Loading…
India Infra Updates on WhatsApp
Join the Tenderkart WhatsApp channel for India Tender Updates
Loading…
Tender ID
Eligibility, documents, scope and key termsEligibility, required documents, scope of work and key terms of this tender, in one click.
| # | Company | Status |
|---|---|---|
| 1 | Admitted-Finance MIRZAPUR MUMTAZ NAGAR AYODHYA AYODHYA UTTAR PRADESH 224001 | AYODHYA | UTTAR PRADESH | 224001 | Admitted-Finance |
| 2 | Admitted-Finance 0 DHANA TEJA BARARI DHANA TEJA MATHURA MATHURA UTTAR PRADESH 281005 | MATHURA | UTTAR PRADESH | 281005 | Admitted-Finance |
| 3 | Admitted-Finance | Admitted-Finance |
Tender Value
₹34.1 L
EMD Value
₹34,500
Closing Date
10 Jul 2023, 11:00 amClosed
Eligibility, documents, scope and key termsEligibility, required documents, scope of work and key terms of this tender, in one click.
SE EWC AYODHYA
OFFICE OF THE SUPERINTENDING ENGINEER ELECTRICITY WORKS CIRCLE AYODHYA
24/SE/EWC/AYO/2023-24
2023_MVVNL_817970_1
24/SE/EWC/AYO/2023-24
Open Tender
Electrical Works
Item Wise
30 days
SULTANPUR
Please refer Tender documents.
2 documents required · 2 mandatory
₹3,540
SUPERINTENDING ENGINEER, ELECTRICITY WORKS CIRCLE
₹34,500
6 Sept 2023
5 Jul 2023
10 Jul 2023
5 Jul 2023
10 Jul 2023
5 Jul 2023
Amount
Carriage of following material from store centre under EEESD Ayodhya to dump store & from dump store to the site of work including loading, unloading and proper satcking at site etc.
33/11 KV 5 MVA T/F
33 KV Bus Isolator
33 KV Post Insulator
33 KV Lightening Arrestor
90 lbs rail Pcs for T/F ( 44.64 Kg/m)
33 KV VCB 800A, 750 MVA
Singe T/F control pannel
C.T. O/D 33 KV CTR 200/100/1-1A
11 KV Incoming switch gear 600/300/5A, 350 MVA
Out going 11 KV switch gear 200/100/5A 250 MVA
11 KV 3 Core Cable 3x300 mm XLPE
11 KV 3x185 mm XLPE
11 KV cable jointing kit indoor 3x300 sq.mm. XLPE
11 KV cable jointing kit outdoor 3x300 sq.mm. XLPE
11 KV cable jointing kit indoor 3x185 sq.mm.
11 KV cable jointing kit outdoor 3x185 sq.mm.
ACSR Dog Conductor
M.S. Channel 125x65 (for Structures)
M.S. Angle 75x75x6 (for Structures)
R.S Joist
33 KV Pin Insulator
ST Pole 11Mtr
ST Pole 9.0 Mtr For lighting
M.S.Angle iron 65x65x6 bracing 2700 mm
M.S.Angle iron 65x65x6 bracing 4300 mm
11 KV Top channel 100X50X2240 mm
Top channel 125X65 mm 3200 mm
11 KV Polymer pin insulator
6 SWG Wire
Stay wire 7/10
Dropper channel
33 KV disc insulator B&S type 70 KN
11 KV disc insulator T&C type
Construction of retaining wall around the 33 KV switchyard in size (30+30) Mtr. By using first class bricks, sand and bricks ballast which includes the following work (including cost of 1st class brick, bricks ballast sand/core sand cement etc.) 1. Excavation of earth in foundation 2. Cement concrete in foundation in ratio 1:5:10 3. Plaster work 1:6 ratio 4. CC 1:2:4 for grounting mid angle post for fencing. 5. 1st class brick work in 1:6 ratio
Fabrication of switchyard fencing by welded mesh with gate in size 30+30 MTR by 10 swg wire mesh , MS angle 50X50X6, MS flat 25x5mm and 40X5mm, Its fitting tightining with nuts and bolt on the studs. Supported by drilling the required poll along with fabrication of 1 No. gate m/o MS angle.
Earth Mat Laying of earth mat in the switch yard by laying of MS round of 32mm Dia in 750mm Deep trenches and grounding of earth mat with MS round 32 mm Dia 3Mtr long earth electrode as per Drawing. The work includes welding/ bolting of the MS round, G.S. strip and connecting all steel structure in the switchyard with the earth mat by means of G.S. strips of size 50X6mm as per item below
Digging of trench of size 500x750mm for laying of 32mm Dia MS round including refilling of earth and ramming the same after laying of MS round/G.S. strip
Laying and welding of lap joints of MS round of 32mm Dia with minimum 150mm overlaping. The MS round shall be welded on both side so as to fill the wedges completely using high quality Arc welding and goodwork Manship. The Joint shall be covered with black bitumen paint
Fabrication of 32mm Dia MS round 3 Mtrlong earth electrodes and driving them into ground so that tip of the electrodes remains atleast 750mm below the ground level and Jointing of earth electrodes 32 mm Dia with the earth mat using high quality Arc welding and goodworkman ship
Jointing of MS round 32 mm Dia in earth mat at cross joints using high quality Arc welding . A 75mm piece of 32 mm Dia MS round shall also be welded to make the joint strong for carrying fault current. The joints shall be covered with black Bitumen Paint
Providing and laying of G.S. strip of size 50x6mm for connecting the earth mat with the super structure, Security fencing post, Including digging of trench 500x500 mm bending, cutting, straightening and welding of the earth strip with the earth mat and various street structure using high quality Arc welding. The work include proper overlapping of the strip and Jointing By weldiing
Plinth of 5 MVA, 33/11 Kv T/Fs Construction of Plinth of size 3.46x3.46 Mtr for 5 MVA T/F having 0.4 Mtr above ground level. The work includes Excavation of foundation, Base concreting in C.C. 1:6:12 ratio ( cement,fine sand and Brick ballast) 1ST Class bricks work in cement mortar of ratio 1:4 foundation, C.C. in 1:4:8 ratio( cement, fine sand and brick ballast) and RCC working ratio 1:2:4 ( cement, coarse sand and stone grit of 20 mm gauge) using MS Bars of 10 mm Dia (Tor) in reinforcement including its cutting, bending and binding in required shape. The work also includes laying of 2 Nos. 3.46 mts long each rail pieces complete with cutting, welding and proper fitting etc. The plinth will be made as per Drawing and shall be plastered/ finished on Top and Side of the plinth. All materials like 90 lbs rail and civil material provided by the contractor.
Cable Stand Fabrication & Erection of Cable Stand with Two leges and Plinth and Foundation of Pits of size 1.075 x 0.9 x0.3 Mtr and grouting of two legs of structure in CC ( cement, coarse sand and stone grit of 20 mm gauge) of ratio 1:4:8 in block of 1.075 mtX 0.3 Mtr including supply of all T&P complete in all respect.(Contractor shall provide all materials )
Bus Bar Gantry Extension Digging of 2 Nos Pits of size 2.2mt x1.4mt x 0.75 Mtr providing stone pad at the bottom of the trench and grouting of the one legs/pair of the Bus Bar Gantry in CC ( cement, Coarse sand and stone grit of 20mm gauge) in the ratio 1:3:6 including supply of all T&P shuttering etc. in a block of size 2.2 mtx1.4 mtx0.75 mt. The work consists of dragging , shifting up to 40 mtr raising and erecting the two pre fabricated legs of Bus Gantry in proper allingment level and plumb. Both the plinths of the termainal gantry shall be properly finished with champering of edges. The work includes fabrication of Bus Bar Gantry 6.23 MtrLong as per RESPO drawing no.38 ( Set of 2) (All the necessary clamp, 33 KV pin 03 Nos , etc and civil materials provided by the contractor.)
Bus Isolator/Line Isolator Structure Fabrication of isolator structures 3.5mtr in height as per drawing No. RES 39 Digging of two Nos. Pits of size 1.075 x 0.9 x0.3 Mtr providing stone pad at the bottom of the pit and grouting pad at the bottom of the pit and grouting of two legs of the isolator structure in CC ( cement, coarse sand and stone grit of 20 mm gauge) of ratio 1:4:8 in block of 1.075 mtX 0.3 Mtr including supply of all T&P complete in all respect. The work includes dragging, Shifting upto 40 Mtr. Raising and erecting the two legs with runner of isolator in proper allingment level and plumb. Both plinths of the Isolator structure shall be properly finished with champering of edges.(All material suppiled by the contractor except steel)
LighteningArrestor Structure Fabrication of Lightening Arrestor per drawing No. RES 39 Digging of two Nos. Pits of size 1.075 x 0.3 x0.3 Mtr providing stone pad at the bottom of the pit and grouting of two legs of the above structure in CC ( cement, coarse sand and stone grit of 20 mm gauge) of ratio 1:4:8 in block of 1.075 Mtr X 0.3 Mtr x 0.3 Mtr including supply of all T&P complete in all respect. The work includes dragging, Shifting upto 40 Mtr. Raising and erecting the two legs with Top frame above structure's in proper allingment level and plumb. Both plinths of the structure shall be properly finished with champering of edges etc.(All material suppiled by the contractor except steel)
Post Insulator/C.T.Structure Fabrication of Post Insulator per drawing No. RES 39 Digging of two Nos. Pits of size 1.075 x 0.3 x0.3 Mtr providing stone pad at the bottom of the pit and grouting of two legs of the above structure in CC ( cement, coarse sand and stone grit of 20 mm gauge) of ratio 1:4:8 in block of 1.075 Mtr X 0.3 Mtr x 0.3 Mtr including supply of all T&P complete in all respect. The work includes dragging, Shifting upto 40 Mtr. Raising and erecting the two legs with Top frame above structure's in proper allingment level and plumb. Both plinths of the structure shall be properly finished with champering of edges etc.
Plinth for 33KV VCB Construction of plinth of size 2.0x1.5x0.9 (Mtr) suitable for erection of super structure for 33 Kv VCB including grouting of Anchor bolts in proper allingment and level. Scope of work includes excavation of foundation base concreting in CC 1:6:12 ( cement, fine sand and brick ballast) 1st class brick work in cement mortor of ratio 1:4 CC in Ratio 1:4:8 and RCC work in ratio 1:2:4 ( Cement, coarse sand and stone grit of 20 mm gauge) as per Drawing
Erection and Installation Of 33/11 Kv 5 MVA Transformer Erection and installation of 33/11 Kv, 5 MVA Transformer in a leveled position on the plinth. The work include shifting of transformer to the site of installation with in the sub-station premises, assembling, fixing and fitting of all accessories and filling of transformer oil to the desired level and ensuring that there is no leakage.
Special Earthing by way of boring and lowering of "B" class G.I. pipe 50 mm Dia 20mtr long from ground upto the water level and it will be connected to the G.S. strip for transformer neutral connection. The earth strip will be welded to the G.I. Pipe. The work also includes Cap & Clamps for pouring water, the cost of all material with all labour & T&P etc. Complete in all respect.
Lightening Arrestor
T/F & Feeder Control panel & Battery Charger Unit
T/F Body
C.T. O/D 33 KV CTR 200/100/1-1A
Delta type Earthing of Power T/F Neutral Earthing of Power T/F Neutral by providing 03 No. of "B" class G.I. pipe 50 mm Dia 20 feet long from ground upto the water level (Delta type) and Providing and laying G.S. strip 50 x 6 mm including cutting, welding, bending etc. complete in all respect. (All the material will be supplied by the contractor)
Earth filling in the Switchyard of size 25x30 mtr including cost of earth handling and cartage upto Switcyard from outside with its unloading and laying in the yard, Leveling, Watering and Ramming till its Compactness
Installation of Isolators Assembling and installation of line/Bus isolator on the Isolator structure , adjusting of opening mechanism in proper alignment so as to ensured smooth operation of the same. In case of line Isolator proper operation of earth links shall also be ensured. The work includes fabrication for proper fixing if required.
Installation of Lightening Arrestors Assembling and installation/ mounting of three Nos.Lightening Arrestors on the L.A. structure/ complete with making earth connection ( Separate ) and line connections. The work includes fabrication for proper fixing if required.
Installation of Post Insulator Installation of post insulators on the post insulators /CTs structure. The work includes fabrication for proper fixing if required
Installation of CTs Installation of 3 Nos CTs of ratio 200/100/1A and 3 No. CT's of 400/200/1 A on the CTs structure. The work includes fabrication for proper fixing if required
Installation of 33 KV VCB, 800 Amp capacity complete in all respect including commissioning
Installation of Switchgears in Control Room Shifting carefully and safely 11 Kv Switchgear from out side of the switch gear room, Including grouting the two Nos. 100x50x6mm channels piceses( each 800mm long including cutting to size) and foundation bolts in 1:2:4 CC ( Including cutting of CC of the floor and finishing of Floor) as per direction of Engineer Incharge, Placing and fixing of switchgear on foundation providing nuts & bolt of proper size in proper position and alignment, complete work with mounting of P.T. on incoming S/G etc.
Fixing and making Bus Bar connection in between all switchgears after cleaning and tapping with H.T. tape, Empire tape and PVC tape properly providing and fixing of 6mm thick bakelite seperators and plugging of all opening and holes with plastic compound. complete work including cost of all material ( Except Copper Bus Bars) Strictly to the satisfaction of site incharge.
Shifting carefully and installation of 33 KV single/Double transformer / FDR pannel in control room including grouting of above and its proper connection.
Earthing of 11KV & 33KV Switchgear Laying of earth mat for earthing of indoor equipments by means of M.S. Strip 50x6mm Connecting to 4 Nos. earthing electrodes of 32 mm (including fabrication of earthing electrodes) 3 Mtr long on each side (as per RESPO Drawing RES-40). This work includes driving of eath electrodes deep down into the earth so that its TOP remains 500 mm below ground level. The work include laying, bending, welding of M.S. earth strips 50 x 6 mm in the control room and connecting to both side squares.
Earthing of all indoor equipment by providing and laying G.S. strip 50 x 6 mm including cutting, welding, bending etc.
Supply and Installation of 24 volt 210 AH cell type Battery bank and Battery Charger with cabinet including its Commissioning.
H.T. Cable Laying Laying & dressing of 11 KV, 3x300 and 3X185 Sq.mm XLPE cable underground from 5 MVA T/F to 11 KV incoming switchgear in the trench 450mm wide, 900mm deep, providing 150mm fine sand cushion bench and 150mm fine sand cushion above the cable. The cable shall be duly protected by 1st class bricks two either side and third on top of the cables, laid in series one after the other, the work includes supplying of fine sand and bricks, refilling and ramming of the left out soil, closing the trench and leveling. Spare cable shall be left and buried in the trench in the safe of rings at both ends. Cable laying work includes unrolling, cutting, meggering and sealing both end of the cable. (All the material will be supplied by the contractor)
33KV Bus Bar & Stringing. Stringing of 33Kv Bus Bar by using and laying of ACSR Dog Conductor including fixing of Disc Insulator. Strings and tension fitting complete with sagging of Bus Bar etc. and making Vertical/Horizontal jumper connection through PG clamps and connecting all the equipments with each other through connecting clamps.
Construction of 11/0.4 KV Double pole Mounted Sub- Station Erection & Grouting of 2 Nos 11Mtr STP support for making D/P structure Including fabrication, Fixing of MS Channel, M.S. angle, Disc Insulators/ Pin Insulators etc. The work also includes grouting of double pole supports in CC 1:4:8 in block of size 0.45Mtr into 0.45Mtr into 2.0Mtr earthing of Double pole with M.S. earthing rod, complete in all respect. Painting of one Coat of Red Oxide Primer and Two Coats of Aluminum paint of good Quality. (Contractor shall provide civil material & 03 no. pin and necessary clamp, disc fitting etc.)
Earthing of 11 mtr Stp by providing 6 SWG G.I wire and earthing rod as per norms.( All materials will be supplied by the contractor.except 6 swg wire)
Nozeling and grouting of stay at sectional pole and extra stay sets at angle locations (All the civil material and stay set, stay clamp will be arranged by the contractor except stay wire )
Providing and fixing of 11 kv TPMO switch with clamp at S/S D/P .All the material will be supplied by the contractor
Providing and fixing of 11KV fuse set with clamp at S/S D/P .All the material will be supplied by the contractor
Providing and fixing Alu Connector for LI/BI/LA
Providing and fixing Copper L-Piece
Breaking the concrete fencing/ Boundary wall in the switchyard of sub. Station for moving 5 MVA Transformer in switchyard after complition the work covered and restore the wall
Installation of 3x300 11 KV Xlpe Indoor and Outdoor and 11 KV 3x185 Xlpe indoor and outdoor jointing kit. As per norms.
Hosting of 11 KV Cable on existing/erected support with provision of MS Pipe 150 mm dia 3 mtr long suitable for 3x185 sq mm cable fixing of 2 No. Ms Angle support, 9 no. p.g. Clamp and 3 no. long barral alu. lug and its clamping, and 02 nos. supporting angle 65X65X6, 2500 mm long, jumpering properly as per RESSPO Norms. (All material will be supplied by the contractor like P.G. clamp, lug,supporting Angle 65X65X6,2500 mm. N&B etc).
Neutral stand Fabrication and grouting of M.S Channel 125x65 mm L shape & in proper size and allignment to provide support for the two separate earthing strips for pwer T/F neutral including supply & fixing of two No.Flexible copper bonds for neutral earthing. (All the materials will be arranged by the contractor such that clamps nut bolts and civil materials , Steel)
Station / Switchyard lighting Erection of STP 9 Mtr long support after excavation of earth and grouting of cc in ratio 1:4:8 (Cement, Coarse sand and Brick ballast) as per RESPO drawing with plinth. Painting of one Coat of Red Oxide Primer and Two Coats of Aluminum paint of good Quality. For making cable LT line for colony and switchyard lighting. (All material will be supplied by the contractor like 09 Mtr STP clamp etc.)
Providing and fixing of Street Light (LED, 90 Watt, ISI Mark) and fitting with propoer clamps and Nut Bolts complete in all respect and suitable for 9.0 Mtr STP support,controlled by mcb of isi mark.
Providing and laying of 2 core 2x16 sq mm LT AL.cable from S/G room to street light supports after digging of trench, Laying of cable providing a brick on TOP of cable, Refilling of trench making connection at poles with street light fittings complete with all respects.
Supply & Laying of 6x2.5 sq.mm. Sq. control cable from power T/F to controle board in the ground as per RESPO Norm with proper connection VCB, CT & Control Pannel with T/F to battery and battrey charger, Bucholz Relay, low higher and winding temperture protection alarm etc with including all the civil material. (All the material will be supplied by the contractor)
Supply & Laying of 4x2.5 sq.mm. Sq. control cable from power T/F to controle board in the ground as per RESPO Norm with proper connection VCB, CT & Control Pannel with T/F to battery and battrey charger, Bucholz Relay, low higher and winding temperture protection alarm etc with including all the civil material. (All the material will be supplied by the contracto)
Supply & Laying of 2x2.5 sq.mm. Sq. control cable from power T/F to controle board in the ground as per RESPO Norm with proper connection VCB, CT & Control Pannel with T/F to battery and battrey charger, Bucholz Relay, low higher and winding temperture protection alarm etc with including all the civil material. (All the material will be supplied by the contracto)
Construction of cable trench of 200 mm wide and 300 mm deep with MS strip at a distance of 1mtr. With brick work 1:4:8 in foundation 12 mm thick plaster of 1:4 cement coarse sand for finishing along with MS strip. (All the material will be supplied by the contractor)
Construction of trench cover of 600 mm long and 75 mm thick for cable trench Including cost of material, labour and T&P. (All the material will be supplied by the contractor)
Laying and Fixing of Interlocking Bricks providing brick balast, local river sand, cement 3 inch for leveling Switchyard and Making approach path with bricks works on both side and interlocking on top and Proper leveling and finishing and digging of earth out side if recured for leveling etc.
Water shoking chambers with covers of size (0.75X0.75X1.0) mtr in switch yard corners for rain water harvesting & for earthing.
Painting of Sub Station Structures (Old+New) with one coat of ready mixed primer and 2 coats of AL.Paint of good quality including cost of material, Labour and T&P complete in all respect.
Scraping Rubbing, cleaning of wiremesh fencing and its gate with one coat of Red Oxide paint as primer then painting with supirior quality of Bus Grean Colour in two Caots including cost of paint & other allied material.
Wiremesh Fencing both side
Gate & its Angle on bothside
Supply, fixing and mounting of following equipments/items in the control room
Sign board and other Sunderyitems of substaion
Fire Extinguisher Mounted Type
Fire Bucket (4 No) with stand Complete
Rubber matting one side chequered and other side plane size 1800x900x12mm
Rubber hand gloves
Providing Round Bar 32 mm
Commissioning of 5 MVA T/F and its equipments installed in switchyard and 11 KV Incoming and Outgoing Panels complete in all respect upto energising.
Hindustan Electric Work
M/s Shukla Enterprises
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .