Loading…
Loading…
| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | L1₹37.2 LAccepted-AOC | ₹37.2 L Quoted ₹37.8 L | L1 | Accepted-AOC Being L1 bid |
| 2 | L2₹38.2 LRejected-Finance 24 824 GOVERDHAN COLONY MAIN BHIND ROAD GOLE KA MANDIR | ₹38.2 L | L2 | Rejected-Finance Being Other Than Lowest |
| 3 | L3₹40.2 LRejected-Finance | ₹40.2 L | L3 | Rejected-Finance Being Other Than Lowest |
| 4 | Rejected-Technical LAL SAHAB KA BAGICHA MALL ROAD MORAR GWALIOR MP | GWALIOR | GWALIOR | MADHYA PRADESH | 474006 | - | - | Rejected-Technical Firm not meeting the eligibility criteria of b iii as per NIT |
| 5 | Rejected-Technical | - | - | Rejected-Technical Firm not meeting the eligibility criteria of b iii as per NIT |
| Sl No | Description | Qty | Unit | anand enterprises L2 | M/s Sagar Construction L1 | Third Wave Services Pvt Ltd L3 |
|---|---|---|---|---|---|---|
| 1.00Disconnecting, testing, cleaning and servicing/ overhauling of following items and taking out and removing unserviceable/ defective parts including greasing, oiling of the parts etc and replacement of unserviceable parts with new one if any, reassembling the items after overhauling/ servicing /Calibration and its testing complete all as specified and directed by Engineer-in-Charge. Note:- i) Servicing and testing will be done by authorised rep of manufacturer. ii) The quoted rates of the contractor includes for fixing the serviceable parts in position and replacement of unserviceable parts with new parts if any. The new replaced parts shall be measured and paid for separately under appropriate item of Sch 'A’ as supply only iii) The Repair / servicing / Overhaling/Calibration shall be Caried out by Authorised Rep of manufacturer. | ||||||
| 1.01 | Oil cooled CTs 33kv outdoor type (Set of three) | 2 | Each Job | 6,000 ₹12,000 | 10,000 ₹20,000 | 12,500 ₹25,000 |
| 1.02 | Oil cooled PTs 33kv outdoor type (Set of three) | 2 | Each Job | 6,000 ₹12,000 | 10,000 ₹20,000 | 12,500 ₹25,000 |
| 1.03 | Control panel and breakers 33 KV | 4 | Each Job | 15,000 ₹60,000 | 12,000 ₹48,000 | 14,200 ₹56,800 |
| 2.00Supply only following spare parts for 33 KV VCB :- Make of the spare parts shall be as SAME as of the make of CTs/ PTs or as recommended by OEM | ||||||
| 2.01 | Micro switch | 3 | Each | 500 ₹1,500 | 3,000 ₹9,000 | 4,100 ₹12,300 |
| 2.02 | Motor cut of limit switch | 3 | Each | 500 ₹1,500 | 1,500 ₹4,500 | 1,550 ₹4,650 |
| 2.03 | LED Indicating lamps R,Y,B,W,G,A 30VAC/110VAC/230VAC | 20 | Each | 210 ₹4,200 | 400 ₹8,000 | 450 ₹9,000 |
| 2.04 | Closing coil 110 VDC | 3 | Each | 1,500 ₹4,500 | 6,000 ₹18,000 | 6,100 ₹18,300 |
| 2.05 | Tripping coil 110 VDC | 3 | Each | 1,500 ₹4,500 | 6,000 ₹18,000 | 6,100 ₹18,300 |
Tender Value
₹45.0 L
EMD Value
₹89,960
Closing Date
28 Oct 2025, 6:00 pmClosed
Cwe AF Gwalior
HQ CWE AF Gwalior 474020
CERTAIN REPAIR /MAINT WORKS IN 33KV/11KV VCBs, CTs,PTs. GODs AND CONNECTED WORKS AT MRS AND OTHER HT INSTALLATION AT AF STN GWALIOR.
2025_MES_733998_1
86033
Open Tender
Electrical and Maintenance Works
330 days
GE AF Adm Area
As per tender documents
9 documents required · 9 mandatory
₹500
GE AF ADM Area
₹89,960
Yes
22 Jan 2026
6 Oct 2025
4 Nov 2025
6 Oct 2025
28 Oct 2025
21 Oct 2025
Amount
Oil cooled CTs 33kv outdoor type (Set of three)
Oil cooled PTs 33kv outdoor type (Set of three)
Control panel and breakers 33 KV
Supply only following spare parts for 33 KV VCB :- Make of the spare parts shall be as SAME as of the make of CTs/ PTs or as recommended by OEM
Micro switch
Motor cut of limit switch
LED Indicating lamps R,Y,B,W,G,A 30VAC/110VAC/230VAC
Closing coil 110 VDC
Tripping coil 110 VDC
Segment gear Assembly (Full Teeth-Big )
Tripping Half shaft
Trip Catch with linkage assembly
Spring charging motor assembly 230 VAC
Motor Gear Box Assembly.
Hold on Catch assembly with spring
Closing Half shaft
Auxiliary switch assembly
Ratchet wheel with key & Set of pawls with pin
Heater assembly
Butterfly Switch assembly
Thermostat assembly
HRC Fuse assembly
TNC Switch assembly
Z switch assembly
Connecter plate and DC box
Volt Meter
Ammeter
Relay assembly with control wiring
Disconnecting and taking down old unserviceable control cable any size any description and supply, fixing, testing and commissioning of LT 1100 volts 2.5 Sqmm 4 core copper conductor armoured cable connecting the cable in positioning properly by providing suitable new copper lugs GI bolts & Nuts washers etc complete all as specified and directed. Make:- Havells,Finolex, Polycabe
Disconnecting and taking down old unserviceable control cable any size any description and supply, fixing, testing and commissioning of LT 1100 volts 2.5 Sqmm 16 core copper conductor armoured cable connecting the cable in positioning properly by providing suitable new copper lugs GI bolts & Nuts washers etc complete all as specified and directed. Make:- Havells, Finolex, Poly cabe
Disconnecting and taking down the unserviceable/damaged/non operational existing lightening arrestor of 33KV Switching yard and supply , fixing & testing and commissioning of new lightening arrestor 33KV, 10KA suitable for 33KV and maximum voltage of 36KV for (MRS) with solid earthed natural system comprising of Metal oxide elements suitable for ACSR Conductor along with the insulating base structural work and all as specified and directed Make : Obleium/ jaipuriya/pactil
Taking down existing unserviceable air break switch gang operated outdoor type up to rating 400 Amps of 33 KV and supply and fix new air break switch gang operated out door type Triple pole mechanically operated mounted on insulator and suitable for verticle mounting complete with explusion fuses, GI operating rod of suitable length for operating mechanisam worked from ground level complete in both OFF and ON positions steel frame with operated mechanism welded from tubular rotating type switch . all as specified and directed Make: Jaipuria Brothers/Atlas/Pactil/HEI/ECE Calcutta/MEC Trivandrum
Disconnecting and taking down 33 KV Air break swich gang operated outdoor type any Amps it shall be replacement and refixing the same all as specified and directed by Engineer-in-Charge :- Make: Jaipuria Brothers/Atlas/Pactil/HEI/ECE Calcutta/MEC Trivandrum
Male contact for AB Switch
Female contact for AB Switch
Blade for AB Switch
Insulator for 33 KV Pin type
Insulator for 33 KV Disc type
Taking down existing unserviceable air break switch gang operated outdoor type up to rating 200 Amps of of 11 KV and supply and fix new air break switch gang operated out door type Triple pole mechanically operated mounted on insulator and suitable for verticle mounting complete with explusion fuses, GI operating rod of suitable length for operating mechanisam worked from ground level complete in both OFF and ON positions steel frame with operated mechanism welded from tubular rotating type switch . all as specified and directed Make: Jaipuria Brothers/Atlas/Pactil/HEI/ECE Calcutta/MEC Trivandrum
Taking down existing unserviceable air break switch gang operated outdoor type up to rating 400 Amps of 11 KV and supply and fix new air break switch gang operated out door type Triple pole mechanically operated mounted on insulator and suitable for verticle mounting complete with explusion fuses, GI operating rod of suitable length for operating mechanisam worked from ground level complete in both OFF and ON positions steel frame with operated mechanism welded from tubular rotating type switch . all as specified and directed Make: Jaipuria Brothers/Atlas/Pactil/HEI/ECE Calcutta/MEC Trivandrum
Taking down unserviceable Drop out fuse set outdoor type ratio 400 Amps of 33 KV and supply and fix drop out fuse set mounted on six insulator and fixed on steel frame complete all as specified and directed.
Disconnecting and taking out existing unserviceable Potential transformer (PT) of any description and in any position and supply, installation, commissioning and testing of 33 KV single phase out door oil cooled potential transformer.IS 3156 all as specified and directed. MANDATORY PARTICULARS OF 33 KV O/D POTENTIAL TRANSFORMER (i) Type :-Dead tank (ii) Rated voltage :-33 KV, Highest voltage :-36 KV and Frequency :-50 HZ (iii) Basic Insulation Level :- Primary: 36 KV/70 KV/170 KV(p) and Secondary : 3KV for 1 minute (iv) Class of Insulation :- Class A (v) Creepace distance :-900 mm (minimum) (vi) Ratio :-33000/√3 - 110/√3 volt (vii) Class of accuracy :-Core - I : 0.5, Core - II :3P (viii) Burden :-Core - I : 100VA, Core - II :100VA (ix) Voltage factor :-1.2 Continuous, 1.5 times for 30 Sec. (x) Core identification :- Core - I : Metering, Core - II : Protection (xi) Primary terminal connector :- Rigid type suitable for PT Stud to Dog ACSR. (xii) Fixing hole dimension & Painting :-330 mm both X & Y direction and Paint shed : Battleship Gray as per IS 5 Paint thickness :60 micron ( minimum) and Secondary terminal box : IP 55 (xiii) Suitability :-Should be suitable for upright mounting on steel structure in outdoor switch yard with matching to WBSEDCL' s Standard base structure. Make: Crompton greaves/Jyoti/Skipper/Kappa/ Alstom(Ariva)
Serving and Testing of OLTC Panel of 5 MVA Transformer complete and repairing the same by replacing the faulty parts for smooth functioning of the panel, charges of authorised engg for attending OLTC, Tap changer Type-EO16, and replacement of following parts all as specified and directed :-
Transistor Resistor.
OLTC Top cover Gasket
Anti Scrubbing Paste-100gm.
Tap changer DSS switch.
TPI Tap Changer counter.
CRC Spray
UG Clamp assy in CT side
UG Clamp assy in PT side
Conductor wire sleeve R, Y, B ( HT)
M&L for surface excavation over the areas around the poles/feeder piler boxes/ sub stations not exceeding 15cm depth including cleaning the bushes and vegetation along with its roots and levelling incl removal of surplus soil in soft/hard dense soil.
M&L for hardcore broken stone/ boulders of gauge n exc. 63 mm, deposited, spread and levelled in layers n exc. 15 cm thick, to a true surface at the places as specified and directed by Engineer-in-charge.
Disconnecting old unserviceable GI watering Pipe of any description and supply and fixing/laying pipe GI medium grade 15mm bore fix on wall or laid under floor complete with all accessories complete all as specified and directed. Make: Tata/Jindal/TT Swastik
Disconnecting old unserviceable GI protection Pipe of any description and supply and fixing/laying pipe GI medium grade 25mm bore fix on wall or laid under floor complete with all accessories complete all as specified and directed. Make: Tata/Jindal/TT Swastik
Disconnecting and taking down old unserviceable existing battery bank of any description and in any position, supplying, fixing, commissioning and testing new battery charging unit of 28 Volts 180 AH DC out let input 230 volts AC enclosed in suitable size sheet metal enclosure with and including volt meter & Ammeter of suitable range & variable output type charging transformer including painting with two coats of synthetic enamel paint over a coat of red oxide primer on all steel surfaces complete all as specified and directed by Engineer - in- charge. Make : Charging unit-SYSTEM Control, R.E.L., ESCORP.
Material and labour for earthing complete with galvanized steel earth plate electrode 600mm x 600mm x 6mm buried directly in ground vertically to a depth not less than 2.25 metre below normal ground level (with top edge of earth plate not less than 1.5 metre below ground level) connected to galvanized iron earth strip 32x6 mm (main earthing lead) by means of galvanized bolts, nuts and washers all as shown in electrical plate No 3 of MES Schedule Part-I (2009) with connected to earth test point & to main switch board with & including adequate quantity of charcoal dust and common salt around earth plate & 40 mm dia GI pipe medium grade for earth lead protection pipe for suitable length and GI pipe 20 mm dia medium grade for watering pipe with funnel & wire mesh including necessary earth work and PCC (1: 3 : 6) type C-1 for earth pit , internal surface of concrete shall be given 10mm thick plaster in CM 1:4 and 40 mm thick precast RCC cover in 1 : 2 : 4 type B1 with 3 Nos 8 mm dia TMT bars both ways with 12mm dia round bar handle complete all as specified & directed by Engineer-in-Charge. Note :- (i) Copper strip and GI protection pipe medium grade, up to 7.5mtr shall be deemed to be included in the rates quoted for earthing. (ii) Excavation and earth work in any type of soil strata shall be deemed to be included in rates quoted for earthing. (iii) The rates quoted by the contractor are deemed to be included for MS sheet of size 300x300x3mm thick, fixed with necessary nuts and bolts on angle iron of size 40X40x5mm, 60cm long and grouted with PCC block of size 200x200x250mm(PCC 1:3:6 using 20mm grade stone aggregate including necessary earth work for marking the result purpose.
Disconnecting and taking down battery for 33 KV power bank and S & F new battery 12 Volt 180 AH including all connected items as specified and directed.
Supply, filling and for topping up the CTs/PTs with new transformer oil in factory sealed container duly filtered with filtration plant. Note:- (a) The transformer oil shall be type EHV confirming to IS 3357 of 1983 (b) Mineral oil grade 'B' shall be used. (c) The transformer oil should have a high dielectric strength not less than 50 KV Make: Indian oil corporation/BPCL/HPCL (d) The empty barrel shall be deposit in MES store yard .
Removing/scraping the existing pre-painted aluminium paint preparing surface for applying new paint with two coats of approved quality aluminium paint on 2 Pole structure, four pole structure and channels along with existing accessories such as clamps, channels, angles, bracing etc of 33 KV substation yard all as directed and required and 0.5 Mtr marking bottom of poles, channels with red colour paint strip of 5 cm thick at a interval of 5 cm up to 0.5 mtr height from the bottom. Note : (i) Painting will be done by part by part as per available of shut down and yard approximate 55 x 60 Mtr area. (ii) Contractor in advance to visit the site before quoting.
Disconnecting and taking out old unserviceable Ammeter of any description and in any position and supply, fixing, connecting, testing and commissioning of new digital Ammeter of size 96mmX96mm of range suitable for panel, 11 KV HT VCB complete all as specified and directed. by Engr in charge (Make: AE/ L&T/ Schneider).
Disconnecting and taking out old unserviceable Volt Meter of any description and in any position and supply, fixing, connecting, testing and commissioning of new digital Volt meter of size 96mmX96mm of range suitable for panel, 11 KV HT VCB complete all as specified and directed. by Engr in charge (Make: AE/ L&T/ Schneider).
Supply only following spare parts for 11 KV VCB 800 Amps capacity of make (Crompton Greaves) conforming to the respective cat part given as under : Note (i) fixing and testing element of following item is deemed to be included under such 'a' item No 25 here-in-before (ii) Quantity of under mentioned items is tentative and contractor shall have no claim on account of variation of quantity or non execution of any of the item)
Vacuum interrupter with complete bottle
Isolating contact Assembly (Flower Type) With Ring
Big Gear Assembly
Small Gear Assembly
Fixed Bottle contact
Flexible Contact
Epoxy Bushing Insulator
Motor and gear Assy for 230 volt AC
Rack in and Rack out gear
Rack in and Rack out Verm
Epoxy Resin Cast Bushing
Charging Assembly
Fixed Bushing
Epoxy mould without vacuum interceptor
Heater assembly complete
Supply only following spare parts for 11 KV VCB 400/630 Amps capacity of make (Crompton Greaves) conforming to the respective cat part given as under : Note:- (i) fixing and testing element of following item is deemed to be included under sch 'a' item No 27 here-in-before (ii) Quantity of under mentioned items is tentative and contractor shall have no claim on account of variation of quantity or non execution of any of the item
Epoxy mould without vacuum interceptor
Sleeves for Epoxy mould
Isolating Contacts (Flower Type )
Sleeves for Isolating Contacts
Closing shaft
Tripping shaft
Big Gear Assembly
Small Gear Assembly
Motor Cut off limit switch
Micro switch assembly (ZZ)
Breaker Control switch
Spring charging Motor 230 VAC
Segment Gear Assembly (square type).
Trips catch assembly
Bus bar support insulator. 61mm dia. Make
Epoxy Bussing insulator for 11kv (Drive rod )
ON/OFF push button Assembly
Charge Discharge indicator assembly
Auxiliary switch 7NO-7NC
Indicating lamps Red,Green,Amber white , 30 VDC
Indicating lamps Blue 230 VAC spring charging
Indicating lamps Red,Yellow,110 VAC
Indicating lamps Blue 110 VAC
NS HRC Fuse Links 2A,4A,6A,10A
Power pack Unit Electronics Make 230VAC/30VDC
Trip circuit healthy push button with auxiliary contact.
Local remote switch .Make:-CG/Schneider
Spout insulator assy (Front) complete
Spout insulator assy (Back) complete
Spout contact (current carrying parts)
Vacuum Interceptor with complete bottle
CGI 14N Numerical Relay (Make. :-CG/Schneider./L&T/Aroba/Ashida/Awana)
Trip circuit supervision relays. Make 30VDC.Make:-CG/Schneider/ABB
Master trip relay 30VDC.Make:-CG/Schneider/Awana/Ashida
CRC Spray bottle 500 ml.
High Tension Electrical Insulation tape 25 RM.
Heater assembly complete
Disconnecting and taking out existing unserviceable current transformer of any description and in any position and Supply, installation, commissioning and testing of cast resin type 11 KV current transformer having ratio of 200+100/5+5 A having protection core class 5P10, burden of 15 VA with suitable match of potential Transformer (PT) as equivalent make and size and metering core class 1.0 and burden of 15 VA breaking capacity of 13.1 KV for 1.0 second all as specified and directed. Make :- Crompton greaves or equivalent
Decarbonising\cleaning complete HT 11 KV 3 Phase bus bar chamber of HT panel electrical connection rods complete HT VCB switch gear arrangement incoming and out going breaker after removing complete monopolist putty cleaning with CRC solution and ensure proper decarbonising refixing the same after applying beacon (red) insulating compound to the spout checking all connections tightening the nut and bolts washers of incoming and out going connections complete all as specified and directed by Engineer-In-Charge. Note : 1. The rate is inclusive for replacement of worn out bolts nuts & washers, lugs, glands etc. 2. Bus Bars used for connecting two VCBs will be measured as one Job.
Testing of Numerical breaker protections relay of various make of 11KV after dismantling of wiring and reassembling /refixing complete all as specified and directed.
Testing of current transformer of various make of 11/33 KV relay all as specified and directed
Testing of Auxiliary relay of various make of 33/11KV panels all as specified and directed
Dismantling and Taking out old Numerical relay wiring any type and any description and replacing wiring with 2.5 sq mm wire, wring materials, lugs, ferrules and cable tie and testing of Auxiliary relay of various make of 33/ 11KV panels all as specified and directed.
Dismantling of inter panel wring , testing and checking of AC/DC supply, S & F Auxiliary relay of various make of 11 kv panels all as specified and directed.
Material and labour for preparation of old painted surfaces of floor mounted indoor/outdoor type VCBs/RMUs/Control Panels for the any capacity/type by cleaning/rubbing with coarse cloth wire brushes to remove dust deposits oil grease and painting with two coats of synthetic enamel paint complete including S&F the SM No/MES No/ Area feeded written on PVC Flex rectangular board in the existing style/pattern/colour complete all as specified and directed.
Cleaning and checking of RMU 3 way/4 way/5 way/6 way/7 way of all parts with coarse cloth wire brushes to remove dust deposits oil grease , including S &F in repairs RMU batteries of various locations all as specified and directed. Note : 1. The rate is inclusive for replacement of worn out bolts nuts & washers, lugs, glands etc.
Disconnecting old unserviceable gate valve and S & F of 15 mm bore gate valve complete with all accessories complete all as specified and directed. Make:
anand enterprises (BID ID -3461352)
Third Wave Services Pvt Ltd (BID ID -3461851)
stage.html
html • 0.06 MB
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Tendernotice_1.pdf
PDF • 0.53 MB
BOQ_821858.xls
BOQ • 0.47 MB
TENDER.pdf
Tender Documents • 1.39 MB
Download all tender documents and submit your bid