| 1 | L1₹1.2 CrAccepted-AOC MANEGAON CHAMPANAGAR KHAMARIA JABALPUR 482005 MP | JABALPUR | JABALPUR | MP | 482005 | ₹1.2 Cr | L1 | Accepted-AOC BEING LOWEST REASONABLE BIDDER |
| 2 | L2₹1.3 CrRejected-Finance MAIN ROAD RANJHI JABALPUR 482005 M P | JABALPUR | MADHYA PRADESH | 482005 | ₹1.3 Cr | L2 | Rejected-Finance OTHER THAN LOWEST BIDDER |
| 3 | L3₹1.3 CrRejected-Finance B 87 SHAM NAGAR KHYALA ROAD NEW DELHI 110018 | WEST | DELHI | 110018 | ₹1.3 Cr | L3 | Rejected-Finance OTHER THAN LOWEST BIDDER |
| Sl No | Description | Qty | Unit | ASHOKA ASSOCIATES L1 | RAVINDRA ELECTRICAL L2 | New Era Engineers L3 |
|---|---|---|---|---|---|---|
| 1.00 | Excavation in trenches, n exc 1.5m wide and n exc 1.5m in depth , for foundation, etc or for shafts, wells, cesspits, manholes, pier holes, laying of cables etc. n exc 10sqm on plan and n exc 1.5m in depth and getting out in any type of soil | 821.9 | Cum | 150 ₹1,23,285 | 200 ₹1,64,380 | 130 ₹1,06,847 |
| 2.00 | M&L for sand cushioning to underground cable providing with a layer 8 cm before laying and 15 cm after laying, jointing and testing the cable all as specified and directed.
Note: Punned thickness of sand shall be measured. | 379.89 | Cum | 700 ₹2,65,923 | 700 ₹2,65,923 | 1,000 ₹3,79,890 |
| 3.00 | Supply and laying the Brick covering with width equal to length of brick as mechanical protection to cable with well burnt sub class ‘B’ bricks laid dry flat complete all as specified and directed by Engr in charge. | 39.74 | EACH 1000 | 5,500 ₹2,18,570 | 7,000 ₹2,78,180 | 6,000 ₹2,38,440 |
| 4.00 | M/L for Removing excavated material to a distance n exc 50m and depositing where directed at a level n exc 1.5m above the starting point complete all as specified and as directed. | 573.82 | Cum | 40 ₹22,952.8 | 50 ₹28,691 | 20 ₹11,476.4 |
| 5.00 | M/L for Returning , filling in, including spreading, leveling, watering and well ramming in layers not exc 25 cm complete all as specified and as directed. | 1,040.71 | Cum | 40 ₹41,628.4 | 50 ₹52,035.5 | 10 ₹10,407.1 |
| 6.00 | Taking down existing worn out/old/broken ACSR conductors of any size and length at any position from LT poles and supply, fixing and stretching new ACSR conductors of any size and type for over head LT poles including binding at site to insulator with suitable size of binding wire etc complete all as specified and directed by Engr in charge. | 2.6 | Qtl | 30,000 ₹78,000 | 17,500 ₹45,500 | 22,000 ₹57,200 |
| 7.00Supply, laying or fixing or passing through pipe commissioning and testing of PVC / XLPE insulated, armoured heavy duty, electric cable with aluminium conductor, 1100 volts grade of the following cross section area including suitable size lugs including taking out /dismantling of existing cable. Note:- Excavation & earth work, sand cushioning, bricks protection & GI pipe where required shall be measured & paid separately under relevant items:- | ||||||
| 8.00 | (a) 10 Sqmm 4 core | 815 | RM | 110 ₹89,650 | 111 ₹90,465 | 160 ₹1,30,400 |
| 9.00 | (b) 16 Sqmm 4 core | 1,080 | RM | 150 ₹1,62,000 | 145 ₹1,56,600 | 175 ₹1,89,000 |
| 10.00 | (c) 25 Sqmm 4 core | 1,300 | RM | 185 ₹2,40,500 | 209 ₹2,71,700 | 225 ₹2,92,500 |
Tender Value
₹1.4 Cr
EMD Value
₹2.1 L
Closing Date
6 Dec 2025, 6:00 pmClosed
CWE JABALPUR
HQ COMMANDER WORKS ENGINEER, SUPPLY MARG, P B NO. 54, JABALPUR
REPAIR AND MAINT OF LT UG CABLE AND OTHER CONNECTED WORKS AND MAINTENANCE OF INTERNAL ELECTRIC SERVICES AND ALLIED WORK IN AOR OF MH, MDC, ECHS AND REPAIR AND MAINT OF LT POLES, ACSR CONDUCTOR, CROSS ARM, JUMPERS, LT PANEL, APFC PANELS ETC
2025_MES_737890_1
81146/E8
Open Tender
Electrical and Maintenance Works
270 days
JABALPUR
As per NIT
7 documents required · 7 mandatory
₹1,000
GE (WEST) JABALPUR
₹2.1 L
Yes
27 Feb 2026
31 Oct 2025
13 Dec 2025
31 Oct 2025
6 Dec 2025
22 Nov 2025
31 Oct 2025 - 21 Nov 2025
Amount
Excavation in trenches, n exc 1.5m wide and n exc 1.5m in depth , for foundation, etc or for shafts, wells, cesspits, manholes, pier holes, laying of cables etc. n exc 10sqm on plan and n exc 1.5m in depth and getting out in any type of soil
M&L for sand cushioning to underground cable providing with a layer 8 cm before laying and 15 cm after laying, jointing and testing the cable all as specified and directed. Note: Punned thickness of sand shall be measured.
Supply and laying the Brick covering with width equal to length of brick as mechanical protection to cable with well burnt sub class ‘B’ bricks laid dry flat complete all as specified and directed by Engr in charge.
M/L for Removing excavated material to a distance n exc 50m and depositing where directed at a level n exc 1.5m above the starting point complete all as specified and as directed.
M/L for Returning , filling in, including spreading, leveling, watering and well ramming in layers not exc 25 cm complete all as specified and as directed.
Taking down existing worn out/old/broken ACSR conductors of any size and length at any position from LT poles and supply, fixing and stretching new ACSR conductors of any size and type for over head LT poles including binding at site to insulator with suitable size of binding wire etc complete all as specified and directed by Engr in charge.
Supply, laying or fixing or passing through pipe commissioning and testing of PVC / XLPE insulated, armoured heavy duty, electric cable with aluminium conductor, 1100 volts grade of the following cross section area including suitable size lugs including taking out /dismantling of existing cable. Note:- Excavation & earth work, sand cushioning, bricks protection & GI pipe where required shall be measured & paid separately under relevant items:-
(a) 10 Sqmm 4 core
(b) 16 Sqmm 4 core
(c) 25 Sqmm 4 core
(d) 35 Sqmm 3.5 core
(e) 50 Sqmm 3.5 core
(f) 70 Sqmm 3.5 core
(g) 95 Sqmm 3.5 core
(j) 120 Sqmm 3.5 core
(k) 150 Sqmm 3.5 core
(l) 185 Sqmm 3.5 core
(m) 240 Sqmm 3.5 core
Taking down old u/s cable any type any size
M&L for GI Tubes in repair of following size, medium grade ,galvanised , with clamp of 25x3 flat iron welded to pipe fixed to wall/pole/ceiling or laid in floors or under road etc complete all as specified and as directed.
(a) 40 mm bore
(b) 50 mm bore
(c) 80 mm bore
Taking down old u/s GI pipe any type any size
Supply, laying & fixing in repair double wall corrugated (DWC) pipes made of high density polythyline (HDPE) with all accessories i.e. all type of joints, Sockets, Elbows, bends and End caps etc. all as specified and directed by Engr in Charge.of size 50 mm outer dia and 38 mm inner dia.
Supply and fixing MCCB 4 pole 63 Amps rupturing capacity 16 KA, with connecting links on LT panel/feeder pillar including dismantling/taking down existing unserviceable MCCB complete all as specified and directed.
Supply and fixing MCCB 4 pole 100 Amps rupturing capacity 16 KA, with connecting links on LT panel/feeder pillar including dismantling/taking down existing unserviceable MCCB complete all as specified and directed.
Supply and fixing MCCB 4 pole 160 Amps rupturing capacity 36 KA, with connecting links on LT panel/feeder pillar including dismantling/taking down existing unserviceable MCCB complete all as specified and directed.
Supply and fixing MCCB 4 pole 200 Amps rupturing capacity 36 KA, with connecting links on LT panel/feeder pillar including dismantling/taking down existing unserviceable MCCB complete all as specified and directed.
Supply and fixing MCCB 4 pole 250 Amps rupturing capacity 36 KA, with connecting links on LT panel/feeder pillar including dismantling/taking down existing unserviceable MCCB complete all as specified and directed.
Supply and fixing MCCB 4 pole 350 Amps rupturing capacity 36 KA with connecting links on LT panel/feeder pillar including dismantling/taking down existing unserviceable MCCB complete all as specified and directed.
Supply and fixing MCCB 4 pole 400 Amps rupturing capacity 36 KA with connecting links on LT panel/feeder pillar including dismantling/taking down existing unserviceable MCCB complete all as specified and directed.
Supply and fixing MCCB 4 pole 630 Amps rupturing capacity 50 KA, with connecting links on LT panel/feeder pillar including dismantling/taking down existing unserviceable MCCB complete all as specified and directed.
Supplying and fixing in repair1100 volts grade heavy duty cable PVC insulated aluminium conductor 10 sqmm, served with inner sheathing of PVC tape and overall PVC sheathed in service connections suspended by insulating hangers not more than 1 metre apart including 4mm suspension wire, one twin core cable flat or circular.
Trimming of tree branches 4 metre all around, from the LT/HT pole, for clearing of LT/HT line, by cutting tree branches, any numbers and of any girth, on any number of conductors/earth wire complete all as specified and as directed by Engr- in- Charge. (Notes : (i) The above work includes cleaning/ pruning of tree branches falling around the conductors (ii) One length shall be measured for complete span of 4/5/6 conductors & GI wire.)
Re - stretching only of existing ACSR of any size, on HT/ LT pole including binding the ACSR with insulators, seperators, aluminium binding wire complete all as specified and as directed. (Note : One length shall be measured for complete span of 4/5/6 conductors & GI wire.)
S&F in repair change over switch 100 Amps ON load in sheet enclosure four pole to be fixed on wall with FI 32X6mm, nuts, bolts, washers etc. complete with all electric connection complete all as specified and directed.
S&F in repair change over switch 200 Amps ON load in sheet enclosure four pole to be fixed on wall with FI 32X6mm, nuts, bolts, washers etc. complete with all electric connection complete all as specified and directed.
Supply & installation of PCC cable route indicator made from M20 grade concrete or equivalent designed to indicate the route of LT underground cables at regular intervals, turning points, junctions etc. Indicator shall be of standard size ( typically not less than 100mm x 100mm x 600mm) with "BLUE" colour engraved cable route markings for clear visibility. The PCC indicator shall be cured, finished & installed vertically in ground with proper alignment and spacing as per site requirements or directed & specified by Engr in charge. Note : All materials, labour, tools required for proper installation shall be included in this item.
S&F in repair change over switch 250 Amps ON load mounted inside chamber box made of 3.15 mm thick CRCA sheet enclosure four pole with FI 32X6mm, nuts, bolts, washers etc. complete with all electric connection. The chamber shall be painted with powder coated paint (Shade : RAL-7032) after 7 tank pre-treatment of surfaces. The bus bar chamber shall be provided with suitable Neoprene rubber gasket to make it completely dust and vermin proof and degree of protection not less than IP-55 and general construction conforming to IS : 13947. The bus bar chamber shall be made of 3.15mm thick CRCA mild steel sheet and 3.00mm thick gland plate , front door (01 layer) and rear Door (01 layer) opening facility and 4 side slanting canopy type roof on top and mild steel channel (75 MC) base frame at bottom. (Note : The bus bar chamber Box shall be designed in such a way that adequate workable space is made available inside the compartments and the size of the chamber shall not be less than 500mm height (without base frame & canopy), 500mm width and 450mm depth).
S&F in repair change over switch 315 Amps ON load mounted inside chamber box made of 3.15 mm thick CRCA sheet enclosure four pole with FI 32X6mm, nuts, bolts, washers etc. complete with all electric connection. The chamber shall be painted with powder coated paint (Shade : RAL-7032) after 7 tank pre-treatment of surfaces. The bus bar chamber shall be provided with suitable Neoprene rubber gasket to make it completely dust and vermin proof and degree of protection not less than IP-55 and general construction conforming to IS : 13947. The bus bar chamber shall be made of 3.15mm thick CRCA mild steel sheet and 3.00mm thick gland plate , front door (01 layer) and rear Door (01 layer) opening facility and 4 side slanting canopy type roof on top and mild steel channel (75 MC) base frame at bottom. (Note : The bus bar chamber Box shall be designed in such a way that adequate workable space is made available inside the compartments and the size of the chamber shall not be less than 500mm height (without base frame & canopy), 500mm width and 450mm depth).
S&F in repair change over switch 400 Amps ON load mounted inside chamber box made of 3.15 mm thick CRCA sheet enclosure four pole with FI 32X6mm, nuts, bolts, washers etc. complete with all electric connection. The chamber shall be painted with powder coated paint (Shade : RAL-7032) after 7 tank pre-treatment of surfaces. The bus bar chamber shall be provided with suitable Neoprene rubber gasket to make it completely dust and vermin proof and degree of protection not less than IP-55 and general construction conforming to IS : 13947. The bus bar chamber shall be made of 3.15mm thick CRCA mild steel sheet and 3.00mm thick gland plate , front door (01 layer) and rear Door (01 layer) opening facility and 4 side slanting canopy type roof on top and mild steel channel (75 MC) base frame at bottom. (Note : The bus bar chamber Box shall be designed in such a way that adequate workable space is made available inside the compartments and the size of the chamber shall not be less than 500mm height (without base frame & canopy), 500mm width and 450mm depth).
S&F in repair change over switch 630 Amps ON load mounted inside chamber box made of 3.15 mm thick CRCA sheet enclosure four pole with FI 32X6mm, nuts, bolts, washers etc. complete with all electric connection. The chamber shall be painted with powder coated paint (Shade : RAL-7032) after 7 tank pre-treatment of surfaces. The bus bar chamber shall be provided with suitable Neoprene rubber gasket to make it completely dust and vermin proof and degree of protection not less than IP-55 and general construction conforming to IS : 13947. The bus bar chamber shall be made of 3.15mm thick CRCA mild steel sheet and 3.00mm thick gland plate , front door (01 layer) and rear Door (01 layer) opening facility and 4 side slanting canopy type roof on top and mild steel channel (75 MC) base frame at bottom. (Note : The bus bar chamber Box shall be designed in such a way that adequate workable space is made available inside the compartments and the size of the chamber shall not be less than 500mm height (without base frame & canopy), 500mm width and 450mm depth).
Taking down carefully any type of old unserviceable point wiring copper or aluminium conductor (light, fan, socket, bell or power) point complete with fittings such as switches, ceiling roses, lamp holders, sockets, fan regulators, call bell, light fittings with PVC conduit surface / concealed or wooden battens including sunken cast iron / pressed steel terminal boxes etc complete all as specified & directed . (Note: Painting work shall be measured and paid seperately under respective items.)
Taking down carefully any type of old unserviceable submain wiring with PVC conduit surface / concealed or wooden battens etc complete all as specified & directed .
M&L for preparing old plastered or unplastered surfaces of walls and applying two coats of cement based paint complete all as specified and directed.
M&L for provision of sub main wiring with two runs of single core FRLSH PVC insulated, unsheathed, mutistranded copper conductor cable of size 4.0 sqmm drawn in and including rigid PVC conduit medium grade ISI marked not less than 20mm dia with its accessories, concealed type, including one run of single core FRLSH PVC insulated, unsheathed, multistranded copper conductor cable of size 4 sqmm as earth continuity and cutting chases as per standard engineering practice & making good the disturbed surfaces as per existing finish complete all as specified & directed. Notes:- (i) Finished sub main wiring with two runs of 4.0 sqmm cable & one run of 4 sqmm cable alongwith PVC conduit and its accessories shall be measured and paid as one unit length. (ii) Connections of cables with MCBs or bus bars shall be done through appropriate size brass/copper thimbles. (iii) Colour coding for wiring/ bus bar/ main connection shall be followed .
M&L for provision of sub main wiring with two runs of single core FRLSH PVC insulated, unsheathed, mutistranded copper conductor cable of size 6.0 sqmm drawn in and including rigid PVC conduit medium grade ISI marked not less than 25mm dia with its accessories, concealed type, including one run of single core FRLSH PVC insulated, unsheathed, multistranded copper conductor cable of size 6 sqmm as earth continuity and cutting chases as per standard engineering practice & making good the disturbed surfaces as per existing finish complete all as specified & directed. Notes:- (i) Finished sub main wiring with two runs of 6.0 sqmm cable & one run of 6 sqmm cable alongwith PVC conduit and its accessories shall be measured and paid as one unit length. (ii) Connections of cables with MCBs or bus bars shall be done through appropriate size brass/copper thimbles. (iii) Colour coding for wiring/ bus bar/ main connection shall be followed .
M&L for provision of sub main wiring with two runs of single core FRLSH PVC insulated, unsheathed, mutistranded copper conductor cable of size 10.0 sqmm drawn in and including rigid PVC conduit medium grade ISI marked not less than 25mm dia with its accessories, concealed type, including one run of single core FRLSH PVC insulated, unsheathed, multistranded copper conductor cable of size 10 sqmm as earth continuity and cutting chases as per standard engineering practice & making good the disturbed surfaces as per existing finish complete all as specified & directed. Notes:- (i) Finished sub main wiring with two runs of 10.0 sqmm cable & one run of 10 sqmm cable alongwith PVC conduit and its accessories shall be measured and paid as one unit length. (ii) Connections of cables with MCBs or bus bars shall be done through appropriate size brass/copper thimbles. (iii) Colour coding for wiring/ bus bar/ main connection shall be followed .
Material & Labour for point wiring with three layer PVC Insulated 1.5 Sqmm multi-strand copper conductor FRLSH cable 1100 Volts grade drawn into and concealed PVC conduits medium grade not less than 20mm( ISI marked) including all fitting and fixing accessories including 1.25 mm thick sunken pressed steel terminal boxes/Modular metal flush box duly painted with two coats of anti-corrosive paint outside and two coats of aluminium paint inside with and including 3mm thick hylam brand laminated white bakelite sheet cover for mounting switches, sockets, fan regulators fixed with CP screws with cup wahsers and PVC insulated 1.5 Sqmm multi-strand copper conductor cable as earth wire and making good the disturbed surfaces with cement sand mortar 1:3 to match with the existing surfaces complete all as specified & directed by Engineer-in-charge for One light Point controlled by one switch.
….do…. but for one Fan Point controlled by one switch.
….do…. but for one Bell Point controlled by one switch.
….do…. but for one socket point 5 Amp controlled by one switch on same board.
….do…. but for one socket point 5 Amp controlled by one switch on Independent board.
….do…. but for one light point controlled by two way switch.
M&L for Point wiring with three layer PVC insulated 2.5 sqmm multi stranded copper conductor FRLS cable 1100 volts grade for 3/6 pin switch socket outlet 15 Amp on independent board, drawn into the concealed conduits including all fitting and fixing accessories including sunken pressed steel terminal boxes suitable of modular switches /sockets and including inner/ outer plates cover for mounting /modular switches sockets ,modular fan regulators fixed with CP screws with cup washers and PVC insulated 2.5 sqmm multi stranded copper conductor cable as earth wire and making good the disturbed surfaces with cement sand mortar all as specified and directed by Engineer in charge .
Material & Labour for point wiring with three layer PVC Insulated 1.5 Sqmm multi-stranded copper conductor FRLSH cable 1100 Volts grade drawn into the existing conduits including all fitting and fixing accessories including 1.25 mm thick sunken pressed steel terminal boxes duly painted with two coats of anti-corrosive paint outside and two coats of aluminium paint inside with and including 3mm thick hylam brand laminated white bakelite sheet cover for mounting switches, sockets, fan regulators fixed with CP screws with cup wahsers and PVC insulated 1.5 Sqmm multi-strand copper conductor cable as earth wire and making good the disturbed surfaces with cement sand mortar 1:3 to match with the existing surfaces complete all as specified & directed by Engineer-in-charge for one light Point controlled by one switch.
….do…. but for one Fan Point controlled by one switch.
….do…. but for one Bell Point controlled by one switch.
….do…. but for one socket point 5 Amp controlled by one switch on same board.
….do…. but for one socket point 5 Amp controlled by one switch on Independent board.
….do…. but for one light point controlled by two way switch.
M&L for Point wiring with three layer PVC insulated 2.5 sqmm multi stranded copper conductor FRLS cable 1100 volts grade for 3/6 pin switch socket outlet 15 Amp on independent board, drawn into the existing conduits including all fitting and fixing accessories including sunken pressed steel terminal boxes suitable of modular switches /sockets and including inner/ outer plates cover for mounting /modular switches sockets ,modular fan regulators fixed with CP screws with cup washers and PVC insulated 2.5 sqmm multi stranded copper conductor cable as earth wire and making good the disturbed surfaces with cement sand mortar all as specified and directed by Engineer in charge .
M&L for point wiring in PVC casing and caping complete with FRLSH PVC insulated, unsheathed stranded copper conductor of nominal area 1.5 Sqmm, 1100 volts grade, along with one single run of same size and type of copper wire as continuous earth wire to common earth dolly in and sunken terminal boxes pressed MS/GI steel terminal boxes not less than 1.20 mm thick for mounting switch, socket etc including 3 mm thick Hylam brand sunmica laminated sheet cover or inner outer plates for modular switches with brass screw and cup washers with all accessories and making good the disturbed surface with cement mortar in 1:3 and applying white/colour wash, oil bound or cement base paint etc to match with existing surface complete all as specified and directed
….do…. but for one socket point 5 Amp controlled by one switch on same board.
….do…. but for one socket point 5 Amp controlled by one switch on Independent board.
….do…. but for one light point controlled by two way switch.
M&L for Point wiring with three layer PVC insulated 2.5 sqmm multi stranded copper conductor FRLSH cable 1100 volts grade for 3/6 pin switch socket outlet 15 Amp on independent board, drawn in with casing and caping point wiring using 2.5 Sqmm (Nominal area)triple layer FRLSH PVC insulated unsheathed copper conductor 1100 volts for one 3/6 pin socket outlet ,suitable for 6/16 amps on “independent board” with 2.5 sqmm one single run copper wire as continuous earth wire to common earth dolly and making good the disturbed surfaces to match with the existing finish complete all as specified and directed .
S&F call bell ding dong sound type suitable for AC 230 volt single pole complete all as specified & directed.
S&F switch bell push flush type suitable for 5 Amp 230 Volt of polycarbonate body complete all as specified & directed.
S&F switch piano flush type suitable for 5 Amp 230 Volt of polycarbonate body complete all as specified & directed.
S&F socket outlet 2 in 1, 5 Pin 5 Amp flush type of polycarbonate body complete all as specified & directed.
S&F Switch socket combination 5 in 1, 5 pin 5/6 Amps flush type universal of polycabonate body complete all as specified & directed.
S&F Switch socket combination 5 in 1, 5 pin 6/16 Amps flush type universal of polycabonate body complete all as specified & directed.
S&F lamp holder / batten or angle holder Insulated body incl 9 w LED bulb with back plate suitable for batten fittings complete all as specified & directed
S&F Ceiling rose surface type 60x30 mm three terminals of polycarbonate body complete all as specified & directed.
S&F Ceiling Fan regulator electronic type 120 Watt capacity of polycarbonate body ISI marked complete all as specified & directed.
S&F in replacement of frame plate for modular switch 1 module including screws and washers etc model/make as per existing in site complete all as specified and as directed.
S&F in replacement of frame plate for modular switch 2 module including screws and washers etc model/make as per existing in site complete all as specified and as directed.
S&F in replacement of frame plate for modular switch 3 module including screws and washers etc model/make as per existing in site complete all as specified and as directed.
S&F in replacement of frame plate for modular switch 4 module including screws and washers etc model/make as per existing in site complete all as specified and as directed.
S&F in replacement of frame plate for modular switch 6 module including screws and washers etc model/make as per existing in site complete all as specified and as directed.
S&F in replacement of frame plate for modular switch 8 module including screws and washers etc model/make as per existing in site complete all as specified and as directed.
S&F in replacement MS Housing box 1/2 module suitable for modular switch as per existing switch box and making good to the disturb surface complete all as specified and as directed.
S&F in replacement MS Housing box 3 module suitable for modular switch as per existing switch box and making good to the disturb surface complete all as specified and as directed.
S&F in replacement MS Housing box 4/5 module suitable for modular switch as per existing switch box and making good to the disturb surface complete all as specified and as directed.
S&F in replacement MS Housing box 6/8 module suitable for modular switch as per existing switch box and making good to the disturb surface complete all as specified and as directed.
S&F in replacement of modular switch 6-10 Amps one module 230 volts AC as per existing model/make complete all as specified and as directed
S&F in replacement of modular switch 16 Amps one module 230 volts AC as per existing model/make complete all as specified and as directed
S&F in replacement of modular socket, 6A -2/3 pin combined 2 module, 230 volts AC as per existing model/make complete all as specified and as directed.
S&F in replacement of modular socket, 6/16A -2/3 pin combined 2 module, 230 volts AC as per existing model/make complete all as specified and as directed .
S&F in replacement modular fan regulator, 2 Module 4 step 180w heavy duty 230 volts as per existing model/make complete all as specified and as directed.
S&F in replacement of 3mm thick hylam sheet of any size including brass screws and washers etc as per required at site complete all as specified and as directed.
S&F in replacement modular bell push switch piano, flush type, 6 Amps complete all as specified and as directed.
Supply & Fixing in repair single pole and netural sheet metal enclosure with a two pin and earth plug and socket complete with 01 number single pole MCB 20 Amps complete all as specified & directed.
Supply & Fixing in repair sheet metal enclosure MCB DB double door [Acrylic], single pole and neutral, 240 volts, 8 way with 200 Amp, 10 KA breaking capacity rated bus bar with blanking plate wherever required and IP-43 degree protection complete all as specified & directed.
Supply & Fixing in repair sheet metal enclosure MCB DB double door [Acrylic], single pole and neutral, 240 volts, 4 way with 200 Amp, 10 KA breaking capacity rated bus bar with blanking plate wherever required and IP-43 degree protection complete all as specified & directed.
Supply & Fixing in repair sheet metal enclosure MCB DB double door [Acrylic], single pole and neutral, 240 volts, 12 way with 200 Amp, 10 KA breaking capacity rated bus bar with blanking plate wherever required and IP-43 degree protection complete all as specified & directed.
S&F in replacement sheet metal enclosure MCB DB double door [Acrylic], Triple pole and neutral, 440 volts, 4 way with 200 Amp, 10 KA breaking capacity rated copper bus bar with blanking plate wherever required and IP-43 degree protection complete all as specified & directed.
S&F in replacement MCB Triple Pole and Neutral 63 Amps,415 V ,10KA breaking capacity complete all as specified & directed.
S&F in replacement MCB Single Pole and Neutral 240Volt, 40-63 Amps,10KA breaking capacity complete all as specified & directed.
S&F in replacement MCB Single Pole 240Volt, upto 32 Amps,10KA breaking capacity complete all as specified & directed.
S&F in replacement switch piano type switch two way AC 230 volts 6 Amps as per on existing switch board .
Supply & Fixing Smart bright Batten Series, LED luminaire using LED 22 watt with diffuser which ensures uniform distribution and comfort batten series features, latest LED which delivers consistent light output with wide voltage protection range, stable color start, Extruded Aluminium housing, Energy efficient, Flicker free start, In-built driver unit suitable for wall and ceiling mounting using brackets (supplied along with the Luminaire to be tested as per Standard Specification IEC 60598-2-1 / IS: 10322(Parts/Sec-l), to establish conformity of the product(s) to the requirements with the following specification:-(a) Size :- 4 ft (b) IP rating = IP 20 (c) Power factor= min 0.9 (d) CRI= max 80% (e) Surge Protection = 2.5KV (f) LED Driver should be complete with all standard portections as per design of Manufacturer. (g) Voltage operating range: 140-270V (h) THD = max 20% (j) Lumen Efficacy= min120 Lumen/Watt (k) CCT=4000K
Supply & Fixing Smart bright Batten Series, LED luminaire using LED 10 watt mirror with diffuser which ensures uniform distribution and comfort batten series features, latest LED which delivers consistent light output with wide voltage protection range, stable color start, Extruded Aluminium housing, Energy efficient, Flicker free start, In-built driver unit suitable for wall and ceiling mounting using brackets (supplied along with the Luminaire to be tested as per Standard Specification IEC 60598-2-1 / IS: 10322(Parts/Sec-l), to establish conformity of the product(s) to the requirements with the following specifications:-(a) Size :- 2 ft (b) IP rating = IP 20 (c) Power factor= min 0.9 (d) CRI= max 80% (e) Surge Protection = 2.5KV (f) LED Driver should be complete with att standard portections as design of manufacturer (g) Voltage operating range: 140-270V (h) THD = max 20% (j) Lumen Efficacy= min 900 Lumen (k) CCT=6500K
S&F Bulk head endura LED light fitting complete with and including 10 Watt LED and making necessary electric connection with copper conductor of suitable size and accessories & length complete all as specified and as directed with the following specifications:-(a) Size:-205mm x 70mm x 100mm (b) Main Current - 0.045 A (c) Power factor:- ≥0.95 (d) CRI: ≥80 (e) Surge Protection :- 4 KV (f) Voltage operating range: 120-270V (g) THD - ≤ 15% (h) Driver efficiency :- 90% (j) Lumen Efficacy:- 100 lm/w (k) Life (Hrs) :- 35,000 (l) CCT:- 4000/6500K (IP Rating) : IP65
Supply & Fixing Smart bright Batten Series, LED luminaire using LED 22 watt with diffuser which ensures uniform distribution and comfort batten series features, latest LED which delivers consistent light output with wide voltage protection range, stable color start, Extruded Aluminium housing, Energy efficient, Flicker free start, In-built driver unit suitable for wall and ceiling mounting using brackets (supplied along with the Luminaire ti be tested as per Standard Specification IEC 60598-2-1 / IS: 10322(Parts/Sec-l), to establish conformity of the product(s) to the requirements with the following specifications:- (a) Size :- 4 ft (b) IP rating = IP 20 (c) Power factor= min 0.9 (d) CRI= max 80% (e) Surge Protection = 2.5KV (f) LED Driver should be complete with all standard portections as per design of Manufacturer. (g) Voltage operating range: 120-240V (h) THD = max 20% (j) Lumen Efficacy= min100 Lumen/Watt (k) CCT=6500K
S&F LED light fitting square 2'x2', 36 Watt, 3000 lumen, Natureal white 6500K, THD max 10 % ,Voltage operating range: 140-270V, Surge Protection :- 2.5 to 3.5KV, CRI min 80 % warm, white along with fixture Surface / Recessed /Pendent mounting LED luminaires with diffuser, channel Luminaires ers, connector block, etc . complete with all accessories, internally pre-wired and including round wooden block, connecting up with three core flexible copper conductor cable of suitable size and length complete all as specified and directed .
S&F LED light fitting square 2'x2', 42 Watt, 3000 lumen, Warm, white 6500K, THD max 10 % ,Voltage operating range: 140-270V, Surge Protection :- 2.5 to 3.5KV, CRI min 80 % warm, white along with fixture Surface / Recessed /Pendent mounting LED luminaires with diffuser, channel Luminaires ers, connector block, etc . complete with all accessories, internally pre-wired and including round wooden block, connecting up with three core flexible copper conductor cable of suitable size and length complete all as specified and directed .
Supply & fixing, in repair, LED light down lighter by recess or surface mounted 12 Watt, warm white/cool white, circular/Square, 1200 lumen with fixing arrangemnts on ceiling complete all as specified & directed with the following specifications:- (a) Size :- dia 180mm x26 mm thick for circular and 180mmx180mm x6mm for Square (Shape as per Site requirements either square or circular) (b) IP rating = IP 20 (c) Power factor= min 0.9 (d) CRI= max 80% (e) Surge Protection = 2.5KV (f) LED Driver should be complete with all standard portections as per design of Manufacturer. (g) Voltage operating range: 140-270V (h) THD = max 20% (j) Lumen Efficacy= min1200 Lumen (k) CCT=4000/6500 (CCT will be as per site requirement either 4000 or 6500)
Supply & fixing, in repair, LED light down lighter by recess or surface mounted 18 Watt, warm white/cool white, circular/Square, 1200 lumen with fixing arrangemnts on ceiling complete all as specified & directed with the following specification:- (a) Size :- dia 220mm x26 mm thick for circular and 220mmx220mm x6mm for Square (Shape as per Site requirements either square or circular) (b) IP rating = IP 20 (c) Power factor= min 0.9 (d) CRI= max 80% (e) Surge Protection = 2.5KV (f) LED Driver should be complete with att standard portections as design of manufacturer. (g) Voltage operating range: 140-270V (h) THD = max 20% (j) Lumen Efficacy= min1800 Lumen (k) CCT=4000/6500 (CCT will be as per site requirement either 4000 or 6500)
Supply & fix, in replacement, LED Light Luminaire 25 Watt with 2500 or more lumen warm white, surge protection device upto 4KV, IP65 or more, IK07 or more, potted driver suitable for 120 to 270 V, 50 Hz & 100 lm /w light engine driver base pole adapter, powder coated pressure die cast aluminium with heat resistant toughened glass with lens type,GI pipe 40 mm dia medium Grade not less than with 1.2 m.long in any shape with 2 nos of pole fitting clamps made out of MS flat , nuts and bolts and painting with aluminum paint with the following specification:- (a) Weight - 2.8 kg (b) Current :- 0.120 A (c) Power factor:- ≥ 0.95 (d) CRI:- ≥70 (e) Surge Protection :- 4KV (f) LED Driver should be complete with all standard portections as per design of Manufacturer. (g) THD - ≤ 10 % (h) System Lumens -2600lm (j) Life (Hrs) :50,000 (k) CCT:- 6500k
Supply & fix, in replacement, LED Light Luminaire 45 Watt with 4500 or more lumen, warm white, surge protection device upto 4KV, IP65 or more, IK07 or more, potted driver suitable for 180 to 270 V, 50 Hz, light engine driver base pole adapter, powder coated pressure die cast aluminium with heat resistant toughened glass with lens type, GI pipe 40 mm dia medium grade not less than with 1.2 m. long in any shape with 2 nos of pole fitting clamps made out of MS flat , nuts and bolts and painting with two coats of aluminium paint over a coat of primer with the following specification:- (a) Weight- 2.8 kg (b) Current :- ≤ 0.215 (c) Power factor:- ≥ 0.95 (d) CRI:- ≥70 (e) Surge Protection :- 4KV (f) LED Driver should be complete with all standard protections as per design of Manufacturer. (g) THD - ≤ 10 % (h) System Lumens min 4850 lm (j) Life (Hrs) :- 50,000 (k) CCT:- 6500K
S&F in repairs LED Bulb 230V AC 7/9 watt cool day light 4000K heavy duty Base B-22 complere all as specified and directed by Engineer-in -charge. Make :- Havells/Philips/ Crompton
S&F decorative wall light fitting made up of Polycarbonate ,Cylindrical shape ,with LED lamp 9 Watt complete with fixing arrangements on wall complete all as specified and directed
Earthing complete with galvanised steel earth plate electrode 60 cm x60 cm x 6 mm thick buried directly in ground ,(Earth pit not less than 2.25 meter deep below ground level) with top edge of plate not less than 1.5 meter below normal ground level ,connected to and including 4 mm GI Wire by means of nut, bolts, check nuts and washers of galvanised iron or steel and provision of charcoal dust and common salt packed all around the earth plate including necessary excavation and earth work in any type of soil and testing complete all as specified and directed and shown in electrical plate number 5 of MES SSR part-I(1991) (a) Excavation and earth work for drilling hole for electrode in any type of Soil. (b) PCC pit in cement concrete 1:2:4 type B-1, Pre cast RCC cover with suitable handle 40 mm thick in PCC 1:2:4 type B-1, reinforced with welded steel wire fabric weighing not less than1.87 Kg/ Sq meter. (c) Funnel with watering pipe of GI 20 mm nominal bore light grade and lugs etc complete all as specified and directed. (d) 15 mm nominal bore medium grade GI protection pipe 5 meter long for protection of earthing lead complete all as specified and directed. (e) Requisite quantity of common salt and charcoal. (f) Testing of earthing.
M&L for servicing for UPS including Opening the UPS of 30KVA capacity including checking IGBT card, Driver card,Control card, Transformer and nesessary wiring also replace if anything unserviceable after repairing to again check the UPS and provide nesessary connection with new batteries including main switch with necessary installation in existing location with testing shall also be carried out by the contractor at own cost at same location complete all as required and directed at site. Note : UPS batteries of seperate item shall not be included in above coated rate.
S&F the EXIDE LEAD ACID battery 12 volts 100 AH maintenance free complete with connecting all as required and directed at site
S&F in replacement metal sheet l enclosure distribution boards, double door factory made VTPN 4 way 3 phase 415 volts 4 way with 200 amps rating copper bus bar and PVC insulated copper jumpers of suitable size from the MCCB to the out going circuits one incoming MCCB 100 amps and MCB TP 63 A -02 Nos,MCB SP -04 Nos circuits comprising of 3 phase 4 wire of suitable rating all as specified and directed.
Excavation in trenches, n exc 1.5m wide and n exc 1.5m in depth , for foundation, etc or for shafts, wells, cesspits, manholes, pier holes, laying of cables etc. n exc 10 sqm on plan and n exc 1.5m in depth and getting out in soft / loose of soil all as specified and directed.
Scrubbing of existing paints of existing LT panel board, LT feeder Pillar boxes, LT bus bar chamber paints of any specification and removing old paints and preparation of surfaces for painting complete and M&L for painting of LT Panels, LT Feeder pillar boxes, LT bus bar chambers internaly and externaly with one coat of superior quality smoke grey paint to achieve fine finishing complete all as specified and directed by Engr - in charge at site.
Dismantling of old unserviceable doors, back sheets, side sheet of LT panels, bus bar chamber or feeder pillar box installed at various places by cutting/descrewing after making the system disconnected from Elect supply and M&L for fabrication of doors/frames/ partition, bottom sheet by bending hot or cold, making holes, notching, welding of MS black sheet for LT panel board, bus bar chamber, feeder pillar box made out of 2 mm thick mild steel sheet including providing hinges for opening or closing of door, making handles, locking arrangement and painting of sheet both side with superior quality smoke grey paint after applying a coat of red oxide primer and matching with the existing complete all as specified and directed by the Engr - in-charge at site. Note : The cost of disconnecting of LT cable and earth strip and reconnecting the same after repair work shall be deemed to be inclussive in the unit quoted rates.
Dismantling/ taking down of existing bus bar of any type and supply and fixing bus bar made out of aluminium with coulour coded sleeves (Red, Yellow, Blue and black) with necessary bus bar insulators and nuts bolts of suitable size as required at site complete all as specified and directed
Supply and fixing in repair square type capacitor of 1 kVAr heavy duty complete all as specified and directed.
Supply and fixing in repair square type capacitor of 2 kVAr heavy duty complete all as specified and directed.
Supply and fixing in repair square type capacitor of 3 kVAr heavy duty complete all as specified and directed.
Supply and fixing in repair square type capacitor of 4 kVAr heavy duty complete all as specified and directed.
Supply and fixing in repair square type capacitor of 5 kVAr heavy duty complete all as specified and directed.
Supply and fixing in repair square type capacitor of 7.5 kVAr heavy duty complete all as specified and directed.
Supply and fixing in repair square type capacitor of 10 kVAr heavy duty complete all as specified and directed.
Supply and fixing in repair square type capacitor of 12.5 kVAr heavy duty complete all as specified and directed.
Supply and fixing in repair square type capacitor of 15 kVAr heavy duty complete all as specified and directed.
Supply and fixing in repair square type capacitor of 20 kVAr heavy duty complete all as specified and directed.
S&F in repair Current transformer for LT/APFC panel CT 100/5 A, CL1, 15VA complete all as specified and directed.
S&F in repair Current transformer for LT/APFC panel CT 600/5 A, CL1, 5VA complete all as specified and directed.
S&F in repair Current transformer for LT/APFC panel CT 400/5 A, CL1, 5VA complete all as specified and directed.
S&F in repair Current transformer for LT/APFC panel CT 250/5 A, CL1, 5VA complete all as specified and directed.
S&F in repair Current transformer for LT/APFC panel CT 200/5 A, CL1, 5VA complete all as specified and directed.
M&L for painting of alternate black & white strips to steel tubular poles/ rail poles of HT/ LT of over head lines with and including synthetic enamelled paint, total 05 Nos each strips on each pole, each strip having 0.15M height total up to 1.50M above from PCC coping and aluminium painting on all mild steel clamps, cross arm etc on poles with and including premium quality aluminium paint after necessary preparation of all surfaces of poles & fixures and fittings complete all as specified and as directed. Note:- All necessary T&P required at site for painting shall be arranged by contractor at his own cost and quoted rate shall be deemed to be included for all these provisions and nothing extra shall be paid on this account.
Material and labour for providing cement concrete 1:2:4 type B-1 (using 20 mm graded crushed stone aggregate) for coping of poles including necessary form work and finished the surface of panel/busbar chamber plinth complete all as specified and directed.
Checking electrical connection of cables at LT panel and tighten the connection including fixing new lugs and new nutbolts after dismantling of old lugs and nut bolts. LT cable insulation to be strengthened/repaired using LT tape or sleeves and gap between cable and panel hole to be filled through rubber gasket to avoid ingress of insects. Cost of excavation to loose the cable through loop deemed to be included in the rate of this item.
M&L for cross arms, bracing, supports, clamps and back plates fabricated from structural steel sections including nuts, bolts, washers, welding, bending cold or hot, drilling holes for bolts, in any shape or size as indicated or directed and inclusive of one primer coat, one under coat and one finishing coat of aluminum paint after taking out the old unserviceable cross arms, bracing, supports etc of any section complete all as specified and dircted.
Notes for items related to LED light fittings : (a) DRIVER COMPLIANCES WITH IS LUMINAIRE CERTIFIED BIOLOGICAL TEST REPORT BY OEM LAB APPROVED BY NATIONAL TEST HOUSE. (b) NABL testing Certificate shall be produced at the time of Make approval by the GE. (c) Bidders shall submit LM-80 Report for LEDs and LM-79 report from NABL accredited Lab. (d) The product will be replaced free of cost by the contractor in the following cases:- (e) Manufacturing defects. (f) Failure due to mechanical and electrical impact.
(g) Drop in lumen (or Lux) below 90% of claimed values of lumens (or lux ) at 1m of the LED/Luminaires. (h) All LED light/luminaire must meet the provisions laid down in IS-16101,16102 Part-I/II, 16103 Part-I, 16104, 16105, 16106, 16108/2012 and 15885 Part-II section 13. (j) Minor items required for completion of job are deemed to be included in the unit rate quoted by contractor. Nothing extra shall be payable on this account. (k) All Tubelights fittings shall be fitted using PVC Grip and screwing bolt duly drilled with Drilling machine all as specified and directed by Engineer-in charge. (l) For LED light fittings: Contractor shall submit min three different make of similar specification as per BOQ from central command Approved group -I list for approval of product and GE will approved one of them in consultation with users.
Schedule of credit amount of Rs 339637.00 to be deducted during AOC
RAVINDRA ELECTRICAL (BID ID -3485886)
New Era Engineers (BID ID -3491244)
stage.html
html • 0.05 MB
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Tendernotice_1.pdf
PDF • 0.94 MB
TENDER1.pdf
Tender Documents • 2.14 MB
BOQ_826241.xls
BOQ • 0.42 MB
Download all tender documents and submit your bid