Loading…
Loading…
| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | L1₹30.8 LAccepted-AOC RZ 18 260 WEST SAGARPUR NEAR MCD SCHOOL NEW DELHI 110046 | NEW DELHI | NEW DELHI | DELHI | 110046 | L1 | Accepted-AOC Lowest bidder | |
| 2 | L2₹38.8 L+₹6.7 L (21.0%)Rejected-Finance 19 62 1ST FLOOR WEST MOTI BAGH SARAI ROHILLA NEW DELHI 110035 | NEW DELHI | NEW DELHI | DELHI | 110035 | L2 | Rejected-Finance Other than lowest | |
| 3 | L3₹40.3 L+₹8.2 L (25.6%)Rejected-Finance WZ 409 0 B 1ST FLOOR PLOT NO 12 JANAK PARK HARI NAGAR NEW DELHI 110064 | NEW DELHI | WEST DELHI | DELHI | 110064 | L3 | Rejected-Finance Other than lowest |
Tender Value
₹45 L
EMD Value
₹90,000
Closing Date
21 Feb 2022, 6:00 pmClosed
GE UTILITY PLANT AND MACHINERY DELHI CANTT-10
GE UTILITY PLANT AND MACHINERY KIRBY PLACE DELHI CANTT-10
SPL REPAIR TO COOLING TOWER OF CENTRAL AC PLANT OF CAMS 505 ABW COD AND CONNECTED WORKS UNDER GE(U) PM DELHI CANTT-10
2022_MES_504595_1
GE(U)/PM/D-62/2021-22
Open Tender
Electrical and Maintenance Works
Item Rate
90 days
DELHI CANTT
MES contractor enlisted under class D category c(i) having deposited standing security of Rs 100000 with department. Contractor not enlisted in MES should meet the MES enlistment criteria corresponding to appropriate class and category.
6 documents required · 6 mandatory
₹500
GE UTILITY PLANT AND MACHINERY DELHI CANTT-10
₹90,000
Yes
28 Feb 2022
29 Jan 2022
23 Feb 2022
29 Jan 2022
21 Feb 2022
7 Feb 2022
Amount
M & L for disconnecting the defective FRP cooling tower of Cap 220/230 TR and repair the same by replacing defective broken/unserviceable spare parts including repair to minor leakages & assembling, tesing & comminssioning for satisfactory performance complete all as specified and as directed. Note:- (i) Required Spare parts shall be measured and paid seperatly as 'Supply only' under relevent items. (ii) Labour charges for taking down old spares and fixing of new spares shall deemed to be included in unit quoted rate.
-ditto- all as per item No.1 above but FRP cooling tower of Capacity 125 TR.
-ditto- all as per item No.1 above but FRP cooling tower of Capacity 60 TR.
-ditto- all as per item No.1 above but FRP cooling tower of Capacity 45/50 TR
-ditto- all as per item No.1 above but FRP cooling tower of Capacity 30 TR.
Supply only following spare parts for FRP cooling tower complete all as specified and as directed.:-
PVC FRP lined branch pipes 63 mm dia as per existing size for water distribution system inside cooling tower.
PVC drift Eliminators.
PVC fills honey comb of size 600 mm x 300 mm x 150 mm.
Polypropylene spray nozzle to be fitted in water distribution system.
Splash caps
PVC FRP lined Pipe 125/150 mm dia as header.
PVC End Cap as per existing size.
PVC Separator PVC 63 mm dia
PVC Socket
Nut Bolt any size
FRP Compound
Tie rod MS Electro plated Note for item No 6.01 to 6.12 :- (i) Materials of item Nos. 6.01 to 6.12 to be incorporated in item Nos 1 to 5 here-in-before. (ii) Labour charge of item Nos. 6.01 to 6.12 are deemed to be included in the quoted rate in item Nos. 1 to 5 here-in-before. (iii) Make of item Nos. 6.01 to 6.12 as approved by Accepting officer.
M & L in replacement of MS hot dipped galvanized Fan Screen with hardware to be placed above FRP fan, complete all as specified and as directed.
M & L in replacement of FRP Fan deck and cylinder suitable for fan dia upto 1200mm for optimum airflow, complete all as specified and as directed.
M & L in replacement of FRP Fan deck and cylinder suitable for fan dia of 1800 mm for optimum airflow, complete all as specified and as directed.
M &L for dismantling the old broken fan hub assembly including blades of cooling tower and replacement with new fan hub assembly with die cast aluminium blades adjustible pitch axial fan of dia 1800 mm heavy duty as per existing size including U-clamps, nuts, bolts & washers suitable for cooling tower for 240 TR capacity cooling tower complete all as specified and as directed.
-ditto- all as per item No.10 above but fan of dia 1200 mm
-ditto- all as per item No.10 above but fan of dia 900 mm
-ditto- all as per item No.10 above but FRP axial fan of dia 1200mm.
M & L in replacement of Heavy duty FRP roof tray with smooth gel coat finish with all fittings complete all as specified and as directed.
M & L in replacement of FRP heavy duty casing with smooth gel coat finish including all fitting accessories like clamps, nuts, bolts etc. complete all as specified and as directed.
M & L in replacement of Hot dipped galvanized mild steel mesh for air intake complete all as specified and as directed.
M & L in replacement of PVC/FRP louvers for air intake complete all as specified and as directed.
M & L in replacement of FRP bottom tray/ Cold water basin including arrangement for float valve, drain, inlet, outlet, overflow and quickfill, complete all as specified and as directed.
M & L in replacement of FRP inspection door with handle for opening complete all as specified and as directed.
Material and Labour for frame work with angle iron for frame support, with fabrication, welding joining including cutting tops to shape as directed, drilling holes, notching for wire, etc.; flat iron fillets (for securing wire mesh etc.) including all necessary drilling, bolting or riveting, etc., and similar work conforming to Fe-290 Gde E-165 including taking down old unserviceable one complete all as specified and as directed.
Supply, installation, testing & commissioning of Cooling Tower Motor of capacity 10 HP (750 RPM) including motor hub suitable for operation on 3 phase, 440V, 50 Hz AC supply including taking out the old burnt out motor & motor hub, complete all as specified and as directed. Make – Oswal/ Crompton/ABB/ Kirloskar
Supply, installation, testing & commissioning of Cooling Tower Motor of capacity 3HP (1000 RPM) including motor hub suitable for operation on 3 phase, 440V, 50 Hz AC supply including taking out the old burnt out motor & motor hub,complete all as specified and as directed. Make – Oswal/ Crompton/ABB/ Kirloskar
Supply, installation, testing & commissioning of Cooling Tower Motor of capacity 2 HP (1000 RPM) including motor hub suitable for operation on 3 phase, 440V, 50 Hz AC supply including taking out the old burnt out motor & motor hub, complete all as specified and as directed. Make – Oswal/ Crompton/ABB/ Kirloskar
M&L for cutting of existing MS water mains of size 25 to 50 mm of chiller/condensor/cooling towers of central AC plant at different points/section for replacement with new MS pipe in short lengths including MS fittings complete all as specified and as directed.
-ditto- all as per item No. 24 here-in-before but of size 80 mm
-ditto- all as per item No. 24 here-in-before but of size 100 mm
-ditto- all as per item No. 24 here-in-before but of size 125 mm
-ditto- all as per item No. 24 here-in-before but of size 150 mm
-ditto- all as per item No. 24 here-in-before but of size 200 mm
-ditto- all as per item No. 24 here-in-before but of size 250 mm
Supplying & laying , testing & commissioning mild steel (Heavy) 'C' class pipe of size 80 mm dia on exposed surface / underground (in trenches) including welding works, connections with existing chiller/condenser water line, chiller/condenser pump, fabrication of bends, MS flange, tees, reducers, shoe, support ( brick masonry block & wooden support for underground / MS angle- clamp & wooden support for exposed surface ) along with priming coat of steel primer as per standard specification including taking down old unserviceable pipe complete all as specified and as directed. Make- JINDAL PIPES/ TATA/ BST/ PRAKASH TUBES/ OSWAL Note:- (i) The rates quoted by the contractor shall deemed to include the cost of MS fittings required during laying of MS Pipes. (ii) The Pipes of sizes 150 mm & below shall be M.S. ‘C’ class as per IS : 1239 and pipes size above 150 mm shall be heavy class of thickness min. 7mm as per IS: 3589
-ditto- all as per item No. 31 here-in-before but of size 100 mm dia
-ditto- all as per item No. 31 here-in-before but of size 125 mm dia
-ditto- all as per item No. 31 here-in-before but of size 150 mm dia
-ditto- all as per item No. 31 here-in-before but of size 200 mm dia
-ditto- all as per item No. 31 here-in-before but of size 250 mm dia
Taking up or down GI water tubing of 40/50 mm dia including all connections complete all as specified and as directed.
-ditto- all as per item No. 37 above but 25 mm dia.
Supply and laying GI Tubing 'Medium grade' of dia 50 mm complete with all fittings in trenches/exposed surface, complete all as specified and as directed. (Make : JINDAL PIPES/TATA/ OSWAL/PRAKASH TUBES/ BST)
-ditto- all as per item No. 39 here-in before but 40 mm dia.
-ditto- all as per item No. 39 above but 25 mm dia.
Screwing of existing steel tubing of dia 40/50 mm dia for alterations or additions (or lengthening screw on pipe to form connector) complete all as specified and as directed.
-ditto- all as per item No. 42 above but 25 mm dia.
Supply and fixing in repairs cast iron butter fly valves lever operated SS disc type nitrile/EPDM rubber lining PN 16 of dia 250 mm complete all as specified and as directed. (Make: - ADVANCE/ AUDCO/ LEADER/CASTLE/ NVR/ ZOLOTO).
-ditto- all as per item No. 44 above but 200mm dia.
-ditto- all as per item No. 44 above but 150mm dia.
-ditto- all as per item No. 44 above but 100mm dia.
-ditto- all as per item No. 44 above but 80 mm dia.
-ditto- all as per item No. 44 above but 65 mm dia.
-ditto- all as per item No. 44 above but 50 mm dia.
Supply and fixing in repairs cast iron Y strainer flanged ends with SS perforated sheet screen of size 125 mm complete all as specified and as directed. (Make: - ADVANCE/ AUDCO/ LEADER/CASTLE/ NVR/ ZOLOTO).
Supply and fixing in repairs cast iron Y strainer flanged ends with SS perforated sheet screen of size 100 mm complete all as specified and as directed. (Make: - ADVANCE/ AUDCO/ LEADER/CASTLE/ NVR/ ZOLOTO).
Supply and fixing in repairs cast iron Y strainer flanged ends with SS perforated sheet screen of size 80 mm complete all as specified and as directed. (Make: - ADVANCE/ AUDCO/ LEADER/CASTLE/ NVR/ ZOLOTO).
Supply and fixing in repairs 200 mm dia cast iron non return valves of pressure class PN 16 including nuts, bolts, washers, gaskets, etc for Central type AC plants complete all as specified and as directed. (Make: - L&T (AUDCO)/ LEADER/KIRLOSKAR/ ZOLOTO).
-ditto- all as per item No. 54 above but 100 mm dia.
-ditto- all as per item No. 54 above but 50 mm dia.
Supply and fixing in repairs MS Pot Strainer of size 250 mm both ends flanged, complete all as specified and as directed. (Make: - EMERALD/ RAPID COOL/ LEADER).
Supply and fixing in repairs gun metal gate valves of size 25 mm bore with iron wheel head, screwed both ends for iron pipe, ISI Marked, as per IS:778 complete all as specified and as directed. (Make:- KIRLOSKAR/ LEADER / VENUS/ ZOLOTO/ AUDCO)
-ditto- all as per item No. 58 above but of size 40 mm bore
Dismantling the existing water cooled condenser of 120-230 TR AC plant of shell and tube type from it's pipe line and gas connection repairing the same by replacing the defective copper tubes of 15mm and 3000mm long by new pipes, cleaning the shell complete assembling the existing serviceable and new tubes, commissioning and testing upto 350 PSI pressure for satisfactory working complete all as specified and as directed. Note :- (i) Copper tubes of dia 15 mm and 3000mm long shall be measured and paid separately as 'Supply only' under relevent item. (ii) Taking down and fixing charge of copper tubes to be included in the quoted rate.
Supply only best quality copper tubes of thickness 1.26mm (18 SWG), dia 15mm and 3000mm long complete all as specified and as directed. (Make- MALASIA/ CAMIPRO/ DIAMOND/ STAR/ MANDAV/ RAJKO/ MAXFLOW) Note :- To be fixed under item No. 60.
Dismantling the existing water cooled condenser of Cap 30-60 TR AC plant of shell and tube type from its pipe line and gas connection repairing the same by replacing the defective copper tubes of 15mm dia and 1500mm long by new one, (No of tube existing is 92 Nos) Cleaning the shell complete assembly the new and serviceable tubes charging testing for 350 PSI pressure complete all as specified and as directed. Note :- (i) Copper tubes of 15mm dia and 1500mm long shall be measured & paid separately as ‘Supply only’ under relevant items. (ii) Taking down & fixing charge of copper tubes to be included in the quoted rate.
Supply only best quality copper pipe of size 15mm dia/ bore , 1500 mm long & 1.41 mm (17 SWG) thick complete all as specified and as directed. (Make:- MALASIA/CEMIPRO/ DIAMOND/ STAR) Note :- To be fixed under item No 62.
M&L for taking out all electrical connections of old unserviceable squirrel cage motor of any capacity, S&F new squirrel cage induction motor of capacity 10 HP (7.5 KW), 3 phase, 440+ 10%, 50 Hz, 1500 RPM, IP-55, 4 Pole protected including necessary arrangements for mouting on existing angle iron frame, nuts, bolts and washers of suitable size, complete all as specified and as directed. Make-ABB/Crompton Greaves/ Siemens
M&L for dismantling the existing condenser pump motor of any capacity and type from the PCC foundation and material & labour for PCC 1:2:4 type B1 with (using 20mm graded stone aggregate) as per existing size with 15mm thick rendering in CM 1:6 finished even and smooth with out using extra cement, grouting bolts, re-connecting the motor after complete of foundation work and making connections and testing, alignment complete all as specified and as directed.
Supply and fixing in repairs Immersion heater of cap 6 KW 230/440 volts as required complete all as specified and as directed. (Make : Dasspass/Crown/Theata)
Supply and fixing in repairs Immersion heater of cap 5 KW 230/440 volts as required complete all as specified and as directed. (Make : Dasspass/Crown/Theata)
Supply and fixing in repairs strip heater of cap 3 KW 230/440 volts as required complete all as specified and as directed. (Make : Dasspass/Crown/Theata)
Supply and fixing in repairs strip heater of cap 2 KW 230/440 volts as required complete all as specified and as directed. (Make : Dasspass/Crown/Theata)
Taking out all electrical connections of old unserviceable squirrel cage motor of any capacity, supply & fix new squirrel cage induction motor of capacity 7.5 HP (5.5 KW), 3 phase, 440+ 10%, 50 Hz, 1500 RPM, IP-55, 4 Pole protected including necessary arrangements for mouting on existing angle iron frame, nuts, bolts and washers of suitable size, connecting with the existing AHU blower complete all as specified and as directed. (Make-ABB/Crompton/ Kirloskar)
Taking out all electrical connections of old unserviceable squirrel cage motor of any capacity, S&F new squirrel cage induction motor of capacity 5 HP (3.7 KW), 3 phase, 440+ 10%, 50 Hz, 1500 RPM, IP-55, 4 Pole protected including necessary arrangements for mouting on existing angle iron frame, nuts, bolts and washers of suitable size, connecting with the existing AHU blower complete all as specified and as directed. (Make-ABB/Crompton/ Kirloskar)
M&L in replacement of providing and filling post/frame work of stainless steel, grade 304 pipes including braces of stainless steel, plates , angle flats , tubular sections etc including cutting, hoisting fixing with argon welding , bright finish , buffing polishing, grouting with PCC 1:2:4 type B1(using 20mm graded stone aggregates) in the existing foundations complete with necessary holes, nuts , bolts, caps and anchor plates for stainless steel, complete all as specified and as directed.
M&L for installation of poly carbonate micro prismatic type retro reflective boards conforming to XI of ASTM, made of 4mm thick substrate of aluminium composite panel having 0.50mm thick skin of aluminium both side. The front side is to covered with full cube poly carbonate prismatic reflecting sheeting conforming to proposed type XI of ASTM with coloured scheme, including subject matter , message (bi-lingual), symbol and borders etc as per IRC 67-2001. The aluminium composite panel shall be suitably fixed inside stainless steel frame work complete all as specified and as directed.
Material and labour for mild steel chequered plates any thickness laid above cable duct conforming to Fe-290 (Gde E-165) including taking down old unserviceable one complete all as specified and as directed.
M&L for 100 mm thick cement concrete type C-2, 1:3:6 ( 40 mm graded aggregate) including finishing surface of concrete topping even and fair ( without using extra cement), and finishing surface of concrete in floors including taking down complete all as specified and as directed.
Demolition of reinforced cement concrete of any description and in any position including cutting of reinforcement as required complete all as specified and as directed.
M&L for RCC 1:1.5:3, type A1 (using 20 mm graded stone aggregate) as in Columns, pillars, piers, posts and struts complete all as specified and as directed.
Materials and labour for RCC 1:1.5:3, type A1 (using 20mm graded stone aggregate) as in slab supported on walls, beams and columns in floors, roofs, landings complete all as specified and as directed.
Supply & finxing TMT bars 10mm dia and over, cut to length, bent to shape required, including cranking, ending spirally for hooping for columns, hooking ends and binding with and including mild steel wire (annealed) not less than 0.9mm dia or securing with clips complete all as specified and as directed.
Ditto- all as per item No. 79 here-in- before but 6mm to 8mm dia.
Ditto, all as per item No 79 here-in-before but 5mm dia and over upto and including 10mm dia in stirrups, spacers and binders complete all as specified and as directed.
Formwork to sides of pillars, posts, struts, piers, columns and stanchions complete all as specified and as directed.
Formwork to soffits of suspended slabs such as roof slabs, floor slabs, landings and similar work; not exceeding 200mm thick (Horizontal or sloping) complete all as specified and as directed.
Dismantling the existing old unserviceable Monoblock Pump of any capacity and supply and fixing new monoblock pump set of 3.0 HP (2.2 KW) suction/delivery of size 65 mm x 50 mm CI casted, head 14.0 Mtrs, discharge, 8.4 LPS, Stainless steel impeller & pump shaft, mechanical seal, including 3.0 HP electric motor, copper wounded with 'B' class insulation & IP-55 protected, Cast Iron body, suitable for voltage range 300 to 440 Volts, ISI Marked, including making all electrical connections and testing for any leakage complete all as specified and as directed. Make - Kirloskar pumps Model No. KDS 325++ or of equivalent in CROMPTON GREAVES/BEST & CROMPTON/BEACON/ KSB/ MOTHER & PLATT/ GRANDFOS)
Dismantling the existing old unserviceable Monoblock Pump of any capacity and supply and fixing new monoblock pump set of 5.0 HP (3.7 KW) suction/delivery of size 80 mm x 65 mm CI casted, head 16.0 Mtrs, discharge, 14.30 LPS, Stainless steel impeller & pump shaft, mechanical seal, including 5.0 HP electric motor, copper wounded with 'F' class insulation & IP-55 protected, Cast Iron body, suitable for voltage range 300 to 440 Volts, ISI Marked, including making all electrical connections and testing for any leakage complete all as specified and as directed. (Make - Kirloskar pumps Model No. KDS 527++ or of equivalent in CROMPTON GREAVES/BEST & CROMPTON/BEACON/ KSB/ MOTHER & PLATT/ GRANDFOS)
Supply and fixing in repairs Star Delta Starter with suitable rating relays for motors upto10 HP Capacity suitable for mounting on existing LT Panels of AC plants and connections with suitable size single core copper conductor wire & brass terminals of 6 way complete all as specified and as directed.. (Make -L&T/Siemens/Legrand/ ABB)
Supply and fixing in repairs DOL starters for motors upto 5 HP capacity with suitable rating relay, suitable for mounting on existing LT Panels of AC plants and connections with suitable size single core copper conductor wire complete all as specified and as directed. (Make -L&T/Siemens/Legrand/ ABB)
Supply and fixing in repairs DOL starters for motors of 7.5 HP capacity with suitable rating relay, suitable for mounting on existing LT Panels of AC plants and connections with suitable size single core copper conductor wire complete all as specified and as directed. (Make -L&T/Siemens/Legrand/ ABB)
Supply and fixing in repair humidity self priming motor pump set of cap 0.5 HP single phase 240 volt complete all as specified and as directed. (Make : Usha/ M/s Seetal /HP/Amcrate )
Disconnecting from mains/taking out existing unserviceable/defective motor of capacity 3 to 7.5 HP of any type, and make including disconnecting all electrical connections removing from foundation transporting to repair workshop,disconnecting unserviceable burn out winding completely including insulating materials and rewinding of the complete stator with super enameled copper wire of existing size applying proper insulation ‘F’ class varnish drying in oven, repair base plate, including nut, bolt for assembling, transporting back to site, re-installating, testing and commissioning complete all as specified and as directed
Disconnecting from mains/taking out existing unserviceable/defective motor of capacity 30 HP of any type, and make including disconnecting all electrical connections removing from foundation transporting to repair workshop,disconnecting unserviceable burn out winding completely including insulating materials and rewinding of the complete stator with super enameled copper wire of existing size applying proper insulation ‘F’ class varnish drying in oven, repair base plate, including nut, bolt for assembling, transporting back to site, re-installating, testing and commissioning complete all as specified and as directed.
S & F in repairs Aluminium bus bars of suitable rating of any size suitable for LT/HT Panels as per existing dimensions including including drilling holes and nuts, bolts and washers of suitable size & taking out old burnout old bars, complete all as specified and as directed.
Supply, laying and testing cable XLPE Insulated ,screened, PVC bedded, armoured, electric power cables (heavy duty) 1100 Volts grade with aluminium conductor of cross sectional area 16 Sqmm, 4 core with galvanized steel strip or wire including taking down old unserviceable one complete all as specified and as directed. (Make:- RR KABEL./ FINOLEX/ POLYCAB/ KEI INDUSTRIES LTD./ HAVELLS.)
Supply, laying and testing cable XLPE Insulated, electric power cables (heavy duty) 1100 Volts grade with copper conductor of cross sectional area 25 Sqmm, single core, including taking down old unserviceable one complete all as specified and as directed. (Make:- RR KABEL./ FINOLEX/ POLYCAB/ KEI INDUSTRIES LTD./ HAVELLS.)
Supply and fixing in repairs of bottom tray for fan and coil section made out of MS sheet 1.6mm thick duly painted with two coats of synthetic enamel paint (1st grade quality) through spray machine o over a coat of red oxide chrome primer with 25mm thick thermocol insulation covered with tarfelt for AHU complete all as specified and as directed. (Make of paint & primer:- ASIAN/ BERGER/ JHONSON & NICHOLSON/ SHALIMAR.)
Material and labour for insulation of pipe line( minimum dia of pipe 80 mm & maximum dia 250mm) with 13mm thickness closed cell cheimically cross linked fire retardant polyethllene foam insulation type W3CF2 of density 30 Kg/cum and covered with aluminium foil complete with application of rubber based adhesive including taking down unserviceable old one complete all as specified and as directed. (Make:- Torceilen/ Paramount/ Thermoflex).
Supplying and fixing Fire Extinguisher Carbon dioxide (CO2) extinguishers consisting of welded M.S. cylindrical body, light weight squeeze lever discharge valve fitted with pressure indicating gauge with internal discharge tube, discharge nozzle suspension bracket of capacity 4.5 Kg as per IS: 2878 complete with holding accessories including taking down old unserviceable onecomplete all as specified and as directed. (Make- Minimax/ Firex/ Newage)
-ditto- all as per item No. 93 above but CO2 of capacity 6 Kg. (Make- Minimax/ Firex/ Newage)
Material & Labour for earthing with galvanised steel earth plate electrode of size 60cmx60cm x6mm thick buried directly in ground (earth pit not less than 2.25m deep below the ground level) with top edge of the plate not less than 1.5m below normal ground level, connected to the galvanised earth lead 25x4mm by means of bolts, nuts check nuts and washers of galvanised iron wire 4mm as earth lead as shown in electrical plate No. 3 of SSR Part-I connected to earthing test point all as specified or indicated including testing on completion including necessary excavation and earth work in soft/loose soil, returning filling, disposal of surplus soil, earth pit in PCC 1:3:6 type C-1 using 20mm graded stone aggregate pit, funnel, 20mm dia GI medium grade watering pipe, 40mm dia GI medium grade earth lead protection pipe and pre-cast earth pit cover 50mm thick made of RCC (1:1.5:3) type A1 duly reinforced with 8mm dia TMT bar @100mm c/c both ways, one lifting handle made out of 10mm dia TMT bar 250mm long embedded in cover slab and cover, wire, copper lugs etc mesh, chorcoal and common salt in alternate layer of 15cm thick including taking down old unserviceable one complete all as specified and directed. (Make of GI Pipe:-JINDAL/ TATA/ BST/ PRAKASH TUBES/ OSWAL) (Note:- Each protection pipe and earthing lead upto and including 7.5 meter lenght is deemed to be included in the qouted rate of this item.)
Supply and fixing in repairs of earth continuity conductor or main earthing lead (GI strip extension) of size 25 X 4mm fixed to plinth or buried in ground or drawn in GI pipe or any other situation as indicated for loop earthing etc complete all as specified and as directed.
Dismantling the old broken Sintex tank of any capacity and Supply & fixing in repairs Sintex tank of capacity 10000 Ltrs including making all water connections by making hole of required size, washers etc complete all as specified and as directed. (Make-SINTEX/ POLYCON/JINDAL)
-ditto- all as per item No. 101 above but tank of capacity 5000 Ltrs
Taking out burnt SMPS board of Hot water generator for AC plant and refixing in original position, after necessary repair by replacing the burnt electronic spares from authorised manufacturer workshop , including reprogramming, resolving the problem and testing complete all as specified and as directed.
Material and labour for leakage detection of chiller and condensor pipe lines by charging dry Nitrogen Gas and with standing pressure for 24 hours, rectification of leakages, evacuation of the system as per manufacturer’s instruction complete all as specified and as directed. for capacity of 3x15 TR at COD. Note :- The rates quoted by the contractor shall deemed to include the cost of Nitrogen gas, charges for T&P and empty cylinders.
-ditto- all as per item No.104 above but Capacity of 3 X 22.5 TR AC plant at COD.
M&L brick work with well burnt best quality locally available brick, old size laid straight or curved on plan to any radius built in cement mortar 1:4, including taking down old unserviceable one complete all as specified and as directed.
M&L for plastering 10 mm thick on fair faces of brick work in cement mortar 1:4 and finishing the surface even & smooth (without using extra cement),complete all as specified and as directed.
M&L for preparation of new plastered surfaces of walls and applying two coats of whitewash complete all as specified and as directed.
SNOWY ENGINEERING INC
Flint India
stage.html
html • 0.05 MB
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.PDF
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.04 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .