Loading…
Loading…
| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | L1₹18.0 LAccepted-Finance RAM KALA MANDIR GALI K K ELECTRICALS COURT ROAD UDHAMPUR RAMNAGAR CHOWK UDHAMPUR JAMMU KASHMIR 182101 | UDHAMPUR | JAMMU AND KASHMIR | 182101 | L1 | Accepted-Finance L1 | |
| 2 | L2₹18.2 L+₹21,750 (1.21%)Accepted-Finance | L2 | Accepted-Finance L2 | |
| 3 | L3₹18.8 L+₹72,750 (4.03%)Accepted-Finance | L3 | Accepted-Finance L3 |
Tender Value
Refer Docs
EMD Value
₹42,500
Closing Date
28 Nov 2023, 4:00 pmClosed
Executive Engineer
Electric Division JPDCL Udhampur
1. Creation of 63 KVA Sub Station at Kawa 2. 25 KVA at Sui Battal 3.25 KVA at Dhanori 4. 25 KVA Peoni Nali 5. 25 KVA Gadana Majalta 6. 25 KVA Sui W.No.6 under UT Capex
2023_PDD_237414_1
ED/UDH/109 of 2023-24 dt. 18-11-2023
Open Tender
Electrical Works
Turn-key
75 days
In villages Udhampur
Please refer Tender documents.
2 documents required · 2 mandatory
₹1,000
Executive Engineer Electric Division JPDCL
₹42,500
18 Dec 2023
18 Nov 2023
30 Nov 2023
18 Nov 2023
28 Nov 2023
18 Nov 2023
18 Nov 2023 - 22 Nov 2023
Survey, Supply, Transportation, Carriage, Erection, Testing and Commissioning for Erection of 11 KV line on 9 mtr long ST poles, 30 mm sq. ACSR Weasel Conductor for Creation of 63 KVA Sub Station at Kawa.
9 mtr. Long ST Pole (To be issued by Department at Divisional Store of Electric Divisional JPDCL Udhampur)
9 mtr. Long PCC Pole (To be issued by Department at Divisional Sore of Electric Divisional JPDCL Udhampur)
GI V Cross -arm with top Bracket including clamps
GI Channel X-arm including clamps and Angle for braces
30 mm sq. ACSR Weasel conductor
11 KV Polymer composite Pin Insulator 12 KV, 5 KN, lighting impulse 75 KV Positive and 80 KV Negative, Creepage distance 320mm.
11 KV Polymeric Composite Disc insulator 12 KV, min failing load 45 kn, lightening impulse 75 Positive and 80 KV Negative, creepage distance 320mm with fitting
Galvanized Nuts and Bolts
Danger Plates with clamps
Anti Climbing device with clamps
Earthing complete by GI Rod 20 mm, 2.5 mtr long through G.I. Strip
Survey, Supply, Transportation, Carriage, Erection, Testing and Commissioning for Creation of 63 KVA Sub Station at Kawa.
11/0.433kV, 3-phase 63 KVA Distribution Transformer (To be provided by department at Divisional Store of Electric Division JPDCL Udhampur)
Gapless surge arrestor 9KV, 10KA, LA with polymer housing station type
11 KV GO, AB Switch 3-phase, 3-pole, 200 Amp. Vertical
11 kV Horn Gap Fuse Set 3 Phase 200A
120 mm² Single Core Cable,1.1kV Grade, PVC Insulated Alumnium Stranded Conductor FRLS type
9 mtr. Long ST Pole (ST 410 SP-33)
11kV Polymeric composite Disc Insulator 12kV, min failing load 45kN, Lightening Impulse 75kV Positive and 80kV Negative, creepage distance 320mm with fitting
GI Channel/Angle/Flat of sizes including clamps
Galvanized Nuts and Bolts.
Earthing of substation --Excavation of earth pit of dia 650 mm & depth 3000 mm, installation of Earthing pipe of 40 mm Nominal bore & 4mm wall thickness & length 2.5 mtr long as Per IS 1239. GI Strip for neutral earthing of size 50 mm x 6 mm & 32mm x 3mm for connection of transformer body, G.O Set & lightening arrestor as per IS 2629/85, GI nuts & bolts,refilled with earth enhancement materials and earth Chamber withRCC Slab cover.
11 KV polymeric composite Pin insulator, 12kv, 5 kn, lightening impulse 75 KV Positive and 80 KV Negative, creepage distance 320mm
LT Fuse Switch made of angle Iron 50X50X6, with aluminium Bus Bar strip 50X6mm fixed on Bus Bar Insualtor including clamps for fixing of switch
Galvanized stay set with 50*8 mm stay clamp, guy insulator(2 nos), anchor plate (200*6mm), nuts-bolts, 2 Nos turn buckets, 1.8m long, 16 mm diameter solid GS stay rod & 7/15 mm dia GI strandard wire complete.
Danger Plates with clamps
GI Barbed wire for Anti climbing
Cement Bottoming 1:2:4 mix as per REC Standard 0.5 cum per pole
Painting of 9 mtr long ST poles with two coat of Aluminium paint.
Survey, Supply, Transportation, Carriage, Erection, Testing and Commissioning for Erection of LT Line single phase two wire on 8 mtr long PCC poles, 30 mm sq. ACSR Weasel Conductor for Creation of 63 KVA Sub Station at Kawa.
8 mtr. Long PCC Pole (WL 200kg)
GI U clamps for Shackle Insulator
30 mm sq. ACSR Weasel Conductor
Shackle Insulator
Galvanized Nuts and Bolts
Survey, Supply, Transportation, Carriage, Erection, Testing and Commissioning for Erection of 11 KV line on 9 mtr long PCC poles, 30 mm sq. ACSR Weasel Conductor for Creation of 25 KVA Sub Station at Sui Battal.
9 mtr. Long PCC Pole (To be issued by Department at Divisional Sore of Electric Divisional JPDCL Udhampur)
GI V Cross -arm with top Bracket including clamps
GI Channel X-arm including clamps and Angle for braces
30 mm sq. ACSR Weasel conductor
11 KV Polymer composite Pin Insulator 12 KV, 5 KN, lighting impulse 75 KV Positive and 80 KV Negative, Creepage distance 320mm.
11 KV Polymeric Composite Disc insulator 12 KV, min failing load 45 kn, lightening impulse 75 Positive and 80 KV Negative, creepage distance 320mm with fitting
Galvanized Nuts and Bolts
Danger Plates with clamps
Anti Climbing device with clamps
Earthing complete by GI Rod 20 mm, 2.5 mtr long through G.I. Strip
Survey, Supply, Transportation, Carriage, Erection, Testing and Commissioning for Creation of 25 KVA Sub Station at Sui Battal.
11/0.433kV, 3-phase 25 KVA Distribution Transformer with Bimetallic Terminal Connectors Energy Level-2, Aluminium wound, and with LV Cable Box having detachable Aluminium Gland plate.
Gapless surge arrestor 9KV, 10KA, LA with polymer housing station type
11 KV GO, AB Switch 3-phase, 3-pole, 200 Amp. Vertical
11 kV Horn Gap Fuse Set 3 Phase 200A
95 mm² Single Core Cable,1.1kV Grade, PVC Insulated Alumnium Stranded Conductor FRLS type
9 mtr. Long PCC Pole (PCC-WL-300 kg)
11kV Polymeric composite Disc Insulator 12kV, min failing load 45kN, Lightening Impulse 75kV Positive and 80kV Negative, creepage distance 320mm with fitting
GI Channel/Angle/Flat of sizes including clamps
Galvanized Nuts and Bolts.
LT Fuse Switch made of angle Iron 50X50X6, with aluminium Bus Bar strip 50X6mm fixed on Bus Bar Insualtor including clamps for fixing of switch
Cement Bottoming 1:2:4 mix as per REC Standard 0.5 cum per pole
Earthing of substation --Excavation of earth pit of dia 650 mm & depth 3000 mm, installation of Earthing pipe of 40 mm Nominal bore & 4mm wall thickness & length 2.5 mtr long as Per IS 1239. GI Strip for neutral earthing of size 50 mm x 6 mm & 32mm x 3mm for connection of transformer body, G.O Set & lightening arrestor as per IS 2629/85, GI nuts & bolts,refilled with earth enhancement materials and earth Chamber with RCC slab cover.
Survey, Supply, Transportation, Carriage, Erection, Testing and Commissioning for Erection of LT Line three phase four wire on 8 mtr long PCC poles, 30 mm sq. ACSR Weasel Conductor for Creation of 25 KVA Sub Station at Sui Battal.
8 mtr. Long PCC Pole (WL 200kg)
GI U clamps for Shackle Insulator
30 mm sq. ACSR Weasel Conductor
Shackle Insulator
Galvanized Nuts and Bolts
Danger Plates with clamps
Anti Climbing device with clamps
Earthing complete by GI Rod 20 mm, 2.5 mtr long through G.I. Strip 25X3 mm
Survey, Supply, Transportation, Carriage, Erection, Testing and Commissioning for Erection of 11 KV line on 9 mtr long PCC poles, 30 mm sq. ACSR Weasel Conductor for Creation of 25 KVA Sub Station at Dhanori.
9 mtr. Long PCC Pole (To be issued by Department at Divisional Sore of Electric Divisional JPDCL Udhampur)
GI V Cross -arm with top Bracket including clamps
GI Channel X-arm including clamps and Angle for braces
30 mm sq. ACSR Weasel conductor
11 KV Polymer composite Pin Insulator 12 KV, 5 KN, lighting impulse 75 KV Positive and 80 KV Negative, Creepage distance 320mm.
11 KV Polymeric Composite Disc insulator 12 KV, min failing load 45 kn, lightening impulse 75 Positive and 80 KV Negative, creepage distance 320mm with fitting
Galvanized Nuts and Bolts
Danger Plates with clamps
Anti Climbing device with clamps
Earthing complete by GI Rod 20 mm, 2.5 mtr long through G.I. Strip
Survey, Supply, Transportation, Carriage, Erection, Testing and Commissioning for Creation of 25 KVA Sub Station at Dhanori.
11/0.433kV, 3-phase 25 KVA Distribution Transformer with Bimetallic Terminal Connectors Energy Level-2, Aluminium wound, and with LV Cable Box having detachable Aluminium Gland plate.
Gapless surge arrestor 9KV, 10KA, LA with polymer housing station type
11 KV GO, AB Switch 3-phase, 3-pole, 200 Amp. Vertical
11 kV Horn Gap Fuse Set 3 Phase 200A
95 mm² Single Core Cable,1.1kV Grade, PVC Insulated Alumnium Stranded Conductor FRLS type
9 mtr. Long PCC Pole (PCC-WL-300 kg)
11kV Polymeric composite Disc Insulator 12kV, min failing load 45kN, Lightening Impulse 75kV Positive and 80kV Negative, creepage distance 320mm with fitting
GI Channel/Angle/Flat of sizes including clamps
Galvanized Nuts and Bolts.
LT Fuse Switch made of angle Iron 50X50X6, with aluminium Bus Bar strip 50X6mm fixed on Bus Bar Insualtor including clamps for fixing of switch
Cement Bottoming 1:2:4 mix as per REC Standard 0.5 cum per pole
Earthing of substation --Excavation of earth pit of dia 650 mm & depth 3000 mm, installation of Earthing pipe of 40 mm Nominal bore & 4mm wall thickness & length 2.5 mtr long as Per IS 1239. GI Strip for neutral earthing of size 50 mm x 6 mm & 32mm x 3mm for connection of transformer body, G.O Set & lightening arrestor as per IS 2629/85, GI nuts & bolts,refilled with earth enhancement materials and earth Chamber with RCC slab cover.
Survey, Supply, Transportation, Carriage, Erection, Testing and Commissioning for Erection of LT Line three phase four wire on 8 mtr long PCC poles, 30 mm sq. ACSR Weasel Conductor for Creation of 25 KVA Sub Station at Dhanori.
8 mtr. Long PCC Pole (WL 200kg)
GI U clamps for Shackle Insulator
30 mm sq. ACSR Weasel Conductor
Shackle Insulator
Galvanized Nuts and Bolts
Danger Plates with clamps
Anti Climbing device with clamps
Earthing complete by GI Rod 20 mm, 2.5 mtr long through G.I. Strip 25X3 mm
Survey, Supply, Transportation, Carriage, Erection, Testing and Commissioning for Erection of 11 KV line on 9 mtr long ST poles, 30 mm sq. ACSR Weasel Conductor for Creation of 25 KVA Sub Station at Peoni Nali.
9 mtr. Long ST Pole (To be issued by Department at Divisional Sore of Electric Divisional JPDCL Udhampur)
GI V Cross -arm with top Bracket including clamps
GI Channel X-arm including clamps and Angle for braces
30 mm sq. ACSR Weasel conductor
11 KV Polymer composite Pin Insulator 12 KV, 5 KN, lighting impulse 75 KV Positive and 80 KV Negative, Creepage distance 320mm.
11 KV Polymeric Composite Disc insulator 12 KV, min failing load 45 kn, lightening impulse 75 Positive and 80 KV Negative, creepage distance 320mm with fitting
Galvanized Nuts and Bolts
Earthing complete by GI Rod 20 mm, 2.5 mtr long through G.I. Strip
Cement Bottoming 1:2:4 mix as per REC Standard 0.5 cum per pole
Survey, Supply, Transportation, Carriage, Erection, Testing and Commissioning for Creation of 25 KVA Sub Station at Peoni Nali.
11/0.433kV, 3-phase 25 KVA Distribution Transformer with Bimetallic Terminal Connectors Energy Level-2, Aluminium wound, and with LV Cable Box having detachable Aluminium Gland plate.
Gapless surge arrestor 9KV, 10KA, LA with polymer housing station type
11 KV GO, AB Switch 3-phase, 3-pole, 200 Amp. Vertical
11 kV Horn Gap Fuse Set 3 Phase 200A
95 mm² Single Core Cable,1.1kV Grade, PVC Insulated Alumnium Stranded Conductor FRLS type
9 mtr. Long PCC Pole (PCC-WL-300 kg)
11kV Polymeric composite Disc Insulator 12kV, min failing load 45kN, Lightening Impulse 75kV Positive and 80kV Negative, creepage distance 320mm with fitting
GI Channel/Angle/Flat of sizes including clamps
Galvinized Nuts and Bolts.
LT Fuse Switch made of angle Iron 50X50X6, with aluminium Bus Bar strip 50X6mm fixed on Bus Bar Insualtor including clamps for fixing of switch
Cement Bottoming 1:2:4 mix as per REC Standard 0.5 cum per pole
Earthing of substation --Excavation of earth pit of dia 650 mm & depth 3000 mm, installation of Earthing pipe of 40 mm Nominal bore & 4mm wall thickness & length 2.5 mtr long as Per IS 1239. GI Strip for neutral earthing of size 50 mm x 6 mm & 32mm x 3mm for connection of transformer body, G.O Set & lightening arrestor as per IS 2629/85, GI nuts & bolts,refilled with earth enhancement materials and earth Chamber with RCC slab cover.
Survey, Supply, Transportation, Carriage, Erection, Testing and Commissioning for Erection of LT Line three phase four wire on 8 mtr long PCC poles, 30 mm sq. ACSR Weasel Conductor for Creation of 25 KVA Sub Station at Peoni Nali.
8 mtr. Long PCC Pole (WL 200kg)
GI U clamps for Shackle Insulator
30 mm sq. ACSR Weasel Conductor
Shackle Insulator
Galvanized Nuts and Bolts
Danger Plates with clamps
Anti Climbing device with clamps
Earthing complete by GI Rod 20 mm, 2.5 mtr long through G.I. Strip 25X3 mm
Survey, Supply, Transportation, Carriage, Erection, Testing and Commissioning for Erection of 11 KV line on 9 mtr long PCC poles, 30 mm sq. ACSR Weasel Conductor for Creation of 25 KVA Sub Station at Gadana Majalta.
9 mtr. Long PCC Pole (To be issued by Department at Divisional Sore of Electric Divisional JPDCL Udhampur)
GI V Cross -arm with top Bracket including clamps
GI Channel X-arm including clamps and Angle for braces
30 mm sq. ACSR Weasel conductor
11 KV Polymer composite Pin Insulator 12 KV, 5 KN, lighting impulse 75 KV Positive and 80 KV Negative, Creepage distance 320mm.
11 KV Polymeric Composite Disc insulator 12 KV, min failing load 45 kn, lightening impulse 75 Positive and 80 KV Negative, creepage distance 320mm with fitting
Galvanized Nuts and Bolts
Danger Plates with clamps
Anti Climbing device with clamps
Earthing complete by GI Rod 20 mm, 2.5 mtr long through G.I. Strip
Survey, Supply, Transportation, Carriage, Erection, Testing and Commissioning for Creation of 25 KVA Sub Station at Gadana Majalta.
11/0.433kV, 3-phase 25 KVA Distribution Transformer with Bimetallic Terminal Connectors Energy Level-2, Aluminium wound, and with LV Cable Box having detachable Aluminium Gland plate.
Gapless surge arrestor 9KV, 10KA, LA with polymer housing station type
11 KV GO, AB Switch 3-phase, 3-pole, 200 Amp. Vertical
11 kV Horn Gap Fuse Set 3 Phase 200A
95 mm² Single Core Cable,1.1kV Grade, PVC Insulated Alumnium Stranded Conductor FRLS type
9 mtr. Long PCC Pole (PCC-WL-300 kg)
11kV Polymeric composite Disc Insulator 12kV, min failing load 45kN, Lightening Impulse 75kV Positive and 80kV Negative, creepage distance 320mm with fitting
GI Channel/Angle/Flat of sizes including clamps
Galvinized Nuts and Bolts.
LT Fuse Switch made of angle Iron 50X50X6, with aluminium Bus Bar strip 50X6mm fixed on Bus Bar Insualtor including clamps for fixing of switch
Cement Bottoming 1:2:4 mix as per REC Standard 0.5 cum per pole
Earthing of substation --Excavation of earth pit of dia 650 mm & depth 3000 mm, installation of Earthing pipe of 40 mm Nominal bore & 4mm wall thickness & length 2.5 mtr long as Per IS 1239. GI Strip for neutral earthing of size 50 mm x 6 mm & 32mm x 3mm for connection of transformer body, G.O Set & lightening arrestor as per IS 2629/85, GI nuts & bolts,refilled with earth enhancement materials and earth Chamber made of brick masonary with RCC slab cover.
Survey, Supply, Transportation, Carriage, Erection, Testing and Commissioning for Erection of LT Line three phase four wire on 8 mtr long PCC poles, 30 mm sq. ACSR Weasel Conductor for Creation of 25 KVA Sub Station at Gadana Majalta.
8 mtr. Long PCC Pole (WL 200kg)
GI U clamps for Shackle Insulator
30 mm sq. ACSR Weasel Conductor
Shackle Insulator
Galvanized Nuts and Bolts
Danger Plates with clamps
Anti Climbing device with clamps
Earthing complete by GI Rod 20 mm, 2.5 mtr long through G.I. Strip 25X3 mm
Survey, Supply, Transportation, Carriage, Erection, Testing and Commissioning for Erection of 11 KV line on 9 mtr long PCC poles, 30 mm sq. ACSR Weasel Conductor for Creation of 25 KVA Sub Station at Sui Ward No. 06.
9 mtr. Long PCC Pole (To be issued by Department at Divisional Sore of Electric Divisional JPDCL Udhampur)
GI V Cross -arm with top Bracket including clamps
GI Channel X-arm including clamps and Angle for braces
30 mm sq. ACSR Weasel conductor
11 KV Polymer composite Pin Insulator 12 KV, 5 KN, lighting impulse 75 KV Positive and 80 KV Negative, Creepage distance 320mm.
11 KV Polymeric Composite Disc insulator 12 KV, min failing load 45 kn, lightening impulse 75 Positive and 80 KV Negative, creepage distance 320mm with fitting
Galvanized Nuts and Bolts
Danger Plates with clamps
Anti Climbing device with clamps
Earthing complete by GI Rod 20 mm, 2.5 mtr long through G.I. Strip
Survey, Supply, Transportation, Carriage, Erection, Testing and Commissioning for Creation of 25 KVA Sub Station at Sui Ward No. 06.
11/0.433kV, 3-phase 25 KVA Distribution Transformer with Bimetallic Terminal Connectors Energy Level-2, Aluminium wound, and with LV Cable Box having detachable Aluminium Gland plate.
Gapless surge arrestor 9KV, 10KA, LA with polymer housing station type
11 KV GO, AB Switch 3-phase, 3-pole, 200 Amp. Vertical
11 kV Horn Gap Fuse Set 3 Phase 200A
95 mm² Single Core Cable,1.1kV Grade, PVC Insulated Alumnium Stranded Conductor FRLS type
9 mtr. Long PCC Pole (PCC-WL-300 kg)
11kV Polymeric composite Disc Insulator 12kV, min failing load 45kN, Lightening Impulse 75kV Positive and 80kV Negative, creepage distance 320mm with fitting
GI Channel/Angle/Flat of sizes including clamps
Galvinized Nuts and Bolts.
LT Fuse Switch made of angle Iron 50X50X6, with aluminium Bus Bar strip 50X6mm fixed on Bus Bar Insualtor including clamps for fixing of switch
Cement Bottoming 1:2:4 mix as per REC Standard 0.5 cum per pole
Earthing of substation --Excavation of earth pit of dia 650 mm & depth 3000 mm, installation of Earthing pipe of 40 mm Nominal bore & 4mm wall thickness & length 2.5 mtr long as Per IS 1239. GI Strip for neutral earthing of size 50 mm x 6 mm & 32mm x 3mm for connection of transformer body, G.O Set & lightening arrestor as per IS 2629/85, GI nuts & bolts,refilled with earth enhancement materials and earth Chamber made of brick masonary with RCC slab cover.
Survey, Supply, Transportation, Carriage, Erection, Testing and Commissioning for Erection of LT Line three phase four wire on 8 mtr long PCC poles, 30 mm sq. ACSR Weasel Conductor for Creation of 25 KVA Sub Station at Sui Ward No. 06.
8 mtr. Long PCC Pole (WL 200kg)
GI U clamps for Shackle Insulator
30 mm sq. ACSR Weasel Conductor
Shackle Insulator
Galvanized Nuts and Bolts
Earthing complete by GI Rod 20 mm, 2.5 mtr long through G.I. Strip 25X3 mm
JAI CHANDI MAA ENTERPRISES
M/S D.K TRADERS
tech_eval.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .