Garrison Engineer North General Cariappa Marg Camp Pune 411001
GE (N) P/TOKEN- 05 OF 2023-2024SPL REPAIR TO EXISTING LT PANELS AND LT INFRASTRUCTURE AT AOR AND MW WORKS IN THE AREA OF AGE E/M SUB DIVISION UNDER GE (N) PUNE
2023_MES_590458_1
GE (N) P/TOKEN- 05 OF 2023-2024
Open Tender
Electrical and Maintenance Works
Item Rate
240 days
GE NORTH PUNE
Refer tender documents.
8 documents required · 8 mandatory
₹500
GE NORTH PUNE
₹89,820
Yes
1 Jul 2023
20 Apr 2023
24 May 2023
20 Apr 2023
17 May 2023
5 May 2023
21 Apr 2023 - 24 Apr 2023
Amount
Taking down old unserviceable feeder pillar box of any type, Supply, fixing, testing and commissioning of LT feeder pillar panel CPRI Approved double door floor mounted outdoor type, as per IP-65 grade, made out of CRCA sheet 3.00 mm thick of outer body and 2mm thick for inner compartment of suitable size with aluminium bus bar (120 x 10 mm) 1200 Amps, 4 strip (3 phase & Neutral) complete drilled, insulated with colour coded insulation tape, mounted on insulators etc with RYB indicator, internal wiring with suitable size of copper wire, panel should be dust proof, vermin proof, powder coated , locking should be screw type, mechanical type, inter locking, shouldhave danger notice for 415 volts, AC, mounted on 50x50x6 mm angle iron frame having minimum 2 feet ground clearance duly embedded in and including PCC block (1:2:4) type B-1 foundation for fixing of panel complete including termination of all incoming and outgoing cables with suitable size thimbles/lugs and glands, Nuts & Bolts, Washers complete with comprising of following and including: - (Ghorpadi Sub station No.01).
Incoming
(a) ACB, 4 Pole, 415 Volts, 800 Amp, Manual Drawout type with microprocessor release with adjustable type with breaking capacity 50 KA at 415 volts Ics=100% Icu -01 No
(b) Alum bus bar (120 x 10 mm ) 1200 Amps Amps TPN -01 Set
(e) Indicator lamp LED type (R,Y,B) complete with bakalite fuse fitting - 01 Set
Outgoing
(a) MCCB 3P, 160 Amp, adjustable Thermal Magnetic relay with breaking capacity 25 KA at 415 volts Ics=100% Icu - 03 Nos
(b) MCCB 3P, 250 Amp, adjustable Thermal Magnetic relay with breaking capacity 25 KA at 415 volts Ics=100% Icu - 02 Nos
(c) MCCB 3P, 63 Amp, adjustable Thermal Magnetic relay with breaking capacity 25 KA at 415 volts Ics=100% Icu - 07 Nos
(d) MCB DP 40 Amp, 16 KA, 415 V AC - 02 Nos
(e) Provision for space to be kept blank for fixing of MCCB - 01 No
Note :- Installation, testing, commissioning and connecting of incoming and outgoing cable connection LT feeder pillar panel is included in rates quoted. All fixing material like thimble, Nuts & Bolts are included in unit rate. Earthing strip to be connected with feeder pillar box with suitable size Nuts & Bolts.
Taking down old unserviceable feeder pillar box of any type, Supply, fixing, testing and commissioning of LT feeder pillar panel CPRI Approved double door floor mounted outdoor type, as per IP-65 grade, made out of CRCA sheet 3.00 mm thick and 2mm thick for inner compartment of outer body of suitable size with aluminium bus bar ( 100 x 10 mm) 1000 Amps, 4 strip (3 phase & Neutral) complete drilled, insulated with colour coded insulation tape, mounted on insulators etc with RYB indicator, internal wiring with suitable size of copper wire, panel should be dust proof, vermin proof, powder coated , locking should be screw type, mechanical type, inter locking, shouldhave danger notice for 415 volts, AC, mounted on 50x50x6 mm angle iron frame having minimum 2 feet ground clearance duly embedded in and including PCC block (1:2:4) type B-1 foundation for fixing of panel complete including termination of all incoming and outgoing cables with suitable size thimbles/lugs and glands, Nuts & Bolts, Washers complete with comprising of following and including: - (Ghorpadi Sub Station No. 03 & Vishwamitra Marg) .
Incoming
(a) ACB, 4 Pole, 415 Volts, 630 Amp, Manual Drawout type with microprocessor release with adjustable type with breaking capacity 50 KA at 415 volts Ics=100% Icu -01 No
(b) Alum bus bar (100 x 10 mm ) 1000 Amps Amps TPN -01 Set
(e) Indicator lamp LED type (R,Y,B) complete with bakalite fuse fitting - 01 Set
Outgoing
(a) MCCB 3P, 250 Amp, adjustable Thermal Magnetic relay with breaking capacity 16 KA at 415 volts Ics=100% Icu - 02 Nos
(b) MCCB 3P, 100 Amp, adjustable Thermal Magnetic relay with breaking capacity 16 KA at 415 volts Ics=100% Icu - 03 Nos
(c) MCCB 3P, 63 Amp, adjustable Thermal Magnetic relay with breaking capacity 16 KA at 415 volts Ics=100% Icu - 04 Nos
(d) Provision for space to be kept blank for fixing of MCCB - 01 No
Note :- Installation, testing, commissioning and connecting of incoming and outgoing cable connection LT feeder pillar panel is included in rates quoted. All fixing material like thimble, Nuts & Bolts are included in unit rate. Earthing strip to be connected with feeder pillar box with suitable size Nuts & Bolts.
Taking down old unserviceable feeder pillar box of any type, Supply, fixing, testing and commissioning of LT feeder pillar panel CPRI Approved double door floor mounted outdoor type, as per IP-65 grade, made out of CRCA sheet 3.00 mm thick of outer body and 2mm thick for inner compartment of suitable size with aluminium bus bar ( 50 x 10 mm) 500 Amps, 4 strip (3 phase & Neutral) complete drilled, insulated with colour coded insulation tape, mounted on insulators etc with RYB indicator, internal wiring with suitable size of copper wire, panel should be dust proof, vermin proof, powder coated , locking should be screw type, mechanical type, inter locking, shouldhave danger notice for 415 volts, AC, mounted on 50x50x6 mm angle iron frame having minimum 2 feet ground clearance duly embedded in and including PCC block (1:2:4) type B-1 foundation for fixing of panel complete including termination of all incoming and outgoing cables with suitable size thimbles/lugs and glands, Nuts & Bolts, Washers complete with comprising of following and including: - (Vishwamithra Marg Bldg No. 198 & 200 ).
Incoming
(a) MCCB, 4 Pole, 415 Volts, 250 Amp, adjustable Thermal Magnetic relay with breaking capacity 36 KA at 415 volts Ics=100% Icu -01 No
(b) Alum bus bar (50 x 10 mm) 500 Amps TPN -01 Set
(e) Indicator lamp LED type (R,Y,B) complete with bakalite fuse fitting - 01 Set
Outgoing
(b) MCCB 3P, 100 Amp, adjustable Thermal Magnetic relay with breaking capacity 16 KA at 415 volts Ics=100% Icu - 04 Nos
(d) Provision for space to be kept blank for fixing of MCCB - 01 No
(e) Street light timer for controlling street light- 01 No
Note :- Installation, testing, commissioning and connecting of incoming and outgoing cable connection LT feeder pillar panel is included in rates quoted. All fixing material like thimble, Nuts & Bolts are included in unit rate. Earthing strip to be connected with feeder pillar box with suitable size Nuts & Bolts.
Taking down old unserviceable feeder pillar box of any type, Supply, fixing, testing and commissioning of LT feeder pillar panel CPRI Approved double door floor mounted outdoor type, as per IP-65 grade, made out of CRCA sheet 3.00 mm thick of outer body and 2 mm thick for inner compartment of suitable size with aluminium bus bar ( 60 x 10 mm) 600 Amps, 4 strip (3 phase & Neutral) complete drilled, insulated with colour coded insulation tape, mounted on insulators etc with RYB indicator, internal wiring with suitable size of copper wire, panel should be dust proof, vermin proof, powder coated , locking should be screw type, mechanical type, inter locking, shouldhave danger notice for 415 volts, AC, mounted on 50x50x6 mm angle iron frame having minimum 2 feet ground clearance duly embedded in and including PCC block (1:2:4) type B-1 foundation for fixing of panel complete including termination of all incoming and outgoing cables with suitable size thimbles/lugs and glands, Nuts & Bolts, Washers complete with comprising of following and including: - (752 TPT Coy).
Incoming
(a) MCCB, 4 Pole, 415 Volts, 150 Amp, adjustable Thermal Magnetic relay with breaking capacity 25 KA at 415 volts Ics=100% Icu -01 No
(b) Alum bus bar ( 60 x 10 mm) 600 Amps TPN -01 Set
(e) Indicator lamp LED type (R,Y,B) complete with bakalite fuse fitting - 01 Set
Outgoing
(a) MCCB 3P, 100 Amp, adjustable Thermal Magnetic relay with breaking capacity 25 KA at 415 volts Ics=100% Icu - 01 Nos
(b) MCCB 3P, 63 Amp, adjustable Thermal Magnetic relay with breaking capacity 25 KA at 415 volts Ics=100% Icu - 02 Nos
(c) Provision for space to be kept blank for fixing of MCCB - 01 No
(d) Automatic timer switch with switches ON/OFF the street lights base on lux level of natural light current rating 40 Amps, 220 Volts, 50 Hz - 01 No.
Note :- Installation, testing, commissioning and connecting of incoming and outgoing cable connection LT feeder pillar panel is included in rates quoted. All fixing material like thimble, Nuts & Bolts are included in unit rate. Earthing strip to be connected with feeder pillar box with suitable size Nuts & Bolts.
Supply, laying and testing in replacement of cable XLPE insulated screened, PVC bedded galvanized steel strip or wire armoured electric power cable (heavy duty) with aluminium conductor 1100 Volts grade cross sectional area 3.5 core x 120 Sq mm. complete all as specified and as directed. Note : Provision of suitable double crimpped lugs and glands deemed to be included in quoted rates.
-ditto- all as per item No 5 above but 3.5 core 95 sqmm
-ditto- all as per item No 5 above but 3.5 core 70 sqmm
-ditto- all as per item No 5 above- but 3.5 core 50 sqmm
-ditto- all as per item No 5 above but 4 core 25 sqmm
-ditto- all as per item No 5 above but 4 core 16 sqmm
M&L for painting to steel tubular pole including cable protection pipe and all iron parts of 9/11 mtr long pole complete with 2 coats of aluminium paint after cleaning all rust and dust and preparing surface with wire brush and including strips of white and red colour of synthetic enamel paint up to the height of 1.5 mtr from the bottm of the pole complete all as specified and as directed.
Supply and lay in trenches /under roads/ crossing or fixed to wall/ pole, GI tubing light grade of size 40mm bore for protection of UG cables complete all as specified and as directed.
-ditto- all as per item No 12 above but 80 mm
Excavation in trenches n exc 1.5 wide and n exc 1.5 m in depth for foundation etc or for laying cable etc n exc 10 Sqm on plan and n exc 1.5 m in depth and getting out in soft/loose soil complete all as specified and as directed.
Returning filling in including spreading, leveling, watering and well ramming in layers n exc 25 cm complete all as specified and as directed.
Removal of excavated material/surplus soil to a distance n exc 50m and depositing where directed at a level n exc 50m above the starting point complete all as specified and as directed.
Supply and laying 40mm outer dia, double walled corrugated (DWC) HDPE duct pipe conforming to IS- 14930 Pt-II with antirodent and non flame propogating properties of approved colour complete with fittings for cable protection complete all as specified and as directed.
Supply and laying 50mm outer dia, double walled corrugated (DWC) HDPE duct pipe conforming to IS- 14930 Pt-II with antirodent and non flame propogating properties of approved colour complete with fittings for cable protection complete all as specified and as directed.
Supply and laying 63mm outer dia, double walled corrugated (DWC) HDPE duct pipe conforming to IS- 14930 Pt-II with antirodent and non flame propogating properties of approved colour complete with fittings for cable protection complete all as specified and as directed.
Supply and laying 77mm outer dia, double walled corrugated (DWC) HDPE duct pipe conforming to IS- 14930 Pt-II with antirodent and non flame propogating properties of approved colour complete with fittings for cable protection complete all as specified and as directed.
Material and labour for PVC flat twin core 2.5 sq mm aluminium wire 1100 volt grade laid in 20 mm dia medium grade rigid PVC conduit (and fixing brackets on PCC pole) from Loop-in-loop out junction box to light fitting terminal complete all as specified and as directed. Note :- PVC conduit shall be clamped properly with suitable clamps and no extra payment will be done on this account.
S & F Junction Box for Street Lights of size 250 x 200 x 105 mm made out of SMC totally enclosed, dust, shock, rust and vermin proof, Rot proof and termite resistant, cable entry/out from bottom, 100 % weather proof, Locking door arrangement with gaskat, water tight IP 42 protection single leaf shutter in front having proper locking arrangements with suitable size of "connectwell" stud teriminal (provision for socket bolting)- 05 Nos suitable for 415 volts, 50 Hz, 3 phase 4 wire internal wiring system including MCB SP 06 amps- 01 No and mounted on security light pole with suitable bracket nuts, bolts including removal of exiting unsv all as specified and directed.
Dismantling cross-arms of MS channel or angle section of GOD, Lightening arresters, DO fuse etc complete all as specified and as directed.
Dismantling insulators any type, any size complete all as specified and as directed.
Dismantling earth wire complete all as specified and as directed.
Dismantling of ACSR or AAC conductors complete all as specified and as directed.
S&F Automatic transfer switch 400 A ,4 pole ,36 KA inbuilt in sheet metal enclosure with adjustable thermal & fixed magnetic setting with bus bar spreader links for connecting both incoming and outgoing cables with suitable connections with suitable size of glands etc complete including testing & commissioning all as specified and as directed by the Engineer-in-Charge.
M & L Air termination, single pointed, copper rod 12mm dia and 300mm long complete all as specified and as directed.
Material and Labour for test point terminal block made of gun metal or phosphorus bronze size 75x75x25mm drilled and screwed including 3 nos. 8mm dia 25mm long hex. head screw complete all as specified and as directed.
Supply and fix Earth continuity conductor or Main Earthing lead fixed to wall or batten or reccess or chasses or buried in ground or drawn in conduit / pipe or fixed to Poles or any other indicated situation for loop copper strip of size 20 x 3.15 mm connected to test point complete all as specified and as directed.
Material & labour for Earthing using Copper earth plate electrode of size 60cm X 60cm X3.15mm thick burried directly in ground vertically at a depth not less than 2.25 mtr below normal ground level with top edge of earth plate at a depth not less than 1.5 mtr below normal ground level, earth plate surrounded from all sides by 15 cm thick and packed layer of charcoal dust and common salt filling in alternate layers including refilling with good earth as specified and electrode connections by using Copper strip of size 20x3mm by means of bolts, nuts, check nuts and washers made of copper/brass and provision of GI pipe medium grade 25 mm dia for protection of earthing lead and 20mm dia for watering arrangement including funnel, wire mesh, CI pit cover and PCC chamber pit with PCC 1:2:4 type B-2 (including necessary excavation and earth work disposal of surplus soil to a distance not exceeding 50 mtr all as specified and shown on plate No 5 of SSR Part-I 2009
M&L Cement Concrete 1:3:6 (40mm graded aggregate) as in Foundation of Poles,/ coping etc. including Formwork (as/if required) complete all as specified and as directed.
Material and Labour for Tubes, 'Medium grade' galvanised, bore of pipe 40mm with all fitting and fixed complete to walls and ceilings or laid in floor complete all as specified and as directed.
Supply and fixing DMC isolation Insulator, Rated Voltage 415 Volt, red in colour 30mm dia for fixing copper earthing strip with necessary copper nut botls washers including grounting on wall, ceiling, roof complete all as specified and as directed.
M & L for flame proof conceled point wiring using approved colour coding as per IS with 1.5 sqmm two nos single core PVC insulated but unsheathed FRLS cable, 1100 volts grade, IS-694 marked with multistranded copper conductor and earth continuity wire with similar 1.5 Sqmm cable (including connecting to earth dolly) drawn through heavy duty ISI marked ERW stove enamelled, steel conduit concealed in wall, not less than 20mm dia with and including flame proof bends and elbows, couplers, bell mouth reducer , junction box all as per relevant IS and type tested/ approved by CMRI Dhanbad fixed with solid backed distance saddles & nettle fold GI screws all as specified for One light point controlled by one no. FLP rotatory switch complete al as specified and directed.
Supply and fix Switch flame proof rotary type with termination box in LM6, 16A, single pole 250V
Supply and fixing LED light fitting 1x16/18 Watt flame proof, CMRI certified recommended for gas/ vapor group of IIA & IIIB, Zone 1 & 2 and IP 65 protection with die cast aluminum hosing with heat resistant toughened glass with LED tube light fixtures driver, holders, connector etc. Complete with all accessories prewired and including connecting up with three core flexible copper conductor cable with suitable size.
M & L for earthing complete with galvanized steel earth plate electrode 60 cm x 60 cm x 6 mm thick buried directly in ground vertically (earth pit not less than 2.25m deep below ground level) with top edge of the plate not less than 1.50 mtr deep below normal ground level, connecting to GI earth strip of size 32 x 6 mm by means of bolts, nuts, check nuts, and washers of galvanized iron or steel including 40 mm dia medium grade protection pipe for earth lead complete with charcoal and common salt including watering arrangement with galvanized iron pipe light grade 20 mm dia, PCC Chamber, CI frame and cover, MS funnel with wire mesh all as shown in electrical plate no 3 of SSR part I including excavation and earthwork in any type of soil/strata and testing on completion. Note :- GI earth wire 4 mm dia and 15 mm dia protection pipe upto 7.5 mtr from earth plate is deemed to be included in rate quoted.
Taking down/out unserviceable UG Cables of any Cross Sectional Area and Connections and joints including Pipes, Bricks, etc of any description complete all as specified and as directed.
Supply, laying and testing cable XLPE insulated screened PVC bedded galvanised steel strip or wire armoured, electric power cables (heavy duty) with stranded aluminium conductors 1100 volts grade of 10 sqmm x 2 core sizes, laid in trenches, fixed on wall etc complete all as specified and directed.
Supply and fixing weather proof street light junction box of size 300 x 200 x 105mm including MCB SP 6 Amps and connecting terminals 4 way and fixing with street light poles using necessary MS clamps, nuts, bolts washers, lugs for incoming and out going cables, gland for cable etc of suitable size complete all as specified and as directed. Make : Hensel/Sintex/Universal Switch Gear control Note : The rates quoted are inclusive of provision and fixing of suitable lugs and glands for cable connection.
S & F Integral decorative LED bollard with polycarbonate diffuser square shaped with IP 65 protection suitable for 16 x 0.5 watts LED bulb with necessary elecrical connections with adequate size including removal of old unserviceable one complete as all specified and as directed.
S & F for LED post top lantern 25 watt light fitting made of cast aluminium spigot housing with decarative opal acrylic diffuser with IP 65 protection complete with all accessories fixed on GI pipe 50 mm dia including removal of old unserviceable one complete all as specified and directed.
Note : 1. Performance security:- Refer Condition 22 of Special Conditions. 2. Quoted Contract Sum shall be arrived at after deducting the amount of Credit Schedule (refer Schedule of Credit in pdf form for quantity, rate and amount etc.) for old unserviceable materials retrieved from site.
Mahindra Electric Stores
TULAJA ENTERPRISES
CHAITANYA WINDWELL
somnath engineering corporation
R K ENTERPRISES
stage.html
html • 0.05 MB
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .