 25,000 ₹25,000 | 2,500 ₹2,500 Lowest |
| 4.00 | Disconnecting of all electric connection of defective distribution transformer 11/0.433 KV outdoor /indoor type , Opening top cover of transformer , taking out insulating oil upto lower level of bushing and keeping in clean & dry container (oil to be reused) for replacement of HT/LT Bushing , gaskets etc incuding refixing the same and refilling the drained out transformer oil complete, reconnection etc complete all as specified and directed
Note :- Spare part and repair will be measured and paid for separately. | 12 | Each Job | 500 ₹6,000 Lowest | 2,500 ₹30,000 | 2,100 ₹25,200 | 2,000 ₹24,000 | 2,000 ₹24,000 | 2,077 ₹24,924 | 1,520 ₹18,240 | 4,000 ₹48,000 | 1,500 ₹18,000 |
| 5.00Replacement of breather assembly of approved make filled with silica gel suitable for transformers of following capacity :- | ||||||||||||
| 5.10 | 100 KVA to 200 KVA | 5 | Each | 500 ₹2,500 Lowest | 800 ₹4,000 | 500 ₹2,500 Lowest | 500 ₹2,500 Lowest | 500 ₹2,500 Lowest | 501 ₹2,505 | 5,500 ₹27,500 | 900 ₹4,500 | 1,500 ₹7,500 |
| 5.20 | 300 KVA to 400 KVA | 2 | Each | 500 ₹1,000 Lowest | 1,200 ₹2,400 | 600 ₹1,200 | 500 ₹1,000 Lowest | 600 ₹1,200 | 501 ₹1,002 | 5,500 ₹11,000 | 900 ₹1,800 | 1,500 ₹3,000 |
| 5.30 | 500 KVA to 630 KVA | 4 | Each | 500 ₹2,000 Lowest | 2,300 ₹9,200 | 700 ₹2,800 | 500 ₹2,000 Lowest | 800 ₹3,200 | 501 ₹2,004 | 5,500 ₹22,000 | 1,200 ₹4,800 | 1,500 ₹6,000 |
| 5.40 | 1500 KVA | 1 | Each | 500 ₹500 Lowest | 2,500 ₹2,500 | 800 ₹800 | 500 ₹500 Lowest | 1,000 ₹1,000 | 501 ₹501 | 8,500 ₹8,500 | 2,000 ₹2,000 | 1,500 ₹1,500 |
| 6.00Replacement of brass spindle for terminal on HT side threaded complete with nut, washers etc of suitable dia for transformers of tollowing capaicty :- | ||||||||||||
Tender Value
₹30.0 L
EMD Value
₹60,000
Closing Date
18 Jul 2025, 6:00 pmClosed
CWE (AF) Tughlakabad
HQ CWE AF TUGHLAKABAD AF STATION, TUGHLAKABAD PO SANGAM VIHAR NEWDELHI-110080
REAPIR MAINT OF HT ELECTRIC SUPPLY NETWORK SYSTEM HT EQUIPMENT TRANSFORMER AND OTHER ALLIED WKS AT 13 BRD AND 16 BRD UNDER GE (AF) GURGAON NO1
2025_MES_716589_1
CWE/TKD/GUR/TOKEN-31 OF 2025-26
Open Tender
Electrical and Maintenance Works
Item Rate
180 days
GE (AF) Gurgaon No 1
AS PER NIT CONDITION
7 documents required · 7 mandatory
₹0
₹60,000
9 Oct 2025
25 Jun 2025
21 Jul 2025
25 Jun 2025
18 Jul 2025
9 Jul 2025
Amount
Finding out, locating and pin point the cable fault of any size and any capacity of cable from LT 1100 volt grade to 33000V with the help of cable fault loacator and with nessary disconnection of cable from two ends and connection after repairs and having the following items with electrician at site up to lenth of 1 KM cable complete all as specified and directed by Engr-in-Charge :- (a) Surge Generator with accessories-01 Nos, (b) Head Phone-01 Nos , (c) Pin Point Set T-505 with accessories-01 Nos, (d) Earthing cable with clamp-01 set, (e) Cable fault Locator T-905 with accessories-01 Nos, (f) TC-808 with accessories-01 Nos, (, g) Soldering Iron-01 Nos, (h) Soldering wire-01 Nos, (j) Plier-01 Nos, (k) Soldering paste-01 Nos, (l) Capacitor Unit-01 Nos, (m) Capacitor connecting cables-01 Nos, (n) Power cable-01 Nos, (o) Nose Plier-01 Nos, (p) Card for SSG-1100-01 Nos Note :- Transportation charges for shifting of cable fault locator will deem to be include in above said job and nothing extra on this account will be admissible. (ii ) The area of this contract is very critical for safety reason so as to contractor has to arrange 24X7 hours fault locating machine and jointing kit when fault occurs and when denied by the contractor, double of quoted rate as panelty will be imposed by Engineer-in-Charge . (iii) Fault to be located within 3 hours of report failing which penality @ Rs. 1000/- per hour to be charged for delay.
M&L for rewinding of burnt out HT/LT coils of transformer of capacity 100 KVA to 1500 KVA with super enamelled copper winding wire of existing gauge and proper number of turns alongwith insulating material i.e leatheroid, paper insulation, cotton tapes, empire tapes, wooden block packings, PVC sleeves, soldering and varnishing with insulating varnish , colding/drying etc complete all as specified and directed.
Taking down/dismantling and refixing of any capacity of transformer by using Hydra mechine/suitable crane complete and including tranportation shifting to approved manufacturer/Workshop including testing and commissioning all as directed. Note- Dismantling and disconnecting HT cable and LT cables and refixing after rewinding and Transportation from 13 BRD to Workshop and workshop to 13 BRD will be paid as one job
Disconnecting of all electric connection of defective distribution transformer 11/0.433 KV outdoor /indoor type , Opening top cover of transformer , taking out insulating oil upto lower level of bushing and keeping in clean & dry container (oil to be reused) for replacement of HT/LT Bushing , gaskets etc incuding refixing the same and refilling the drained out transformer oil complete, reconnection etc complete all as specified and directed Note :- Spare part and repair will be measured and paid for separately.
Replacement of breather assembly of approved make filled with silica gel suitable for transformers of following capacity :-
100 KVA to 200 KVA
300 KVA to 400 KVA
500 KVA to 630 KVA
Replacement of brass spindle for terminal on HT side threaded complete with nut, washers etc of suitable dia for transformers of tollowing capaicty :-
100 KVA to 200 KVA
300 KVA to 400 KVA
500 KVA to 630 KVA
All as per item No 06 here-in-before but for LT side of transformers of folliwing capacity :-
100 KVA to 200 KVA
300 KVA to 400 KVA
500 KVA to 630 KVA
Replacement of ceramic bushing with Gasket on LT side of transformers of following capacities. Make : Mysore Potteries/BHEL
100 KVA to 200 KVA
300 KVA to 400 KVA
500 KVA to 630 KVA
All as per item No 08 above, but on HT side of transformer of following capacites :-
100 KVA to 200 KVA
300 KVA to 400 KVA
500 KVA to 630 KVA
Replacement of arc horn surge arrester complete with amounting ring, nut bolt etc of approved make suitable for transformers of following capacity :-
100 KVA to 200 KVA
300 KVA to 400 KVA
500 KVA to 630 KVA
Dehydration/filtration of transformer/STABILIZER oil by means of centrifugal filtration plant to achieve the specified dielectric strength of 40 KV at 2.5 mm gap in existing position of transformer/stabilizer of any capacity and transformer oil for topping up at various sub station complete all specified and as directed. Note: Transformer oil for TOP UP shall be measured and paid separately under respective item of this schedule
Supply only transformer oil of approved quality (Dielectric strength not less than 40 KV) ISI marked for filling in transformer for topping up all as directed by Engr-in-Charge. Note : Factory sealed container of transformer oil will be accepted.
M&L for painting of transformer after cleaning the body surface of transformer by rubbing with emery paper to remove oil stains, dust etc and applying two coat of snthetic enamel paint by spray paint incl writing SM No/MES No , capacity of transformers of following capacity all as directed by Engr-in-Charge. Note :- The contractor has to arrange their own local generator for supply to the spray painting machine.
100 KVA to 200 KVA
300 KVA to 400 KVA
500 KVA to 630 KVA
Supply and fix top cover gaskets of any size Transformer of any capacity after taking down unserviceable gaskets from the top cover of transformer complete all as specified and directed.
M&L for replacement of Off load tap changer of Transformer Rating from 100 KVA to 500 KVA as per the existing make of transformer complete all as specified and directed.
Material and Labour for synthetic insulation mat confirming to IS 15652/2006, 2.5 mm thick, suitable for 11 KV substation all as specified and as directed. Make: Jyothi or Safevolt or Burhani associate.
Caliberation of Micro processor based numerical relay by conducting primary injection on rescpective CTs and secondary injection tests on relays,checking of current transformer including CTR Ratio, IR Value, CT Secondary Resistance Measurement Test, rectifiation of defects in control wiring for proper tripping of circuit breakers through CTs, relays and tripping coils,adjustment/setting of the relay to restrict fault to upstream breakers,re-installation of the relay in circuit complete all as specified and as directed. NOTE:- (a) The contractor shall provide necessary testing kits, testisng equipments,tools etc and shall also prepare the detailed test reports panel wise duly bound and submit to the department. Rate for the kits and equipment is deemed to be included in rate quoted. Testing and turning shall be carried out in the presence of Engineer-in-Charge to the satisfaction of department, failing which payment for the above item will not be made to the contractor. No claim from the contractor be enterained on this account. (b) Rate is inclusive of setting the parameters in differential relay and connecting after carrying out necessary polarity tests etc (C) This item includes all routine test of VCB for proper tripping in case of fault and tripping time should be set lesser than GE (U) Delhi Sekhawati Grid end so as to fault will not feed back to GE (U) Delhi Sekhawati Grid . The contractor has to collect the data of tripping time from GE (U) Delhi Sekhawati Grid and tripping time should be set lesser timing in our end. All control wiring of VCB should be cleaned and serviced and change the unserviceable part as per directed by Engr-in-Charge. The u/s item will be paid sepeartely. (d) Contractor will take the prior permission for shutdown of HT Line in written at least one week in advance for getting permission from user by MES to avoid any administration issue. Note- The test should be done be authorised dealer of VCB.
Taking down the HT vacuum circuit breaker of capacity up to 800A, of any make, 11 KV, for servicing and re-assembling complete, comprising of the following including testing and commissioning to the entire satisfaction of Engineer-in-Charge. Note: Quoted rate is inclusive for the following services:- (i)Taking out the VCB from the enclosure & checking the serviceability of the following parts carefully including cleaning, adjustments and re-assembling the unit complete. (ii) Cleaning the external surface of bushings with CTC/CRC to remove the accumulation of dirt or any other deposits. Inspection of bushings and make sure that vibration due to breaker operation have not caused the bushings to move resulting misallignment of contacts. (iii) Checking the breaker bushing of bus bar and circuit side inspecting the interval surface carefully for any charging/trackings,replacement of bushings. (iv) Dismantling the spring charging mechanism of the VCB, checking the operations of the closing/tripping trough closing/tripping coils electrically as well as manual charging including cleaning adjustments complete for the following. (v) Checking the condition of the spring charging motor along with gear box including servicing to the motor commulator bushes, lubrication of bearing surfaces etc. (vi) Cost of additional hardware like, bolts, nuts , washers and spring washers, petrolium jelly ctc, to put the breaker in serviceable condition is deemed to be included in the rates quoted. (vii) Making functional by carrying out minor repairs all the non functional circuits and indicating system like VCB Trip, CB ON, CB OFF, CB Service, Spring Charging etc (viii) Test shall include IR, CRM and time Test. (ix) Contractor will take the prior permission for shutdown of HT Line in written at least one week in advance for getting permission from user by MES to avoid any administration issue. Note : The u/s item will be paid sepeartely. Note- The test should be done be authorised dealer of SF6.
Replacement of TCS Relay, suitable for 11 KV VCB complete with necessary electricial connection complete all as specified and directed. Make : L&T/Crompton/Ashida
Replacement of 11 KV CTs Dual Core , Dual Ratio 100/5+5, Class 0.5 and 5P10 suitable for 11 KV VCB complete with necessary electricial connection complete all as specified and directed.
Replacement of TNC switch, suitable for 11 KV VCB complete with necessary electricial connection complete all as specified and directed.
Replacement of Delco make Spring Charging motor of capacity 20 V to 30 V DC, suitable for 11 KV VCB complete with necessary electricial connection complete all as specified and directed.
Replacement of Big Gear, Small Gear and & Half Gear Set assembly suitable for VCB 11 KV complete with all mechanical connection complete all as specified and directed.
Replacement of Motor charged mechanasim assembly and charging handle suitable for VCB 11 KV, with all mechanical connection complete all as specified and directed.
Replacement of LED indicatorrs suitable for 11 KV VCB complete with necessary electricial connection complete all as specified and directed.
Replacement of Push Button suitable for 11 KV VCB complete with necessary electricial connection complete all as specified and directed.
Replacement of Vaccum Interrupter suitable for 11 KV VCB complete with necessary electricial and mechanical connection complete all as specified and directed.
Replacement of Housing for Vaccum Interrupter suitable for 11 KV VCB complete with necessary electricial and mechanical connection complete all as specified and directed.
Replacement of Hooter suitable for 11 KV VCB complete with necessary electricial and mechanical connection complete all as specified and directed.
Replacement of trivector meter suitable for 11 KV VCB complete with necessary electricial and mechanical connection complete all as specified and directed. Make : L&T Cat No WR-300BC52RS or equivallent.of Secure/HPL
Replacement of Insulator 60x130 suitable for 11 KV VCB complete with necessary electricial and mechanical connection complete all as specified and directed.
Replacement of Insulator 75x130 suitable for 11 KV VCB complete with necessary electricial and mechanical connection complete all as specified and directed.
Replacement of Spout suitable for 11 KV VCB complete with necessary electricial and mechanical connection complete all as specified and directed.
Replacement of Jaw Contact suitable for 11 KV VCB complete with necessary electricial and mechanical connection complete all as specified and directed.
Replacement of HRC Fuse 6A/10A suitable for 11 KV VCB complete with necessary electricial and mechanical connection complete all as specified and directed.
Replacement of 11 KV PT Fuse 6A/10A suitable for 11 KV VCB complete with necessary electricial and mechanical connection complete all as specified and directed.
Replacement of HRC Fuse holder suitable for 11 KV VCB complete with necessary electricial and mechanical connection complete all as specified and directed.
Replacement of Auxiliary switch suitable for 11 KV VCB complete with necessary electricial and mechanical connection complete all as specified and directed.
Replacement of 32 way pin plug and socket suitable for 11 KV VCB complete with necessary electricial and mechanical connection complete all as specified and directed.
Replacement of space heater suitable for 11 KV VCB complete with necessary electricial and mechanical connection complete all as specified and directed.
Replacement of thermostate suitable for 11 KV VCB complete with necessary electricial and mechanical connection complete all as specified and directed.
Replacement of Limit Switch suitable for 11 KV VCB complete with necessary electricial and mechanical connection complete all as specified and directed.
Replacement of closing/triping coil suitable for 11 KV VCB complete with necessary electricial and mechanical connection complete all as specified and directed.
Replacement of Anti Pumping device suitable for 11 KV VCB complete with necessary electricial and mechanical connection complete all as specified and directed.
Material and Labour for decarbonsing/cleaning the cable compartment of Ring Main Unit 3 Way, 11 KV, consists of End joints,Current transformers, cable boots, bushings, by opening compartment cover by carefully switching off the main input cable supply and necessary switching ON of Earth switch of RMU thereby inspecting the end joints, current transformer, bushings and cable boots, checking the bushings for any flash overs/tracks, applying Becktol red solution to the bushings having moderate tracking, applying suitable HT insulated tape over anti tracking tube to prevent further tracking on, cleaning of end joints, CTs & cable boots with CTC and ensure proper decarbonisation and re-assembling complete all as directed by Engineer-in-Charge.
Replacement of of Contactor RT - 24VDC, suitable for RMU 11 KV including necessary electrical and mechanical connection complete all as specified and as directed.
Replacement of of Close Push button, suitable for RMU 11 KV, ncluding necessary electrical and mechanical connection complete all as specified and as directed.
Replacement of of Open push button, suitable for RMU 11 KV, ncluding necessary electrical and mechanical connection complete all as specified and as directed.
Replacement of of Operating handle Standard, suitable for RMU 11 KV, ncluding necessary electrical and mechanical connection complete all as specified and as directed.
Supply and fix in replcement battery bank of capacity 24 V, consisting of (12 Nos) of 02 Volts Each 70 AH maintenance free "exide" make for system voltage 24 V, including disconnection of old U/S Battery bank complete all as specified and directed by Engr-in-Charge.
M&L for replacement of U/S DC Power pack with battery back up complete enclosed in a sheet metal enclosures size not less than 2mm thick duly compartmentlise for battries, charging system and control system with LED indicator lamps and toggle switch and push button ON/OFF system for charging, discharging etc as per requirement , front openable and lockable with proper ventilaation as per latest IS, suitable for supply of 24 volt DC 30 AH duly banked with 2 volt LED acid maintenance free battries including float and trickle battery charging system suitable for input single phase 220 volt/3 phase 440 volt 50 Hz AC supply including all electrical and control connection upto existing socket for charging and DC Supply to the existing VCBs upto 2 Nos. The connection of incomming and outgoing battery bank to VCBs willl be made by stranded copper conductor size not less than 2.5 sqmm for each core in case of multi core cable or single core cable PVC insulated unscoldhed cable duly drawn into medium grade PVC conduit on floor/wall complete all as specified and as directed. Location- Substation-1
Replacement of 11 KV PTs, 110V, Class 0.5, 1 phase suitable for 11 KV VCB complete with necessary electricial connection complete all as specified and directed.
Excavation in trenches n.exc 1.5 mtr wide and n.exc 1.5 mtr in depth and getting out hard/dense soil complete all as specified and as directed for foundation of stay, laying of cable etc.complete all as specified and directed.
Excavation in trenches n.exc 1.5 mtr wide and n.exc 1.5 mtr in depth and getting out soft/loose soil complete all as specified and as directed for foundation of stay, laying of cable etc.complete all as specified and directed.
Returning filling in soil including spreading, levelling, watering and well ramming in layers not exc 25 cm complete all as specified and directed.
Removing excavated material soil n.exc 50 m and depositing where directed at a level n.exc 1.5 mtr above the starting point all as directed.
Supply and laying reinforced precast concrete cable cover, class HV,type 1,flat ,size 300 mm X 180mm X 40 mm of approved make complete all as specified and as directed.
Re-laying/re-routing serviceable reinforced precast concrete cable cover, class HV,type 1,flat ,of any size obtained from from item No. (a) here-in-beforecomplete all as specified and directed.
M&L for sand filling in trenches for cushioning of cable complete all as specified and directed.
M &L for demolition of cement concrete in ground floors and pavings n.exc 15 cm thickness (below or above ground level) complete all as specified and directed.
M&L for PCC 1:3:6 type C-1 using 20mm graded stone aggregates for filling in road cuts/hard standing etc all as specified and as directed.
Supply and layingbore galvanised iron tubing, light grade with all fittings for passing of cables under ground complete 100 mm ISI marked all as specified and as directed.
Supply and laying galvanised iron tubing, light grade with all fittings for passing of cables under ground complete 80 mm bore ISI marked all as specified and as directed.
Boring of holes under road, pavement, hard standing for more than 5 mtr in length by trenchless, technology using ultra sound technique and necessary machine, including HDPE pipe of 80 mm dia suitable for 0.4 mpa working pressure complete all as specified and directed.
Boring of holes under road, pavement, hard standing, drain etc by conventional method not exceeding 5 mtr in length for laying of cable for protection of pipe etc complete all as specified and directed.
M&L for cutting the existing bitumen us road/payment/footpath upto 0.75 mtr in depth, 0.45 mtr in width and getting out excavated material and making good the damaged portion after laying the pipe, returning filling in mass concrete PCC 1:2:4 type B2 upto top of the road all as directed by Engr-in-Charge. Note :-(i) M&L for laying of pipe shall be measured and paid separately.
Taking down U/S cable of size 95 sqmm 3 core to 300 Sqmm 3 core from trench, duct, wall, road and panel complete with necessary disconnection of electrical line complete all as specified and directed.
Supply, laying, jointing and testing in replacement of HT XLPE insulated ,screened,PVC bedded galvanised steel strip or wire armoured ,electric power cables (heavy duty) with aluminium conductor,11000 volts (earthed) , grade cross sectional area 300 sqmm 3 core ISI marked for working voltage upto 11000 Volts, including cable lugs for providing connections as in repair complete all as specified and as directed.
Supply, laying, jointing and testing in replacement of HT XLPE insulated ,screened,PVC bedded galvanised steel strip or wire armoured ,electric power cables(heavy duty) with aluminium conductor,11000 volts(earthed) , grade cross sectional area 240 sqmm 3 core ISI marked for working voltage upto 11000 Volts, including cable lugs for providing connections as in repair complete all as specified and as directed.
Supply, laying, jointing and testing in replacement of HT XLPE insulated ,screened,PVC bedded galvanised steel strip or wire armoured ,electric power cables(heavy duty) with aluminium conductor,11000 volts(earthed) , grade cross sectional area 185 sqmm 3 core ISI marked for working voltage upto 11000 Volts, including cable lugs for providing connections as in repair complete all as specified and as directed.
Supply, laying, jointing and testing in replacement of HT XLPE insulated ,screened,PVC bedded galvanised steel strip or wire armoured ,electric power cables(heavy duty) with aluminium conductor,11000 volts(earthed) , grade cross sectional area 150 sqmm 3 core ISI marked for working voltage upto 11000 Volts, including cable lugs for providing connections as in repair complete all as specified and as directed.
Supply, laying, jointing and testing in replacement of HT XLPE insulated ,screened,PVC bedded galvanised steel strip or wire armoured ,electric power cables(heavy duty) with aluminium conductor,11000 volts(earthed) , grade cross sectional area 120 sqmm 3 core ISI marked for working voltage upto 11000 Volts, including cable lugs for providing connections as in repair complete all as specified and as directed.
Supply, laying, jointing and testing in replacement of HT XLPE insulated ,screened,PVC bedded galvanised steel strip or wire armoured ,electric power cables(heavy duty) with aluminium conductor,11000 volts (earthed) , grade cross sectional area 95 sqmm 3 core ISI marked for working voltage upto 11000 Volts, including cable lugs for providing connections as in repair complete all as specified and as directed.
Re-laying/re-routing serviceable HT cable of size 95 Sqmm to 185 Sqmm 3 core, 11000 volts grade,after testing of inulation value obtained from here-in-before items complete all as specified a dndirected.
S & F in replacement of HT 11000 volts Danger notice plate of size 25cm x 20cm made of 1.6mm thick mild steel plate, vitreous enamelled white, with letters, figures and conventional skull and bones in signal red colour and fixed with MS clamps, bolts and nuts of approved size complete all as specified and directed.
S & F HT UG cable PCC route marker of size 175mm width x150mm thickx 750 mm long dully written HT UG Cable, AGE E/M Palam with red strip marking of suitable size inclued embeded in earth with necessary PCC works 40cmx40cmx40cm complete all as specified and directed by Engr-in-Charge.
Supply, fixing and testing cold shrinkable type, straight through cable jointing kit, outdoor type suitable for XLPE insulated cable, upto 50 to 95 Sqmm size 3 core, 11 KV, ISI marked as fixed in repairs including taking out of old u/s joints complete all as specified and directed.
Supply, fixing and testing cold shrinkable type, straight through cable jointing kit, outdoor type suitable for XLPE insulated cable, upto 120 to 185 Sqmm size 3 core, 11 KV, ISI marked as fixed in repairs including taking out of old unserviceable joints complete all as specified and directed.
Supply, fixing and testing cold shrinkable type, straight through cable jointing kit, outdoor type suitable for XLPE insulated cable, upto 240 to 400 Sqmm size 3 core, 11 KV, ISI marked as fixed in repairs including taking out of old unserviceable joints complete all as specified and directed.
Supply, fixing and testing cold shrinkable type end termination cable jointing kit, indoor type suitable for XLPE insulated cable, 240 to 300 Sqmm size 3 core, 11 KV, ISI marked as fixed in repairs including taking out of old unserviceable joints complete all as specified and directed.
Supply, fixing and testing cold shrinkable type end termination cable jointing kit, indoor type suitable for XLPE insulated cable, 120 to 185 Sqmm size 3 core, 11 KV, ISI marked as fixed in repairs including taking out of old unserviceable joints complete all as specified and directed.
Supply, fixing and testing cold shrinkable type end termination cable jointing kit, indoor type suitable for XLPE insulated cable, 50 to 95 Sqmm size 3 core, 11 KV, ISI marked as fixed in repairs including taking out of old u/s jointscomplete all as specified and directed.
Supply and fix battery charger of capacity 24 V, 100 Amp single phase 3 feeder BATTERY CHARGER and D.C distribution board in common cubicle . The charger is schedule for 230V+/-10%, AC input and the output is suitable to charge of 24V DC 100Ah batteries and also supply load, The output voltage remains constant within +/-2% for AC input voltage variation 230V +/- 10% and load variation 0-100%, current ratings 100 A, over charging, overvoltage, undervoltage, over load and current limit protection complete all as specified and directed.
Schedule of Credit
M/S S.K.Electricals (BID ID -3363108)
SANWARIYA ENTERPRISES (BID ID -3363541)
A B K Enterprises (BID ID -3363438)
M/s Prakash Enterprises (BID ID -3358805)
Commercial Traders (BID ID -3362652)
YANSHIKA SECURITY SERVICES (BID ID -3363176)
Ruchi enterprises (BID ID -3358683)
PARAS ENTERPRISES (BID ID -3363217)
stage.html
html • 0.07 MB
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .