Loading…
Loading…
| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | L1₹4.0 LAccepted-AOC 01 VILLAGE BABOORI BARARI MATHURA UTTAR PRADESH 281005 | MATHURA | UTTAR PRADESH | 281005 | L1 | Accepted-AOC Shortlisted | |
| 2 | L2₹5.1 L+₹1.1 L (26.8%)Rejected-AOC | L2 | Rejected-AOC Rejected | |
| 3 | L3₹5.7 L+₹1.7 L (43.1%)Rejected-AOC | L3 | Rejected-AOC Rejected |
Tender Value
₹4.1 L
EMD Value
₹8,120
Closing Date
23 Apr 2020, 3:00 pmClosed
Executive Engineer
Behind PWD Rest House Jawhar Nagar Camp Palwal, Distt. Palwal (Haryana)
Supply, installation testing and commissioning of 1 No. electromagnetic Flow Meter alongwith RTU at Inlet pipe of 9.00 MLD. STP at Palwal Town and all other works contingent thereto
2020_HRY_125872_1
SEPwl No. 3427 dated 03.04.2020
Open Tender
Civil Works
Works
90 days
Palwal
Refer to the tender documents
3 documents required · 3 mandatory
₹500
Executive Engineer
₹8,120
Yes
30 Apr 2020
9 Apr 2020
23 Apr 2020
9 Apr 2020
23 Apr 2020
9 Apr 2020
Amount
Supply, Installation, testing and commissioning Electromagnetic Flow Meter size for 400mm Model No: 151 MFM W R 4 2 2 0 N 400 3 D 1 2 6 1 4 2 8 P W:Accuracy Class & Display:± 0.5% of measured flow; 2 Line LCD R:Indicator Converter Type: Remote, field mounted 4:Power Supply: Universal Power Supply 85 to 265VAC@45to 65 Hz 2:Output:4 to 20mA 2:Communication Interface: RS 485 (MODBUS RTU) 0:Data Logger: Not Applicable N:Cable Entry:1/2"NPT 0300:Sensor Size (mm):250 mm(10”) 3:Pressure Rating(Kg/cm2):16 Kg/cm2 D:Design of the Measuring Sensor: Flanged-DIN 1:Flange Material: CS 2:Sensor Lining: PTFE 6:Electrode Material:SS316 1:Earthing ring: None. With built-in earthing electrode. 4:Measuring Tube:SS304 2:Coil Housing: CS 8:Protection Class for Sensor:IP68 P:Approval:Non Hazardous area Cable L=20 mtrs Make –Iotaflow, Emkometer, Apator
Supply, Fixing, testing & commissioning of Remote Terminal Unit with power analyzer having inbuilt GSM / GPRS modem. iRTU configuration is 6 Digital inputs, 2 Digital Outputs & 2 Analog Inputs. iRTUiinstallation inside a panel having isolation transformer. RTU suitable for multi parameter for transferring data to MCS complete in all respect. Make Iotaflow, Emkometer,Apotor.
Installation & accessories like Cabling as per site requirements, Panel Box etc.. Commissioning Charges of Flow Meter, Customization and programming of flow meter, Configurations as per site requirements & making connection with the existing SCADA software, Head Office, HSPCB & CPCB to the satisfaction of Engineering In‐charge, including one year maintenance charges .
Providing & fixing D.I. fitting duly ISI marked as per IS : 9523-2000 (K-12) (PN-10) (suitable size) 1. Flanged socket including the cost of nut bolt rubber ring etc. 2. Flange SPIGOT(Tail Pcs) including the cost of nut bolt rubber ring etc. 3.Hire charges of JCB for fixing of tail piece (Excavation & refilling)
JAINN CONTRACTOR
Dinesh Kumar Conteractor
stage.html
html • 0.04 MB
tech_eval.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .