Loading…
Loading…
| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | L1₹32.4 LAccepted-AOC | L1 | Accepted-AOC Found lowest and reasonable | |
| 2 | L2₹36.8 L+₹3.3 L (9.92%)Rejected-Finance | L2 | Rejected-Finance In order but L2 | |
| 3 | L3₹37.9 L+₹4.4 L (13.1%)Rejected-Finance H NO 206 RAJAPUR DUJANIA MOHALLA DASNA DEHAT VILLAGE TOWN INDERGARHI CITY GHAZIABAD GHAZIABAD UTTAR PRADESH 201002 INDIA | GHAZIABAD | UTTAR PRADESH | 201002 | L3 | Rejected-Finance In order but L3 | |
| 4 | L4₹39.1 L+₹5.6 L (16.7%)Rejected-Finance | L4 | Rejected-Finance In order but L4 | |
| 5 | L5₹39.4 L+₹5.9 L (17.6%)Rejected-Finance 289 KASERU KHERA MAWANA ROAD MEERUT 250001 U P | MEERUT | UTTAR PRADESH | 250001 | L5 | Rejected-Finance In order but L5 |
Tender Value
₹45.2 L
EMD Value
₹90,440
Closing Date
15 Oct 2024, 6:00 pmClosed
GE (U) Meerut Cantt
Roorkee Road Meerut Cantt
PROVN OF 01X HIGH MAST LIGHT 20 MTR HEIGHT WITH 9 X LIGHT (200 W) AT GOLDEN FISH PARK AND SPL REPAIR / REPLACEMENT OF OH LINE, JBS, LT PANEL AND ALLIED WORKS AT PASHCHIM VIHAR, KVK RAO AND RACE ROAD OFFRS MD ACCN UNDER AGE E/M (ES) AT GE(U) MEERUT CA
2024_MES_657048_3
8606/E8
Open Tender
Electrical and Maintenance Works
Item Rate
180 days
Meerut
Please refer Tender documents.
11 documents required · 11 mandatory
₹500
GE (U) Meerut Cantt
₹90,440
Yes
20 Jan 2025
24 Sept 2024
22 Oct 2024
24 Sept 2024
15 Oct 2024
1 Oct 2024
Amount
Supply, installing, testing and commissioning, factory made and tested . LT feeder pillar box (KIOSK) , outdoor type, (Size900 x 800x 500mm) platform mounted, suitable for 415 volts 3 phase 4 wire, 50 Hz AC supply system, having bus bar chamber with insulated aluminum bus bars 250 Amps rating installed with colour code hydrographic insulation tape of capacity minimam 250 Amps on Smc / porcelain insulators. The panel shall be dust and vermin proof, IP 65 class protection and made of 3.15mm CRCA MS sheet and 40x40x4mm thick angle iron frame work, powder coated finish over one coat of red oxide primer outside and two coats of red oxide primer on inside, front opening type, with aprons for cable entry, with double door shutter and locking arrangement (including provn of 65mm Godrej (Freedom) stranded lock with 2 keys, internal wiring with PVC insulated, stranded copper conductor, FRLSH cables, IS-694 marked of adequate size but not less than 2.5 Sqmm. The following items accomadated this feeder piller incl 2 nos danger notice plate made of 1.6 mm thick mild steel sheet, vitreous enamelled white of size 25 x 20 cm with letter figures and conventional skull bones in signal red colour and fixed nuts, bolts and washers etc with voltage and danger indicated in Hindi and English complete all as specified and directed Engr in Charge.The scope of work includes the following items accomadate the same panel:-
Incoming :-
MCCB TPN 4 pole, 415 Volts 200 Amps rating 25 KA rupturing cap : 1 No
Indicator lamp LED type (R, Y, B) complete with fuse -01 Set
Outgoing :-
MCCB TPN 4 pole, 415 Volts 100 Amps rating 16 KA rupturing cap : 2 No
TPN MCB 63 Amps 'C' curve - 1
Platform for the panel with PCC 1:4:8 type D-2 with 40mm graded crushed stone , 15 cm thick in foundation, brick work in CM 1:6 with sub class `B’, old size bricks, rendering 15mm thick in CM 1:6 on exposed surfaces and 100mm thick PCC padding 1:3:6, type C-1 using 20 mm graded crushed stone aggregate on top and grouting bolts etc for panel. The platform shall be such that it is of a height 60cm above ground level and below ground level 40cm.
M&L for plate earthing for feeder pillar box complete with galvanised mild steel plate electrode 60 cm x 60 cm x 6.3 mm thick buried directly in ground vertically (in earth pit not less than 2.25 m below normal ground level) with the top edge of the earth plate at a depth not less than 1.5 m below normal ground level, the earth electrode surrounded by adequate quantity of charcoal dust and salt to a packed thickness of 15 cm on all sides and incl GI earth strip 32 x 6 mm bolted (with GI nuts, bolts & check nuts) and riveted to earth plate at one end and connected to metallic bodies of LT equipments etc at the other, earth strip encased in and including 50mm bore GI grade pipe with all fittings from top of electrode to body of equipment fixed with and including 25 x 4 mm flat iron clamps, bolts, nuts and washer and also including providing watering pipe 20mm bore GI pipe medium grade from bottom of earth pit to top of electrode complete with earth pit in PCC 1:2:4 type B-O using 12 mm graded crushed stone aggregate and RCC cover complete all specified and shown in electrical plate No 3 of SSR Pt-I.The scope of work also includes necessary excavation and earthwork
Supply, errection, Installation , Commissioning& testing of High Mast lights, and heigh mast lights detail under mentioned Technical data cart part Specification inclosed) comprising of the following-
Supply of galvanized Steel mast of 20 mrts height Mast lighting system technical data with the scope of work
Steel mast height 20 Mtr (galvanizing std IS 4759 )( Material construction of high mast sheet will be of BSEN 10025 / lS 5986 Gr Fe 510 or equivatent) cross section of mast 20 sided polygon ;No of parts along length 2 ( Top dia 150 mm (A/F) & bottom dia 460 mm (A/F)
Part 1: 8301 mm (Bottom) thickness 4mm ; Part 2: 8300 mm thickness 3 mm
Metal Protection - Hot dip galvaizing internally & externally
Tickness of galvanization - avarage coating 86 microns for > 5mm sheet thickness/65 microns for <5mm sheet thickness
Base plate details :- base plate dia : 670 mm, thickness : 25mm
Lightning protection finial - 1.2m Galvanized, single spike
HD bolts dia 24mm/ HD bolts Nos : 8 / HD bolts PCD 445 mm/ HD bolts embedded length as per manufacturer TDS
Material construction : 40 NB ERW class B Sq pipes or circulor pipe with 6 arms
Dia of lantern ring - asper head frame design in two halves
LED flood light 210 watt 230 V AC outdoor type with thermal management in multiple optics and equipped with IP66 protection, with impact and corrosion resistant complete with driver and lamp. -9 Nos ( Make : Philips/Surya/Bajaj/CG and Equivalent)
LED type twin Aviation obs light (cat no ; 108 DD LDR- SEN IP 66) - 01No
Wind 2 drum manual and power operated , Speed 50m/sec; terrain category- 2, Class-A, incl 3 phase 415 volts 1.5 HP power tool)
Stainless Steel wire Rope : grade AISI 316, 7/19 Con , dia 8 mm braking load minium -2500 Kg
Service Wiring feeder to flood light FRLSH , IS- 694 copper cable size 4 Sqmm (minuium) x 3 core
M&L plate earthing for feeder pillar box complete with galvanised mild steel plate electrode 60 cm x 60 cm x 6.3 mm thick buried directly in ground vertically (in earth pit not less than 2.25 m below normal ground level) with the top edge of the earth plate at a depth not less than 1.5 m below normal ground level, the earth electrode surrounded by adequate quantity of charcoal dust and salt to a packed thickness of 15 cm on all sides and incl GI earth strip 40 x 6 mm bolted (with GI nuts, bolts & check nuts) and riveted to earth plate at one end and connected to metallic bodies of LT equipments etc at the other, earth strip encased in and including 50mm bore GI grade pipe with all fittings from top of electrode to body of equipment fixed with and including 25 x 4 mm flat iron clamps, bolts, nuts and washer and also including providing watering pipe 20mm bore GI pipe medium grade from bottom of earth pit to top of electrode complete with earth pit in PCC 1:2:4 type B-O using 12 mm graded crushed stone aggregate and RCC cover complete all specified and shown in electrical plate No 3 of SSR Pt-I.The scope of work also includes necessary excavation and earthwork.- 3 Nos
Supply, installing, testing and commissioning, factory made and tested . LT feeder pillar box (KIOSK) , outdoor type, (600x500x450mm) platform mounted, The panel shall be dust and vermin proof, IP 65 class protection and made of 3.15mm CRCA MS sheet and 40x40x4mm thick angle iron frame work, powder coated finish over one coat of red oxide primer outside and two coats of red oxide primer on inside, front opening type, with aprons for cable entry, with double door shutter and locking arrangement (including provn of 65mm Godrej (Freedom) stranded lock with 2 keys, internal wiring with PVC insulated, stranded copper conductor, FRLSH cables, IS-694 marked of adequate size but not less than 2.5 Sqmm. The following items accomadated this feeder piller incl 2 nos danger notice plate made of 1.6 mm thick mild steel sheet, vitreous enamelled white of size 25 x 20 cm with letter figures and conventional skull bones in signal red colour and fixed nuts, bolts and washers etc with voltage and danger indicated in Hindi and English complete all as specified and directed The scope of work includes the following items accomadate the same panel:-
(i) Stag type,4 way terminal(I/P) 63 Amps - 1 No (PCB 150 ACBC)
(ii) MCCB 40Amps 4 pole - 1No
(iii) Contactor 3pole 32Amps -1 No
(iv) toggle Switch 6Amps - 1 No (unique)
(v) timer (analogue) with battery backup -1
(vi) Stage type, 4way terminal (O/P) 63A - 1 No (PCB 150 ACBC
(vii) Over load relay 2/3.5A - 1 No
(viii) F. contactor 9A - 1No
(ix) R. contactor 9A - 1No
(x) Motor terminal 32Amps -1 No
(xi) Push switch terminal(STD)-1No
(xii) Push switch (F/R) STD - 1 No
(i) Work to be executed as per standard engineering practices and as per manufacturers instruction
(ii) Before placing the order the design/ drawing of high mast of there manufacturer shall be got approved by GE
(iii) Work to be executed by the manufacturer or there authorized rep and and undertaking of the same from the manufacturer be submitted prior to excution / completion
(iv) Size of RCC foundation Shall be carried out as per manufacturers drawings
M&L including jointing testing and commissioning XLPE insulated heavy duty electric cable with aluminium conductor 1100 volts cross section area (ISI marked) laid in trenches, ducts, pipe or fixed on pole etc of size 50 Sqmm, 3.5 core cable complete all as specified and directed by Engr -in- Charge.
Excavation in trenches in soft/loose soil n. exc. 1.5 meter wide and n. exc. 1.5 mtr depth and getting out, including trimming the sides and forming bottom surface to required levels for laying cables, foundation of poles, stay etc complete all as specified.
Returning, filling trenches including spreading, levelling, watering and well ramming in layers n. exc. 25 cm thick complete all as specified and directed.
Removing of excavated material (soil) to a distance n. exc. 50 Mtr and dispositing where directed at a level n. exc. 1.50 Mtr above the starting point complete as directed.
M & L Sand cushioning to UG cables (8cm deep before laying of cable and 15 cm deep over the cable). Note :- Punned thickness18 cm only will be considered for payment.
M & L Bricks for protection cover to under ground cable (with standard size fly ash bricks) with width equal to length of brick laid dry and flat abutting each other with gaps between adjacent brick not exceeding 10mm as directed.
M & L for boring in any type of soil under road 1.5 Mtr below the top surface of road by convential method complete for passing through 80mm to 100mm dia GI pipe and filling earth after laying of pipe including disposal of surplus soil complete all as specified and directed. NOTE:- Pipe will be measured and paid for separately. Any damage to existing cables of any type and road will made good by the tenderer without any extra payment.
Supply & laying galvanised steel water tubing 50mm bore , light grade, IS-1239 marked with all fittings (IS marked) and laid in trenches / under roads / in drains / fixed to poles/walls ( with required size flat iron clamp bolts, nuts and washers )
Supply, installing, testing and commissioning of LT out door type factory made(CPRI Approved ), Junction box of size 750mmX600mmX500mm (over all dimension )with mild steel angle iron of size 50X50X6mm vertical frame and legs with mild steel Angel iron 50x50X6 mm in horizontal sides of the frame LT Junction box (KIOSK), outdoor type, platform mounted, suitable for 415 volts 3 phase 4 wire, 50 Hz AC supply system, The panel shall be dust and vermin proof, IP 65 class protection and made of 3.15mm CRCA MS sheet and 50x50x6 mm thick angle iron frame work, powder coated finish over one coat of red oxide primer outside and two coats of red oxide primer on inside, front & back opening type, with aprons for cable entry, and fixing danger notice plate made of 1.6mm thick mild steel sheet, vitreous enamelled white, of size 20 x 15cm with letter, figures and conventional skull bones in signal red colour and fixed front & back door pillar box etc with voltage and danger indicated in Hindi and English complete all as specified and directed. With double door shutter and locking arrangement . Aluminium bus bar (LxWxH) 400 x 10x50 mm with drilled holes for incoming /out going cable core connection including aluminium lugs ,GI bolts ,Nuts and washers of suitable size . Porcelain / synthetic bridge insulators, heavy duty with necessary steel / GI screws ,bolts, nuts and washers -08 Nos , complete all as specified and as directed. , The platform shall be such that it is of a height 45 cm above the nearest road level. complete all as specified and directed including connections of all out going/in coming existing cables of size 25 to 300 sqmm by drawing /digging out cable from loops in trenches out side the Bldg inclusive of necessary excavation and earth work as required and relaying the cables with retrieved bricks and providing new sand cushioning and crimping suitable size lugs for terminal connections of cables, necessary brick foundation with plastering to the Panel board complete all as specified and as directed by Engr-in-Charge (NOTE:-LT Panel board should be as per IS/ICE 61439-part I&II Type Test certificates and Panel Builder should submit all Certificates before executing the job.)
Supply, installing, testing and commissioning, factory made and tested , LT Panel (KIOSK), outdoor type, minimum size 900 x 800x 600mm and platform mounted, suitable for 415 volts 3 phase 4 wire, 50 Hz AC supply system, having bus bar chamber with insulated aluminium bus bars 400 Amps rating installed on porcelain insulators. The panel shall be dust and vermin proof, IP 65 class protection and SMC/made of 3.15mm CRCA MS sheet and 40x40x4mm thick angle iron frame work, powder coated finish over one coat of red oxide primer outside and two coats of red oxide primer on inside, front opening type, with aprons for cable entry, with double door shutter and locking arrangement , internal wiring with PVC insulated, stranded copper conductor, FRLS cables, IS-694 marked of adequate size but not less than 2.5 Sqmm. The platform shall be such that it is of a height 45 cm above the nearest road level. complete all as specified and directed including connections of all out going/in coming existing cables of size 25 to 240 sqmm by drawing /digging out cable from loops in trenches out side the Bldg including of necessary excavation and earth work as required and relaying the cables with retrieved bricks and providing new sand cushioning and crimping suitable size lugs for terminal connections of cables, necessary brick foundation with plastering to the Panel board, All out going feeders shall be connected and The various feeders shall be indicated by 50 mm size letters in synthetic enamel white paint and and fixing danger notice plate made of 1.6mm thick mild steel sheet, vitreous enamelled white, of size 20 x 15cm with letter, figures and conventional skull bones in signal red colour and fixed front & back door pillar box etc with voltage and danger indicated in Hindi and English complete all as specified and as directed by Engr-in-Charge , The scope of work includes the following: (NOTE:-LT Panel board should be as per IS/ICE 61439-part I&II Type Test certificates and Panel Builder should submit all Certificates before executing the job.)
Incoming :-
MCCB 4 Pole, Thermal Magnetic Based 250 A, Breaking capacity 36 KA, 415 V, 50 Hz with OL, SC, EF protection, -01 No along with Spreader terminals
Indicator lamp LED type (R, Y, B) complete with fuse -01 Set
Outgoing :-
MCCB 4 Pole, Thermal Magnetic Based 200 A, Breaking capacity 36 KA, 415 V, 50 Hz with OL, SC, EF protection, -01 No along with Spreader terminals
MCCB 4 Pole, Thermal Magnetic Based 160 A, Breaking capacity 16 KA, 415 V, 50 Hz with OL, SC, EF protection, -01No along with Spreader terminals
MCB TPN 63 Amp C-Curve - 2 No
Supply, installing, testing and commissioning, factory made and tested , LT Panel (KIOSK), outdoor type, minimum size 900 x 800x 600mm and platform mounted, suitable for 415 volts 3 phase 4 wire, 50 Hz AC supply system, having bus bar chamber with insulated aluminium bus bars 400 Amps rating installed on porcelain insulators. The panel shall be dust and vermin proof, IP 65 class protection and SMC/made of 3.15mm CRCA MS sheet and 40x40x4mm thick angle iron frame work, powder coated finish over one coat of red oxide primer outside and two coats of red oxide primer on inside, front opening type, with aprons for cable entry, with double door shutter and locking arrangement , internal wiring with PVC insulated, stranded copper conductor, FRLS cables, IS-694 marked of adequate size but not less than 2.5 Sqmm. The platform shall be such that it is of a height 45 cm above the nearest road level. complete all as specified and directed including connections of all out going/in coming existing cables of size 25 to 240 sqmm by drawing /digging out cable from loops in trenches out side the Bldg including of necessary excavation and earth work as required and relaying the cables with retrieved bricks and providing new sand cushioning and crimping suitable size lugs for terminal connections of cables, necessary brick foundation with plastering to the Panel board, All out going feeders shall be connected and The various feeders shall be indicated by 50 mm size letters in synthetic enamel white paint and and fixing danger notice plate made of 1.6mm thick mild steel sheet, vitreous enamelled white, of size 20 x 15cm with letter, figures and conventional skull bones in signal red colour and fixed front & back door pillar box etc with voltage and danger indicated in Hindi and English complete all as specified and as directed by Engr-in-Charge , The scope of work includes the following: (NOTE:-LT Panel board should be as per IS/ICE 61439-part I&II Type Test certificates and Panel Builder should submit all Certificates before executing the job.)
Incoming :-
MCCB 4 Pole, Thermal Magnetic Based 250 A, Breaking capacity 36 KA, 415 V, 50 Hz with OL, SC, EF protection, -01 No along with Spreader terminals (Make : Siemens: / L&T/ Legrand & Equivalent Schneider )
Indicator lamp LED type (R, Y, B) complete with fuse -01 Set (Make: Siemens/Schneider/Legrand /AE/SELEC)
Outgoing :-
MCCB 4 Pole, Thermal Magnetic Based 160 A, Breaking capacity 16 KA, 415 V, 50 Hz with OL, SC, EF protection, -02 No along with Spreader terminals (Make : Siemens: / L&T/ Legrand & Equivalent Schneider )
MCB TPN 63 Amp C-Curve - 2 No (Make-Schneider / Legrand L&T )
Supply, installing, testing and commissioning, factory made and tested , LT Panel (KIOSK) (FPB ), outdoor type, minimum size 900 x 800x 600mm and platform mounted, suitable for 415 volts 3 phase 4 wire, 50 Hz AC supply system, having bus bar chamber with insulated aluminium bus bars 350 Amps rating installed on porcelain insulators. The panel shall be dust and vermin proof, IP 65 class protection and SMC/made of 3.15mm CRCA MS sheet and 40x40x4mm thick angle iron frame work, powder coated finish over one coat of red oxide primer outside and two coats of red oxide primer on inside, front opening type, with aprons for cable entry, with double door shutter and locking arrangement , internal wiring with PVC insulated, stranded copper conductor, FRLS cables, IS-694 marked of adequate size but not less than 2.5 Sqmm. The platform shall be such that it is of a height 45 cm above the nearest road level. complete all as specified and directed including connections of all out going/in coming existing cables of size 25 to 240 sqmm by drawing /digging out cable from loops in trenches out side the Bldg including of necessary excavation and earth work as required and relaying the cables with retrieved bricks and providing new sand cushioning and crimping suitable size lugs for terminal connections of cables, necessary brick foundation with plastering to the Panel board, All out going feeders shall be connected and The various feeders shall be indicated by 50 mm size letters in synthetic enamel white paint and and fixing danger notice plate made of 1.6mm thick mild steel sheet, vitreous enamelled white, of size 20 x 15cm with letter, figures and conventional skull bones in signal red colour and fixed front & back door pillar box etc with voltage and danger indicated in Hindi and English complete all as specified and as directed by Engr-in-Charge , The scope of work includes the following: (NOTE:-LT Panel board should be as per IS/ICE 61439-part I&II Type Test certificates and Panel Builder should submit all Certificates before executing the job.)
Incoming :-
MCCB 4 Pole, Thermal Magnetic Based 250 A, Breaking capacity 36 KA, 415 V, 50 Hz with OL, SC, EF protection, -01 No along with Spreader terminals (Make : Siemens: / L&T/ Legrand & Equivalent Schneider )
Indicator lamp LED type (R, Y, B) complete with fuse -01 Set (Make: Siemens/Schneider/Legrand /AE/SELEC)
Supply, installing, testing and commissioning, factory made and tested , LT Panel (KIOSK), outdoor type, minimum size 1200 x 1000x 600mm and platform mounted, suitable for 415 volts 3 phase 4 wire, 50 Hz AC supply system, having bus bar chamber with insulated aluminium bus bars 800 Amps rating installed on porcelain insulators. The panel shall be dust and vermin proof, IP 65 class protection and SMC/made of 3.15mm CRCA MS sheet and 40x40x4mm thick angle iron frame work, powder coated finish over one coat of red oxide primer outside and two coats of red oxide primer on inside, front opening type, with aprons for cable entry, with double door shutter and locking arrangement , internal wiring with PVC insulated, stranded copper conductor, FRLS cables, IS-694 marked of adequate size but not less than 2.5 Sqmm. The platform shall be such that it is of a height 45 cm above the nearest road level. complete all as specified and directed including connections of all out going/in coming existing cables of size 25 to 240 sqmm by drawing /digging out cable from loops in trenches out side the Bldg including of necessary excavation and earth work as required and relaying the cables with retrieved bricks and providing new sand cushioning and crimping suitable size lugs for terminal connections of cables, necessary brick foundation with plastering to the Panel board, All out going feeders shall be connected and The various feeders shall be indicated by 50 mm size letters in synthetic enamel white paint and and fixing danger notice plate made of 1.6mm thick mild steel sheet, vitreous enamelled white, of size 20 x 15cm with letter, figures and conventional skull bones in signal red colour and fixed front & back door pillar box etc with voltage and danger indicated in Hindi and English complete all as specified including taking out of old Skelton type panel with control switches complete all as specified and as directed by Engr-in-Charge , The scope of work includes the following: (NOTE:-LT Panel board should be as per IS/ICE 61439-part I&II Type Test certificates and Panel Builder should submit all Certificates before executing the job.)
Incoming :-
MCCB 4 Pole, Thermal Magnetic Based 500 A, Breaking capacity 36 KA, 415 V, 50 Hz with OL, SC, EF protection, -01 No along with Spreader terminals (Make : Siemens: / L&T/ Legrand & Equivalent Schneider )
Indicator lamp LED type (R, Y, B) complete with fuse -01 Set (Make: Siemens/Schneider/Legrand /AE/SELEC)
Outgoing :-
MCCB 4 Pole, Thermal Magnetic Based 200 A, Breaking capacity 25 KA, 415 V, 50 Hz with OL, SC, EF protection, -02 No along with Spreader terminals (Make : Siemens: / L&T/ Legrand & Equivalent Schneider )
MCCB 4 Pole, Thermal Magnetic Based 250 A, Breaking capacity 36 KA, 415 V, 50 Hz with OL, SC, EF protection, -02 No along with Spreader terminals (Make : Siemens: / L&T/ Legrand & Equivalent Schneider )
MCB TPN 63 Amp C-Curve - 2 No (Make-Schneider / Legrand L&T )
Supply, installing, testing and commissioning, factory made and tested , LT Panel (KIOSK), outdoor type, minimum size 1200 x 1000x 600mm and platform mounted, suitable for 415 volts 3 phase 4 wire, 50 Hz AC supply system, having bus bar chamber with insulated aluminium bus bars 800 Amps rating installed on porcelain insulators. The panel shall be dust and vermin proof, IP 65 class protection and SMC/made of 3.15mm CRCA MS sheet and 40x40x4mm thick angle iron frame work, powder coated finish over one coat of red oxide primer outside and two coats of red oxide primer on inside, front opening type, with aprons for cable entry, with double door shutter and locking arrangement , internal wiring with PVC insulated, stranded copper conductor, FRLS cables, IS-694 marked of adequate size but not less than 2.5 Sqmm. The platform shall be such that it is of a height 45 cm above the nearest road level. complete all as specified and directed including connections of all out going/in coming existing cables of size 25 to 240 sqmm by drawing /digging out cable from loops in trenches out side the Bldg including of necessary excavation and earth work as required and relaying the cables with retrieved bricks and providing new sand cushioning and crimping suitable size lugs for terminal connections of cables, necessary brick foundation with plastering to the Panel board, All out going feeders shall be connected and The various feeders shall be indicated by 50 mm size letters in synthetic enamel white paint and and fixing danger notice plate made of 1.6mm thick mild steel sheet, vitreous enamelled white, of size 20 x 15cm with letter, figures and conventional skull bones in signal red colour and fixed front & back door pillar box etc with voltage and danger indicated in Hindi and English complete all as specified including taking out of old Skelton type panel with control switches complete all as specified and as directed by Engr-in-Charge , The scope of work includes the following: (NOTE:-LT Panel board should be as per IS/ICE 61439-part I&II Type Test certificates and Panel Builder should submit all Certificates before executing the job.)
Incoming :-
MCCB 4 Pole, Thermal Magnetic Based 500 A, Breaking capacity 36 KA, 415 V, 50 Hz with OL, SC, EF protection, -01 No along with Spreader terminals (Make : Siemens: / L&T/ Legrand & Equivalent Schneider )
Indicator lamp LED type (R, Y, B) complete with fuse -01 Set (Make: Siemens/Schneider/Legrand /AE/SELEC)
Outgoing :-
MCCB 4 Pole, Thermal Magnetic Based 200 A, Breaking capacity 25 KA, 415 V, 50 Hz with OL, SC, EF protection, -03 No along with Spreader terminals (Make : Siemens: / L&T/ Legrand & Equivalent Schneider )
MCCB 4 Pole, Thermal Magnetic Based 250 A, Breaking capacity 36 KA, 415 V, 50 Hz with OL, SC, EF protection, -03 No along with Spreader terminals (Make : Siemens: / L&T/ Legrand & Equivalent Schneider )
MCB TPN 63 Amp C-Curve - 2 No (Make-Schneider / Legrand L&T )
M&L for plate earthing for sub station equipments complete with galvanised mild steel plate electrode 60 cm x 60 cm x 6.3 mm thick buried directly in ground vertically (in earth pit not less than 3.5 m below normal ground level) with the top edge of the earth plate at a depth not less than 2.75 m below normal ground level, the earth electrode surrounded by adequate quantity of charcoal dust and salt to a packed thickness of 15 cm on all sides and incl GI earth strip 32 x 6 mm bolted (with GI nuts, bolts & check nuts) and riveted to earth plate at one end and connected to metallic bodies of HT/LT equipments etc at the other, earth strip encased in and including 40mm bore GI light grade pipe with all fittings from top of electrode to body of equipment fixed with and including 25 x 3mm flat iron clamps, bolts, nuts and washer and also including providing watering pipe 20mm bore GI pipe medium grade from bottom of earth pit to top of electrode complete with earth pit in PCC 1:2:4 type B-O using 12 mm graded crushed stone aggregate excavation & earth work and RCC cover complete all specified and shown in electrical plate No 5 of SSR Pt-I.
Supply, laying, jointing, testing and commissioning LT underground cables, 1100 volts grade, XLPE insulated and PVC sheathed, heavy duty armoured, with multistranded aluminium conductors, IS-7098 (marked, laid in trenches / ducts / fixed on poles / walls / laid under roads / paths / drain / culverts or encased in GI pipe and removing unsv any size cable complete all as specified and directed. Cables of the following sizes:-(Note;- Rate quoted includes terminal Lugs / road cutting/ wall cutting/ floor cutting and making good damaged portion matching with existing surface with all existing finishes.)
16 Sqmm 4core
50 Sqmm 4 core
95 Sqmm 3.5 core
120 Sqmm 3.5 core
150 Sqmm 3.5 core
185 Sqmm 3.5 core
300 Sqmm 3.5 core
Taking out relaying, laying, jointing, testing and commissioning LT underground cables, any type and type , laid in trenches / ducts / fixed on poles / walls / laid under roads / paths / drain / culverts or encased in GI pipe complete all as specified and directed. Cables of the following sizes:-(Note;- Rate quoted includes terminal Lugs / road cutting/ wall cutting/ floor cutting and making good damaged portion matching with existing surface with all existing finishes.)
Excavation in trenches not exceeding 1.5 m wide and not exceeding 1.5 m in depth and getting out in Soft/Loose soil including trimming sides and bottom of trenches complete all as specified in the following type of soils:
Returning, filling-in, including spreading, watering and well ramming in layers not exceeding 25 cm thick each, in soft /loose soil complete all as specified in the following type of soils
Removing excavated surplus soil to a distance not exceeding 50 m and depositing where directed at a level not exceeding 1.5 m above the starting point complete all as specified.
Material and labour for river washed and screened, dry sand for filling in trenches below and around underground cables for cushioning of cables complete all as specified.
M & L Bricks for protection cover to under ground cable (with standard size fly ash bricks) with width equal to length of brick laid dry and flat abutting each other with gaps between adjacent brick not exceeding 10mm as directed.
Supply and laying galvanised steel water tubing, light grade, IS-1239 marked with all fittings (IS marked) and laid in trenches / under roads / in drains / fixed to poles/walls ( with required size flat iron clamp bolts, nuts and washers ) pipes of the following sizes :-
50 mm bore
80 mm bore
100 mm bore
M&L for auguring of hole suitable for passing 40mm to 100mm bore pipe in true horizontal position under road, PCC paths etc., by means of mechanical ring/ auger after doing ultrasound to prevent any damage to existing cables pipe line specified and directed coming in the route not exceeding 1.5 m in depth below existing surface level of road and not excd 30M in length complete all as specified. Note: Pipe shall be measured and paid separately under appropriate items and any damage to existing cables of any type shall be made good by the Bidder without any extra cost to department.
Cutting of worn-out / burnt aluminium cable terminal lugs from the HT/LT cable , crimping of new aluminium cable core and fixing with transformer/ Panel MCCB terminal/ FPB/ JB/ pole/DBs/ stud including cutting/ dressing of cable, disconnecting under ground / OH line cable conductor , cutting down worn-out portion and refixing with suitable lugs complete , including under ground cables of any type and size for repairs including taking out underground cable loop from ground and making connections of restoration of electric supply complete all as specified and directed Engr-in-Charge .Note:- (Excavation, earth work , taking out cable protection covers, and sand cushion and relaying the same shall be deemed included in the unit rate quoted by Contractor)
S&F service main distribution (SMC JUNCTION BOX ) box minimum inside size 395 x 235 x 150 mm with Bus bar 200 amps 4 pole for distribution of multiple no's of service connection, (ISI marked )weather and moisture-proof, nuts and bolted bus bar system, 200 Amps capacity and fixing on pole/wall with suitable FI clamp nuts and bolt complete all as specified and directed. (Make : Mahendra/ Sintex /Shalabh (I) ltd and equivalent )
S&F pole mounting type junction box factory made of size 350x250x150mm of FRP sheet duly powder coated with front openable hinged door , locking arrangements, with 4 Nos aluminium bus bars 40 Amps rating mounted on porcelain insulator, cable glands and lugs consisting DIN type rails for fixing MCB DP 6/10 Amps, 10 kA suitable for domestic loading , -01 no. including mild steel flat iron clamp made out of 40x4mm FI, nuts, bolts and washers duly painted with two coats of synthetic enamel paint over a coat of red oxide primer complete all as specified and directed Engr in Charge. (Make : Mahendra/ Sintex /Shalabh (I) ltd and equivalent )
Supply and fixing three core 1.5 Sqmm x3 core (nominal area) Confirming to FRLS cables, IS-694 ,PVC insulated and PVC sheathed multi stranded unarmed conductor cable LT 1100 volt grade including removed unsv any type cable complete all as specified and as directed by Engr in charge
Supplying and fixing street light timing switch having lighting control (ON-OFF) through Astronomical Calculation of Sun rise/ sun set by setting date, time and degree of longitude and latitude without separate light sensors and prewired with suitable size of copper conductor single core PVC insulated and sheathed cable and all mechanism fitted into panel, outdoor type , pole mounted with FI 25x4mm clamps , nuts, bolts and washers dully painted, connecting and testing factory made , epoxy powder coated, Single Phase street light panel, digital 24 hrs, suitable for 6KW (max) complete with 63 Amps TP Contactor, and 63 Amps TPN MCBs and fixed on pole/ wall/ feeder pillar complete all as specified and directed by Engr in Charge
Dismantling old existing ACSR conductor of any type/size.
Dismantling old existing MS cross arms of any type/shape.
Dismantling old existing Insulators of any type/shape.
Dismantling old existing LT stay complete
Microsys Automation India (BID ID -3129421)
PARADISE INFRA POWER COMPANY (BID ID -3128558)
D S Enterprises (BID ID -3132828)
Shikha Enterprises (BID ID -3132985)
Jain Traders (BID ID -3127591)
stage.html
html • 0.06 MB
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.04 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .