Loading…
Loading…
| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | L1₹18.5 LAccepted-AOC | L1 | Accepted-AOC L1 | |
| 2 | L2₹20.6 L+₹2.2 L (11.9%)Rejected-Finance | L2 | Rejected-Finance L2 FOR REJECTED | |
| 3 | Rejected-Technical NOT FOUND | - | Rejected-Technical The firm is not Enlisted in Appropriate Category i.e. b(ii) |
Tender Value
Refer Docs
EMD Value
₹28,940
Closing Date
7 Oct 2021, 6:00 pmClosed
HQ COMMANDER WORKS ENGINEER SRI GANGANAGAR
HQ CWE POST BOX 48 SRI GANGANAGAR-335001 (Rajasthan)
CA NO CWE SGNR 87 OF 2020-21 PROVISIONOF TROLLEY MOUNTED SEWAGE PUMP SET FOR STP AND 33 KV VCB OUTDOOR TYPE FOR MAIN INCOMING WITH ALL ACCESSORIES AT MAIN RECEIVING STATION AT MILITARY STATION LALGARH JATTAN (8TH CALL)
2021_MES_421531_8
CA NO. CWE SGNR - 87 OF 2020-21
Open Tender
Electrical and Maintenance Works
Item Rate
180 days
GE LALGARH JATTAN
CLASS-E
CATEGORY-b(ii)
9 documents required · 9 mandatory
₹500
₹28,940
Yes
13 Sept 2022
13 Sept 2021
9 Oct 2021
13 Sept 2021
7 Oct 2021
23 Sept 2021
Amount
Supply, installation and fixing on portable trolley, testing and commissioning Horizontal End Suction Non clog, solid handling pump suitable for 100 mm solid, 30 KW , for sewage water, capacity 70 LPS, total head 19 Mtr, NPSH reqd 3mtr, 1450 RPM, Suction and delievery 150 mmx150 mm made out of cast iron casing and CI impeller mounted on SS shaft of grading EN8/SS410 and sleeve made out of AISI - 410 fixed on MS fabricated base plate with suitable anti vibration mounting and coupled to and including 3 pole, 440V, 50 Hz, AC, energy efficient, squrrel cage induction motor to suitable rating ,VFD campatible complete with connection to LT panel starter and earthings complete all as specified and directed by Engineer-in-Charge Pump make : Kirloskar Brothers Ltd, Pump Model : SHM-150/26 or similar specification in KSB, Mather & Platt, Kishor pumps (Astra series) or latest as approved by GE
Supply and fix HDPE pipe 160 mm for delivery with necessary clamps for fixing with pump including reducer/enlarger 160 to 150 mm on pump side complete all as specified and directed by Engineer-in-Charge Make: KISSAN/SUPREME/FINOLEX
Supply and fix CI Foot valve suitable for 150 mm dia suction pipe duly fixed with fasteners and clamps complete all as specified and directed by Engineer-in-Charge
Supply and fix Ribbed flexible pipe suitable for suction of pump 150mm size with fasteners and clamps, coupling to pump suction complete all as specified and directed by Engineer-in-Charge Make: KISSAN/SUPREME/FINOLEX
M&L for fabricating, by arc/gas welding or with fastners, nut, bolts, washers as required, portable trolley made out of rolled steel Fe-410- W/I section, angle or tee section, plate, girder etc, semi open covered with galvanised sheet canopy at the top, designed to accommodate sewage pump set, motor, LT Panel, LT cable, inlet and outlet pipes including errection/fixing on trolley bed and provision of suitable towing arrangement swivel type for towing with the vehicles complete with double axle and 04 Nos solid rubber wheels to suit the ground clearance of approx 45 cm and size of trolley approximate 1.6 m x 2.75 m (May vary as per site requirement) and height of canopy suitable to house LT panel and Pump having enough working space and shall be as per drawing submitted by contractor and approved by GE/AO complete all as specified and directed by GE/Engineer-in-Charge Note: (i) Design and drawing of trolley shall be got approved by contractor before fabrication. (ii) The solid rubber wheel shall be measured and paid as part of trolley weight.
Supply, laying and testing copper conductor flexible wire PVC insulated, sheathed, of size 16 sqmm single core in flexible PVC conduit for connection from starter to motor complete with terminal/lugs complete all as specified and directed by Engineer-in-Charge
Supply , laying and testing cable XLPE insulated, screened, PVC bedded, galvanised steel strip armoured, electric power cables (heavy duty) 1100 conductor of size 35 sqmm 3.5 core complete all as specified and directed by Engineer-in-Charge
Excavation in trenches, not exc 1.5 m wide and n. exc 1.5 m depth; or n exc 10 Sqm on plan and n exc 1.5 m in depth for foundations of poles, struts, stays etc. or laying underground cable etc. in soft/loose soil, & getting out complete all as specified and directed by Engineer-in-Charge
Returning, filling in, including spreading, levelling, watering and well ramming in layers n.exc 25cm thick complete all as specified and directed by Engineer-in-Charge
Removal of excavated surplus soil to a distance n.exc 50m and depositing where directed at level not exceeding 1.5 m above the starting point complete all as specified and directed by Engineer-in-Charge
M&L brick protection with sub class'B' brick laid flat across the cable complete all as specified and directed by Engineer-in-Charge
M & L for sand cushioning with locally available sand to under ground cable below & around the cable gently punning after laying the cable complete all as specified and directed by Engineer-in-Charge Note : Thickness after punning shall be considered for payment.
M&L for earthing complete with Galvanized steel earth plate electrode of size 600x600x6mm thick buried directly in ground with earth pit not less than 2.25 m deep below the normal ground level with top edge of plate not less than 1.5m below normal GL connected to GI earthing strip of size 32 x 6mm flat by means of bolts, nuts, check nuts and washers of Galvanized iron or steel all as shown in electrical plate No. 3 of SSR Part-I connected to earthing test point all as specified or indicated including testing on completion complete all as specified and directed by Engineer-in-Charge. [Note: The unit rate shall be deemed to include for excavation & earth work in any type of soil, PCC (1:3:6) type C1 chamber, MS angle iron frame 40x40x6mm, RCC 1:2:4, Type B-1 cover 40mm thick reinforced with 8mm dia CTD bars @ 75mm c/c both ways, MS handle 12mm dia, CI funnel and wire mesh, GI watering pipe 20mm dia medium grade for watering, GI protection pipe light grade 40mm dia, earthing lead upto 7.5m test point complete all as specified in preambles of SSR Part-II and shown in electricl plate No. 3 of SSR Part-I.]
Ganganagar Enterprises
stage.html
html • 0.05 MB
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.04 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .