Shri Vinay Kumar, IDSE, SE (SAG) CWE
HQ Commander Works, Engineer CWE (Army) Mumbai, 24 Assaye Building Colaba, Mumbai-05
REPAIR/ MAINT OF HT CABLES, SWITCH GEARS INCL CONNECTED ITEMS UNDER GE (WEST) COLABA, MUMBAI
2026_MES_798192_1
85377/W/E8
Open Tender
Electrical and Maintenance Works
Item Rate
90 days
GE (WEST) COLABA
All as per NIT and tender documents
8 documents required · 8 mandatory
₹500
Yes
GE (west) Colaba
₹90,000
Yes
11 Nov 2026
11 Nov 2026
7 Dec 2026
11 Nov 2026
5 Dec 2026
26 Nov 2026
| Sl No | Description | Qty | Unit | Est. Rate | Est. Amount |
|---|---|---|---|---|---|
| 1 | Material and labour of Opening the bus -bar chamber,CT chamber, PT Chamber and Meter chamber of HT 11KV, panel board and carry out following activities as mentioned below complete all as directed and specified by Engineer-in-Charge.
(Note: spare parts shall be measured and paid seperately.) :-
(i) Inspecting/cleaning/overhauling of bus bar chamber by checking of bus bars, spout insulators, space heaters and removing dust with vacuum cleaner/Blower and moisture by hot air blower and checking tightness of bus bars, insulators and applying STRIPPEX(A), STRIPPEX(B) and HT tape and test with High Voltage(DC) and meggering before and after high voltage test complete.
(ii) Inspecting/cleaning/overhauling of CT/PT chamber by checking of Bus bars, spout insulators, space heaters and checking of wiring system and removing dust with vacuum cleaner/blower and moisture by hot air blower and checking tightness of bus bars, insulators and applying anti tracking paint on CT's and insulators and HT Tape.
(iii) Inspecting/cleaning/overhauling metering chamber by checking of entire wiring system, all meters, selector switches, control fuses and removing dust with vacuum cleaner/blower and moisture by hot air blower and checking tightness of wiring system. | 33 | Each Job | - | - |
| 2 | Disconnecting and dismantling the existing indoor type, 11 KV horizontal draw out type VCB trolly of rupturing capacity 250/350 MVA, 400/630/800 Amps from location and repair /overhauling and carrying out with the following activities as mentioned below and replacement of unserviceable following items as and where required complete all as specified and directed by Engineer-in-Charge.
(Note: spare parts will be measured and paid separately.)
(i) Inspecting / overhauling of manual / motorised spring drive mechanism by checking mechanism, motor and gear assembly, big gear assembly, stop bolt assembly, main shaft interlocking assembly, closing spring assembly, small cam with screw, motor cut -off limit switch, butter fly switch assembly and apply multi grease lubricant to function smoothly.
(ii) Inspecting / overhauling of tripping assembly,earthfault release assembly, tripping coil, auxiliary switch and checking of electrical wiring system.
(iii) Inspecting / overhauling /cleaning and inspecting through insulators, vacuum interuptors by carbon cleaner solution and apply dry graphite conductive sealant for electrical contacts to avoid carbon deposits on contact surfaces.
(iv) Assembling all items/components parts to the respective postion and testing the breaker with High Voltage(DC) and meggering before and after high voltage test complete. | 33 | Each Job | - | - |
| 3 | Dismantling of Old Damaged/burnt spare parts from VCB and Supply and fixing in repair of following Spare parts suitable for - VCB 11 KV , 630/800 Amps indoor type of Make Schnieder(PIX -MV)/ABB(VD4) /CG/AREVA(VMX) all as specified and directed by Engineer-in-Charge. | - | - | - | - |
| 4 | Isolating Contacts flat type | 10 | Each | - | - |
| 5 | Vaccum InterupterVG2 | 3 | Each | - | - |
| 6 | Insulating Rod | 3 | Each | - | - |
| 7 | Closing coil 110V /24V DC | 3 | Each | - | - |
| 8 | Tripping Coil 110V /24V DC | 2 | Each | - | - |
| 9 | Spring Charging Motor 110V-230V AC/DC | 3 | Each | - | - |
| 10 | Breaker Auxiliary Switch 6NO +6NC | 2 | Each | - | - |
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Tendernotice_1.pdf
PDF • 0.33 MB
Tenderdocuments85377.pdf
Tender Documents • 1.05 MB
BOQ_895422.xls
BOQ • 1.09 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .