SE ETC MUZAFFARNAGAR
NEAR 132 KV SUB STATION BHOPA ROAD MUZAFFARNAGAR
WORK TENDER
2023_UPTCL_770089_1
ETC MU T 113 2022 23
Open Tender
Electrical Works
Item Rate
60 days
SHAMLI SHYAMLA
Please refer Tender documents.
2 documents required · 2 mandatory
₹590
EE ETD MUZAFFARNAGAR
₹4,000
25 Feb 2023
28 Jan 2023
9 Feb 2023
28 Jan 2023
8 Feb 2023
28 Jan 2023
Amount
Dismantling of 20 MVA 132/33 KV TAL makeT/F-II with shifting and carrying out the work of erection and making ready for commissioning of New 40 MVA 132/33 KV Technical Associate make transformer at 132 KV S/S Shamli Shyamla.
Drain out of T/F oil of conservator in empty oil drums and then dismantling of 20MVA T/F-II. Works includes Opening of jumpers of HV/LV side, removal of earthing strip from neutral bushings and transformer body, dismantling of 20 MVA T/F-II & its accessories including radiator HV/LV, turret HV/LV, neutral bushing, buchholz relay, oil pipe lines to conservator tank to main tank, oil pipe line to OLTC and surge relay, conservator tank.
Packing of HV bushing of dismantled 20 MVA 132/33 KV T/F-II in empty carets of new 40 MVA T/F.
Packing of LV/NUETRAL bushing of dismantled 20 MVA 132/33 KV T/F-II in empty carets of new 40 MVA T/F.
Shifting/Dragging of TAL make 20 MVA T/F-II from its plinth to near open space (Distance about 20 Mtr.) including turning of main tank up to required angle.
(a) additional shifting 01 job for every 5 Mtr.
Shifting/Dragging of oil filled TAL make New 40 MVA 132/33 KV transformer from unloading place to T/F plinth (Distance up to 20 Mtr.)
(a) additional shifting 01 job for every 5 Mtr
Complete erection of TAL make New 40 MVA 132/33 KV transformer by erection of radiator conservator tank bushing with its turrets connecting of all oil pipe line erection of cooling fans making control cable connections buchholz relay etc. for completing conservator tank and all other associated work for completion of job.
Centrifusing of Complete T/F oil (approx., 20 KL) in T/F tank by connecting centrifusing pipes circulating the T/F oil through private centrifusing machine and taking the BDV & ppm value of the oil periodically till the required value is achieved.
Earthing of Main Tank at two designated points & neutral bushing of HV & LV side of 40 MVA T/F by using MS Flat 50x6/75x10 mm size its jointing with already laid earth mat/Deltas neutral bushing support for its earthing work.
Opening of cable connection of RTCC Panel & MB of 20MVA T/F-II , including its termination and dismantling of RTCC Panel & Marshalling Box.
Cabling and interconnection of RTCC Panel of New 40MVA T/F in the control room with Marshalling Box in the switchyard.
Electrical Connection of 40MVA T/F with laying of cable and termination in between WTI,OTI Buchholtz relay, cooling fans with marshalling box etc. with proper ferruling as per cable schedule.
Jumpering of T/F from HV side with single moose/zebra/panther.
Jumpering of T/F from LV side with double zebra/moose/panther complete up to 33 KV main bus.
Replacement of all three phase 33KV CT of 20MVA T/F-II as per instruction manual of various equipments and technical specifications including shifting of material/equipment from store to site including all other associated work to complete the job satisfactorily including cabling work.
Replacement of 36KV Bus Isolator of 20MVA T/F-II and erection of new 36KV 2000A Bus Isolator including shifting of material/equipment from store to site including all other associated work to complete the job satisfactorily.
Opening of jumper , cutting of earthing strip and dismantling of 132KV LA complete with structure after shifting of 20MVA T/F-II and then re-erection of 132KV LA after the erection of New 40MVA T/F.
Technocrat Electrical
M/s S.S. Refregeration
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .