| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | L1₹34.9 LAccepted-AOC C 40 BHAGAT SINGH NAGAR BHIND ROAD GWALIOR MP 474005 | NA | NA | 474005 | L1 | Accepted-AOC Being a L1 bidder | |
| 2 | L2₹36.6 L+₹1.2 L (3.32%)Rejected-Finance 640 MAIN ROAD BABINA CANTT JHANSI UP 284401 | JHANSI | JHANSI | UP | 284401 | L2 | Rejected-Finance Other than
lowest
bidder | |
| 3 | L3₹43.9 L+₹8.4 L (23.8%)Rejected-Finance | L3 | Rejected-Finance Other than
lowest
bidder |
Tender Value
₹49.2 L
EMD Value
₹98,400
Closing Date
14 Dec 2023, 6:00 pmClosed
Eligibility, documents, scope and key termsEligibility, required documents, scope of work and key terms of this tender, in one click.
GE BABINA
GE BABINA CANTT 284401
PROVN OF CERTAIN SPECIAL REPAIR WORK AT AGE B/R-I AND AGE E/M UNDER GE BABINA CANTT
2023_MES_627319_1
8176/E8
Open Tender
Civil Works
Item Rate
180 days
GE BABINA
AS PER TENDER DOCUMENTS
8 documents required · 8 mandatory
₹500
GE BABINA
₹98,400
Yes
17 Feb 2024
7 Nov 2023
16 Dec 2023
7 Nov 2023
14 Dec 2023
24 Nov 2023
Amount
Demolition of PCC/lime concrete (Other than Ground flooors) terracing including felt in any description and in any position over roof etc complete all as specified and as directed by the Engineer-in-Charge.
M&L for P.C.C 1:2:4 type B-0 using 12.5 mm graded stone aggregate as in padding over roof finished and laid to required slope complete all as specified and as directed.
M&L, roughening surfaces of old concrete roof by picking ,sweeping, clean and washing down with water to remove dust etc and applying a coat of cement slurry @ 3 Kg per Sqm complete all as specified and directed.
M&L for P.C.C 1:2:4 type B-0 using 12.5 mm graded stone aggregate as in coping or roof kerbs on roof chamfered on edge including troweling slightly complete all as specified and as directed.
M&L for 10 mm thick rendering in cement mortar 1:4 on concrete surfaces when concrete is stil green finished even and fair including mixing of water proofing compound as per manufacturer instruction etc complete all as specified and as directed.Note :- Water proofing compound shall be measured separately as supply only in item no 06
Supply only integral water proofing compound complete all as specified and as directed.
M&L for applying water proofing treatment with the following:- (a) First coat of bitumen primer conforming to IS-3384 @ 0.3Kg / sqm to be applied on prepared surface till the surface is properly impregnated. (b) The water proofing memberne minimum weight 3kg/sqm and minimum 3mm thick reinforced with polyestered non woven fabric (weight not less then 160gms/sqm) shall be laid on the primed surface by torch application method as per manufactured instruction including Aluminium paint complete as spd. (c) All joints and change in direction should be curved with cement mortar (1:3) mixed with SBR latex @ 200ml per bag on cement and cured well before laying of membrane.
Cutting chases, pinning in, making good to facings where required and pointing in cement mortar 1:3 to ends or edges of landings, steps, cills, sunshades, shelves, lintels etc., and cutting chases for concealed water tubing or concealed conduit wiring, etc., and making good, cuttingexceeding 10 cm but not exceeding 20 cm girth in brick walls complete all as specified and as directed.
Taking up or down existing steel water tubing 15 mm bore and connections including cleaning for refixing or removal to store complete all as specified and as dircted
Taking up or down existing steel water tubing 20 mm bore and connections including cleaning for refixing or removal to store complete all as specified and as dircted
Supply and fixing, jointing and testing galvanised iron tubing 15 mm bore medium grade with all fittings such as bends, elbows sockets, reduces etc and fixed to wall, ceiling or laid in floor etc with new fittings complete all as specified and directed.
Supply and fixing, jointing and testing galvanised iron tubing 20 mm bore medium grade with all fittings such as bends, elbows sockets, reduces etc and fixed to wall, ceiling or laid in floor etc with new fittings complete all as specified and directed.
Fixing only old steel tubing 15mm dia and connections obtained from taken down against item No 3 herein before in new or old position fixed to wall, ceiling or laid in floor with new fittings etc complete all as specified and as directed.
Fixing only old steel tubing 20mm dia and connections obtained from taking down against item No 4 herein before in new or old position fixed to wall, ceiling or laid in floor with new fittings etc complete all as specified and as directed.
S & F 500ltr rotational moulded polyethylene water storage tanks, (cylindrical vertical with closed top) hoisted and fixed in position, all as specified in SSR part I-1991 including 20 mm dia GI pipe light grade washout pipe 450 mm long with plug and 20 mm dia GI pipe light grade over flow pipe 600 mm long with fitting and dismantling of existing unserviceable tank and removing from site, complete all as specified and directed.
S&F 20mm bore ball valve high pressure of PTMT with epoxy coated aluminium rod & high density plastic ball screwed for iron pipe and fixed (Minium weight 210 gms ), complete all as specified and directed
S & F in repair 20mm dia Gun metal gate valve with iron wheel head, screwed both ends for iron pipe complete all as specified and as directed.
Demolition of Brick work or stone/ boulder masonry, built in cement mortar or cement lime mortar including all quoins, arches, pillars, etc, but excluding ashlar facings, dressed stonework and precast concrete articles etc complete all as specified and as directed
M & L for brickwork with fly ash bricks, straight or curved on plan exc 6m mean radius, built in cm (1:6) to raise the hight of brick wall complete all as specified and as directed.
M& L, Brickwork, with subclass ‘B’ bricks old size straight or curved on plan exc 6 M radius built in CM 1:6 but except Bricks etc complete all as specified and directed.
Taking down cement plaster on brick or stone wall including raking out joints, hocking for key scrubbing down with water etc complete all as specified and as directed.
M&L for rendering 15mm thick on fair faces of wall, finish even and smooth without using extra cement on concrete/brick surfaces in CM 1:4, complete all as specified and as directed
M&L for rendering 10mm thick on fair faces of wall, finish even and smooth without using extra cement on concrete/brick surfaces in CM 1:4, complete all as specified and as directed
Dismantling floor, hearth or wall tiling including cement mortar bedding (but not backing), removing serviceable tiles to store and rubbish off the premises and complete all as specified and as directed.
M&L for non skid coloured joint free ceramic tiles 7 to 8 mm thick (square / rectengular) area of each tile exceeding 0.11sqm but not exc 0.18 sqm, in floors etc. set and jointed in neat cement slurry and pointed in white or coloured cement to match to floor etc including 15 mm screed bed with CM(1:4) and 25 mm thick PCC(1:2:4)type B0 complete all as specified and as directed.
M&L for joint free glazed coloured tiles 350x250x7mm/450x350x7mm thick for work on vertical surface, set & jointed in cement slurry and pointed in white or coloured cement to match etc including rendering 10mm thick on fair faces of wall or conc surfaces in CM 1:4 finished rough for wall tiling complete all as specified and as directed
Demolition of PCC in any description and in any position etc complete all as specified at site complete all as specified and as directed
M&L for 75mm thick cement concrete 1:3:6, type C-1 (using 20mm graded aggregate) as in plinth protection finished even and smooth without using extra cement complete all as specified and directed
M&L PCC 1:4:8 type D2 using 40mm graded stone agg as in filling and mass concrete, Sub base/flooring complete all as specified and directed.
M&L for river sand filling under floors or in foundations including watering and consolidation complete all as specified and directed.
M&L 80 mm thickness M-40 Grade , machine pressed precast concrete Inter locking paver blocks any shape & size with grey cement and pigment conforming to IS-15658-2006 laid dry over sand cushion.(Sand cushion shall be measured and paid separately) complete all as specified and directed.
M&L for 100mm thick cement concrete type B2, 1:2:4 (40mm graded aggregate) as in floor/hardstanding finished even and smooth without using extra cement complete all as specified and directed.
M & L for Preparation of new plastered surfaces of wall and applying two coat of OBD over a coat of putty complete all as specified and as directed.
M & L for preparation of new plastered surface of wall and applying two coats of cement base paint on external wall surface over a coat of alkali resistant primer complete all as specified and as directed.
Dismantling of plain or corrugated steel sheeting etc complete all as specified and as directed.
S & F Pre painted galvalume aluminium zinc coating GI based corrugated steel sheet 0.50mm thick of any colour having tensile strngth of 550 Mpa as in roof covering/cladding to wall, fixed with self tapping screw complete all as specified and as directed.
S & F MS steel work in tubular trusses and tubular posts, purlin including special shaped washers etc., complete using ERW or induction butt welded tubes conforming to I.S.I 1161-1998 Grade St-240 with one shop coat of zinc chromate primer paint complete all as specified and as directed.
M & L for preparation of new steel surfaces of any description n.exc 10 cm width or girth and applying two coats of synthetic enamel paint over one coat of primer complete all as specified and directed.
S & F Post and struts in fencing including cutting tops to shape as directed , drilling holes notching for barbed wires etc ;flat iron fillets (for securing wire mesh) including all necessary drilling, bolting or riveting etc all as specified and directed.
S & F Galvanised 2 strand, steel barbed wire 2.24 mm dia barbed with with 2 mm dia barbs at 75 mm at spacing and straining and fixing to any type of standard rails straining bolts including securing or tying at crossings with land provision of galvanised mild steel pins etc complete all as specified and as directed.
S&F Bands, straps, supports or stays for rainwater, ventilating pipes, including bolts, if required:hooks (stay), heavy, for large gates; hook and pintle hinges:large hasps and staples; chains;hand made sliding bolts; clamps; hold fasts; wall ties; hooks for hanging fans; plain angle cleats for securing purlins to wood trusses or rafters; knee piece inserts; two way and three way straps, plate washers and similar small articles conforming to Fe-290 Gde-E-165 complete all as specified and directed
M & L for complete removal of existing treatment from surface of wall copmlete all as specified and as directed by the Engineer-in-Charge
M & L for applying one coat of putty all as per manufacturere instruction complete all as specified and as directed by the Engineer-in-Charge
M & L for applying two coat of oil bound distemper including preparation of new surfaces complete all as specified and as directed by the Engineer-in-Charge
M&L Preparing old decorated surfaces of wall and applying two coats cement base paint complete all as specified and as directed.
M&L, Preparing old plastered/unplastered surfaces of ceiling and applying one coat of white wash complete all as specified and directed.
M&L for preparation old wooden surface of any description not otherwise described over 10 cm width or girth and applying two coat synthetic enamel paint over one coat of pink primer etc complete all as specified and as directed
Taking down chowkhat or frames with shutters (without taking off shutters from the frame) not exe 1.5 Sqm each complete all as specified and as directed.
S&F 35mm thick flush shutters, factory made, solid core construction with block board core and plywood face panelled with decorative face veneers on both faces with lipping to match complete all as specified and as directed.
M&L for preparation old steel surface of any description not otherwise described over 10 cm width or girth and applying one coat synthetic enamel paint over one coat of pink primer etc complete all as specified and as directed
Excavation in trenches in soft/loose soil not exc 1.5 mtrs wide and not exc 1.5 mtr in depth for laying of pipe/ cables/ poles etc and getting out complete all as specified and as directed.
Returning filling in any type of soil including spreading leveling watering and well ramming in layers n.exc 25 cm complete all as specified and as directed.
Removing excavated soils to a distance n.exc. 50 mtr and depositing where directed at a level not exc 1.5 m above the starting point complete all as specified and as directed.
M & L for laying of fine, clean sand (river sand) free from sharp materials and stone particals in trenches for cushioning of cable 8 cm thick under cable and 15 cm thick over the cable including gently punning complete all as specified and directed. Note:- The total thickness of sand shall be measured 18 cm after punning.
Supply and laying un-reinforced precast.concrete cable protection cover of class LV, type-1, flat size 250mm x 150mm x 40 mm, factory made of specified make , complete all as specified and directed.
Supply, laying and testing in repair/replcement of XLPE insulated cable, screened, PVC bedded galvanised steel strip or wire armoured electric power cable (heavy duty) 1100V grade with multistranded aluminium conductor of size 120Sqmm 3.5 core as per IS 7092 Pt -I including taking down old pipe complete all as specified and directed.
Supply, laying and testing in repair/replcement of XLPE insulated cable, screened, PVC bedded galvanised steel strip or wire armoured electric power cable (heavy duty) 1100V grade with multistranded aluminium conductor of size 95Sqmm 3.5 core as per IS 7092 Pt -I including taking down old pipe complete all as specified and directed.
Supply, laying and testing in repair/replcement of XLPE insulated cable, screened, PVC bedded galvanised steel strip or wire armoured electric power cable (heavy duty) 1100V grade with multistranded aluminium conductor of size 70Sqmm 3.5 core as per IS 7092 Pt -I including taking down old pipe complete all as specified and directed.
Supply, laying and testing in repair/replcement of XLPE insulated cable, screened, PVC bedded galvanised steel strip or wire armoured electric power cable (heavy duty) 1100V grade with multistranded aluminium conductor of size 50Sqmm 3.5 core as per IS 7092 Pt -I including taking down old pipe complete all as specified and directed.
Supply, laying and testing in repair/replcement of XLPE insulated cable, screened, PVC bedded galvanised steel strip or wire armoured electric power cable (heavy duty) 1100V grade with multistranded aluminium conductor of size 25Sqmm 3.5 core as per IS 7092 Pt -I including taking down old pipe complete all as specified and directed.
Supply, laying and testing in repair/replcement of XLPE insulated cable, screened, PVC bedded galvanised steel strip or wire armoured electric power cable (heavy duty) 1100V grade with multistranded aluminium conductor of size 16Sqmm 4 core as per IS 7092 Pt -I including taking down old pipe complete all as specified and directed.
S & F in replacement of MCCB, 04 Pole, capacity 63 Amps with ultimate breaking capacity 16 KA at 415 volts with fixed thermalsettings conforming to IEC 60947 Part-I/IS-13947 Part-I , (Ics=Icu=100%) in the existing panel with suitable connecting copper terminals at site complete all specified and directed.
S & F in replacement of MCCB, 04 Pole, capacity 100 Amps with ultimate breaking capacity 25 KA at 415 volts with fixed thermalsettings conforming to IEC 60947 Part-I/IS-13947 Part-I , (Ics=Icu=100%) in the existing panel with suitable connecting copper terminals at site complete all specified and directed.
S & F in replacement of MCCB, 04 Pole, capacity 160 Amps with ultimate breaking capacity 25 KA at 415 volts with fixed thermalsettings conforming to IEC 60947 Part-I/IS-13947 Part-I , (Ics=Icu=100%) in the existing panel with suitable connecting copper terminals at site complete all specified and directed.
S & F in replacement of MCCB, 04 Pole, capacity 200 Amps with ultimate breaking capacity 25 KA at 415 volts with fixed thermalsettings conforming to IEC 60947 Part-I/IS-13947 Part-I , (Ics=Icu=100%) in the existing panel with suitable connecting copper terminals at site complete all specified and directed.
S & F in replacement of MCCB, 04 Pole, capacity 250 Amps with ultimate breaking capacity 36 KA at 415 volts with fixed thermalsettings conforming to IEC 60947 Part-I/IS-13947 Part-I , (Ics=Icu=100%) in the existing panel with suitable connecting copper terminals at site complete all specified and directed.
S & F in replacement of MCCB, 04 Pole, capacity 315 Amps with ultimate breaking capacity 36 KA at 415 volts with fixed thermalsettings conforming to IEC 60947 Part-I/IS-13947 Part-I , (Ics=Icu=100%) in the existing panel with suitable connecting copper terminals at site complete all specified and directed.
S & F in replacement of MCCB, 04 Pole, capacity 400 Amps with ultimate breaking capacity 50 KA at 415 volts with fixed thermalsettings conforming to IEC 60947 Part-I/IS-13947 Part-I , (Ics=Icu=100%) in the existing panel with suitable connecting copper terminals at site complete all specified and directed.
S & F in replacement of off load change over switch, 100 Amps, 4 pole, AC 415 Volt, 50Hz in SS enclosure side handle operated complete all as specified and directed.
S & F in replacement of off load change over switch, 63 Amps, 4 pole, AC 415 Volt, 50Hz in SS enclosure side handle operated complete all as specified and directed.
Supply, fixing, testing and commissioning of outdoor type bus bar panel pedestal type weather proof CPRI approved MS cubical panel board made of 3 mm CRCA MS sheet of size 110 cm x 80 cm x 40 cm, 4 Nos of aluminium bus bar of 300 Amp capacity with MCCB 4 pole of Capacity 200 Amp 25 KA (Ics =Icu=100%) including painting with one coat of red oxide primer and two coat of enamel paint powder coated, mounted on angular frame work of 50x50x5mm thick angle iron base frame, minimum 60 cm hight and fixed with PCC 1:4:8 type D-2 (using 40mm graded crushed stone aggregate) in foundation for fixing panels, powder coated finish over one coat of red oxide primer outside and two coats of red oxide primer on inside and PCC 1:4:8 type D-2 (using 40mm graded crushed stone aggregate) in foundation for fixing panels & aluminium busbar chanel insulated with colour coated heat shrinkable sleaves and mounted on DMC/Epoxy insulator all as specified & directed.
Supply, erecting and fixing in replacement of true vertical position, prestressed concrete pole 9.0 mtr long 102 mm x 172 mm at top and 152 mmx 279 mm at bottom class 10 (Numbering of the poles shall be done with synthetic enameled painted letter of shape & size) including taking down of old unserviceble pole & shifting of cross arms ACR conductor , GI wire, insulator, street light brackets etc complete all as directed. Note :- Excavation incl earth work and PCC foundation will be measured and paid separately. The old unserviceable pole obtained from dismanting shall be remove by the contractor form cantt area/MOD. If the contractor has not removed the dismantled item a penality of Rs.500.00 per pole will be charged from the contractor as a penality.
Supply, erecting and fixing in true vertical position, steel tubular swaged pole (410 SP-31) 9.0 mtr long, complete with cast iron base plate, pole cap / finial taper plug, bolts, nuts and washers, welded reduced section and longitudinal weld throughout entire length of pole including 2 coats of black bituminous paint externally upto planting depth and remaining exterior portion of pole shall be provided with two coats of aluminium paint over one coat of red oxide primer and incl taking down existing old unserviceable poles complete all as specified and directed. (Numbering of the poles shall be done with synthetic enameled painted letter of shape & size as directed.) Note :- Excavation incl earth work and PCC foundation will be measured and paid separately.
Supply & fixing GI tube 50 mm bore light grade with all fittings for laid in trenches/fixed along with poles/walls & floor of buildings etc under crossing of road for protection of cables including demolition and taking down of the old existing pipe including repair of the floor/wall and matching with the existing surface if required complete as directed by Engineer-in-Charge.
M & L for road cutting incl necessary excavation 45 cm wide and 90 cm in depth as in trenches in any type of soils/rock for laying HT/LT UG cable through pipe after laying /through the cable trenches will be filling top with M&L PCC 1:3:6 type C-1 using 20 mm grdaeds stone aggregates from top over 15 cm thick hard good of broken boulders , 63 mm gauge over 15 cm bolders 100 mm dia over filled and rammed earth to make good the disburbed surface etc complete all as specified and directed.
M&L for PCC 1:3:6 type C-2 (using 40mm graded stone aggregates) as in foundation filling and mass concrete including form work for poles all as specified and directed by Engr-in-Charge.
M&L for PCC 1:2:4 type B-1 (using 20mm graded stone aggregates) as in coping etc including form work for poles all as specified and directed by Engr-in-Charge.
S&F in replacement of new generation energy saving and environmental friendly long life LED flood light made up of innovative die cast aluminium housing high power LED as lighting source with IP - 65 power consumption 70/72 watt colour white complete input voltage of 150-240 Volt (nominal rated voltage 240 Volt) complete including replacement of twisted 3 core copper cable of size 1.5 Sqmm dia for connecting phase, neutral and earth from junction box to light through connectors complete as specified and as directed.
S&F in replacement of new generation energy saving and environmental friendly long life LED flood light made up of innovative die cast aluminium housing high power LED as lighting source with IP - 65 power consumption 90 watt colour white complete input voltage of 150-240 Volt (nominal rated voltage 240 Volt) complete including replacement of twisted 3 core copper cable of size 1.5 Sqmm dia for connecting phase, neutral and earth from junction box to light through connectors complete as specified and as directed.
S&F in replacement of new generation energy saving and environmental friendly long life LED flood light made up of innovative die cast aluminium housing high power LED as lighting source with IP - 65 power consumption 100 watt colour white complete input voltage of 150-240 Volt (nominal rated voltage 240 Volt) complete including replacement of twisted 3 core copper cable of size 1.5 Sqmm dia for connecting phase, neutral and earth from junction box to light through connectors complete as specified and as directed.
M & L for decorative LED post top gate light with IP 65 pretection resistant to impact and corrosion, glare free and better uniformity complete all as specified and as directed.Make:- Surya Cat Part No SLE PT 40W ETPP or equivalent make as mentioned in appendix B to PS
M & L for decorative LED bollard stainless steel 9 watt weather proof light(warm white) with acrylic diffuser complete with all accessaries complete all as specified and as directed.
S & F GI brackets for fixing LED street light fitting fabricated out of GI tubing 32 mm dia, medium grade, 1.2 mtr long , bend to 120 degree shape by cutting, welding and well finishing including MS clamp of flat iron of size 32 x 5 mm -02 Nos complete for steel poles / PCC pole as per site requirement with nut, bolt & washers for fixing of GI bracket complete all as specified and directed.
S&F in replacement kiosk box for luminaires ,weather proof made out of HDPE/FRP housing fire retardant, non fusing, shock & rust proof, single piece moulded and cover with hinged door, pole mounting type comprising of four pole copper connectors of 16 Amps capacity with 6 Amp MCB single pole , of minimum size 300x200x125mm, fixed on pole with MS, clamps 30 x 5mm with necessary nuts, washer and incl applying two coats of synthetic enamel paint over a red oxide primer on steel surface/clamps and embossing/painting of Danger sign of size not less than 10cms x 7.5cms with letter and conventional skull and bones in single red color on front face of kiosk box complete all as directed. The quoted rate also includes cost for material & repalcement of 4 sqmm multistranded twincore aluminium cable ISI marked from overhead conductor to junction box and replacement of 3 core copper cable of 1.5 Sqmm ISI marked from junction box to security light length as per required at site. Note:- The quoted rate includes cost of excavation of cable for removing cable from loop /demolition of coping of pole by taking out the cable for connection in new pole box through aluminium lugs, repair of coping of polles , returning and filling of the cable excavated.Make-Syntex/Supreme/Hensal
M & L for earthing in repairs complete with galvanized steel earth plate electrode 600 x 600 x 6 mm thick burried directly in ground (earth pit not less than 2.25m deep below normal ground level) with top edge of the plate not less than 1.5 mtr below normal GL and connected to earth plate . Earth plate surrounded by 15 cm thick packed layers of charcoal dust and common salt upto 1.5 meter depth all around the earth plate and connected to earth lead of GI strip 25x4 mm by means of bolts, nuts, check nuts and washers of galvd iron or steel surronded by charcoal of coke and salt and protected by galvanized iron or steel pipe light grade 40 mm bore and water pipe 20mm bore GI medium grade with funnel and wire mesh, including all necessary excavation and earth work PCC chamber in cement concrete 1:3:6 type C-2 and RCC cover and all as shown in electrical plate No 3 of MES schedule Pt I of 2009 and also including making test point for testing of earthing made out of gun metal or phosphorous bronge size 75x75x25 mm complete . Note : 1. RCC pit cover shall be pre-cast of RCC (1:2:4) type B-I , 80mm thick reinforced with XPM weighting not less than 4 KG/sqmm in lieu of CI cover. 2. Charcoal dust and common salt upto 1.5 meter depth shall be filled in layers of 15 centimeters all around the earth plate inside earth pit . On testing after completion of earthing if desired earth resistance is not achieved , the earthing will be redone at no extra cost to obtain the desired earth values less than 2 ohms.3. The cost of GI earth lead and GI pipe of 7.50m lenth for protection of GI wire and excavationwork fpr pit shall deemed to be included in this item.
S&F in replacement Factory made sheet metal enclosure of CRCA sheet 2 mm thickness suitable for fixing of MCCB 4 with fixing arrangement including provision of MCCB 100Amp, 25KA, 4Pole ( Ics=Icu=100%) with cable connection with copper glands etc complete all as specified and direcetd.
M/s Ravi Traders
m/s gupta trading
stage.html
html • 0.05 MB
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .