Executive Engineer, PWD, Malda Electrical Division
O/O, Executive Engineer, PWD, Malda Electrical Division, Singatala, Malda - 732101.
Electrical Installation works for the proposed Mini Mother and Child Hub at Silampur Rural Hospital of Malda District - SITC of Fire Detection and Alarming System.
2019_WBPWD_234549_1
WBPWD/EE/MED/e-NIT-04/2019-20
Open Tender
Electrical Work/ Equipment
Item Rate
30 days
SILAMPUR
Please refer Tender documents.
6 documents required · 6 mandatory
₹11,953
O/O THE EXECUTIVE ENGINEER PWD MALDA ELECT DIVN
4 Mar 2020
24 Jul 2019
19 Aug 2019
25 Jul 2019
16 Aug 2019
31 Jul 2019
30 Jul 2019
Amount
SITC of Microprocessor based Intelligent, addressable 2 Loops fire alarm control panel ( VDS / UL / FM / ULC approved ) fully networkable with each loop capable of taking minimum 125 devices, 1/4 VGA display character alpha-numeric liquid crystal display.The panel shall be soft addressable type.The panel shall be able to give pin point location of all fire/ fault conditions. Further, the panel must be able to automatically switch off respective control switches when ever any alarm is triggered.The Panel should be able to store sufficient numbers of log events in its Memory as per recommended standards.
The panel shall have in built rectifier, provision for external & internal printer ( if required ), Loop cards, LCD unit to indicate Fire/Fault Signal with address and analog output, complete in all respects, in built Surge protection facility, integral SMF lead acid batteries with sealed cells of 24 V capable of running for 24 hours normal working and then be capable of operating the system for 30 minutes during Emargency condition, with integral battery charger complete as required. The panel shall have extra loop card to serve as stand by in case of burntout or malfunctioning of any operating loop cards. The FACP shall be capable of being networked ( future expansion ) with other similar FACP located at different part of the premises through single RS 485 bus. The panel should have modbus output & ready to communicate with remote computer. The system must be preloaded with licenced software. (Approved Make: Esser/ Cerberus Pro/Secutron/ Notifer / Edward / Bosch / Apollo / Morley / System Sensor / Johnson Controls).
SITC of Analog Addressable Intelligent multisensor detector ( VDS / UL / FM / ULC approved ) with two inbuilt optical smoke sensors as well as additional heat detector sensor with decentralise intelligence, soft addressable Photothermal type with inbuilt fault isolator as per NFPA style 7 wiring complete with base having IP as per recommended standard.(Note : Detectors without built-in fault isolator is also acceptable but in such case the contractor shall provide one independent fault isolator module for every group of addressable devices (Numbers of addressable devices in a group will be as per latest recommended standards) without any additional cost). (Approved Make: Esser/Cerberus Pro/Secutron/ Notifer / Edward / Bosch / Apollo / Morley / System Sensor / Johnson Controls).
SITC Addressable Manual Call Point ( VDS / UL / FM / ULC approved )soft addressable type with in built fault isolator as per NFPA style 7 wiring complete as required. (Approved Make: Esser/Cerberus Pro/Secutron/ Notifer / Edward / Bosch / Apollo/ Morley / System Sensor / Johnson Controls).
SITC of Addressable Loop Powered Hooter ( sound output of minimum 90 db ) cum strobe (strength of light 10 cd)complete with inbuilt isolator & IP65 base and ( VDS / UL / FM / ULC approved) approved. (Approved Make: Esser/Cerberus Pro/Secutron/ Notifer / Edward / Bosch / Apollo / Morley / System Sensor /Johnson Controls).
SITC of LED type Response Indicator ( VDS / UL / FM / ULC approved) having 2 Nos. red coloured LED lamps including connections etc. (Approved Make: Esser/Cerberus Pro/Secutron/ Notifer / Edward / Bosch / Apollo / Morley / System Sensor /Johnson Controls).
Supply & Laying of 2 Core 1.5 sq.mm FRLS shielded copper Cable (For Loop) (Make. Finolex / KEI ) with 20 mm NB PVC rigid conduit pipe(Make: Precisson-Medium) on the surface of the wall.
NOTE : The Fire Alarm system shall comply with latest requirements of - 1. National Fire Protection Association (NFPA) Standards. 2. IS 2189. 3. NFPA 70 National Electric Code. 4. NFPA 72 National Fire Alarm Code. 5. Local Statutory Regulations. 6. Manufacturer Recommendation.
TESTS : 1.The system shall be tested and commissioned by a qualified competent, trained engineer or technician authorized by the manufacturer of the fire alarm equipment to technically supervise and participate during all of the adjustments and tests for the system. 2. Before energizing the cables and wires, check for correct connections and test for short circuits, ground faults, continuity, and insulation and other tests as per above standards must be done.
MAGNUM SAFETY INDIA
Fire Guard Syndicate
stage.html
html • 0.05 MB
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.04 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .