Tender ID
Tender Value
₹34.2 L
EMD Value
₹68,360
Closing Date
18 Mar 2026, 6:00 pmClosed
GE UTILITY PLANT AND MACHINERY DELHI CANTT-10
GE UTILITY PLANT AND MACHINERY KIRBY PLACE DELHI CANTT-10
PROVISION OF AIR CONDITIONING IN ANTE ROOM OF P3 BUILDING WITH ASSOCIATED INFRASTRUCTURE AT NOM VARUNA UNDER GE (U) PM DELHI CANTT10
2026_MES_753087_1
GE(U)/PM/D-63/2025-26
Open Tender
Miscellaneous Works
Item Rate
120 days
Delhi Cantt
Please refer tender documents
6 documents required · 6 mandatory
₹500
GE UTILITY PLANT AND MACHINERY DELHI CANTT-10
₹68,360
Yes
17 Feb 2026
17 Feb 2026
21 Mar 2026
17 Feb 2026
18 Mar 2026
4 Mar 2026
| Sl No | Description | Qty | Unit | Est. Rate | Est. Amount |
|---|---|---|---|---|---|
| 1 | Supply installation testing and commissioning of 100% Inverter VRF units of Cap 16 HP/12.8 TR (Note: 1 HP = 0.8 TR) complete with Inverter Scroll compressor fitted with Conentrated winding, air cooled condenser with low noise fan having interconnected control wiring and refrigerant piping housed in compact housing duly powder coated, Conformal Coating on PCB, Hydrophilic Blue Fins, Twin Accumulator & Two Compressors in each Outdoor Unit. All units are Cooling & Heating both with Eco Friendly Refrigerant (R-410a). Unit should deliver 100% capacity without deration upto 45°C Ambient Temperature. Operating Outdoor Ambient Temperature Range Cooling 10°C to 56°C & for Heating -10°C to 24°C. IPLV should be more than 6.7 complete all as specified and directed.
Note:
a) Heat load to be done by considering Outside Temperature 45°C & Inside Atrium 24°C.
b) Roof in not Insulated (Under deck Insulation)
c) Deration Chart to be submitted by OEM.
d) HVAC Layout to be submitted by Contractor with Sign & Stamp of OEM.
e) VRF Installation work to be execute by OEM or OEM Authorised Vendor.
f) Refnet to be added in Quoted Rates.
g) The installation of VRF under this contract shall be done through any OEM i.e.
Make:-Mitsubishi Electric, O-General, Bluestar or Toshiba, Daikin, Voltas, Carrier, LG, Samsung. | 4 | Each | - | - |
| 2 | Supply, Installation, testing and commissioning of TFA Type, Air Handling Unit capacity 25 TR-9000 CFM (25 mm Static Pressure) with AHU unit, Floor Mounted type, Double Skin Casing consist of Outer Skin of 0.6mm Pre Coated GI, Inner Skin of 0.6mm Plain SS-304, Frame work consist of Thermal Break Aluminium profile with thermal barrier, insulated panels of Thickness 45mm CFC Free PUF injected (Density: 40 kg / Cu. m.), Drain tray material consist of 20 G SS-304 Tray duly insulated with 13 mm closed cell Nitrile insulation, GSS Base Channel complete all as specified and directed with following specifications.
(i) Coil Casing / Blank offs SS-304,
(ii) Coil section with 8 row deep DX cooling coil with double distributors.
(iii) For Supply: Fan section with DIDW centrifugal backward curved fan,
(iv) With Copper tube(IGT):-
Tube Dia 9.52 mm / 3/8” O.D,
Thickness of Tube 0.5mm,
(v) Fins Thickness of 0.15mm of Plain Aluminium Fins,
Copper tube with hydrophilic coating 11 to 13 Nos. per Inch.
(vi) Filter : Media of Filters-Synthetic (non woven type) / Fiber Glass for (EU-13),
(vii) Efficiency of Pre-filters (EU-4)-90 % down to 10 micron,
(viii) Motor - Plug Fan motor.
(ix) ADP- 54°F
Total Refrigerant gas flow pressure drop including distributor : Max 4 Psig | 2 | Each | - | - |
| 2.01 | (Coil to be selected at below parameter:-
a. 7.2°C Evaporative Temp
b. 54°C Condensing Temp
c. 4° C Superheat
d. 5°C Subcooling
e. Fluid Pressure Drop not more than 35 Pascal)
Make: Zeco, Edgetech, Wave, Citizen and Balance Air, Ventilair, Carrier,Daikin
DISTRIBUTORS SHOULD BE IN VERTICAL POSITION | - | - | - | - |
| 3 | Supply only Corded Remote Control for VRF and AHU above complete all as specified and directed | 2 | Each | - | - |
| 4Supply and Installation of Refrigerant Copper piping insulated with Nitrile Rubber Tubular insulation and covered (with PVC pipe covering only for external copper piping ) for complete VRF System as per OEM Recommendation for the following pipes complete all as specified and directed. | |||||
| 4.01 | 12.7 mm with 13 mm thick insulation | 40 | RM | - | - |
| 4.02 | 19.1 mm with 13 mm thick insulation | 40 | RM | - | - |
| 4.03 | 28.6 mm with 19mm thick insulation | 40 | RM | - | - |
| 4.04 | 34.9 mm with 19 mm thick insulation | 40 | RM | - | - |
| 5 | Supply, fixing, testing and commissioning of the control wiring 2 Core x 0.75 Sqmm copper conductor cable ( Sheilded Wire) from outdoor to indoor units with all necessary accessories to make it functional as per OEM Recommendation complete all as specified and directed. | 100 | RM | - | - |
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Tendernotice_1.pdf
PDF • 0.41 MB
D63TENDER.pdf
Tender Documents • 1.00 MB
BOQ_843503.xls
BOQ • 0.26 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .