| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | L1₹30.3 LAccepted-AOC MAIN ROAD OBEDULLAHGUNJ RAISEN M P 464993 | OBEDULLAHGUNJ | RAISEN | MADHYA PRADESH | 464993 | L1 | Accepted-AOC Being L1 bidder | |
| 2 | L2₹30.4 L+₹9,742.50 (0.32%)Rejected-Finance | L2 | Rejected-Finance NOT LOWEST | |
| 3 | L3₹31.4 L+₹1.1 L (3.54%)Rejected-Finance HOUSE NO 251 E BLOCK ADARSH NAGAR BALLABHGARH FARIDABAD 121004 HARYANA | FARIDABAD | FARIDABAD | HARYANA | 121004 | L3 | Rejected-Finance NOT LOWEST | |
| 4 | L4₹33.2 L+₹2.9 L (9.70%)Rejected-Finance NEAR INDUSTRIAL ESTATE THANDA PADDAR UDHAMPUR J K 182101 | UDHAMPUR | JAMMU AND KASHMIR | 182101 | L4 | Rejected-Finance NOT LOWEST | |
| 5 | L5₹34.0 L+₹3.7 L (12.2%)Rejected-Finance | L5 | Rejected-Finance NOT LOWEST |
Tender Value
₹27.7 L
EMD Value
₹55,400
Closing Date
16 Oct 2023, 6:00 pmClosed
Eligibility, documents, scope and key termsEligibility, required documents, scope of work and key terms of this tender, in one click.
Cdr, HQ 138 WE
HQ 138 Works Engineers PIN-914138 C/O 56 APO
SPL REPAIR AND UPGRADATION OF EXTERNAL ELECTRIC SUPPLY AND PROVN OF REFRIGERATOR AND DEEP FREEZER UNDER GE 865 EWS AT LEH
2023_MES_618433_1
138WE/L-64/2023-24
Open Tender
Electrical and Maintenance Works
Item Rate
180 days
GE 865 EWS
Please refer Tender documents.
6 documents required · 6 mandatory
₹500
GE 865 EWS
₹55,400
Yes
17 Jan 2024
12 Sept 2023
23 Oct 2023
12 Sept 2023
16 Oct 2023
26 Sept 2023
Amount
Supply, installation testing and commossioning of Outdoor type transformer with standard fittings and accessories , step down copper wound 11 KV on HT side and 433 volts on LT side at no load 3 phase 4 wire system 50 C/S AC supply of 630 KVA oil immersed laminated iron core naturally cooled with external tubes, delta connected on HT side and star connected on LT side corresponding to vector group DY-11 with neutral brought out seperately for earthing including off load changing tap arrangement up to +7.5% in steps of + 2.5% each complete with first filling of transformer oil up to appropriate level and LT side suitable for connection with trunk bus bar including RCC foundation for TFR at sitable height and cattle fencing of 1.5 m height around the transformer, incl necessary oil as per capacity of said transformer. Conforming with IS : 2026 complete all as specified and directed by Engr-in-Charge
Supply and Laying in trenches or passing through pipe or fixed on surface XLPE insulated, armoured, heavy duty electric cable with aluminium conductor, 1100 volts grade of under mentioned sizes, complete all as specified and directed by Engr-in-Charge. (a) 500 Sqmm 3.5 core
(b) 120 Sqmm 3.5 core
(c) 50 Sqmm 3.5 core
Excavation in trenches not exc. 1.5m wide and not exc. 1.5m in depth, for foundation etc. or for shafts, welles cesspitsm, manholes, pier holes, etc. n exc 10 sqm on plan and n exc 1.5m in depthe in hard/dense soil and getting out , complete all as specified and as directed by Engr in Charge.
Returning, filling in (soil), including spreading, leveling, watering and well ramming in layers not exc. 25m, complete all as specified and as direted by Engr in Charge.
Removing excavated material to a distance not exc. 50m and depositing where directed at a level not exc. 1.5m above the strating point, complete all as specified and directed by Engr in Charge.
M&L for Sand cushioning to underground cables 8 cm below the cable before laying & 15 cm above the cable after laying, complete all as specified in clause 19.75 of SSR Par-I, complete all as specified and directed by Engr in Charge.
Replacement of factory made, machine pressed, unreinforced, pre-cast concrete cable cover class LV type-I flate size 250 x 150x40mm , complete all as specified and directed by Engr in Charge.
Earthing complete with galvanised iron earth plate electrode 600x600x6mm buried directly in ground (earth pit not less than 2.25mtr deep below ground level) with top edge of earth plate not less than 1.5mtr below normal ground level, connected with 25x4mm size GI strip as earth lead, by means of bolts, nuts, check nuts and washers of galvanized iron or steel complete with 40mm dia GI light grade protection pipe, 20mm dia GI medium grade watering pipe with funnel including charcoal, dust, salt, PCC M-15, type B-1 in pit with precast RCC M-15(1:2:4), type B-1 (using 20mm graded crushed stone aggregates) in cover reinforced with XPM not less than 4.0 Kg per Sqm, test point etc. all as shown in electric plate No-3 of SSR Part-I (2009), complete with necessary earth work in any type of soil, removal to a distance not exceeding 50mtr, including testing on completion, complete all as specified and as directed by Engineer-In-Charge. Note: Earth pit chamber and RCC pit cover shall be painted with two coats of red synthetic enamel paint over one coat of primer including preparing of surfaces, complete all as specified and directed by Engr in Charge.
Supply and installation refrigerator, electric driven (single phase), capacity more than 195 litres BEE 5 star rated, complete all as specified and directed by Engr-in-charge.
Supply and installation refrigerator, electric driven (single phase), capacity 310 Litres BEE 5 star rated, complete all as specified and directed by Engr-in-charge
Supply and installation, commissioning of Glass Top Deep Freezer single phase 240 volt, 50 Hz Capacity 220 ltr complete all as specified and directed by Engr-in-charge.
Supply and installation, commissioning of Glass Top Deep Freezer single phase 240 volt, 50 Hz Capacity 320 ltr complete all as specified and directed by Engr-in-charge.
Supply and fix Voltage stabilizer for automatic operation, single phase naturally air cooled indoor type & designed for input variation between 170 V to 250 V with output voltage stabilized at 230 V with accuracy of ± 2.5% and of capacity 2 KVA complete all as specified and directed by Engr-in-charge.
Supply and fix Voltage stabilizer for automatic operation, single phase naturally air cooled indoor type & designed for input variation between 170 V to 250 V with output voltage stabilized at 230 V with accuracy of ± 2.5% and of capacity 3 KVA complete all as specified and directed by Engr-in-charge.
Supply and fix Voltage stabilizer for automatic operation, single phase naturally air cooled indoor type & designed for input variation between 170 V to 250 V with output voltage stabilized at 230 V with accuracy of ± 2.5% and of capacity 5 KVA complete all as specified and directed by Engr-in-charge.
RAVI KUMAR
national engineering
K S BUILDERS
M/S MALIK CHAND SIRI RAM
M.S Sharma Enterprises
M/S NANCY ENTERPRISES
stage.html
html • 0.06 MB
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .