Loading…
Loading…
| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | L1₹17.5 LAccepted-AOC | L1 | Accepted-AOC Accepted | |
| 2 | L2₹19.6 L+₹1.4 L (7.89%)Rejected-Finance | L2 | Rejected-Finance NOT LOWEST | |
| 3 | L3₹20.0 L+₹1.8 L (10.1%)Rejected-Finance UDHAM SINGH SARANI ASHRAMPARA PO SILIGURI DISTT DARJEELING 734 001 | JALPAIGURI | WEST BENGAL | 734001 | L3 | Rejected-Finance NOT LOWEST | |
| 4 | L4₹21.1 L+₹2.9 L (16.0%)Rejected-Finance | L4 | Rejected-Finance NOT LOWEST | |
| 5 | L5₹22.0 L+₹3.9 L (21.2%)Rejected-Finance | L5 | Rejected-Finance NOT LOWEST |
Tender Value
₹23 L
EMD Value
₹46,000
Closing Date
26 Dec 2019, 6:00 pmClosed
GE SEVOKE ROAD
GE SEVOKE ROAD PO SALUGARA DIST JALPAIGURI
REPAIR MAINT OF DG SET STP SEWAGE PUMP OPEN WELL PUMP AND FEEDER PILLER BOX WITH CONNECTED ITEMS AT DIFFERENT LOCATIONS AT SEVOKE MIL STN UNDER GE SEVOKE ROAD
2019_MES_299580_1
GE/SEV/19 OF 2019-20
Open Tender
Civil Works
Item Rate
270 days
GE SEVOKE ROAD
Class E Category b (i)
8 documents required · 8 mandatory
₹500
Yes
GE SEVOKE ROAD
₹46,000
Yes
20 Mar 2020
20 Nov 2019
28 Dec 2019
20 Nov 2019
26 Dec 2019
5 Dec 2019
20 Nov 2019 - 30 Nov 2019
Amount
M & L for disconnecting defective sewage non clog type sewage pump set upto 10/7.5 HP capacity at site, opening suction, delivery pipe line connections,coupling nut bolts and taking out the pump set, and transportation to workshop for repair, machine work including refixing, assembling, coupling with motor,lowering down and testing on full load for 04 hours incl providing gland packing and making the pump leak proof incl any other minor work as directed by Engineer-in-Charge.
Note item No 01 :- (i) Spare parts replaced shall be measured and paid separately as supply only under respective item of schedule ii) Transportation charges for the pump sets to workshop & back are deemed to be included in rates quoted, no extra payment will be made on this account. iii) Pump sets issued for repair must be returned & installed duly repaired within seven days otherwise Rs 100 per day per pump will deducted from the bill as penalty. iv) Minor items like nut/bolts, bearing grease, packing gaskets of required size to be taken in consideration while quoting the rates. No extra payment will be made on this account.
Supply only spare parts for submersible sewage pump set up to 10HP
i) Impeller sets for one pump
ii) Mechanical seal set
iii) Oil Seal
iv) rubber gasket sealing
M & L for rewinding burnt coils of Induction Motor stator of following capacity with super enamelled copper winding wire as per existing size and guage to achieve the required /specified RPM including taking out old unserviceable winding ,cleaning/ repairing damaged slots , complete all as specified and as directed.
Note item No 03 :- i) Transportation charges to workshop & back are deemed to be included in rates quoted, no extra payment will be made on this account. ii) Motor issued for repair must be returned & installed duly repaired within seven days otherwise Rs 100 per day per motor will deducted from the bill as penalty. iii) Minor items to be taken in consideration while quoting the rates. No extra payment will be made on this account.
M & L for disconnecting defective Openwell submersible Pump of Capacity 5 to 10HP including transpotation to work shop, taking out burnt winding wire from the stator, cleaning of the casing and the stator with wire brush, rewinding of motor with superior quality copper winding wire of existing size including varnishing and drying, cable jointing, reassembling installing the motor and pump , reconnecting all pipe after cleaning and painting two coats of synthetic enamel paint with preparation of metallic surface and electric connections and testing on full load complete as directed by Engr-in-Charge.
Note item No 05 :- (i) Spare parts replaced shall be measured and paid separately as supply only under respective item of schedule ii) Transportation charges for the submersible pump to workshop & back are deemed to be included in rates quoted, no extra payment will be made on this account. iii) Submersible Pump issued for repair must be returned & installed duly repaired within seven days otherwise Rs 100 per day per pump will deducted from the bill as penalty. iv) Minor items like nut/bolts, bearing grease, packing gaskets of required size to be taken in consideration while quoting the rates. No extra payment will be made on this account.
Supply only following spare parts of submersible pump of 5 to 10 HP capacity : -
(a) CI stage casing
(b) Bearing bush rubber
(c) Stainless Steel sleeve at staging
(d) Brass impellers
(e) Neck ring brass
(f) Key for impellers
(h) MS stud with nuts of size of 3/8" X 2" for stage casing
(j) Bush gun metal at intermediate section
(k) Steel sleeve at intermediate section
(l) CI intermediate section
Stainless steel coupling & key common for submersible pump and motor shaft.
Supply and fixing GI submersible column pipe 100 mm bore "Heavy duty" of length 3 meter each, long threaded at both male & female ends and fixed with separate integral female long threaded socket,of 100 mm bore complete all as specified & directed by Engineer-in-Charge.
S&F flat submersible cable 3 core multi stranded copper conductor of size 6 sqmm. ISI marked complete all as specified and as directed.
Supply and fix in replacement of Steel wire rope, PVC insulated of size 10 mm dia of suitable size/ length as directed with clamps, nuts & bolts and washers etc for holding column pipes / GI pipes of submersible pump set complete all as directed by Engr-in-Charge.
Supply, install, jointing with necessary fittings & testing lever operated CI butterfly valve with neoprene rubber sealing confirming to IS:13095 including taking down of unserviceable butterfly valve all as specified and directed by Engr-in-Charge.
(a) 100 mm bore
(b) 50mm bore
M & L for Scraping old paint of Electric Panel and Painting with two coats of synthetic enameal paint over a coat of red oxide primer including disconnecting electric connection and re-wiring without any damage of existing parts as directed by Engnr-in-Charge complete as all specified and as directed.
S & F in repair DOL submerssible pump controller in sheet metal enclosure MUG type Make: L & T Cat Part SS97756 or equivalent in ABB/SIEMENS/BCH for 6 HP Motor Rating AC-3 Duty, 415V, 50Hz, 3 phase all as specified and directed by Engr-in-Charge
S & F in repair DOL submerssible pump controller in sheet metal enclosure MUG type for Make: L & T Cat Part No.SS95974, or equivalent in ABB/SIEMENS/BCH for 10 HPMotor Rating AC-3 Duty, 415V, 50Hz, 3 phase all as specified and directed by Engr-in-Charge
Dismantling of GI Pipe Connections from the Pressure Flter Plant capacity 6000 to 10000 Gallons, opening the Manhole and removal/taking out old Filter Medias completely from Oxidation Chamber, Pre-filter, Iron Removal Filter and depositing the same to a distance not exc. 100 Metre and re-fixing the pipes in the original/existing Position after replacement of unserviceable PVC Nozzale (Dome type) including replacement of Gasket of Manhole Cover and necessary Bolts, Nuts, Washers, etc. as required, complete all as specified and as directed. NOTE :- (a) PVC Nozzale shall be measured and paid separately under appropriate Item as 'Supply only' here-in-after. (b) Filling of Filter Media shall be measured and paid separately.
Supply and incorporation of MNO2 of size 1/8'' x 1/10'' as filter media of iron removal plant ,complete all as specified & directed.
Supply and incorporation of GRAVEL of size 1 1/4'' x 1 1/2''(collection sourceBARAKAR river bank) as filter media of iron removal plant complete all as specified & directed.
Supply and incorporation of GRAVEL of size 1/2'' x 1''(collection sourceBARAKAR river bank) as filter media of iron removal plant complete all as specified & directed.
Supply and incorporation of GRAVEL of size 1/4'' x 1/2''(collection sourceBARAKAR river bank) as filter media of iron removal plant complete all as specified & directed.
Supply & incorporation of SAND of size 1/6" x 1/8'' mesh (collection source BARAKAR river bank) as filter media of iron removal plant complete all as specified & directed.
Supply & incorporation of Anthracite grit of size 1/8" x 1/4'' as filter media of iron removal plant complete all as specified & directed.
Supply & fixing PVC strainers of sizes as dismantled of Make: PHI/RMCO, complete all as specified & directed.
Testing of water sample of various pump houses of sevoke militry station for bacteriological and chemical testing (systematic analysis) from government approved laboratory including submitting the report to the department ,complete all as specified & directed.
Desiliting / Taking out accumulated sludge, Silt, Mud etc. from sewage sump and connected channels including scrapping down and cleaning internal surface of walls, Floors, Roofs, Mechanical Parts and cleaning blockage of wash out channels, pipes Drainage system etc. and removing the same to a distance not exc. 50 Metre complete all as specified and as directed.
Desiliting / Taking out accumulated sludge, Silt, Mud etc. from Equilaizer tank,FAB-1,tube settler tank, TWT and connected channels including scrapping down and cleaning internal surface of walls, Floors, Roofs, Mechanical Parts and cleaning blockage of wash out channels, pipes Drainage system etc. and removing the same to a distance not exc. 50 Metre complete all as specified and as directed.
S & F as in repairs Dry run protection relay with detection of single phase preventor,VI meter(current based), 3 Phase Motor Starter or as per existing size complete all as specified and as directed. Make: L & T Model: i-ADSM, Cat part No.-CS90863 or equivalent in ABB/SIEMENS/BCH.
M&L Painting to Internal Surfaces of Iron Removal Chamber, Pre- filter Chamber and Oxidation Chamber including Pipes complete of Filteration Plant capacity 8000 GPH with Two Coats of Black Bituminous Paint (Lead Free) suitable for Drinking Water grade including necessary surface preparation by means of scraping, brushing, cleaning, complete all as specified and as directed.
M&L Painting to External Surfaces of Iron Removal Chamber, Pre-filter Chamber, Oxidation Chamber including Pipes complete of Fiteration Plant capacity 8000 GPH with Two Coats of Sythetic Enamel Paint of approved colour over a coat of Red Oxide Primer including neccessary preparation of surfaces, complete all as specified and as directed.
M & L for PCC (1:3:6) type C1 (using 20mm graded stone aggregate) as in cement concrete work in pavement/hard-stading inside the STP installation all as directed by Enginner- in -Charge
M&L Construction Brick Masonry Valve Pit of size 900x900x1200 mm (Internal Dimension) one Brick thick Wall in Cement Mortar 1:4 on 100mm thick PCC 1:4:8 (40mm graded stone aggre-gate) in Foundation, Rendering 15mm thick internally and externally upto 150mm below GL, providing 3.0mm thick MS Sheet Valve Pit Cover, welded with 40x5mm Flat Iron Frame alround including provision of Hinges, Handle with Locking Arrangement and 40x40x6mm Angle Iron Frame fixed on top of Valve Pit by means of holdfast 150mm long, embedded in PCC 1:2:4 (20mm graded aggregate) Block of size 230x200x100 mm, applying two coats of Anti-corrosive Paint to all exposed Steel Surfaces over a coat of red oxide zinc chrome Primer after preparation of Surfaces and necessary Earth Work in Soft/ Loose Soil including demolition of unserviceable Valve Pit, complete all as specified and as directed.
Display board indoor type of size 150x60cm fabricated on 6 mm thick ply board and acrylic sheet of 2 mm thick for writing instructions and line diagram, with aluminium bedding fixing on 40mm dia GI pipe medium grade of (2x3=6Mtr) with 2x 9watt 2' light fitting inside board complete including dismantling existing unserviceable one complete all as specified and as directed.
Maintenance & servicing of existing DG set including tappaet cover adjustment & replacement of gasket of capacity 12.5 KVA including necessary replacement of following spares complete as specified and directed: ( Note: Spares will be measured & paid separately under respective items)
(i) Supply only of Fuel Filter
(ii) Supply only of Lubricant oil filter
(iii) Supply only of Coupling
(iv) Supply only of Fan belt
(v) Supply only of carbon bush
(vi) Supply only lubricant oil supply pipe
Maintenance & servicing of existing DG set including tappaet cover adjustment & replacement of gasket of capacity 25 KVA &30KVA DG Set including necessary replacement of following spares complete as specified and directed: ( Note: Spares will be measured & paid separately under respective items and Rate will be quoted for each DG set).
(a) Supply only of Fuel Filter
(b) Supply only of Lubricant oil filter
(c) Supply only Carbon Bush
(d) Supply only Air Filter element
(e) Supply only Radiator hose pipe set
(f) Supply only Fan belt
(g) Supply only LLOP Sensor
Maintenance & servicing of existing DG set including tappaet cover adjustment & replacement of gasket of capacity 40KVA DG Set including necessary replacement of following spares complete as specified and directed: ( Note: Spares will be measured & paid separately under respective items)
(a) Supply only of Fuel Filter
(b) Supply only of Lubricant oil filter
(c) Supply only Radiator hose pipe set
(d) Supply only Fan belt
(e) Supply only rpm meter with lead
(f) Supply only LLOP Sensor
Maintenance & servicing of existing DG set including tappaet cover adjustment & replacement of gasket of capacity 75KVA and 82.5 KVA DG Set including necessary replacement of following spares complete as specified and directed: ( Note: Spares will be measured & paid separately under respective items and Rate will be quoted for each DG set).
(a) Supply only of Fuel Filter
(b) Supply only of Lubricant oil filter
(c) Supply only Radiator hose pipe set
(d) Supply only Fan belt
(e) Supply onlu carbon bush
(f) Suppluy only High pressure oil pipe
(g) Supply only LLOP Sensor
Maintenance & servicing of existing DG set including tappaet cover adjustment & replacement of gasket of capacity 250KVA DG Set including necessary replacement of following spares complete as specified and directed: ( Note: Spares will be measured & paid separately under respective items & Rate will be quoted for each DG set)
(a) Supply only of Fuel Filter
(b) Supply only of Lubricant oil filter
(c) Supply only Radiator hose pipe set
(d) Supply only Fan belt
(e) Suppluy only High pressure oil pipe
M & L for taking out old U/S engine oil from DG Sets sumps, cleaning the sump throughly, supply & filling new engine oil complete of Make: Servo Super 20W40 of Indian Oil or Equivalent grade of Hindustan Petroleum as approved by GE, complete all as specified and directed
M & L for topping up of water coolant in radiator of DG set of Make: TVS Grilling/Volvo line or equivalent make as approved by GE,complete all as specified and as directed.
M & L for dismantling of FIP for overhauling and calibration in authorised workshop including replacement of worn-out rings plungers, damper plate, gasket etc reassembling and testing complete all as specifed and as directed for following DG Set:
(b) 25KVA to 30KVA
Repair Overhauling of self starter including replacement of worn out clutch assembly bush, spring, plunger assembly, solenoid switch, carbon brushes,spring etc complete all as specified and as directed for the following DG sets:
(b) 25KVA to 30KVA
Repair/Overhauling of dynamo/charging alternator including replacement carbon, brushes holder, spring commutator/slip ring assembly bearing regulator of any make , type and capacity complete all as specified and as directed
Cleaning of the fuel tank of DG sets of following capacity after decaning the diesel, after through cleaning with kerosene oil including replacement of level indicator pipe complete all as specified and as directed:
25KVA to 30KVA
Dismantling and removing of water pump assembly complete from the engine, repair/overhauling the same by replacing worn out components like bearing, impeller, bushes, oil seal, water seal, gasket etc. re-assembling, refixing and testing complete all as specified and directed for the following capacity of DG sets:
(a) 30KVA/40KVA/75KVA
M & L for replacement of old U/S fuel shutdown valve assembly complete testing including replacement of old unserviceable valves of any capacity DG set, complete all as specified and as directed.
M & L for replacement of old U/S bendix assembly of self starter of capacity 30 KVA to 250KVA DG set complete all as specified and as directed
M & L for replacement of old U/S existing make and model fly wheel ring including heating for press fitting for engine of DG set of capacity 30KVA to 75 KVA, complete all as specified and as directed.
M & L for replacement of old U/S stop solenoid 25 KVA to 30KVA DG Set complete all as specified and as directed
(a) All as per Item No. 47 but for 62.5 to 75KVA
(b) All as per Item No. 47 but for 125 to 250 KVA
Dismantaling of radiator of DG Setof capacity 25 to 50 KVA and transporting to work shop for servicing/cleaning after dismantling twin tanks, replacement of gasket packing, nuts bolts, washers, descaling with appropriate chemical and elding of copper brazing of damaged fins/tubes and reassembling & refixing in same position after tesing complete all as specified and as directed.
(a) All as perItem No. 48.00 but of capacity 75KVA
(b) All as per Item No. 48.00 but of capacity 250KVA
Dismantaling and fixing of following spare parts of DG set capacity 75 KVA Make: Kirloskar to its original location and testing complete all as specified and directed.( Note: Spares will be measured & paid separately under respective items
(a) Supply only complete piston assy
(b) Supply only complete piston ring set
(c) Supply only C R bearing
(d) Supply only Main Bush
(e) Supply only main bush housing
(f) Supply only Valve set
(g) Supply only valve spring
(h) Supply only valve guide with sheet
(j) Supply only cylinder head gasket
(k) Supply only set of O ring
M & L for replacement of moulded rectifier unit on existing DG set of capacity 120 Ohms for alternator exciter unit complete all as specified and as directed
All as per item No.50.00 but of capacity 140 Ohms
M & L for battery teriminals including removal of existing unserviceable one compete all as specified.
Excavation in trenches not exc 1.5 Mtr wide and not exc 1.5 Mtr deep soft/loose type of soil getting out and levelling of bottom surface to required level for poles/stay assembly/cable all as specified and as directed.
Returning filling in including spreading, leveling, watering and well ramming in layers not exc 25cm thick all as specified and directed.
Removing excavated material from site to a distance not exc 50mtr away and depositing where directed not exc 1.5mtr from the starting point all as directed.
Supply and laying un reinforced pre cast concrete cable cover, class LV type 1, flat size 250x150x40mm perpendicular to the axis for the cable in trenches for protection to cable complete.
Relaying only old recovered cable cover of any size in trenches complete all as directed by Engr-in-Charge.
M & L Sand Cushioning (dry) in trenches/ducts for protection of UG Cables (below, above and around the UG Cable laid in Trenches) of 23 Cm Spread thickness (8 Cm in depth before laying the Cable and 15 Cm in depth after laying the Cable) and consolidated (punned) upto 180 mm thickness, complete all as specified and as directed. Note : Punned thickness of Sand Cushioning only shall be measured for payment.
M&L for PCC 1:3:6 (40 mm graded stone aggregate) Type C2 for foundation of pole, stay including form work where reqd complete all as directed.
M&L for PCC (1:2:4) type B-1 coping 20 mm graded stone aggregate for grouting, finished even and smooth without using extra cement complete all as directed.
M & L for LT underground Cable, including takingdown existing u/s XLPE insulated, heavy duty armoured sheathed 1100 volts grade 10 Sq mm, 2 core, with aluminium conductor, ISI marked as per IS : 7098(Part-1) complete with all as specified.
(a) All as per item No 61 above but 16sqmm, 4 core.
(b) All as per item No 61 above but 25sqmm, 3.5 core.
(c) All as per item No 61 above but 35sqmm, 3.5 core
(d) All as per item No 61 above but 70sqmm, 3.5 core
(e) All as per item No 61 above but 95sqmm, 3.5 core
(f) All as per item No 61 above but 120sqmm, 3.5 core
(g) All as per item No 61 above but 185sqmm, 3.5 core
Taking down existing unserviceable/faulty LT UG cable 1100V of any size from existing location and relaying the same after necessery repair work all as specified and as directed.
Supply and fixing cable joining kit for 1.1 KV grade for straight through joint complete with Jointing material heat Shrink type and accessories suitable for 3.5 /4 core XLPE, armoured, AI conductor cable of size 25 to 50 Sqmm, Indoor/Outdoor type, including taking out & relaying damaged UG cable after repair complete all as specified and as directed. Make : Birla-3M / DENSON /Raychem (Note: Excavation and connected items will be measured and paid separetely).
(a) All as per item No 63 above but size 70-120sqmm, 4 core all as specified.
(b) All as per item No 63 above but size 150-185sqmm, 4 core all as specified.
Restring/Fixing only of existing ACSR conductor any size/any type drawn on fixed to insulator on the pole complete as with permissible sags for OH Conductor as per Indian Electricity Rules 1956 - Para 77 and 79 all as specified and directed.
Labour for cutting of trees branches 2 mtr above the conductor which are touching to the HT/LT over head lines in vertically & horizontally conductor and poles etc. Complete clear in a standard span in between two poles and removing cutting material not exc 50 mtr and depositing where directed at a distance level no exc 3 mtr from starting point, minium 04 Nos of mazdoor man with ropes/cutting tools complte will be engaged for a standard one span at a forest/high gradient/any type of surfaces, follows safety measures as per IE Rules, complet all as speciied and as directed.
M & L in repair GI tubing of 50 mm bore medium grade with all fitting fixed to wall/ceiling as cable protection laid on floor all as specifed and directed.
M & L in repair GI tubing of 80 mm bore Medium grade with all fitting fixed to wall/ceiling as cable protection laid on floor all as specifed and directed.
M&L MCCB 4 Pole, including taking down old u/s having current rating 400 Amp, thermal magnetic and microprocessor release setting adjustable 70%-100% breaking capacity 36 KA at 415V,50Hz, Frame size/type CH .Make-Legrand Cat Pt No 422007 or equivalent model of Havell's/L&T
M&L MCCB 4 Pole, including taking down old u/s having current rating 250 Amp, thermal magnetic and microprocessor release setting adjustable 70%-100% breaking capacity 25 KA at 415V,50Hz, Frame size/type CH. Make-Legrand Cat Pt No-420219 or equivalent model of Havell's/L&T.
M&L MCCB 4 Pole, including taking down old u/s having current rating 200 Amp, thermal magnetic and microprocessor release setting adjustable 70%-100% breaking capacity 25 KA at 415V,50Hz, Frame size/type CH .Make-Legrand Cat Pt No-420218 or equivalent model of Havell's/L&T
M&L MCCB 4 Pole, including taking down old u/s having current rating 160 Amp, thermal magnetic and microprocessor release setting adjustable 70%-100% breaking capacity 25kA at 415V,50Hz, Frame size/type CH .Make-Legrand Cat Pt No 420217 or equivalent model of Havell's/L&T
M&L MCCB 4 Pole, including taking down old u/s having current rating 63-100 Amp, thermal magnetic and microprocessor release setting adjustable 70%-100% breaking capacity 25 KA at 415V,50Hz, Frame size/type CH .Make-Legrand Cat Pt No-420053-55 or equivalent model of Havell's/L&T
M&L cutting for raod crossing, PCC hard standing for laying of cable/protection pipe including making good the existing damaged surface with same finish PCC 1:3:6 type C-2( using 40 mm graded stone aggregate) to match the original finish complete all as specified and as directed.
M & L for Earthing complete with galvanized steel earth plate electrode 600x600x6mm thick buried directly in ground earth pit not less than 2.25mtr deep below normal ground level with top edge of the plate not lessthan 1.5 mtr below ground level connected to galvanized iron 4mm dia as earth lead by mean of nut/bolt and washer of galvanized iron or steel as shown in electrical plate no 3 of SSR part-I including necessary excavation ad earth work GI pipe 20 mm dia light grade for watering and GI 15 mm dia ligt grade pipe for protection of GI earth wire etc, PCC chamber with PCC cover in cement concredte 1:2:4 Typoe B1 (20mm graded aggregate), funnel, wire mesh, charcoal dust, salt etc, connected to LT panel board as indicated including testing complete all as specified and as directed.
SHRI JIBANDHAN PAUL
M/S AJIT GARAGE
CHANDAN TRADERS
BIJAN KUMAR DHAR
D.D. BROTHERS
M/S S.B. CONSTRUCTION
stage.html
html • 0.06 MB
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .