| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | L1₹97.0 LAdmitted-Finance 1 39A KATTUR POOLAMPATTI PO EDAPPADI TK SALEM DISTRICT 637107 | SALEM | TAMIL NADU | 637107 | ₹97.0 L | L1 | Admitted-Finance |
| 2 | L2₹99.3 L+₹2.3 L (2.40%)Admitted-Finance | ₹99.3 L+₹2.3 L (2.40%) | L2 | Admitted-Finance |
| 3 | L3₹1.0 Cr+₹4.9 L (5.03%)Admitted-Finance NO 60 CHITTOOR MAIN ROAD SENGUTTAI KATPADI TALUK VELLORE DISTRICT 632 007 | VELLORE | TAMIL NADU | 632007 | ₹1.0 Cr+₹4.9 L (5.03%) | L3 | Admitted-Finance |
| 4 | Not Admitted-Fee/PreQual/Technical | - | - | Not Admitted-Fee/PreQual/Technical Not Complied with technical specification |
| 5 | Not Admitted-Fee/PreQual/Technical | - | - | Not Admitted-Fee/PreQual/Technical Not Complied with technical specification |
| Sl No | Description | Qty | Unit | P SHANMUGAM CONTRACTORS L2 | Balu & Co L1 | K KUTTI L3 |
|---|---|---|---|---|---|---|
| 1.00Supply and delivery of Vertical type water/Oil lubricated statically, dynamically, hydraulically balanced turbine pump capable of discharging the following duty condition as given below due to all causes with surface discharge head confirming to IS 1710 and as amended as on date with accessories as per IS 5120/1977 (Reaffirmed 2011) and as amended thereafter to suit the site condition. The speed, No. of stages, sizes of column pipes and line shaft indicated is based on site condition prevailing during investigation. The pump should be supplied with non reversible ratchet pin housing safety clutch, suction strainer etc. The Pump Bowl assembly shall be with bronze impeller running at 1450 rpm. The pump includes suitable head shaft, suitable 1.5 metre long SS line shaft required Nos. to suit the well depth, Rubber line shaft bearing of required Nos., C.I Bearing retainer of required Nos., 100 litre HDPE Pre- lubricating tank with 20mm PVC Rigid pipe connection along with GM gate valves, Suitable ERW column pipe of each 1.5m long of required Nos. to suit the well depth, Suction bell mouth of suitable size, M.S. clamps suitable for column pipe/line shaft -2 set and Spanner - 1 set etc complete | ||||||
| 2.00 | 5000 lpm x 60 m Turbine pump M-1874 | 2 | Nos | 17,72,000 ₹35,44,000 | 14,00,000 ₹28,00,000 Lowest | 15,94,800 ₹31,89,600 |
| 3.00 | Supply and delivery of vertical Hollow/Solid shaft Squirrel cage induction motor (IS 325) suitable for the above pump continuous rated TEFC/SPDP type with Class ‘F’ insulation for operation in AC, three Phase/50 HZ (±5%), 415V (±10%) running with a speed of pump noted above and with inbuilt thrust bearing assembly capable of taking up the entire load and non - reverse ratchet assembly etc., complete. The motor rating noted above is the minimum and shall be such that it should never be over loaded when the pump works at MWL condition and shall be 10% over and above the maximum HP absorbed by the pump. The motor offered should be energy efficient to have maximum efficiency at high power factor. Separate thrust bearing assembly could also be supplied to take up the down load. -110 HP 2025-2026 | 2 | Nos | 7,40,154 ₹14,80,308 | 6,50,000 ₹13,00,000 | 4,95,655.2 ₹9,91,310.4 Lowest |
| 4.00Electromagnetic Flow Meter shall be a velocity sensing Electromagnetic type, microprocessor based signal converter, sealed housing, flanged tube meter for 1.0 Mpa working pressure, manufactured to highest standard available for mag-meters, equipped with minimum six digit digital totalizers, reading in units of (kilolitres/ cubicmeter) and shall be accurate within 0.5% of Measured value, shall operate within a range of 0.3m/sec to 4 m/sec and be constructed as follows:Meter tube (Sensor) shall be fabricated from stainless steel tube and use class PN10 flat face carbon steel flanges in accordance with IS 1538. These flanges shall be welded to the flow tube. The internal and external of the meter tube shall be blasted to near white and lined with hard rubber/ Polyurethrene/ PTFE preferably by SBR or EPDM. Meter tube shall have a constant nominal inside diameter offering no obstruction to the flow. The accuracy should be inclusive of linearity, hysteresis, repeatability, temperature and pressure effects Coil Housing shall be fabricated from stainless steel (SS 304) with Anticorrosive paint for corrosion resistance and welded to the tube providing a completely sealed environment for all coils, electrode connections and wiring harness capable of submerged or buried operation with IP 68 protection. | ||||||
| 5.00Signal Converter shall be pulsed DC coil excitation type with auto zeroing. The signal converter shall be remotely mounted away from the meter. The converter shall indicate direction of flow and provide a flow rate indication and a total of flow volume for both forward and reverse directions. The converter shall provide an isolated 4-20 mA output into minimum 500-ohm load and a frequency output of a maximum of 0-10 KHZ and a scaled pulse output, Communication interface is RS485, HART output, . The microprocessor based signal converter shall have a selfdiagnostic test mode and a backlit display that continuously displays “Rate of Flow” and “Total Volume”. Converter shall be supplied with a programmable low flow drop out Higher flow and empty pipe zero return. The signal converter housing should be die-cast aluminium with glass window. The converter cum transmitter should be fully programmable form the front facia. The programming should be user friendly, self-prompting menu driven. Flowmeter test calibration certificate from FCRI, flow test lab/ NABL accridiated lab to be furnished. | ||||||
| 6.00 | 600mm WD- M1401 TWAD 2025-26 | 1 | No | 3,89,990 ₹3,89,990 Lowest | 4,50,000 ₹4,50,000 | 4,38,739.7 ₹4,38,739.7 |
| 7.00 | 500mm WD- M1400 TWAD 2025-26 | 1 | No | 3,39,934 ₹3,39,934 Lowest | 4,00,000 ₹4,00,000 | 3,82,426.7 ₹3,82,426.7 |
| 8.00 | 350mm WD- M1397 TWAD 2025-26 | 1 | No | 2,12,524 ₹2,12,524 Lowest | 2,50,000 ₹2,50,000 | 2,39,089.97 ₹2,39,089.97 |
| 9.00 | FLEX COMPENSATED MAGNETIC AMPLIFIER SOFT STARTER SUITABLE FOR L.T. SQUIRREL CAGE MOTOR
Supply and delivery of floor mounted type FCMA Air/ Oil Cooled soft starter suitable for the LT motor offered for operation in AC three Phase 50Hz (+/- 5%), 415V (+/-10%) including line contactors suitable for next standard higher KW rating, Over load relay, instrument panel with frequency meter, Ammeter, Voltmeter, indicating lamp 6Nos, LED ON/OFF type and Start /Stop push button. - 75 KW WD- M1923 TWAD 2025-26 | 2 | Sets | 3,16,950 ₹6,33,900 Lowest | 4,50,000 ₹9,00,000 | 3,56,558.4 ₹7,13,116.8 |
| 10.00MIXED DI ELECTRIC CAPACITOR WITH TNEB TEST CERTIFICATE WITH ACCESSORIES INCLUDING BANKING CONFIRMING TO IS 2834. Supply and delivery of KVAR in single bank automatic power factor control unit to maintain 0.95 leading power factor by automatic control of capacitor banks to maintain system power factor under varying load conditions with duly banked with copper busbars of ample capacity cable gland unit etc.., completed and as directed by the Officers | ||||||
Tender Value
₹1.2 Cr
EMD Value
₹1.2 L
Closing Date
13 Aug 2026, 3:00 pmClosed
Commissioner
Infantry Road, Vellore Corporation, Vellore-632001
Supply, Delivery and Erection of Turbine Pumpsets at Ponnai Head Works in Vellore Corporation.
2026_MAWS_691044_1
5013/2026/E3/SDRF-2026-27/P3
Open Tender
Civil Works
Works
120 days
Vellore
Please refer Tender documents.
3 documents required · 3 mandatory
₹10,000
₹1.2 L
Vellore Corporation
15 Sept 2026
5 Aug 2026
13 Aug 2026
5 Aug 2026
13 Aug 2026
5 Aug 2026
10 Aug 2026
| Sl No | Description | Qty | Unit | Est. Rate | Est. Amount |
|---|---|---|---|---|---|
| 1 | Supply and delivery of Vertical type water/Oil lubricated statically, dynamically, hydraulically balanced turbine pump capable of discharging the following duty condition as given below due to all causes with surface discharge head confirming to IS 1710 and as amended as on date with accessories as per IS 5120/1977 (Reaffirmed 2011) and as amended thereafter to suit the site condition. The speed, No. of stages, sizes of column pipes and line shaft indicated is based on site condition prevailing during investigation. The pump should be supplied with non reversible ratchet pin housing safety clutch, suction strainer etc. The Pump Bowl assembly shall be with bronze impeller running at 1450 rpm. The pump includes suitable head shaft, suitable 1.5 metre long SS line shaft required Nos. to suit the well depth, Rubber line shaft bearing of required Nos., C.I Bearing retainer of required Nos., 100 litre HDPE Pre- lubricating tank with 20mm PVC Rigid pipe connection along with GM gate valves, Suitable ERW column pipe of each 1.5m long of required Nos. to suit the well depth, Suction bell mouth of suitable size, M.S. clamps suitable for column pipe/line shaft -2 set and Spanner - 1 set etc complete | - | - | - | - |
| 2 | 5000 lpm x 60 m Turbine pump M-1874 | 2 | Nos | - | - |
| 3 | Supply and delivery of vertical Hollow/Solid shaft Squirrel cage induction motor (IS 325) suitable for the above pump continuous rated TEFC/SPDP type with Class ‘F’ insulation for operation in AC, three Phase/50 HZ (±5%), 415V (±10%) running with a speed of pump noted above and with inbuilt thrust bearing assembly capable of taking up the entire load and non - reverse ratchet assembly etc., complete. The motor rating noted above is the minimum and shall be such that it should never be over loaded when the pump works at MWL condition and shall be 10% over and above the maximum HP absorbed by the pump. The motor offered should be energy efficient to have maximum efficiency at high power factor. Separate thrust bearing assembly could also be supplied to take up the down load. -110 HP 2025-2026 | 2 | Nos | - | - |
| 4 | Electromagnetic Flow Meter shall be a velocity sensing Electromagnetic type, microprocessor based signal converter, sealed housing, flanged tube meter for 1.0 Mpa working pressure, manufactured to highest standard available for mag-meters, equipped with minimum six digit digital totalizers, reading in units of (kilolitres/ cubicmeter) and shall be accurate within 0.5% of Measured value, shall operate within a range of 0.3m/sec to 4 m/sec and be constructed as follows:Meter tube (Sensor) shall be fabricated from stainless steel tube and use class PN10 flat face carbon steel flanges in accordance with IS 1538. These flanges shall be welded to the flow tube. The internal and external of the meter tube shall be blasted to near white and lined with hard rubber/ Polyurethrene/ PTFE preferably by SBR or EPDM. Meter tube shall have a constant nominal inside diameter offering no obstruction to the flow. The accuracy should be inclusive of linearity, hysteresis, repeatability, temperature and pressure effects Coil Housing shall be fabricated from stainless steel (SS 304) with Anticorrosive paint for corrosion resistance and welded to the tube providing a completely sealed environment for all coils, electrode connections and wiring harness capable of submerged or buried operation with IP 68 protection. | - | - | - | - |
| 5 | Signal Converter shall be pulsed DC coil excitation type with auto zeroing. The signal converter shall be remotely mounted away from the meter. The converter shall indicate direction of flow and provide a flow rate indication and a total of flow volume for both forward and reverse directions. The converter shall provide an isolated 4-20 mA output into minimum 500-ohm load and a frequency output of a maximum of 0-10 KHZ and a scaled pulse output, Communication interface is RS485, HART output, . The microprocessor based signal converter shall have a selfdiagnostic test mode and a backlit display that continuously displays “Rate of Flow” and “Total Volume”. Converter shall be supplied with a programmable low flow drop out Higher flow and empty pipe zero return. The signal converter housing should be die-cast aluminium with glass window. The converter cum transmitter should be fully programmable form the front facia. The programming should be user friendly, self-prompting menu driven. Flowmeter test calibration certificate from FCRI, flow test lab/ NABL accridiated lab to be furnished. | - | - | - | - |
| 6 | 600mm WD- M1401 TWAD 2025-26 | 1 | No | - | - |
| 7 | 500mm WD- M1400 TWAD 2025-26 | 1 | No | - | - |
| 8 | 350mm WD- M1397 TWAD 2025-26 | 1 | No | - | - |
| 9 | FLEX COMPENSATED MAGNETIC AMPLIFIER SOFT STARTER SUITABLE FOR L.T. SQUIRREL CAGE MOTOR
Supply and delivery of floor mounted type FCMA Air/ Oil Cooled soft starter suitable for the LT motor offered for operation in AC three Phase 50Hz (+/- 5%), 415V (+/-10%) including line contactors suitable for next standard higher KW rating, Over load relay, instrument panel with frequency meter, Ammeter, Voltmeter, indicating lamp 6Nos, LED ON/OFF type and Start /Stop push button. - 75 KW WD- M1923 TWAD 2025-26 | 2 | Sets | - | - |
| 10 | MIXED DI ELECTRIC CAPACITOR WITH TNEB TEST CERTIFICATE WITH ACCESSORIES INCLUDING BANKING CONFIRMING TO IS 2834.
Supply and delivery of KVAR in single bank automatic power factor control unit to maintain 0.95 leading power factor by automatic control of capacitor banks to maintain system power factor under varying load conditions with duly banked with copper busbars of ample capacity cable gland unit etc.., completed and as directed by the Officers | - | - | - | - |
stage.html
html • 0.05 MB
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Tendernotice_1.pdf
PDF • 1.56 MB
Tendernotice_2.pdf
PDF • 0.65 MB
BOQ_830896.xls
BOQ • 0.30 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .