Loading…
Loading…
| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | L1₹17.4 LAccepted-AOC HOUSE NO 251 E BLOCK ADARSH NAGAR BALLABHGARH FARIDABAD PIN 121004 HARYANA | FARIDABAD | FARIDABAD | HARYANA | 121004 | L1 | Accepted-AOC BEING LOWEST BIDDER | |
| 2 | L2₹26.0 L+₹7.8 L (42.9%)Rejected-Finance AIRPORT ROAD SKALZANGLING LEH LADAKH 194101 | LEH LADAKH | LADAKH | 194101 | L2 | Rejected-Finance OTHER THAN LOWEST | |
| 3 | L3₹26.3 L+₹8.1 L (44.3%)Rejected-Finance H NO 1346 SECTOR 13 P HISAR 125005 HARYANA | HISAR | HISAR | HARYANA | 125005 | L3 | Rejected-Finance OTHER THAN LOWEST | |
| 4 | L4₹26.9 L+₹8.7 L (47.8%)Rejected-Finance | L4 | Rejected-Finance OTHER THAN LOWEST |
Tender Value
₹40 L
EMD Value
₹80,000
Closing Date
4 Jul 2023, 6:00 pmClosed
GE 865 EWS
GE 865 EWS, PIN-913 865 C/o 56 APO
REPAIR PERIODICAL MAINT OF DG SETS AND CONNECTED WORKS AT SECTOR B AND ADJACENT AREA UNDER AOR OF AGE EM II OF GE 865 EWS
2023_MES_601622_1
865/EWS(NIT-65)/2023-24
Open Tender
Civil Works
Item Rate
270 days
GE 865 EWS
As per tender documents and as per policy in vogue
9 documents required · 9 mandatory
₹500
GE 865 EWS
₹80,000
Yes
14 Sept 2023
7 Jun 2023
11 Jul 2023
7 Jun 2023
4 Jul 2023
21 Jun 2023
Amount
M&L for PCB card controller of type ausiliary 105 suitable for PCC 3300 of digital controller panel of following capacities of DG Sets Make Kirlosker/Cummins/Greaves complete all as specified and directed by Engr-in-Charge Make :- Kirloskar/Mico/TVS
400 KVA DG Set
380 KVA DG Set
320 KVA DG Set
200 KVA DG Set
M&L for repair of broken door hinges, handles of acoustic enclosure of following capacities of DG Sets Make Kirlosker/Cummins/Greaves complete all as specified and directed by Engr-in-Charge
400 KVA DG Set
380 KVA DG Set
320 KVA DG Set
200 KVA DG Set
160 KVA DG Set
125 KVA DG Set
100 KVA DG Set
63 KVA DG set
S&F in replacement of Fuel filter Element (Primary & Secondary) for following capacity of DG Sets Make Kirlosker/Cummins/Greaves complete all as specified and directed by Engr-in-Charge
400 KVA DG Set
380 KVA DG Set
320 KVA DG Set
200 KVA DG Set
160 KVA DG Set
125 KVA DG Set
100 KVA DG Set
63 KVA DG set
25 KVA DG set
Repair and replacement of Dynamo for following capacity DG Sets Make Kirlosker/Cummins/Greaves complete all as specified and directed by Engr-in-Charge
400 KVA DG Set
380 KVA DG Set
320 KVA DG Set
200 KVA DG Set
160 KVA DG Set
125 KVA DG Set
100 KVA DG Set
63 KVA DG set
M & L for Calibration of FIP including supply & fixing in replacement plunger, DV, governor wet O-Ring, Pin roll, barrel, Pin ball bearing spring, washer and testing for following capacity of DG Set complete all as specified and directed by Engr in Charge.
400 KVA DG Set
380 KVA DG Set
320 KVA DG Set
160 KVA DG Set
125 KVA DG Set
100 KVA DG Set
63 KVA DG set
25 KVA DG set
M&L for Checking, Inspection, maintanance and servicing complete including replacement of unserviceable spare parts of the DG set (comprising of Engine/ Alternator/ Control panel) of the following capacity for smooth functioning complete all as per manufacturers instructions and all as directed by Eng in Charge including the following works also: - A:(a) Checking of lubricating oil condition, (b) Checking engine for oil, water leakage and correcting the same (c) Checking of all the nut bolts of engine and alternator, (d) Checking of all belts and adjust the tension properly, (e) Cleaning of air filters, (f) Checking and readjusting the valve clearance, (g) Change of Oil/Fuel filters and engine oil if necessary, (h) Checking of starter motor battery and charger, (i) Checking of cooling system and fuel system, (j) checking of all power cables and AVR connections and mounting bolt tightnees of alternator, (k) checking the function of AVR genaral checks, (l) Checking of control panel meters and gadgets functioning, (m) Checking of all control and safety wirings. B. (a) Checking of flexible coupling of engine and alternator, (b) Cleaning of crank case ventilation pipe, (c) Checking of injectors and fuel pump, (d) Checking of alternator and carbon brushes of following capacity DG sets: - NOTE (1) Cost of Spare parts required will be measured and paid separately, (2) Servicing/routine check up carried out through authorised service centre of manufacturer, (3) Make of spare recommendation by auth service centre of manufacturer.
400 KVA DG Set
380 KVA DG Set
320 KVA DG Set
200 KVA DG Set
160 KVA DG Set
125 KVA DG Set
100 KVA DG Set
63 KVA DG set
25 KVA DG set
Replacement of 'V' belt for radiator/water pump suitable for following capacity DG Sets Make Kirlosker/Cummins/Greaves complete all as specified and directed by Engr-in-Charge
400 KVA DG Set
380 KVA DG Set
320 KVA DG Set
200 KVA DG Set
160 KVA DG Set
125 KVA DG Set
100 KVA DG Set
63 KVA DG set
25 KVA DG set
S&F in replacement of Air Cleaner Assembly (inner & outer) suitable for following capacity of DG Set Make Kirlosker/Cummins/Greaves complete all as specified and directed by Engr-in-Charge
400 KVA DG Set
380 KVA DG Set
320 KVA DG Set
200 KVA DG Set
160 KVA DG Set
125 KVA DG Set
100 KVA DG Set
63 KVA DG set
25 KVA DG set
S&F in replacement of Oil Filter Element with 'O' ring washer for DG Sets of following capacity Make Kirlosker/Cummins/Greaves complete all as specified and directed by Engr-in-Charge Make :- Kirloskar/Mico/TVS
400 KVA DG Set
380 KVA DG Set
320 KVA DG Set
200 KVA DG Set
160 KVA DG Set
125 KVA DG Set
100 KVA DG Set
63 KVA DG set
25 KVA DG set
Replacement of fuel pipe with banjo bolt at both side suitable for following capacity DG sets Make Kirlosker/Cummins/Greaves complete all as specified and directed by Engr-in-Charge
400 KVA DG Set
380 KVA DG Set
320 KVA DG Set
200 KVA DG Set
160 KVA DG Set
125 KVA DG Set
100 KVA DG Set
63 KVA DG set
25 KVA DG set
M & L for changing /toping up of best quality of engine oil 20W40 type for various type/capacity DG sets including removing of old burnt engine oil from DG Sets complete all as specified and directed
Supply only cotton waste for daily use for cleaning the DG sets complete all as specified and directed.
S&F replacement of auotmatic voltage regulator (AVR) 24 volt suitable for following capacity of DG Sets Make Kirlosker/Cummins/Greaves complete all as specified and directed by Engr-in-Charge
400 KVA DG Set
380 KVA DG Set
320 KVA DG Set
160 KVA DG Set
125 KVA DG Set
100 KVA DG Set
63 KVA DG set
25 KVA DG set
M& L for Replacement of water pump assembly for following capacity DG sets Make Kirlosker/Cummins/Greaves complete all as specified and directed by Engr-in-Charge
400 KVA DG Set
380 KVA DG Set
320 KVA DG Set
160 KVA DG Set
125 KVA DG Set
100 KVA DG Set
63 KVA DG set
25 KVA DG set
M&L for Replacement of Fan Hub assembely for following capacity of DG Set Make Kirlosker/Cummins/Greaves complete all as specified and directed by Engr-in-Charge
400 KVA DG Set
380 KVA DG Set
320 KVA DG Set
M & L Cleaning of radiator for following capacity DG sets by using Kerosene oil and radiator cleaning solution (Ready to Wash) by pressure of pump and brush and removing radiator from the Gen Set including taking to work shop, making necessary welding/brazing to the leakage and Re-assembling after painting of the same complete all as directed by Engr-in-Charge.
400 KVA DG Set
380 KVA DG Set
320 KVA DG Set
200 KVA DG Set
160 KVA DG Set
125 KVA DG Set
100 KVA DG Set
63 KVA DG set
25 KVA DG set
S&F in Replacement of self starter for following capacity DG Set Make Kirlosker/Cummins/Greaves complete all as specified and directed by Engr-in-Charge
400 KVA DG Set
380 KVA DG Set
320 KVA DG Set
160 KVA DG Set
125 KVA DG Set
100 KVA DG Set
63 KVA DG set
25 KVA DG set
Replacement of Turbo charger assy for following capacity DG sets Make Kirlosker/Cummins/Greaves complete all as specified and directed by Engr-in-Charge
400 KVA DG Set
380 KVA DG Set
320 KVA DG Set
160 KVA DG Set
100 KVA DG Set
63 KVA DG set
25 KVA DG set
Supply & fixing in replacement of Hose Pipe of following capacity of DG Sets Make Kirlosker/Cummins/Greaves complete all as specified and directed by Engr-in-Charge
400 KVA DG Set
380 KVA DG Set
320 KVA DG Set
200 KVA DG Set
160 KVA DG Set
125 KVA DG Set
100 KVA DG Set
63 KVA DG set
25 KVA DG set
M & L for taking out burnt winding of exciter of following capacity of DG Sets including re-winding copper wire of super quality, of existing size, No of turns, varnishing, heating complete including testing on full load to entire satisfaction of Engr in Charge.
400 KVA DG Set
380 KVA DG Set
320 KVA DG Set
160 KVA DG Set
125 KVA DG Set
100 KVA DG Set
63 KVA DG set
25 KVA DG set
Supply & fixing in replacement of DC wiring of digital control panel of following capacity of DG Sets Make Kirlosker/Cummins/Greaves complete all as specified and directed by Engr-in-Charge
400 KVA DG Set
380 KVA DG Set
320 KVA DG Set
M&L for disconnecting the U/S DC alternator of following capacity DG Set, 3 Phase any make & type form engine, transporting to workshop dismantling it for repairing and rewinding by taking out burnt armature winding aleading the alternator coil with existing gauge/size of super enamelled copper wire, providing new insulation, sleeves, varnishing cotton taping etc reassembling the alternator complete including aligning with engine and testing in all aspects for smooth functioning all as specified and directed by Engr-in-Charge
400 KVA DG Set
380 KVA DG Set
320 KVA DG Set
160 KVA DG Set
125 KVA DG Set
100 KVA DG Set
63 KVA DG set
25 KVA DG set
Note: Re-assembling all the component of the alternator and mounting the same on the existing foundation including welding of alternator foundation plate by electric arc welding, aligning the alternator with engine and testing on full load as specified in particular specification and as directed by Engr-in-Charge.
S&F in Replacement of lub oil pump suitable for following Capacity DG Sets Make Kirlosker/Cummins/Greaves complete all as specified and directed by Engr-in-Charge
400 KVA DG Set
380 KVA DG Set
320 KVA DG Set
160 KVA DG Set
S&F in replacement of Synthetic Insulating mat of Size 2Mx1Mx10MM complete all as specified and as directed.
S&F in Replacement of Oil seal front and rear suitable side for following Capacity DG Sets Make Kirlosker/Cummins/Greaves complete all as specified and directed by Engr-in-Charge
400 KVA DG Set
380 KVA DG Set
320 KVA DG Set
200 KVA DG Set
160 KVA DG Set
125 KVA DG Set
100 KVA DG Set
63 KVA DG set
25 KVA DG set
S&F in Replacement of Thermostate valve suitable for following Capacity DG Sets Make Kirlosker/Cummins/Greaves complete all as specified and directed by Engr-in-Charge
400 KVA DG Set
380 KVA DG Set
320 KVA DG Set
200 KVA DG Set
Supply and laying in replacement of LT underground cable ISI marked XLPE insulated heavy duty electric cable armoured and PVC sheathed heavy duty 1100 volts grade with aluminium conductor multistranded including cable connecting lugs, glands, jointing materials etc., laid in trenches, floors, ducts and fixing with fixing material on pole, wall complete of 50 SQMM 3.5 core complete all as specified and directed.
Supply and laying in replacement of LT underground cable ISI marked XLPE insulated heavy duty electric cable armoured and PVC sheathed heavy duty 1100 volts grade with aluminium conductor multistranded including cable connecting lugs, glands, jointing materials etc., laid in trenches, floors, ducts and fixing with fixing material on pole, wall complete of 150 SQMM 3.5 core complete all as specified and directed.
Supply and lay in replacement of LT underground cable ISI marked XLPE insulated heavy duty electric cable armoured and PVC sheathed heavy duty 1100 volts grade with aluminium conductor multistranded including cable connecting lugs, glands, jointing materials etc., laid in trenches, floors, ducts and fixing with fixing material on pole, wall complete of 185 SQMM 3.5 core complete all as specified and directed.
S&F in Replacement of battery terminal for DG Sets complete all as specified and directed by Engr-in-Charge.
S&F in replacement battery cable assy. with copper conductor multistranded RED and BLACK colour 2mtr long 21 Sqmm for connection to self starter unit to Battery unit complete.
Supply and topping up of best quality antifreezing, inhabitor (Coolant) liquid for DG Set of various capacity and locations complete all as specified and directed.
Supply and topping up of best quality distilled water for batteries of DG Set of various capacity and locations complete all as specified and directed.
Supply and topping up of best quality electrolite for batteries of DG Set of various capacity and locations complete all as specified and directed.
S&F in replacement Oil pressure gauge upto 1010 KVA capacity DG sets complete all as specified and directed by Engr -in-Charge
M/S NANCY ENTERPRISES
Horizon Construction Company
M/S NISSAR ALI
stage.html
html • 0.05 MB
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .